Featured

IEC 61000-4-30 Class A Edition 3

The IEC 61000-4-30 Class A standard defines the measurement methods, time aggregation, accuracy, and evaluation, for each power quality parameter to obtain reliable, repeatable and comparable results between various brands and models of PQ instruments and systems.

IEC 61000-3-30 Class A Edition 2

IEC 6100-4-30 Class A Edition 2 standardizes the measurements of:

  • Power frequency
  • Supply voltage magnitude
  • Flicker (by reference to IEC 61000-4-15)
  • Voltage dips/sags and swells
  • Voltage interruptions
  • Supply voltage unbalance
  • Voltage harmonics, and interharmonics (referenced to IEC 61000-4-7)
  • Mains signaling voltage
  • Rapid voltage changes
  • Magnitude of current
  • Current harmonics and interharmonics (referenced to IEC 61000-4-7)
  • Current unbalance


IEC 61000-4-30 Edition 3 Introduced new measurements definitions and PQ parameters.

“This third edition cancels and replaces the second edition published in 2008. This edition constitutes a technical revision”.

  • Rapid voltage changes
  • Flicker class F1
  • Magnitude of the current
  • Current unbalance
  • Current harmonics (by reference to IEC 61000-4-7)
  • Current interharmonics (by reference to IEC 61000-4-7)

Additional changes in harmonic parameters from IEEE 519 2014

The number of harmonics to be evaluated. In many application, 50 harmonics are not enough and modern DC to AC inverters used in Wind and Solar generation have significate harmonic component up to the 100th.


Recording resolution – the latest edition of the IEEE 519 requires a daily and weekly harmonic evaluation of both voltage and current at 150/180 cycles (~3sec) resolution per phase. An edition 3 compliant instrument must record this data and prepare a report from the instrument.

Why these revised standards are important to electric utilities?

1. Rapid Voltage Change (RVC) parameter captures voltage changes (sags) that can be disruptive to some loads without exceeding the standard of +/- 5% voltage change limit. An instrument that does not make RVC measurements will miss these events. So a utility may receive customer complaints (most common is light flickers) and not have any data to find the source of the complaint. (most common is large motor starts or other sudden load or distributed generation switching. (tripping)

2. The Edition 3 revision transfers the responsibility for measurement methods continue in this standard, but responsibility for influence quantities, performance, and test procedures are transferred to IEC 62586 -1 and -2.

Part 1, namely IEC 62586-1, was constructed to define a comprehensive PQ device product standard, coined within as PQIs. The standard outlines safety, electromagnetic compatibility (EMC), climatic, and mechanical requirements, and refers to IEC 62586-2 for functional aspects. These requirements serve to ensure the instrument’s robustness will be suitable for its installation within the severe environments of a power station or substation.

Part 2, IEC 62586-24, defines the functional tests cited in the first part of the series. These tests are intended to comprehensively verify the PQ measurement methods outlined in 4-30. This chapter was established to provide traceable and repeatable procedures to verify the compliance of each PQ metric outlined in 4-30. This firstly addresses the main shortcoming of 4-30 and ensures better method adherence between PQ meter manufacturers. Additionally, the standard allows regulatory laboratories adhering to ISO/IEC 170255 to issue conformance reports and certificates according to IEC 62586-1 or IEC 62586-2 (with compliance to IEC 62586-2 meaning compliance to IEC 61000-4-30). The latter provides PQ meter manufacturers a way to provide internationally recognized compliance for the entire scope of PQI requirements.

3. To help ensure accurate PQ metrics in the harsh installation environment of a power station or substation, a number of electromagnetic compatibility (EMC) and influence quantity tests were also added to the scope of the IEC 62586 series.

“IEC 62586-2:2013 specifies functional tests and uncertainty requirements for instruments whose functions include measuring, recording, and possibly monitoring power quality parameters in power supply systems, and whose measuring methods (class A or class S) are defined in IEC 61000-4-30. This standard applies to power quality instruments complying with IEC 62586-1. This standard may also be referred to by other product standards (e.g. digital fault recorders, revenue meters, MV or HV protection relays) specifying devices embedding class A or class S power quality functions according to IEC 61000-4-30. These requirements are applicable in single, dual- (split phase) and 3-phase a.c. power supply systems at 50 Hz or 60 Hz.”

4. Environmental impact on the instrument from a laboratory environment. (25 Degrees C to a substation environment 40 Degrees C + ) is now part of the requirement of this standard. Detailed measurement procedures for Harmonics including to the 100th are included. Reporting of the harmonics to IEEE 519-2014 with harmonic limits specified for 1 and 1 week are included.

5. Detailed measurement procedures for Harmonics including to the 100th are included.

6. Reporting of the harmonics to IEEE 519-2014 with harmonic limits specified for 1 and 1 week are included.

All of these issues can be defined as IEC 61000-4-30 Class A, Edition 3 compliant.

Testing the SDC memristors in Three Phase Systems

Published by 1. Bartłomiej GARDA, 2. Karol BEDNARZ, AGH University of Krakow
ORCID: 1. 0000-0001-6150-5617; 2. 0009-0007-6857-4851


Abstract. The objective outlined in the paper is to conduct reliable measurement tests on memristor behavior in three-phase systems. Memristors, acting as nonlinear elements, exhibit intriguing phenomena within such systems. Various configurations, including Delta and Wye connections with three and four wires, have been tested. The collected data has been analyzed and presented, with additional frequency analysis using FFT and assessment of total harmonic distortion factors. The acquired data has been modelled using the MMS memristor model and compared with the actual data.

Streszczenie. W artykule przedstawiono wyniki testów pomiarowych opisujących zachowania memrystorów w systemach trójfazowych. Memrystory, jako nieliniowe elementy, wykazują˛ intrygujące zjawiska w takich systemach. Przetestowano różne konfiguracje, w tym połączenia w trójkąt, w gwiazdę z trzema i czterema przewodami. Zebrane dane zostały przeanalizowane i przedstawione. Dokonano analizy częstotliwościowej FFT oraz wyznaczono współczynniki całkowitego zniekształcenia harmonicznego THD. Następnie uzyskane wyniki pomiarowe zostały zamodelowane z wykorzystaniem modelu memrystora MMS i porównane z danymi rzeczywistymi. (Pomiary memrystorów w układach trójfazowych)

Keywords: memristor, measurements, memristive element, three-phase systems, nonlinear systems.
Słowa kluczowe: memrystor, pomiary, element memrystorowy, układy trójfazowe, układy nieliniowe.

Introduction

The successful discovery of the feasible memristor device in 2008, reported by HP Laboratories [1], marked a significant turning point, sparking considerable interest among scientific researchers. Faced with the limitations of computer memories, the primary focus shifted towards utilizing memristors as memory cells. Memristors, serving as non-volatile memory with the potential for multistability, emerged as promising candidates. Numerous research papers have explored this avenue, suggesting that the integration with CMOS technology may soon supplant current solutions. So, the applications of magnetic devices focus on microelectronics, which is not the only correct direction.

Fig.1. Examples of three wire connection setup. Wye connection with the memristor in positive polarity in the neutral wire (here YN−mP).

Beyond memory applications, research has unveiled various other potential implementations for memristors, such as electrostatic discharge protection [2], regulation elements in signal amplifiers [3], oscillators [4] or logic circuits [5]. In recent years, the concept of the so-called ’power memristor’ has grown. The idea is to use memristive elements in lightning protection systems, i.e. instead of traditional varistors. In [6] author proposes a combined over-voltage protecting device consisting of a memristor connected in series with a spark gap. The memristor is applied to dissipate the lightning surge energy and to break the short-circuit current. This simple example shows that analyzing the usage of memristive device in three-phase systems is noteworthy and can provide a basis for further research. In [7] authors carried out the computer simulations of symmetric three-phase systems with memristive loads. Continuing the work in this paper the aim of the research is to provide trustworthy laboratory experiment results of the three-phase systems with memristors. Memristors, acting as nonlinear elements, exhibit intriguing phenomena within such systems. Various configurations, including Delta and Wye connections with three and four wires, have been tested. The collected data has been analyzed and presented, with additional frequency analysis using FFT and assessment of total harmonic distortion factors. The high non-linearity of the memristor results in deformation of most of the signals in the system. Since the voltage of the neutral point is highly non-sinusoidal it affects other signals like phase voltage, phase currents, and delta voltages. A Fast Fourier Transform (FFT) is applied to the chosen signals in order to provide a frequency spectrum. On this basis a Total Harmonic Distortion (THD) parameter was calculated. All measurements were modeled using the MMS memristor model and further compared using the Simulink simulations.

Measurement

The authors used the three-channel generator NI-9263 and all data have been acquired by the compact 12-bit NI9201 device. The synchronization and acquisition process was performed using the LabVIEW environment. The tested device was a resistive device with chalcogenide ion conducting commonly known as SDC memristors, described in [8, 9]. Memristor SDCs can be doped with various metals, and in this work tungsten-doped memristors were used. To reduce the current, all memristors have been connected in series with the linear resistor Rs =5.1kΩ. All tests have been performed automatically for different frequencies and amplitudes of a three-phase symmetrical generator. The memristors have been connected in Delta and Wye, with and without the neutral wire. The example of a Wye conception with the neutral is shown in Figure 1. During the measurement five combinations of connections of the three-phase receiver have been applied, i.e. Delta (D), Wye (Y), Wye with neutral (YN), Wye with memristor in negative polarity in the neutral (YN−mN), and Wye with memristor in positive polarity in neutral (YN−mP). Hardware tests have been performed for all described connection combinations. The three-phase symmetrical generator was the three sinusoidal sources connected to the Wye of the same amplitude: {1.5,2,2.5,3} V for the Wye variation systems. In case of a Delta connection system, the above amplitudes were divided by 3 to obtain the same phase voltages on the load. The applied frequency belonged to the set {1,2,5,20,50,100} Hz. During the experimental procedure, a certain degree of measurement error was discerned. To mitigate errors attributed to high-frequency components present in the acquired data, the SavitzkyGolay filter [10] was used. The total acquired and filtered signals for 100 periods have been averaged down to one period.

Fig.2. Phase currents averaged over one period, for different types o circuit connections, with a supply signal amplitude of 2.5V and a frequency of 2Hz. a) Y, b) YN, c) YN−mP, d) YN−mN, e) D.

The example of the acquired and processed current signals for each connection combination can be observed in Figure~2. As expected, for all connections the all three phase currents are similar and shifted by ±120deg. Although the system seems to be symmetric, in the case when the fourth wire is attached, the neutral current is present. The effect is more noticeable for the YN connection. The presence of the memristor in the neutral wire decreases the neutral current value especially for the YN−mN connection. The memristor on the neutral wire works as some kind of diode and the current shape is similar to the three wire connection (Y). e)

Fig.3. Phase voltages across memristors, averaged over one period, for different types o circuit connections, with a supply signal amplitude of 2.5V and a frequency of 2Hz. a) Y, b) YN, c) YN−mP, d) YN−mN, e) D.

Anyhow it has to be point out that due to memristor’s high nonlinearity the respond signals are highly deformed from the sinusoidal. In the Figure 3 the corresponding voltages over memristors for all combinations of the connection are depicted. The voltage shape are also deformed but looks more similar and as expected shifted. The problem noticed here is the voltage peek values are different. For example, for D connection the problem can be neglected, but in case of YN the voltage vmc is much lower than vmb, especially for negative voltage.

Fig.4. Amplitudes of individual harmonics of the phase current ia in relation to the first harmonic amplitude for each connection type. The voltage amplitude was 3V. a) f =1Hz, b) f =100Hz.
Fig.5. The Rratio = ROFF/RON for different combination of frequencies and the connection type. The amplitude of the voltage is 3V

The order of the mentioned current signal deformation can be analyzed using the fundamental THD (Total Harmonic Distortion) parameter [11]. To calculate the THD parameter first the Fast Fourier Transform (FFT) needs to be carried out. In Figure 4 the amplitudes of the individual harmonics compared to the first harmonic are depicted. It can be observed that the amplitudes of the higher harmonic contribution become significantly smaller for the frequency of 100Hz compared to 1Hz. The actual values of the THD parameters can also be read in table 1.

Simulations

The acquired measurement data has been processed, and the parameters of the MMS memristor model [12] have been fitted using the nonlinear optimization method Sequential Quadratic Programming (SQP) [13]. A comprehensive explanation of fitting the memristor time series data to the specified model is provided in [14].

Fig.6. Comparison of simulation results in the Simulink environment with actual measurements of memristors, averaged over one period, for YN connection type, with a supply signal amplitude of 2.5V and a frequency of 5Hz. The simulation results are represented by a dashed line, and the measurements by a solid line. a) comparison of time series of the memristors current im, and voltage across them vm, b) The typical hysteresis loops on vm− im domain.

Using the model with the optimal parameters, Simulink simulations were conducted. The comparison between the measurements and the simulations for the Wye with neutral connection is illustrated in Figure 6. The high degree of agreement between the signals obtained from the measurements and the Simulink simulations validates the selection of the appropriate memristor model. Figure 6 depicts the characteristic memristor hysteresis loop, pinched at the origin in the v−i domain. Among the parameters of the MMS memristor model, RON and ROFF define the resistance range within which the memristor operates. The values of these resistances are presented in Table 1. The resistance ratio, defined as Rratio = ROFF/RON, is observed to be significantly higher at lower frequencies. This trend is further illustrated in Figure 5, where the resistance ratio decreases with increasing frequency for all connection combinations. This observation aligns with one of the memristor’s fingerprints defined by Chua, which states that “the hysteresis lobe area should decrease monotonically as the excitation frequency increases” [15], indicating that the resistance range between RON and ROFF is narrowing. This phenomenon also explains the increase in the RMS current value with frequency, as then the mean resistance decreases. The memristor element is not portwise symmetric, which results in a DC component in the current response. The values of the DC component are provided in

Table 1. It should be noted that the presence of a DC component also tends to decrease as the frequency increases. Table 1. Comparison of various connection types in terms of resistance ratio (Rratio), on-state resistance (RON), off-state resistance (ROFF), total harmonic distortion in linear scale (THDlin), total harmonic distortion in logarithmic scale (THDlog), RMS and mean value of phase a current. With power supply parameters: amplitude voltage Vs =3V, and frequency a) fs =1Hz, b) fs =100Hz.

.
Summary

As anticipated, the highly nonlinear memristor element exerts a significant impact in three-phase systems, specifically affecting the DC components across all phase signals. When connected in a Wye configuration with the memristor in positive polarity on the neutral wire, the memristor exhibits an intriguing low-frequency current signal, effectively acting as a rectifier. In particular, the total harmonic distortion (THD) factor decreases as the excitation signal frequency increases. This effect is less pronounced in Wye connections with a neutral wire. Depending on the connection type, the memristors behave differently, which can be observed with the RON and ROFF values. In addition, the effect of narrowing the interval between RON and ROFF is observed during frequency increase. Employing a Simulink simulation with the MMS memristor model yields highly reliable results, closely mirroring laboratory experiments.

Acknowledgments The research presented in the article was financed by the Polish Ministry of Science and Higher Education as part of a subsidy for AGH University of Krakow.

REFERENCES

[1] Dmitri B. Strukov et al. “The missing memristor found”. In: Nature 453.7191 (2008), pp. 80–83.
[2] G. Elmer et al. “Design thinking for innovation in 3D VR Over-Voltage Protection with Memristor”. In: 2020 11th IEEE International Conference on Cognitive Infocommunications (CogInfoCom). Mariehamn, Finland, 2020, pp. 417–424.
[3] Q. Li et al. “Study of the Noninverting Amplifier Based on Memristor with Linear Dopant Drift”. In: 2012 Second International Conference on Intelligent System Design and Engineering Application (ISdea). Sanya, China, 2012, pp.1136–1139.
[4] S. Weiheng, Chunfu Li, and Juebang Yu. “A memristor based chaotic oscillator”. In: 2009 International Conference on Communications, Circuits and Systems (ICCCAS). Milpitas, CA, USA, 2009, pp. 955–957.
[5] Yamtim S. and Tooprakai S. “Multi-input Memristor Rationed Logic Full Adder Circuit for Efficient Processing Time”. In: Przegla˛d Elektrotechniczny 98.6 (2022), pp. 88–94. ISSN: 0033-2097.
[6] Ildikó Horváth. “Simulation of a memristor-spark-gap model for lightning protection purposes”. In: Tehnicki Vjesnik 21 (Oct. 2014), pp. 1047–1050.
[7] Garda B. and Zegarmistrz P. “Memristive Devices In Three-Phase Systems”. In: Przegla˛d Elektrotechniczny 96.1 (Jan. 2020), pp. 11–14. ISSN: 0033-2097.
[8] Bartłomiej Garda and Karol Bednarz. “Comprehensive Study of SDC Memristors for Resistive RAM Applications”. In: Energies 17.2 (Jan. 2024), p. 467. ISSN: 1996-1073.
[9] Valerii Ostrovskii et al. “Structural and Parametric Identification of Knowm Memristors”. In: Nanomaterials 12.1 (2022). ISSN: 2079-4991.
[10] A. Savitzky and M.J.E. Golay. “Smoothing and Differentiation of Data by Simplified Least Squares Procedures”. In: Analytical Chemistry 36.8 (1964), pp.1627– 1639.
[11] D. Shmilovitz. “On the definition of total harmonic distortion and its effect on measurement interpretation”. In: IEEE Transactions on Power Delivery 20.1 (2005), pp. 526–528.
[12] T. W. Molter and M. A. Nugent. “The Generalized Metastable Switch Memristor Model”. In: CNNA 2016; 15th International Workshop on Cellular Nanoscale Networks and their Applications. 2016, pp. 1–2.
[13] Philip Gill and Elizabeth Wong. “Sequential Quadratic Programming Methods”. In: vol. 154. Nov. 2012, pp. 147–224. ISBN: 978-1-4614-1926-6.
[14] Bartłomiej Garda. “Modeling of Memristors under Periodic Signals of Different Parameters”. In: Energies 14.21 (2021). ISSN: 1996-1073.
[15] Shyam Prasad Adhikari et al. “Three Fingerprints of Memristor”. In: IEEE Transactions on Circuits and Systems I: Regular Papers 60.11 (2013), pp. 3008–3021.


Authors: Ph.D. Bartłomiej Garda, M. Sc Karol Bednarz, Department of Electrical and Power Engineering, Faculty of Electrical Engineering, Automatics, Computer Science and Biomedical Engineering, AGH University of Kraków, al. Mickiewicza 30 30–059 Kraków, Poland, email: bgarda@agh.edu.pl, kbednarz@agh.edu.pl


Source & Publisher Item Identifier: PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 101 NR 2/2025. doi:10.15199/48.2025.02.13

Selecting An Inverter for a PV Micro-Installation

Published by Konrad SEKLECKI, Leszek S. LITZBARSKI, Marek OLESZ, Emanuel GIFUNI, Grzegorz REDLARSKI, Jacek GROCHOWSKI


Abstract. The article describes recommendations related to the optimal selection of inverters for PV micro-installations. It presents different types of inverters used in PV installations depending on their type and power. Regardless of the case, attention should be paid to the maximum voltage and input current of the device. However, the appropriate quality of the inverter and its compliance with applicable regulations, as evidenced by appropriate certificates, are equally important. Undersizing the inverter in relation to the peak power of the PV installation results in its more efficient operation. Based on the analysis of real examples of PV micro-installations, it was found that in many cases there is a problem with the selection of appropriate inverters.

Streszczenie. Artykuł opisuje zalecenia związane z optymalnym doborem falowników do mikroinstalacji PV. Przedstawiono w nim różne rodzaje falowników stosowanych w instalacjach PV w zależności od ich typu i mocy. Niezależnie od przypadku należy zwrócić uwagę na maksymalne napięcie i natężenie prądu wejściowego danego urządzenia. Ważna jest odpowiednia jakość wykonania falownika oraz jego zgodność z obowiązującymi przepisami, o czym świadczą odpowiednie certyfikaty. Niedowymiarowanie mocy falownika w stosunku do szczytowej mocy instalacji PV skutkuje jego wydajniejszą pracą. Na podstawie analizy rzeczywistych przykładów mikroinstalacji PV stwierdzono, że w wielu przypadkach występuje problem z doborem odpowiednich falowników.

Keywords: photovoltaic installation, solar panels, PV inverter, optimum inverter sizing, balance of system
Słowa kluczowe: instalacja fotowoltaiczna, panele fotowoltaiczne, falownik PV, optymalny dobór falownika, równowaga systemu

Introduction

The main element of every photovoltaic installation are the PV panels, which are responsible for generating electricity. However, they would not be able to fulfil their task without other components such as: cabling, switches, mounting system, inverters, energy storage, etc. All these components, which contribute to the operation of the system, constitute an “equivalent system”, usually indicated by the acronym BoS (Balance of System) [1]. A properly balanced PV system is characterized by high efficiency [2]. A modern PV installation should include a number of elements necessary for efficient and safe production of electricity [3]. In addition to typical components such as PV panels, support structure, cabling and inverter, appropriate safety systems should also be included. In the case of some PV installations (off grid and hybrid), one of the BoS elements is also an energy storage facility enabling storage of generated surplus electricity (most often implemented in the form of battery rooms based on lead or lithium-ion batteries).The ratio of the BoS expansion costs to the expected financial benefits from such an investment should be analyzed for each individual case. A similar situation occurs with regard to systems increasing the safety of PV installation operation [4], [5], [6], [7]. In certain situations, even significant financial outlays for additional safety systems may be justified in the face of potential losses resulting from a PV installation failures.

This article focuses on issues related to the correct selection of inverters for PV micro-installations (i.e. installations, which peak power do not excess 40 kWp), which are the most common type of PV installation [8]. It describes the most frequently used technical solutions and the most important factors determining the optimal parameters of the inverter. In addition, it presents the results of experimental studies regarding the selection of the optimal power of the inverter. Furthermore, the selection of inverters was analyzed on the example of several real PV microinstallations located in different regions of Poland.

Types of inverters for PV micro-installations

Depending on the type of PV installation, inverters adapted to network operation, i.e. on-grid or island operation (off-grid) can be distinguished. The former enable connection to the power grid by adjusting the voltage of the photovoltaic installation to the grid voltage in order to transfer surplus electricity produced in it. The latter are used when it is not possible to connect to the power grid. In this case, surplus generated energy is stored in batteries constituting a local energy storage. There are also so-called hybrid inverters that combine the features of both of the above solutions.

Fig.1. PV micro-installation using: micro-inverters (A), central inverter (B)

Typical PV micro-installations are equipped with a central inverter to which PV modules are connected in series (Fig. 1A). This solution means that all modules must operate with the same power, which translates into a decrease in the efficiency of the system. An alternative is systems with microinverters, which involve the introduction of direct DC/AC conversion on individual panels (Fig. 1B). Their use improves the possibilities of expanding the installation and minimizes losses associated with partial shading of the panels. Microinverters sometimes have a module enabling remote communication, which allows monitoring the operation of each module separately. This allows for a detailed examination of the operating conditions of the installation and their optimization. Unfortunately, the use of microinverters is associated with an increase in installation costs and a reduction in its operating time [9]. These elements are exposed to operation in extreme conditions (large temperature gradients up to 120 °C, precipitation, etc.), which reduces their service life and increases the risk of failure. It should also be taken into account that all operating activities are significantly difficult due to the location of the microinverter directly next to the PV panel. According to many PV system installers, in most cases access to the microinverters is difficult. In order to perform service activities, it is usually necessary to dismantle one or even several PV panels, which significantly complicates and prolongs the repair process.

It should be also mentioned that there are single-phase and three-phase inverters. The former are most often used in low-power installations, because according to the recommendations of the EN 50438 standard, the rated current of a single phase should not exceed 16 A [10], which in the case of a standard voltage of 230 V translates into a power of 3.68 kW. The latter is used in higher power installations, as they allow for limiting the current value and evenly introducing energy into each phase. This affects smaller voltage fluctuations in the network and allows for the use of smaller cross-sections of wires.

Major criteria for inverter selection

The criteria for selecting an inverter for an installation vary depending on its type. In the case of an installation using microinverters, it should be checked whether the open circuit voltage (Uoc) and short circuit current (Isc) of a single module do not exceed the maximum value supported by the device. Traditional PV micro-installations with a central inverter should be designed in such a way that the voltage generated by the individual strings falls within the range of the inverter input voltage. In addition, the permissible number of strings supported by a given inverter and its maximum input current should be taken into account. The International Protection Rating (IP) that determines the location of the inverter installation is also important – in the case of outdoor applications, IP65 or higher is required [11] Regardless of which of the above technical solutions will be used, it is worth considering that they have appropriate certificates proving their quality, which translates into long-term failure-free operation. In addition, such devices provide output parameters compatible with the power grid and meet legal requirements. For economic reasons, it is also worth paying attention to the efficiency of the inverter, because devices with higher efficiency provide better energy conversion and lower losses. Additionally, it is worth considering the use of inverters with built-in protection (e.g. against overvoltages) and the ability to monitor the condition of the PV installation. This significantly improves the operational safety of a given PV system [12].

Another aspect is the issue of selecting the appropriate ratio of the peak power of the PV installation (PPV) to the rated power of the inverter (Pinv). This problem concerns primarily systems with a central inverter. This issue is not regulated by law, but inverter manufacturers recommend that the value of Pinv/PPV < 1. The need to undersize the inverter power results from ensuring optimal conditions for its operation – it achieves the highest efficiency when working under rated load [13]. The power of the PV installation is usually determined in the so-called STC (Standard Test Conditions) or NOCT (Normal Operating Cell Temperature) conditions, but in reality the achieved values of this parameter are significantly lower [14]. The actual performance of the PV installation should be determined based on properly conducted as-builts measurements [15].

Optimal selection of PV inverter power

In order to illustrate the issue of selecting the inverter power for a PV installation, an experiment was conducted using a three-phase HPT-4000 inverter (Imax = 15.6 A; 180 V < UPV < 850 V; Pinv = 4 kW). The Keysight PV8921A PV installation simulator was used in the investigations, which has the following parameters: Uout = 1500 V; Imax = 30 A Pmax = 20 kW. The measurements were carried out employing MI2292 power quality analyzer. In Fig. 2 is presented the dependence of the inverter efficiency (η = PAC/PDC) in a function of a power generated by the PV installation. It can be observed, that the efficiency of the energy conversion process is highest when the inverter input is loaded with power close to its maximum power. Exceeding the Pinv results in the activation of the built-in protections, therefore the η value drops. The efficiency of the inverter also decreases when it is underloaded. In addition, the Total Current Distortion coefficient (THDI) increases, which reflects the quality of the generated electricity [16]. In Fig. 3 shown, that both the maximum and minimum values of the mentioned coefficient decrease with the load on the inverter, which indicates a decrease in the share of higher harmonics in the waveform of the generated current.

Fig.2. The efficiency of PV inverter in a function of power of PV installation

It should be emphasized here, that the actual power of the PV installation is lower than PPV, therefore it is recommended to use inverters with lower power. On the other hand, it is necessary to avoid a situation in which the inverter is unable to process the supplied electrical energy due to too low power. The optimal selection of the inverter is based on the fact that the energy losses resulting from the power limitation are lower than the increased energy gain resulting from the higher efficiency of the inverter.

Fig.3. The Total Current Distortion coefficient in a function of power of PV installation

PV Inverter Selection Case Study

In order to better illustrate the issue of selecting inverters for PV micro-installations, 14 real cases were analyzed. The research object was PV micro-installations located in northern Poland, which were checked in the context of the correctness of the inverter selection. The obtained results are gathered in Table 1.

Table 1. Summary of real cases of PV micro-installations in the context of the correctness of the inverter selection

.

It can be observed that the main problem related to the selection of inverters is their oversizing in relation to the PV installation. In all the cases examined, the Pinv/PPV ratio was higher than 1, which, as shown above, is associated with reduced installation efficiency, i.e. lower power generated to the power system. In addition, the use of an oversized inverter increases the cost of the PV installation, thus extending the payback period. Another issue concerns exceeding the maximum permissible inverter current (Imax), which occurred in more than 57% of cases. This situation is potentially dangerous because it can lead to overheating of the inverter components and, consequently, to fire. It is also worth mentioning that in almost 79% of the examined cases the maximum permissible voltage (Umax) was exceeded, which may result in a shortened lifespan of the inverters.

Conclusions

The appropriate selection of an inverter for a PV microinstallation is crucial due to aspects related to efficiency and operational safety. The principles of selecting inverters vary depending on the type of PV installation (installation with a central inverter or microinverters) and its power (in the case of installations with higher power, three-phase inverters are usually used). Nevertheless, care should be taken not to exceed the maximum permissible values of input voltage and current for a given device. Moreover, the designer should ensure that the components used are characterized by high quality of workmanship and comply with applicable regulations, as evidenced by appropriate certificates. It is also worth choosing inverters with higher efficiency. Another issue is the selection of the optimal power of the inverter for a PV micro-installation. Undersizing the inverter in relation to the power of the PV installation results in a higher electrical energy yield due to its more efficient operation. Furthermore, in the long term, PPV decreases due to the aging processes of PV modules, which additionally reduces the efficiency of micro-installations with underloaded PV inverters. Analysis of real cases has shown that there are problems with the appropriate selection of inverters for PV micro-installations (especially with the appropriate selection of Pinv/PPV). In this matter, specialist software such as BlueSol [17] can be helpful, however, the final decision on the selection of specific components always remains with the designer.

Thanks to ERKON Tech Sp. z o.o. for providing the data necessary for the analyses described in this article.

REFERENCES

[1] F. Baumgartner, “5 – Photovoltaic (PV) balance of system components: Basics, performance,” in The Performance of Photovoltaic (PV) Systems, N. Pearsall, Ed., Woodhead Publishing, 2017, pp. 135–181. doi: https://doi.org/10.1016/B978-1-78242-336-2.00005-7.
[2] N. G. Dhere, “Reliability of PV modules and balance-of-system components,” in Conference Record of the Thirty-first IEEE Photovoltaic Specialists Conference, 2005., 2005, pp. 1570–1576. doi: 10.1109/PVSC.2005.1488445.
[3] S. Czapp, K. Seklecki, L. Litzbarski, and M. Olesz, “Zagrożenie porażeniem podczas gaszenia pożaru w budynkach z fotowoltaicznymi źródłami energii ,” Przegląd Elektrotechniczny, vol. 12, pp. 66–72, 2024.
[4] L. Litzbarski, M. Olesz, K. Seklecki, and M. Nowak, “Ryzyko strat odgromowych a systemy fotowoltaiczne,” Przegląd Elektrotechniczny, pp. 293–295, 2023.
[5] H. Boryń, “Ochrona odgromowa fotowoltaicznych źródeł energii elektrycznej,” Zeszyty Naukowe Wydziału Elektrotechniki i Automatyki Politechniki Gdańskiej, pp. 21–26, 2010.
[6] K. Seklecki, L. Litzbarski, K. Wójcik, Z. Cieślikowska, M. Włas, and J. Grochowski, “Instalacje fotowoltaiczne w budownictwie wielorodzinnym,” Przegląd Elektrotechniczny, pp. 79–81, 2024.
[7] M. C. Falvo and S. Capparella, “Safety issues in PV systems: Design choices for a secure fault detection and for preventing fire risk,” Case Studies in Fire Safety, vol. 3, pp. 1–16, 2015,
[8] M. Sarniak, “Fotowoltaika w układach zasilania budynków,” Elektro Info, vol. 9, pp. 64–68, 2015.
[9] Ö. Çelik, A. Teke, and A. Tan, “Overview of micro-inverters as a challenging technology in photovoltaic applications,” Renewable and Sustainable Energy Reviews, vol. 82, pp. 3191–3206, 2018, doi: https://doi.org/10.1016/j.rser.2017.10.024.
[10]K. Sereja and R. J\kedrychowski, “System zarz{\k{a}}dzania sieci{\k{a}} nn w świetle wymagań normy PN-EN 50438,” Poznan University of Technology Academic Journals. Electrical Engineering, 2018.
[11]PN EN 60529 : 2003 AC 2017Degrees of protection provided by enclosures (IP Code). 2003.
[12]K. Sarita, R. K. Saket, and B. Khan, “Reliability, availability, and condition monitoring of inverters of grid-connected solar photovoltaic systems,” IET Renewable Power Generation, vol. 17, no. 7, pp. 1635–1653, 2023, doi: https://doi.org/10.1049/rpg2.12700.
[13]M. Pilinski, “Optymalny dobór falownika do instalacji PV,” GLOBEnergia: Odnawialne Źródła Energii, no. 2, 2018.
[14]H.-F. Tsai and H.-L. Tsai, “Implementation and verification of integrated thermal and electrical models for commercial PV modules,” Solar Energy, vol. 86, no. 1, pp. 654–665, 2012, doi: https://doi.org/10.1016/j.solener.2011.11.014.
[15]L. Litzbarski, M. Olesz, and K. Seklecki, “Measurement practice of photovoltaic installations leading to the determination of the actual technical condition; [Praktyka wykonywania pomiarów instalacji fotowoltaicznych prowadząca do określenia rzeczywistego stanu technicznego],” Przeglad Elektrotechniczny, vol. 2024, no. 3, pp. 82 – 84, 2024, doi: 10.15199/48.2024.03.14.
[16]J. A. Pomilio, J. P. Bonaldo, H. K. Morales-Paredes, and P. Tenti, “About power factor and THDi in the smart micro-grid scenario,” in 2015 IEEE 13th Brazilian Power Electronics Conference and 1st Southern Power Electronics Conference (COBEP/SPEC), 2015, pp. 1–5. doi: 10.1109/COBEP.2015.7420183.
[17]K. Kut Paweł and Nowak, “Design of Photovoltaic Systems using Computer Software,” Journal of Ecological Engineering, vol. 20, no. 10, pp. 72–78, 2019,


Authors: mgr inż. Konrad Seklecki, E-mail: konrad.seklecki@pg.edu.pl; dr inż. Leszek Litzbarski, E-mail: leszek.litzbarski@pg.edu.pl; dr hab. inż. Marek Olesz, E-mail: marek.olesz@pg.edu.pl; Emanuel Gifuni, E-mail: s194407@student.pg.edu.pl; prof. dr hab inż. Grzegorz Redlarski, , E-mail: grzegorz.redlarski@pg.edu.pl; Gdansk University of Technology, Faculty of Electrical and Control Engineering, Gabriela Narutowicza 11/12, 80-233 Gdańsk; Jacek Grochowski, Poznan University of Technology, Faculty of Control, Robotics and Electrical Engineering Piotrowo 3a, 60-965 Poznań, E-mail: jacek.grochowski@student.put.poznan.pl


Source & Publisher Item Identifier: PRZEGLĄD ELEKTROTECHNICZNY, R. 101 NR 5/2025. DOI: 10.15199/48.2025.05.26

Automated Power Factor Correction Through Microcontroller in Energy Sector

Published by 1. Pawan Kumar PANDEY1, 2. Ramesh KUMAR2, 3. Manish SINGLA2,3, 4. Sergey KOKIN4, 5. Murodbek SAFARALIEV4, 6. Javod AHYOEV3, Gyan Ganga Institute of Technology and Sciences (1), Chitkara University Institute of Engineering and Technology (2), Applied Science Private University (3), Ural Federal University (4), Tajik Technical University Named After Academician M.S. Osimi (5)
ORCID: 1. 0000-0002-5157-2485; 2. 0000-0001-9822-8246; 3. 0000-0003-1028-2729; 4. 0000-0001-7493-172X; 5. 0000-0003-3433-9742; 6. 0000-0002-9869-288X;


Abstract. Presently, the energy sector is more important for everyone according to consumption, production, distribution, and monitoring. So this study mainly focuses on the improvement of the power factor through fully automated. This paper introduces a system, which is based on the Internet of Things (IoT). This system works fully automated with improvements in power factor and also monitors the consumption of energy, which will accurately calculate all the parametrical data to display such as power, current, power factor consumption etc. The parametrical data can be accessed and obtained from the wireless technology Through the IoT Blink platform with a Web server. The parametrical data measurement and monitoring through the Controller unit, which is calculated and transmitted to the bank of capacitors through the relays compensates for the lagging power factor in this system. In the end the show the result of the correction in power factor, can be more efficient monitored the power losses and consumption in energy.

Streszczenie. Obecnie sektor energetyczny jest ważniejszy dla wszystkich ze względu na zużycie, produkcję, dystrybucję i monitorowanie. Dlatego też niniejsze badanie koncentruje się głównie na poprawie współczynnika mocy poprzez pełną automatyzację. W artykule przedstawiono system oparty na Internecie Rzeczy (IoT). System ten działa w pełni automatycznie, poprawiając współczynnik mocy, a także monitoruje zużycie energii, co dokładnie oblicza wszystkie dane parametryczne do wyświetlenia, takie jak moc, prąd, zużycie współczynnika mocy itp. Dostęp do danych parametrycznych i ich uzyskanie można uzyskać za pośrednictwem bezprzewodowego technologia Poprzez platformę IoT Blink z serwerem WWW. Pomiar i monitorowanie danych parametrycznych za pośrednictwem jednostki sterującej, które są obliczane i przesyłane do zespołu kondensatorów za pośrednictwem przekaźników, kompensują opóźniony współczynnik mocy w tym systemie. Na koniec pokaż wynik korekty współczynnika mocy, dzięki czemu możliwe będzie bardziej efektywne monitorowanie strat mocy i zużycia energii. (Automatyczna korekcja współczynnika mocy za pomocą mikrokontrolera w sektorze energetycznym)

Keywords: energy, power factor, internet of things, controller, capacitor bank.
Słowa kluczowe: energia, współczynnik mocy, Internet rzeczy, kontroler, bateria kondensatorów.

Introduction

Nowadays, the energy sector is based on consumption, production, distribution, and monitoring, which relates to the direct or indirect power factor. The power factor gives an important analysis of the electric supply system, which is more important as per all views of the energy sector [1]. And also identifies all types of losses in the utilization of the supply power such as power factor and losses are inversely proportional if the power factor is low then losses continually increase and power factor is high then losses continually improve. So the modern industry fully focuses on this factor and improves power factor use of different types the techniques and uses that relate the reactive power. The power consumption may be defined through the power factor, which is close to unity, and maintaining the help of shunt capacitor banks for Power Factor Correction (PFC) is an exceptionally established methodology [2].

Recently research in the energy sector mainly focused on automatic switching methodology, which is more important in real-time applications. Such as using the MCU embedded-based system [3], IoT embedded provides all types of correction monitoring and also controls all types of switching and monitoring [4]. This type of concept is used in modern industry and gets much more control as per the power factor, to provide the overall improvement in efficiency in the electrical system. The low power factor creates lots of losses and those losses reduce the shorter life of the equipment in the energy sector [5]. Therefore always maintain the power factor value between 0 and 1. The near value of power factor 0.95 is good for any electric system. So the above improvement in power factor is much more important in the electric system as per the electric standard [2-9].

Literature Review

The energy sector today revolves around the consumption, production, distribution, and monitoring of energy, all of which relate to the power factor. A key focus in the energy industry is on automatic switching methods to control the power factor, as this is crucial for real-time applications and others. Past research on improving the power factor in the advancing energy sector has been limited, with only a few studies on power factor correction, as summarized below.

In a 2017 paper, Machado et al. proposed a novel single-phase power factor correction (PFC) method using a parallel configuration, claiming it to be more efficient than the traditional two-stage cascade approach [10]. Earlier, Oommen and Kohler (1988) explored the advantages of proper power factor compensation, examining various compensator types, their optimal sizing, and placement strategies [11]. They also provided a brief economic analysis to highlight the cost-effectiveness of implementing such compensation techniques.

Choudhury (2008) designed a cost-effective power factor improvement device for small signal loads by modeling the load, selecting suitable capacitors, and implementing switching circuits to choose appropriate capacitor combinations [12]. Shohel et al. (2013) proposed a dynamic method for power factor correction and voltage regulation in light rail systems. This approach uses thyristors controlled by automatic power controllers to switch main reactors based on real-time power factor calculations derived from continuous current and voltage monitoring. The system improves the power factor by connecting inductive loads (reactors) in parallel with a capacitive system [7].

Shahid et al. (2013) proposed a cost-effective power factor correction circuit using a PIC microcontroller. This design prioritizes minimal components while maintaining efficiency. It utilizes an algorithm to analyze power factor and activate specific capacitors, ultimately compensating for reactive power and improving the overall power factor [15]. Mather et al. (2011) focused on this specific application. Through simulation and analysis, they proposed a modified boost converter with active control and a PI controller to ensure stable operation. Additionally, they designed a capacitor and inductor combination to address voltage and current ripple, input current distortion, and output voltage regulation [16, 17].

Power Factor and Correction

Power factor (PF) in an AC electrical power system measures the efficiency of power transmission. It’s the ratio of real power (the power actively doing work) to apparent power (the total power flowing in the circuit) [14]. Due to energy stored in the load or distortions in the current waveform, real power can be less than apparent power, resulting in a less efficient system [18]. The power factor is low due to the significant phase difference between the voltage and current at the load (May be distorted waveform/disrupted waveform sample or harmonic distortion contents) and this result directly reflated the result of the inductive loads, which relates to the motor, transformer, etc. So, we can say that the power factor has a poor nature affected due to inductive load and improves through the correction methodology, to improve all the parametrical data like distorted waveform, and harmonic distortion filters to gain an appreciable improvement [2]. The consumption of power to maintain the power factor between 0.9 to 0.95 and also beneficial to the all-electric system in all views of the energy sector [19-26].

The reason for the low power factor is due to the used equipment operated by the chokes (vapor lamps), in the transformer and induction motor. The transformer as per the distribution case has used a much more active nature and in this case, the power factor must be low [5]. On the other hand condition of the load (With load and without load) is due to the use of inductive loads such as pumps, converges, shovels, etc. Many methods and techniques are used for the improvement in power factor in the energy sector, which is implemented according to load conditions such as through automatic, fixed, and mixed (Automotive with fixed), which is under the Central unit based correction. In the other ways like individual power factor correction and group power factor correction. Both methods are much more important as compared to the central power factor correction because they relats on cost and maintenance in the energy sector [6].

The above methodologies have some benefits for correction in power factor and continuously improving using many ways such as to encourage efficiency surcharge of power factor, decreasing in demand charges, carrying capabilities are increased in used circulatory, advancement in regulation in voltage, reduce in losses of power system. The capacitor effect directly reduces the losses as per the current and those losses are directly proportional to the current squared. So we say that the reduction in current is directly proportional to improvement in the power factor and the losses are inversely proportional to the square of the power factor [7]. Which is a relatively small one-third of 1 percent of the KVAr rating.

Design Methodology

The proposed electric system is fully automated through the IoT-embedded technology. This system calculates the voltage and current from the sample obtained from the system after that to define the phase angle with the help of the input concerning the difference of the arrival waveforms. The assessment of difference with the help of an internal timer and phase angle, calculates the simple power factor.

Fig.1. The Proposed system

The system compared its power factor against a target level. This difference is used to automatically turn on or off the needed number of capacitors from the bank. The current power factor and phase lag are displayed for easy monitoring. As per the algorithm step wise, from the input, take the value of the current and voltage in the electric circuit. After that to calculate the phase lagging, power factor, and reactive power requirements. From the obtained parametrical data to create the differentiation between reactive power requirement and power factor. After Differentiate to define the Switching system (ON/OFF), which is connected to the capacitor bank depending on reactive power supplied by each step. In the Final step, compare the targeted value of the power factor with the simple power factor, afterward, correct the power factor and move on to the initial step.

Fig.2. Flowchart of the algorithm
Design & Implementation

This part outlines the in-depth design of each module of the suggested power factor correction device as well as the functioning of each component. Every module comprises numerous parts linked in the necessary manner to produce the intended result. The full schematic diagram is given at the conclusion based on which the construction was finished. Particular attention was paid during the assembly to prevent any short circuit of tracks during intersection of paths. The PZEM-004T Current Transformer is also the PZEM-004T 100 Ampere which utilizes the Current Transformer split core model. Since it uses a split core, it naturally has benefits in its simplicity of use as it can be directly set up on an already installed power network cable without having to remove the power cable. In the power supply utilizing 3 phase induction motor, 440-volt supply is provided to the load by an auto transformer and the microcontroller Arduino UNO needs 5v DC supply which is given by an adapter.

The PZEM-004T is an electronic module that functions to measure, like power, Current, Voltage, Frequency, Energy and Power Factors. With the fullness of these proficiencies, the PZEM-004T module is ideal for use in this experiment for measuring power on an electrical system. The MCU unit used the Arduino UNO, It is a microcontroller board founded on the ATmega328P. It possesses 14 digital input/output pins (of which 6 can be utilized as PWM outputs), 6 analog inputs, a 16 MHz ceramic resonator, a USB connection, a power jack, an ICSP header and a reset button. In an IoT Based embedded system, the microcontroller engages with the exterior world employing input and output devices that connect straight with a human being [16]. One of the most prevalent devices attached to the microcontroller is an LCD display.

Three control lines and four or eight I/O lines are required for the data bus connection to the microcontroller. A relay is a switch that operates electrically. Relays are used when several circuits need to be governed by a single signal or when it is necessary to regulate a circuit with a low-power signal (with complete electrical segregation between control and regulated circuits). Relay driver ULN2003 is utilised since the microcontroller’s output pin cannot supply enough current for the relay coil to activate the relay. An array of Darlington transistors with high voltage and high current is called ULN2003.

Large air conditioners and other strong three-phase equipment are controlled by a specialized switch called a three-phase contactor. Regular switches are unable to withstand the enormous power (480 volts or more) demanded by these devices, hence they are necessary. A shunt capacitor bank is an additional device that enhances the efficiency and flow of power. It functions similarly to a tiny battery that may be turned on or off based on the requirement for electricity. As a result, less energy is lost and the voltage level is kept constant. They are simple to put anyplace in the system and are reasonably priced. Lastly, a frequent electric motor type found in a variety of applications is the three-phase squirrel cage motor. The “cage” of wires within the motor, which resembles a squirrel cage, is where the term comes from.

Fig.3. Circuitry based architecture of the system

The load is three phase induction motor thus to improve the power factor APFC is developed. There is different type of components are used such as PZEM-004TV30, Arduino Uno, relay, 3 pole contactors, 50 micro farad capacitors, x/1 current transformer ,16*2 LCD display. 440 v supply is given to the motor and PZEM is directly connected to the phase to measure the current and voltage, PZEM calculated the angle between voltage and current waveform to determine power factor. A microcontroller is used to give the command by programming so that capacitor is being connected to the load when there is a condition of low power factor. Microcontroller is connected to the relay that operates the contactor to add the capacitor in the circuit it is also connected to the display which shows the different parameters such as voltage, current, angle power factor, frequency, active power, reactive power, apparent power.

Results & Discussions

The validation of the proposed system is verified after it is used and the expected result is achieved. The correction in power factor using this system and verifying the desired correction with the working for suitability. Finally to achieve a suitable parametrical analysis for all monitoring desired outcomes for the electric system and load. From the Proposed system, the parametrical analysis is according to load conditions (With and without load) as shown in Table 1.

The parametrical analysis consists of different parameters measured values like current, voltage, power factor, phase angle, etc. by the load, power consumed, and power factor are essential to be measured for each case. That analysis is important of necessary to monitor for the consequent energy savings.

Table 1. Parametrical Analysis of the System

.
Conclusion

This study investigated the effectiveness of power factor correction equipment employing a microcontroller and capacitor banks. The equipment was designed for measurement and monitoring of a demonstrated electrical load, and the results demonstrated significant improvement in power factor. Under full load conditions, the device successfully enhanced the power factor from 0.80 to 0.99. Similarly, during no-load conditions, the power factor increased from 0.22 to 0.82. This design holds promise for real-world application with safety standards according to the energy sector. However, frequent load fluctuations in automatic power factor correction systems can lead to harmonic issues due to repeated capacitor bank switching. This research outcomes can be directed towards designing suitable filters and optimizing algorithms based on specific load change patterns, thereby minimizing preventable capacitor switching.

Acknowledgment: This research received no external funding.

REFERENCES

[1]. Yasin K., Yusuf M. M., and Mohammad M. K. (2017). Automated Power Factor Correction and Energy Monitoring System. Department of Electrical and Computer Engineering, North South University Bashundhara R/A, Dhaka1229, Bangladesh, 6pp
[2]. Yadav, A. R., Waghmode, S.S., Gawade, G. B., Zinjade, S. S. and Patil, P. T. (2016): A review on Microcontroller Based Automatic Power Factor Correction. International Journal of Advanced Research in Electrical, Electronics and Instrumentation Engineering, 5 (3): 1517-1520.
[3]. Kumar, R., Ratnesh, R. K., Singh, J., Chandra, R., Singh, G., & Vishnoi, V. Recent Prospects of Medical Imaging and Sensing Technologies Based on Electrical Impedance Data Acquisition System. In Journal of The Electrochemical Society, Vol. 170, Issue 11, p. 117507, 2023
[4]. Kumar, Ramesh, Ratneshwar Kumar Ratnesh, Jay Singh, Ashok Kumar and Ramesh Chandra, IoT-Driven Experimental Framework for Advancing Electrical Impedance Tomography, ECS Journal of Solid State Science and Technology, Volume 13, Number 2, 13 027002, 7 February 2024
[5]. Tiwari K., Sharma D., and Sharma V. (2014), Automatic Power Factor Correction Using Capacitor Bank, International Journal of Engineering Research and Applications, 4 (2): 393-395.
[6]. Taye, A. (2018). Design and Simulation of Automatic Power Factor Correction for Industry Application. International Journal of Engineering Technologies and Management Research, 5 (2): 10-21.
[7]. Shohel, M. R., Miah, M. N., and Rahman H. (2013). Automatic Power Factor Improvement by using Microcontroller. Global Journal of Researches in Engineering Electrical and Electronics Engineering, 13(6): 29-34.
[8]. M. Sharma et al., “Miniaturized Quad-Port Conformal Multi-Band (QPC-MB) MIMO Antenna for On-Body Wireless Systems in Microwave-Millimeter Bands,” in IEEE Access, vol.11, pp. 105982-105999, 2023, doi:10.1109/ACCESS.2023.3318313.
[9]. Gupta, Anupma, Vipan Kumar, Shonak Bansal, Mohammed H. Alsharif, Abu Jahid, and Ho-Shin Cho. “A Miniaturized Tri-Band Implantable Antenna for ISM/WMTS/Lower UWB/Wi-Fi Frequencies.” Sensors 23, no.15 (2023): 6989.
[10]. Machado, P.P. Jr., and Abud T. P. (2017). Power Factor Metering System Using Arduino. Fluminense Federal University, Electric and Telecommunications Engineering Master Program – PPGEET Niterói, Rio de Janeiro, Brazil. 6pp.
[11]. M. Oommen and J. L. Kohler, “Power factor and power factor control alternatives for mines,” Conference Record of the 1988 IEEE Industry Applications Society Annual Meeting, Pittsburgh, PA, USA, 1988, pp. 1209-1215 vol.2, doi: 10.1109/IAS.1988.25213.
[12]. Choudhury, S.M. “Design and Implementation of a low cost power factor improvement device”, IEEE Region 10 Conference, 2008.
[13]. Gupta, A., Yadav, S.K., Sharma, N. et al. Optimization of Bandwidth and Reflection Coefficient with HighGain Truncated Triangular-Shaped DRA Antenna Using NSGAII Algorithm. Iran J Sci Technol Trans Electr Eng 47, 1731–1742 (2023).
[14]. Nikita Hamilpurkar , Bhagyashree , P Sharadha , Shweta , Prashant, Minimizing Penalty in Industrial Power Consumption by Engaging APFC Unit, ICONIC RESEARCH AND ENGINEERING JOURNALS, IRE Journals, Volume 6 Issue 1, 1703702 531 , 2022
[15]. Shahid and A. Shabir, “Microchip based embedded system design for achievement of high power factor in electrical power systems,” 2013 IEEE PES Asia-Pacific Power and Energy Engineering Conference (APPEEC), Hong Kong, China, 2013, pp. 1-5, doi: 10.1109/APPEEC.2013.6837130.
[16]. Kumar, R., Kumar, S., & Sengupta, A. (2022). Optimization of Bio-Impedance Techniques-Based Monitoring System for Medical & Industrial Applications. IETE Journal of Research, 68(5), 3843-3854.
[17]. Mather, B.A.; Maksimovi ć, D. A simple digital power factor correction rectifier controller, IEEE Transactions on Power Electronics, pp 9-19, 2011.
[18]. Md. Abdur Rahman, Saleh Mohammad Tahsin, Dipta Das, Raihan Chowdhury, “Power factor Controlling and Monitoring wirelessly through computer”, 2020 IEEE Region 10 Symposium (TENSYMP), pp.547-551, 2020.
[19]. Dzhuraev, S. et al., Computation of the zero-wire current under an asymmetric nonlinear load in a distribution network, Energy Reports, 8(2022), 563-573
[20]. Senyuk M., Beryozkina S., Ahyoev J., Zicmane I., Safaraliev M. Solution of the emergency control of synchronous generator modes based on the local measurements to ensure the dynamic stability, IET Generation, Transmission and Distribution, (2023), 17(1), 52-56
[21]. Bumtsend, U. et al., The unbalanced modes analyze of traction loads network, In 2020 Ural Symposium on Biomedical Engineering, Radioelectronics and Information Technology (USBEREIT) IEEE, (2020), 0456-0459
[22]. Asanov M.S. et.al.,The use of Petri computing networks for optimization of the structure of distribution networks to minimize power losses. Energy Reports, 6 (2020), 1337-1343
[23]. Asanov M.S. et al., Algorithm for calculation and selection of micro hydropower plant taking into account hydrological parameters of small watercourses mountain rivers of Central Asia, Int. J. Hydrogen Energy, 46 (2021), № 75, 37109-37119.
[24]. Asanova S.M., et. al. Optimization of the structure of autonomous distributed hybrid power complexes and energy balance management in them, International Journal of Hydrogen Energy 46.70 (2021), 34542-34549.
[25]. Ghulomzoda A. et al., Recloser-Based Decentralized Control of the Grid with Distributed Generation in the Lahsh District of the Rasht Grid in Tajikistan, Central Asia, Energies, 13 (2020), p. 3673.
[26]. Ghulomzoda A. et al., A Novel Approach of Synchronization of Microgrid with a Power System of Limited Capacity. Sustainability, 13(2021), p. 13975.


Authors: PhD Pawan Kumar Pandey, Department Electrical Engineering, Gyan Ganga Institute of Technology and Sciences Jabalpur, Jabalpur, Madhya Pradesh 482003 India. E-mail: pkpnitj@gmail.com;

PhD Ramesh Kumar, Department of interdisciplinary courses in Engineering, Chitkara University Institute of Engineering and Technology, Chitkara University, Punjab, India 140401, rameshkumar.meena@chitkara.edu.in.;

PhD Manish Singla, Department of interdisciplinary courses in Engineering, Chitkara University Institute of Engineering and Technology, Chitkara University, Punjab, India 140401, Applied Science Research Center, Applied Science Private University, Amman 11931, Jordan. manish.singla@chitkara.edu.in.;

D.Sc Sergey Evgenevich Kokin, Department of Automated Electrical Systems, Ural Federal University, 19, Mira Street, Yekaterinburg, 620002, Russian Federation, e-mail: s.e.kokin@urfu.ru;

PhD Murodbek Kholnazarovich Safaraliev , Department of Automated Electrical Systems, Ural Federal University, 19, Mira Street, Yekaterinburg, 620002, Russian Federation, e-mail: murodbek_03@mail.ru;

PhD Ahyoev Javod Salamshoevich, Department of Electric stations, academicians Rajabov’s avenue 10, 734042, Dushanbe, Republic of Tajikistan, e-mail: javod@ttu.tj;

Conflict of Interest: The authors declare no conflict of interest


Source & Publisher Item Identifier: PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 100 NR 10/2024. doi:10.15199/48.2024.10.12

PV Fed Boost Converter Efficiency Improvement using Neural Networks and Model Predictive Control

Published by 1. Kheira MELOUK1, 2. Mohamed DELLA KRACHAI1, 3. Saidia DELLA KRACHAI2, Faculty of Electrical Engineering, Department of Automatics, University of Science and Technology of Oran. U.S.T.O.M.B (1), Spatial Development Center, Algeria (2)
ORCID: 1. 0000-0002-9300-649X; 2. 0000-0002-0899-8923; 3. 0000-0002-0710-1037


Abstract. This paper presents a model predictive control (MPC) technique applied to a DC-DC boost converter powered by a photovoltaic ( PV ) generator. The control objective is to ensure the maximum power point tracking (MPPT) using neural networks and achieve a stable output voltage under varying environmental conditions. Photovoltaic systems are highly dependent on solar irradiance and temperature, which affect their output characteristics. The proposed method leverages predictive control algorithms to anticipate system behaviour and adjust the converter’s duty cycle in real-time, thereby improving the system’s overall efficiency and response time compared to conventional control methods. Simulation results validate the effectiveness of the proposed control scheme in terms of response time, voltage regulation, and robustness against environmental changes.

Streszczenie. W artykule przedstawiono technikę modelowego sterowania predykcyjnego (MPC) zastosowaną w przetwornicy podwyższającej˙ napięcie DC-DC zasilanej z generatora fotowoltaicznego (PV). Celem sterowania jest zapewnienie śledzenia punktu maksymalnej mocy (MPPT) przy użyciu sieci neuronowych i osiągnięcie stabilnego napięcia wyjściowego w zmiennych warunkach środowiskowych. Systemy fotowoltaiczne są w dużym˙ stopniu zależne˙ od natężenia promieniowania słonecznego i temperatury, które wpływają na ich charakterystykę wyjściową. Proponowana metoda wykorzystuje algorytmy sterowania predykcyjnego do przewidywania zachowania systemu i dostosowywania cyklu pracy przekształtnika w czasie rzeczywistym, poprawiając w ten sposób ogólną wydajność systemu i czas reakcji w porównaniu z konwencjonalnymi metodami sterowania. Wyniki symulacji potwierdzają skuteczność proponowanego schematu sterowania pod względem czasu reakcji, regulacji napięcia i odporności na zmiany środowiskowe. (Poprawa wydajności konwertera podwyższającego zasilanego energią fotowoltaiczną przy użyciu sieci neuronowych i sterowania predykcyjnego modelem)

Keywords: Model predictive control, DC / DC boost converter, maximal power point tracking, artificial neural networks.
Słowa kluczowe: Modelowe sterowanie predykcyjne, konwerter podwyższający DC/DC, śledzenie punktu mocy maksymalnej, sztuczne sieci neuronowe.

Introduction

Photovoltaic (PV) energy has become a crucial element of modern renewable energy systems [1][2]. The intermittent nature of solar energy presents challenges in efficiently converting and controlling the power output of PV generators [1][2]. To extract maximum power from a PV array, it is essential to employ efficient control techniques that adapt to changing environmental conditions, such as irradiance and temperature. One widely used topology is the boost converter, which steps up the variable DC output from the PV generator to a higher, more usable level for energy storage or grid connection. Several MPPT algorithms have been proposed in literature, with P&O and IC being the most commonly implemented [1][2][3][4]. These methods, though simple and reliable, often fail to achieve satisfactory performance in rapidly changing environments. They suffer from oscillations around the MPP and slow dynamic response. Therefore, the efficiency of PV systems is critically determined by their ability to continuously operate at their maximum power point (MPP). The present paper explores the use of neural networks (NNs) for tracking the MPP [1][2]. Model Predictive Control (MPC) has emerged as an advanced technique that can handle system non-linearity and constraints more effectively [58]. MPC uses a dynamic model of the system to predict future behavior and adjusts the control input accordingly [8]. In this paper, we focus on implementing MPC for a boost converter powered by a PV system and demonstrate its superior performance over conventional approaches.

System modelling

Figure 1 depicts the overall block diagram of the system. The system is composed of a photovoltaic module as a power source. A voltage step-up converter is connected to this generator in order to raise the input voltage to supply the load. The measurement of the system currents/voltages is carried out in order to control the duty cycle of the converter by the MPC technique, while ensuring transfer of the maximum power of the photovoltaic module by the use of neural networks.

Table 1. PV module parameters

.
Photovoltaic generator

Electricity is generated by a photovoltaic (PV) panel that converts sunlight into electrical energy [1-3]. Table 1 provides the key parameters of the PV module used in this study. The current generated by a photovoltaic panel can be represented by this equation, which is based on the single-diode model of a solar cell [1]:

.

Where:

• IPV -Total current produced by the PV panel.

• NS– Number of cells connected in series in a module (increases the voltage).

• NP – Number of cells connected in parallel in a module (increases the current).

• Iph– Photocurrent (current produced by sunlight).

Fig.1. System model under study

• Ish– is the current through the shunt resistor (Rsh).

• IS– Saturation current (current in the diode when reverse biased).

• VPV – Voltage across the PV panel.

• Rs– Series resistance.

• A– Diode ideality factor (a measure of how ideal the diode behaves).

• Vt– Thermal voltage (a function of temperature).

As illustrated in Figure 2, the generated current and voltage demonstrate a non-linear relationship, with the I-V curve. being divided into three distinct operating regions. On the left side of the curve, the PV module behaves as a constant current source, while on the right side, it operates in a constant voltage mode. Between these two operating modes lies the point of maximum power output, which corresponds to the highest efficiency.

Figure 2. left illustrates the effect of irradiance on the I-V and P-V characteristics. An increase in irradiance results in higher current and output power increases as well. As temperature increases, as shown in Figure 2.right, the current shows a small increase, but the voltage drops significantly indicating that higher temperatures negatively affect the overall performance of the PV panel.

Maximal power point tracking

Neural networks are well-suited for dynamic environments where they can learn to map nonlinear relationships between inputs (e.g., irradiance and temperature) and the desired output (voltage, current or power). The neural network used for MPPT (figure 3) is a feedforward architecture with one hidden layer, optimized for real-time tracking of the maximal power [1-2]. Feed Forward neural network type is in this paper. It is designed as an interconnected layers. Each layer consists of a set of neurons. Increasing the number of layers and neurons in hidden layers leads to the best representation of non-linearities of the system, however, it exhibits complex computations, and therefore, hardware implementation constraints. The input layer consists of two neurons representing the irradiance one hidden layer with five (5) neurons which gives a satisfactory prediction.

Fig.2. Irradiance and Temperature impact on PV module characteristics

The neural network is trained offline using data generated from the PV module under various irradiance and temperature conditions. Once trained, the neural network is deployed for real-time simulation, where it dynamically adjusts the duty cycle to maximize the output power. Supervised learning is employed to train the neural network. The training is performed using Levenberg-Marquardt algorithm, which minimizes the mean square error (MSE) between the predicted and actual MPP current. The training process is carried out using Levenberg Marquardt Algorithm. The database was partitioned as follows:

  • Training data: 70% of dataset
  • Validation data: 15% of dataset
  • Testing data: 15% of dataset
Fig.3. Neural network architecture

Fig.4. Regression plot at the end of the network training

Fig.5. Mean squared error issued from training process

Network outputs (predicted values) are equal to the target values provided in the training, validation and testing phases. The performed fit exhibits a good approximation for all of the data sets. To provide a measure of how well the predictions of the model are compared to actual outcomes, correlation coefficient R is used as a tool. The regression plot in figure 4 displays the network predictions (output) with respect to responses (target) for the training, validation, and test sets. The tracking operation gives a satisfactory result for training, testing, and validation sets, and the R-value is 1.0 equal to the previously smallest validation error for six consecutive validation iterations. A plot of the training errors, validation errors, and test errors are shown in figure 5. It is observed that the final mean-square error is small, the test set and the validation set errors have similar behaviors, which concludes that no overfitting has occurred. To further investigate the distribution of errors in the model, figure 6 gives a plot of the error histogram. The error histogram plot looks fairly symmetric and the peak of the distribution lies exactly in the middle of the error’s interval indicating the absence of any bias.

Model predictive control

Predictive control involves using the system model to anticipate its future behavior while minimizing the cost function [8-10]. This approach requires solving a finite dimensional optimization problem at each sampling interval (figure 7) [4][8]. For the boost converter, MPC continuously predicts behaviors, which concludes that no overfitting has occurred. To further investigate the distribution of errors in the model, figure 6 gives a plot of the error histogram. The error histogram plot looks fairly symmetric and the peak of the distribution lies exactly in the middle of the error’s interval indicating the absence of any bias. for the total data set and shows a very satisfactory accuracy. Training finished when the validation error was larger than or the output voltage and current over this horizon and determines the optimal duty cycle D that minimizes a cost function subject to system constraints [6][8-12]. The predictive model of the boost converter is derived from its state-space representation. The state variables are the inductor current iL and the output voltage vC (or vload, as the output capacitor is parallel to the load), governed by the following equations [6-12]:

.

where L is the inductance and C is the capacitance of the boost converter. These equations are discretized for implementation in the MPC framework, and the future values of iL are predicted based on inductance current measurements and control inputs.

Fig.6. Error histogram resultant from training process

Fig.7. Model Predictive Control workflow

Taking into account the predictive control horizon over n samples, the prediction equations for the current iL and the voltage vC are provided as follows [6-8]:

.

And the two-step prediction horizon is:

/

The typical cost function is defined as:

.

where:

  • iLref : is the reference current (desired output),
  • iL(k) : is the predicted inductance current at future step k,
  • D(k): is the duty cycle,
  • λ : is a weighting factor, and
  • ∆D(k): is the change in duty cycle.

By minimizing J, the MPC algorithm ensures that the output voltage follows the reference as closely as possible, while avoiding large variations in the duty cycle, which could result in instability or excessive switching losses.

Simulation and Results

To validate the effectiveness of the proposed predictive control method, simulations were performed using MATLAB/Simulink. The parameters of the PV system and the boost converter were selected based on typical commercial photovoltaic module and converter components. Figure 8 shows the performance of the proposed control strategy under variable irradiance and temperature conditions. The MPC controller successfully tracked the maximum power point and maintained stable output voltage, demonstrating its robustness and fast response to irradiance and temperature changes.

Fig.8. System response to variation of irradiance and temperature

First, PV module is exposed to an irradiance of 500W/m2 and a temperature of 25◦C. The neural network estimates with high precision the maximal output current. Second, a change at 3s and 6s of irradiance and temperature respectively is injected to test the dynamic response of the system. It is observed that the tracking of maximal power is performed with a high accuracy.

The proposed MPC controller provided superior performance in terms of transient response, steady-state accuracy, and handling of non-linearities.

Figure 9 shows the voltage boosted (load voltage) from PV voltage. The combination of neural network and MPC controller was able to converge to the MPP much faster, while, maintaining the load voltage to the desired values with less oscillations.

In figure 10, MPC controller was also able to drive the inductor current to its reference value, ensuring thus good dynamic response of the system.

Fig.9. PV voltage and Load voltage for the corresponding conditions

Fig.10. Inductance reference and actual currents

Conclusion

This paper has demonstrated the feasibility and effectiveness of using neural networks for MPPT and MPC control in PV systems coupled with a boost converter. The integration of neural networks into MPPT allows for real-time learning and adaptability to changing environmental conditions, thus offering improved tracking speed and accuracy.

By leveraging the learning capabilities of neural networks, the controller is able to adapt quickly to changing environmental conditions. This results in faster convergence to the MPP, reduced power oscillations, and improved overall efficiency. On the other hand, MPC exhibited superior performance in terms of response time, accuracy, and robustness. Future work will focus on the implementation of MPC in hardware and investigating its performance in real-world scenarios.

REFERENCES

[1] Della Krachai. M, Melouk. k, Keddar. M: Investigating sineband hysteresis control of photovoltaic-grid connected inverter, International Journal of Power Electronics and Drive System (IJPEDS), 11(2), pp. 969 976, 2020.
[2] Della Krachai. S, Boudghene Stambouli. A, Della Krachai. M, Bekhti: Experimental investigation of artificial intelligence applied in MPPT techniques, International Journal of Power Electronics and Drive System (IJPEDS), 10(4), pp. 2138 2147 , 2019.
[3] KACIMI, Nora et al.: New improved hybrid MPPT based on neural network-model predictive control-kalman filter for photovoltaic system, Indonesian Journal of Electrical Engineering and Computer Science, 20(3), pp. 1230 1241, 2020.
[4] Ma, C., Li, N., Li, S.: Maximum Power Point Tracking for Photovoltaic System Using Model Predictive Control, Intelligent Computing for Sustainable Energy and Environment ICSEE (2013), pp. 515 525, 2013.
[5] Zhao, Y., An, A., Xu, Y. et al.: Model predictive control of gridconnected PV power generation system considering optimal MPPT control of PV modules, Prot Control Mod Power Syst, 6(32), pp. 2 12, 2021.
[6] M. B. Shadmand, X. Li, R. S. Balog and H. A. Rub: Model predictive control of grid-tied photovoltaic systems: Maximum power point tracking and decoupled power control, First Workshop on Smart Grid and Renewable Energy (SGRE), pp. 1 6 , 2015.
[7] Ahmed, M.; Harbi, I.; Kennel, R.; Rodríguez, J.; Abdelrahem, M.: Maximum Power Point Tracking-Based Model Predictive Control for Photovoltaic Systems: Investigation and New Perspective, Sensors, vol. 22, pp. 1 18, 2022.
[8] M. Metry, S. Bayhan, R. S. Balog and H. A. Rub: Model predictive control for PV maximum power point tracking of singlephase submultilevel inverter, IEEE Power and Energy Conference at Illinois (PECI), pp. 1 8, 2016.
[9] Irmak, E and Güler. N: A model predictive control based hybrid MPPT method for boost converters, International Journal of Electronics, vol. 107, no. 1, pp. 1 16, 2020.
[10] Ravi K. M., Jyoti P. M., Ashish A. D.: MPC-based DC microgrid integrated series active power filter for voltage quality improvement in distribution system, International Journal of Circuit Theory and Applications, vol. 51, no. 3, pp. 1349 1371 , 2022.
[11] Marahatta. A, Rajbhandari. Y,Shrestha. A, Phuyal. S, Thapa. A, Korba. P.: Diagnostic Model predictive control of DC/DC boost converter with reinforcement learning, Heliyon, vol. 83 , pp. 1 13, 2022.
[12] Sowparnika. G.C, Sivalingam. A, Thirumarimurugan. T: Modeling and Control of Renewable Source Boost Converter using Model Predictive Controller, International Journal of Computer Application, vol. 5, no. 7, pp. 2250 1797, 2015.


Authors: Dr. Melouk Kheira, Dr. Della Krachai Mohamed, Faculty Electrical Engineering, Department of Automatics, University of Science and Technology of Oran. U.S.T.O.M.B, PO. Box 1505 El Menaouer USTO, Oran, Algeria, email: kheira.melouk@univ-usto.dz, mohamed.dellakrachai@univ-usto.dz, Dr. Della Krachai Saidia, Spatial Development Center, Algeria email:saidia.dellakrachai@univ-usto.dz


Source & Publisher Item Identifier: PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 101 NR 2/2025. doi:10.15199/48.2025.02.41

Blockchain Technology and Peer-to-Peer Energy Trading

Published by Anna ZIELIŃSKA, AGH University of Science and Technology, Faculty of Management


Abstract: The article describes new legal regulations in Poland and the EU, which are to introduce the possibility of peer-to-peer trading in electricity. The text presents the possibility of using blockchain technology for this purpose. It describes how blockchain can revolutionize the traditional energy model, enabling direct trade between producers and consumers, eliminating intermediaries. It presents the advantages and challenges in this area, explains the key features of the technology, and discusses its potential applications in the energy sector, focusing on peer-to-peer trading (P2P) of energy from renewable sources.

Streszczenie: Artykuł opisuje nowe regulacje prawne w Polsce i UE, które wprowadzają handlu partnerskiego energią elektryczną. Tekst przedstawia możliwość wykorzystania do tego celu technologii blockchain. Opisuje, jak blockchain może zrewolucjonizować tradycyjny model energetyczny, umożliwiając bezpośredni handel między producentami a konsumentami, eliminując pośredników. Prezentuje zalety i wyzwania, wyjaśnia kluczowe cechy technologii, oraz omawia jej potencjalne zastosowania w energetyce, skupiając się na handlu peer-to-peer (P2P) energią z odnawialnych źródeł. (Technologia blockchain i handel partnerski energią elektryczną)

Keywords: electricity trading, blockchain technology, peer-to-peer trading, electricity
Słowa kluczowe: handel energią elektryczną, technologia blockchain, handel partnerski, peer-to-peer handel, energia elektryczna

Introduction

Energy trading in decentralized electricity markets is a revolution in the way electricity can be bought and sold. By using blockchain technology, traditional models of central management and intermediation are being replaced by distributed networks that can enable direct trading between energy producers and consumers.

In the traditional energy model, energy is produced by large producers, transmitted through the distribution network to consumers and settled by central institutions such as electricity suppliers. The development of blockchain technology can enable the creation of decentralized energy markets that enable direct trade of energy between producers and consumers, without the intermediation of traditional institutions. In decentralized energy markets, energy producers, such as owners of home photovoltaic panel installations or small wind farms, can offer excess energy for sale to other market participants. For the consumers, this gives them the opportunity to buy energy directly from local producers, which often translates into lower costs and can increase flexibility in choosing energy sources [1,2,3].

The procedure cited above, in great simplification, describes the amendment to the Act of 28 July 2023 amending the Energy Law Act [4] and certain other acts (Journal of Laws of 2023, item 1681). The amending Act implemented a number of European energy law acts into the Polish legal order, in particular Directive (EU) 2019/944 of the European Parliament and of the Council of 5 June 2019 on common rules for the internal market in electricity [5] and Directive (EU) 2018/2001 of the European Parliament and of the Council of 11 December 2018 on the promotion of the use of energy from renewable sources, the so-called “RED II Directive” [6], and amending Directive 2012/27/EU, the socalled market directive. Among the most important changes introduced on the basis of the above-mentioned amendment to the Act, the following should be mentioned:

• creation of a civic energy community,

• possibility of peer-to-peer trading in energy from renewable energy sources,

• obligation to conclude only comprehensive contracts with recipients of gas fuels or electricity in households;

• increasing the availability of direct line institutions for recipients;

• creation of an electronic comparison tool for offers from electricity sellers for recipients;

• changes in the functioning of the Central Energy Market Information System (CSIRE);

• extension of the competences of the President of the Energy Regulatory Office, and others [1].

As you can see, there are many changes, all of which are dictated by European law. One of them, in which, due to the possibility of using blockchain technology, great hopes are placed, is the aforementioned partner trade, which can introduce completely new possibilities and a new order to the energy sector.

Key Features of Blockchain Technology in the Energy Sector

Blockchain is a decentralized and distributed data recording technology that enables the creation of an immutable and transparent blockchain, where each transaction or piece of information is cryptographically secured and linked to the previous ones. This makes the data tamper-proof and fraud-proof, and the network functions without the need for a central governing body, as participants jointly verify and confirm records.

Key features of blockchain include:

• Decentralized structure – the possibility of no central control unit.

• Peer-to-peer (P2P) transactions – direct exchange of resources or information between network participants, the so-called “each with each other” concept.

• Cryptographic security – data is protected against unauthorized changes.

• Immutability – once added, information is practically impossible to remove or modify.

• Transparency – each network participant has access to the full transaction history [7].

Blockchain technology is used in many areas, such as finance (cryptocurrencies), energy, logistics, supply chain management and electronic voting. In the light of the currently applicable directives and the above-mentioned amendment to the act, these features perfectly fit into the assumptions of the changes, providing the possibility of creating decentralized databases and carrying out transactions between prosumers and electricity consumers [8].

In addition to its basic features, blockchain technology has several additional key aspects that have a significant impact on its operation and applications in the energy sector. These include the lack of trusted intermediaries. Blockchain can function without the need for intermediaries (e.g. banks, government institutions, sales agents) in processes such as financial transactions, data transfer or trade agreements. This allows transactions to be made directly between parties (peer-to-peer), which reduces the costs and risks associated with trusting a third party. An important element is the use of consensus mechanisms, which are based on an algorithm that allows network participants to agree on the state of the ledger without the need for central supervision. Another feature is the aforementioned transparency, to which the auditability feature can be added. Each P2P transaction recorded in the blockchain is visible to all network participants, which increases transparency. This makes this technology ideal for applications where it is crucial to track the origin of data or products, e.g. in the supply chain (tracking products from source to consumer). Although blockchain is often associated with transparency, many solutions offer mechanisms to ensure transaction privacy. There are also private blockchains that allow controlled access to data only for selected participants [9]. Another key aspect of blockchain technology that is applicable to electricity transactions is speed and automation through the use of smart contracts. Smart contracts are programs running on the blockchain that automatically execute agreements or transactions when certain conditions are met. This allows for the automation of complex processes without the need for human intervention. Examples include automatic settlements, insurance systems or even selfgoverning organizations (DAOs). Resilience to attacks and failures is also an important feature of the distributed nature of blockchain. The network is much more resistant to failures and attacks than centralized systems. Even if some nodes go down, the rest of the network remains operational and data is still available. The last feature of this technology is the possibility of multi-sector applications, in various industries and business models. Blockchain is a technology with a wide range of applications that also go far beyond finance. It covers sectors such as:

• Finance and cryptocurrencies: The most well-known applications of blockchain are cryptocurrencies such as Bitcoin or Ethereum. Blockchain enables safe, fast and cheap transfer of funds without intermediaries such as banks.

• Supply chain: Blockchain allows products to be tracked at every stage of production and distribution, which increases transparency and helps fight counterfeiting. The origin of raw materials can be traced, and the quality of products can be monitored, which is particularly important in the food, pharmaceutical or fashion industries.

• Intellectual property protection: Blockchain allows copyrights and intellectual property to be registered in an immutable way, making it easier to prove the rights to works or inventions.

• Electronic voting: Blockchain enables safe and transparent voting, which eliminates the risk of manipulation of results and increases trust in democratic systems.

• Identity management: It allows for the secure storage and management of digital identities, eliminating the need for central institutions to store personal data.

• Energy: Blockchain supports peer-to-peer energy trading, micro-energy pool management, and automated settlement based on smart contracts, as we discussed earlier [10].

The cited features and properties of blockchain technology are the answer to the question of whether this technology finds its application in the energy sector of the economy. Of course, one cannot forget about the limitations. For example, about the efficiency of the system. Blockchain requires significant computing resources and energy to maintain the network, which can be a challenge with a large scale of applications. Costs cannot be ignored either, because the implementation of blockchain systems in the energy sector is associated with high implementation and maintenance costs, which may be a barrier to the wide use of this technology.

Despite the above (and other) limitations, there are arguments in favour of using this solution, which allow for more efficient, transparent and safe management of energy flows and settlements of its purchases and sales between market participants, thus also supporting the development of decentralised renewable energy production.

Electricity trading market

Currently, the Polish electricity trading market is complex, dominated by regulations, several key entities and the dynamically developing renewable energy sources (RES) segment. That is why such great hope is seen in the use of blockchain technology in this sector of the economy. In Poland, electricity trading takes place on several levels and differs depending on the type of entities participating in the market. The market structure can be divided into two main segments, i.e. the wholesale market – a place where large producers and recipients (e.g. companies) trade energy, and the retail market – where individual consumers and small and medium-sized companies buy energy. The main entities on the energy market are producers, operators and distributors of energy. In Poland, producers are both large state-owned energy companies such as PGE, Tauron, Energa, Enea, as well as smaller private producers, including wind farm and photovoltaic installation operators. Transmission of energy is the responsibility of transmission and distribution system operators – Polskie Sieci Elektroenergetyczne (PSE). Energy distribution is handled by distribution companies, which transport energy to end users. The next market participants include energy sellers – companies offering energy to end users, both businesses and individual consumers, and end users – consumers of electricity, including households, industry, the service sector, and others.

Transactions of purchase and sale of electricity take place mainly thanks to the Polish Power Exchange (TGE), where energy is traded in the form of futures contracts and on the spot market (short-term energy trading). We have at our disposal the Day-Ahead Market, where transactions for energy delivery take place the day before the actual delivery, and the Intraday Market, where transactions for energy delivery are possible during the same day on which the energy is consumed. Energy can also be purchased on the basis of bilateral contracts, i.e. where large companies can enter into direct contracts for the supply of energy with producers under the so-called bilateral agreements (PPA – Power Purchase Agreement). The above explanation is of course brief and does not present the entire spectrum of market mechanisms. It is important to mention the fact that on the electricity market in Poland, an important role is played by the institution of URE and PSE, which are to some extent regulators of activities. The transformation towards renewable energy sources and the development of technologies such as energy storage and smart grids also operate according to their regulations, thus influencing further changes in the market structure and the way it functions [11].

Currently, the Polish Power Exchange (TGE) does not use blockchain technology on a large scale in its electricity trading operations. TGE relies on classic IT and market solutions. However, in the recent years, due to international political decisions (European Union directives), the growing interest in blockchain technology does not seem to be waning, which directly translates into its development and possible markets for its implementation.

Peer-to-peer trading in electricity

The role of blockchain technology is strengthened in relation to the provisions of the above-mentioned directives ((EU) 2019/944 of 5 June 2019, (EU) 2018/2001 of 11 December 2018), which stipulate that the Member States are obliged to ensure that prosumers have the right to produce renewable energy, including for their own needs, store and sell their surplus energy production, including through peer-to-peer trading arrangements. In relation to such a provision, and in particular to ensuring the possibility of peer-to-peer trading, the features of blockchain technology seem to correspond perfectly.

In accordance with the directives, the amendment to the Polish legal system (the Act of 10 April 1997 – Energy Law) introduced many new institutions, also expanded the competences of the President of the Energy Regulatory Office (URE), and introduced a number of regulations related to the need for the Central Information System on the Energy Market (CSIRE).

One of the significant changes in the law and thus a strong reference to the possibility of using decentralized databases is the introduction of the possibility of partner trade in energy from renewable energy sources (peer-topeer, P2P). Its definition is given in the amended art. 3 point 55c of the Act of 10 April 1997 – Energy Law (consolidated text: Journal of Laws of 2023, item 295, as amended; hereinafter: “p.e.”). Peer trading is a new formula for selling energy generated by a prosumer or collective prosumer to other system users based on an agreement specifying, in particular, the conditions for automated execution of the transaction and payment for it directly between the parties to the agreement, or through a third-party system user or a company operating a commodity exchange. As it can be interpreted, “the purpose of the draft regulations is to leave P2P trade participants the greatest possible margin of freedom in deciding whether to participate in this form of energy trading, choosing the method of organizing P2P, or finally choosing the provider of the electronic platform enabling trading. In the opinion of the drafter, such an approach will allow for gathering the necessary experience in a relatively limited local “environment” of P2P market participants, which at a later stage may result in extending the scope of P2P trading and adapting the appropriate regulatory instruments to it” [1, 2, 4].

As the authors of the amendment to the RES Act explain, the peer-to-peer concept is an element of a new model of operation of the power system, which is based on the exchange of energy between two or more users and, as a consequence, on the constant and short-term switching of recipients between different suppliers. The divergence of this concept from the previously established relations occurring in the electricity market means that it does not correspond to the current state of law and regulations in the field of energy. Considering the above, it is therefore necessary to enable the design of the necessary communication and control networks that could guarantee the possibility of P2P trading between individual entities in local micro-networks or between them, via dedicated national or regional internet platforms and appropriate technologies, the role of which will be similar to the role of the seller in the electricity sector [4]. Such an interpretation of the law absolutely composes the system to use blockchain technology and market decentralization and the use of smart contracts to execute energy purchase and sale orders. The introduction of a new energy trading model should provide prosumers with “additional opportunities, while also constituting another element of activation of the usually passive energy recipients, and also allow for the initiation of cooperation between the most important participants of the energy market, such as active recipients and aggregators1 [4]. Such an assumption is nothing more than Peer-to-Peer (P2P) Trading, i.e. P2P platforms enabling direct trade in electricity between producers and consumers, bypassing the traditional structures of suppliers and distributors. Such a possibility is far from the above-described procedures of the Energy Exchange, such a possibility is in a way allowing prosumers who are not legal entities to enter the market. P2P electricity trading can therefore be compared to purchases at online auctions available to everyone. Blockchain technology supports such initiatives by its assumptions, also enabling tracking and authorization of transactions [1]. It can therefore be expected that blockchain technology, properly promoted and implemented, will open up new possibilities of action and improve the system [12].


1 Aggregator – activity consisting in combining the volume of power or electricity offered by recipients, electricity producers or owners of electricity storage facilities, taking into account the technical capabilities of the network to which they are connected, in order to sell electricity, provide system services or flexibility services on electricity markets.


Perspectives and opportunities for peer trading

The idea of peer trading described above has the potential to enable owners of small renewable energy source (RES) installations, e.g. photovoltaic panels, to directly sell surplus energy to other network users. Thanks to the amendment and appropriate legal provisions, prosumers could more easily conclude P2P agreements, sell energy on the local market or use digital platforms that facilitate transactions. As a result, it will increase the number of prosumers and local energy producers, which also supports the development of civic energy and reduces dependence on large producers.

The possibility of peer trading and blockchain also means the possibility of dynamic energy exchange between entities in real time, which contributes to better management of demand and supply in the energy system. Introducing appropriate regulations facilitating such transactions could help stabilize the network, especially in the context of the increase in the number of RES sources, which are characterized by production variability. The effect of such actions may be to improve network stability and reduce the costs of balancing the energy system [3].

There is also great hope for change in direct transactions between energy producers and consumers, where, thanks to the use of blockchain technology, costs resulting from the elimination of intermediaries and reduction of the costs of energy transmission over long distances could be reduced. The amendment enabling the development of partner trade could also affect the diversification of prices depending on location and time, which could bring tangible benefits to consumers [13].

The amendment to the act also supports the development of digital platforms and tools enabling P2P energy trading. These platforms could use technologies such as blockchain to automate and secure transactions. The introduction of appropriate regulations would also encourage investments in this type of innovative solutions. New technologies also mean the development of new business models and the integration of modern technologies, which supports the digitalization of the sector [14].

The use of the idea and the possibility of partner trade could thus significantly affect the development of the energy sector in Poland and Europe. It would facilitate the integration of renewable energy sources, it would be possible to promote local energy production and consumption and reduce costs for consumers. P2P trade is also an opportunity to participate in the energy market for consumers and prosumers who are private persons – this fact seems very promising. However, it should not be forgotten that such activities would of course require the development of modern infrastructure, transmission networks and the creation of a new legal framework that will balance the interests of various market participants.

Summary

To sum up, the Act of 28 July 2023 amending the Energy Law and certain other acts (Journal of Laws of 2023, item 1681) implementing Directive 2019/944 into the Polish legal system introduces a number of changes and new institutions (the entry into force of which has been extended in time). The provisions found in the law encourage the possibility of using blockchain technology. The aspects that speak in favor of this are the fact that blockchain technology is known for its high transparency, security and decentralization, so it has the potential to revolutionize the way energy is sold and consumed, especially in the context of dynamically developing distributed energy and renewable energy sources (RES).

Blockchain enables direct transactions between energy producers and consumers without the participation of intermediaries, which is crucial for the development of partner trade. Thanks to smart contracts, transactions can be carried out automatically, which increases efficiency and reduces the risk of errors. This technology also enables tracking the origin of energy, which supports the development of green energy and increases consumer trust.

The paper also discusses the current energy trading model and the challenges related to blockchain implementation, i.e. the need to modernize energy infrastructure, create an appropriate legal framework and ensure data security. Despite these challenges, the use of blockchain in P2P trading has the potential to significantly impact the energy transformation by reducing transaction costs, supporting local energy production and integrating renewable energy sources in energy systems. To sum up, blockchain technology can play a key role in the future of the energy market, especially in the peer trading model, offering a new quality in energy management and enabling decentralization and democratization of the energy sector.

REFERENCES

[1]. https://hww.pl/nowelizacja-prawa-energetycznegonajwazniejsze-zmiany-przepisow-i-co-one-oznaczaja-dlauczestnikow-rynku-energetycznego/ z dnia 20.09.2024
[2]. https://energyid.org/service/energia-elektryczna-formyhandlu/ z dnia 20.09.2024
[3]. https://www.gramwzielone.pl/energiasloneczna/107429/prosumenci-dostana-nowa-mozliwoschandlu-energia z dnia 20.09.2024
[4]. USTAWA z dnia 28 lipca 2023 r. o zmianie ustawy – Prawo energetyczne oraz niektórych innych ustaw
[5]. DYREKTYWA PARLAMENTU EUROPEJSKIEGO I RADY (UE) 2019/944 z dnia 5 czerwca 2019 r. w sprawie wspólnych zasad rynku wewnętrznego energii elektrycznej oraz zmieniająca dyrektywę 2012/27/UE
[6]. DYREKTYWA PARLAMENTU EUROPEJSKIEGO I RADY
(UE) 2018/2001 z dnia 11 grudnia 2018 r. w sprawie promowania stosowania energii ze źródeł odnawialnych (wersja przekształcona)
[7]. Mataczyńska E., Blockchain Technology Impact on the Energy Market Model. Energy Policy Studies, (2017)
[8]. ZIELIŃSKA A., Possibilities of using blockchain technology in the area of electricity trade settlements, Przegląd Elektrotechniczny, ISSN 0033-2097., (2021), R. 97, nr 12, doi: 10.15199/48.2021.12.32
[9]. Piech K., „Leksykon pojęć na temat technologii blockchain i kryptowalut”, (2016)
[10]. Rafał K., Radziszewska W., Król P., Bazior G., Grabowski P., Model funkcjonowania energetyki rozproszonej w oparciu o blockchain i systemy zarządzania energią, Nowa Energia, (2021).
[11]. https://tge.pl/ z dnia 20.09.2024
[12]. Zielińska A., Application possibilities of blockchain technology in the energy sector, E3S Web Conf., 154 (2020), doi: 10.1051/e3sconf/202015407003K
[13]. Manish Kumar Thukral, Emergence of blockchain-technology application in peer-to-peer electrical-energy trading: a review, Clean Energy, (2021), 104–123, doi: 10.1093/ce/zkaa033
[14]. https://brandsit.pl/energetyka-2-0-blockchain-jako-klucz-dooptymalizacji-sieci-energetycznych-i-handlu-zasobami/ z dnia 2.08.2023.


Author: dr inż. Anna Zielińska, AGH University of Science and Technology, Faculty of Management, al. A. Mickiewicza 30, 30-059 Krakow, e-mail: azielinska@agh.edu.pl;


Source & Publisher Item Identifier: PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 101 NR 3/2025. doi:10.15199/48.2025.03.30

Disturbances Occurring in the Electrical Installation, with Particular Emphasis on the Negative Impact of Non-Linear Receivers on the Supply Network

Published by Marta BĄTKIEWICZ-PANTUŁA, Wrocław University of Science and Technology. ORCID: 0000-0002-1628-1818


Abstract. Receivers such as power electronic devices, due to their widespread use and non-linear characteristics, are the most common cause of poor quality electricity. The share of non-linear receivers in the overall balance of power installed at a single customer increased to the level that the power supply voltage was affected by such phenomena as: overload of the neutral conductor, higher harmonics, and asymmetry. The article presents the assessment of electricity quality parameters based on measurements carried out at consumers. The assessment was based on the Regulation of the Minister of Economy of. May 4, 2007. On the detailed conditions for the operation of the power system and the PN-EN 50160: 2010 standard – Parameters of the supply voltage in public power networks. The analysis was carried out on the example of real measurements of electricity quality parameters. The assessment of electricity quality parameters was carried out on the basis of the analyzes discussed.

Streszczenie. Odbiorniki jakimi są urządzenia energoelektroniczne ze względu na swoje powszechne zastosowanie i charakterystykę nieliniowa są najczęstszą przyczyna złej jakości energii elektrycznej. Udział odbiorników nieliniowych w ogólnym bilansie mocy zainstalowanej u pojedynczego odbiorcy wzrósł do poziomu, że w napięciu zasilającym pojawiły się zjawiska takiej jak: przeciążenie przewodu neutralnego, wyższe harmoniczne, asymetria. W artykule zaprezentowano ocenę parametrów jakości energii elektrycznej pozyskiwaną od odbiorców. Ocena została oparta na Rozporządzeniu Ministra Gospodarki z dnia. 4 maja 2007 r. W sprawie szczegółowych warunków funkcjonowania systemu elektroenergetycznego i normy PN-EN 50160: 2010 – Parametry napięcia zasilającego w publicznych sieciach elektroenergetycznych . Analiza została przeprowadzona na przykładzie rzeczywistych pomiarów parametrów jakości energii elektrycznej. Ocena parametrów jakości energii elektrycznej została przeprowadzona na podstawie omówionych analiz (Zakłócenia występujące w instalacji elektrycznej, ze szczególnym uwzględnieniem negatywnego oddziaływania odbiorników nieliniowych na sieć zasilającą).

Keywords: power quality, non-linear loads, negative impact on the electricity grid
Słowa kluczowe: jakość energii elektrycznej, odbiorniki nieliniowe, negatywny wpływ na sieć

Introduction

The power quality is a concept that is difficult to define. This is due to how electricity is defined. It can be defined as a physical phenomenon resulting from the transformation of energy from e.g. mechanical, thermal or chemical form into electricity, or it can be understood as a commodity, a product that can be produced and sold to recipients who need this energy [1]. And it is in this aspect that the power quality is usually defined because each product, through its physical properties, should be able to determine whether it is good or not. The definition of electricity quality also depends on the entity that describes it. Different meanings of quality will be defined by electricity suppliers, different by manufacturers of electronic equipment, and still different by electricity consumers, because everyone has their own individual needs regarding this issue [2].

Currently, the most accurate description of the power quality is the definition proposed by the Advisory Committee on Electromagnetic Compatibility IEC, which says that the power quality is the parameters that describe the properties of electricity supplied to the consumer during normal operation [3]. They determine the continuity of the supply, i.e. short and long interruptions in the supply, and describe the supply voltage, namely its value, asymmetry, frequency and shape of the waveform.

The power quality in question is not only dependent on the power supply conditions, but also on the electronic equipment used, which may be more or less susceptible to electromagnetic interference, and may also generate and send it into the grid. Therefore, for the poor power quality cannot be blamed solely on the service provider, because the quality of energy also depends on the manufacturers of electrical devices, which should comply with applicable standards and regulations, as well as on the user, who should use the equipment purchased in accordance with the attached instructions for use.

Power Quality Parameters

Charging The parameters characterizing the power quality include easily measurable quantities that can be parameterized and normalized [4]. These are:

• frequency,
• voltage changes,
• asymmetry,
• harmonics voltage.

All these parameters are standardized by the relevant normative documents, which include:

• EN 50160 Voltage characteristics of electricity supplied by public electricity networks [5].

• Regulation of the Minister of Economy of Poland dated. May 4, 2007 on detailed conditions of functioning of the power system (Journal of Laws of 29 May 2007, item 623) [6].

• Distribution Network Operation and Operation Manual applicable to a given distribution system operator.

The above legal acts normalize the permissible values of given parameters in normal conditions, in power connectors of consumers supplied from public power grids. The PN-EN 50160:2010 standard explains in detail what normal conditions mean, namely it describes them as a state of equilibrium in which the electrical energy demand is equal to the generated energy and switching operations are performed, and all disturbances are automatically removed by means of protection automation.

For the professional power industry, the biggest problem is to ensure the reliability of power supply [7]. The most sensitive to the poor quality of electric energy are recipients from industries such as:

• hospitals,
• airports,
• chemical industry,
• refineries,
• metallurgical industry,
• IT sector,
• plastics industry.

Depending on the type of facility, in the event of an unplanned failure, there may be threats in the form of material damage, e.g. damage to the installation, production losses, poor quality of the product, or human risk, e.g. damage to the health of employees and bystanders, and in extreme cases even death (chlorine, propylene/ethylene and other hazardous media), and environmental hazards, e.g. environmental pollution.

Receivers such as power electronic devices, due to their widespread use and non-linear characteristics, are the most common cause of poor quality electricity.

The share of non-linear receivers in the overall balance of installed power at a single customer increased to the level that the following phenomena appeared in the supply voltage:

• harmonics voltage,
• asymmetry,
• overload of the neutral conductor

The most common disturbances are harmonics of the supply voltage, therefore they will be discussed in the following paper.

On their example, the average levels of supply voltage disturbances encountered in the distribution network were discussed, starting from 110 kV voltage (point P1, Fig. 1) through medium voltage (point P2, Fig. 1) to low voltage (point P3, Fig. 1) in the city municipal network.

Fig.1. A simplified diagram illustrating the discussed places of electricity quality measurements, indicating the levels of rated voltages, measurement points P1, P2 and P3 as well as power and transformer connection groups

From the UN = 10 kV switching station, apart from the analyzed T2 transformer, also many other loads in the city municipal network were supplied, including the tram network converter station equipped with six-pulse rectifiers. The only building powered by the T2 transformer was a large office building.

Harmonics voltage in the supply

The main reason for the presence of higher harmonics in the supply voltage is the consumption of currents distorted from the sinusoidal waveform by non-linear receivers connected to the network. These currents cause the appearance of voltage drops on the elements of the transmission system not only for the fundamental harmonic, but also for the next higher harmonics of the current, as a result of which there is a distortion of the voltage at the considered supply point [8-10]. Standard [5,11,12] and regulation [6] specify the acceptable levels of harmonic content in such a way that they are calculated according to the relationship (1) up to h = 25 and according to (2) up to h = 40 as averaged values for a 10-minute time window .

The standard time for assessing the voltage quality according to [5] and [6] is 1 week, i.e. 1008 such 10-minute measurement sections.

The permissible levels are determined in such a way that for normal working conditions, during each week, 95% according to [5] and 100% according to [6] of measurements should not exceed the given limit values.

The measurement results presented in the paper are primarily intended to illustrate typical waveforms at various voltage levels (P1, P2, P3, Fig. 1) in the city municipal network.

Measurements on both sides of the T1 transformer (Fig. 1) were made as a simultaneous 4-day measurement, while the measurements in the low-voltage switchgear as a 1- week measurement at a different time than the high-voltage measurements.

Fig.2. Weekly trends of changes in the THDU(RMS)% factor, respectively for point P1 (fig. 1)

Fig.3. Weekly trends of changes in the THDU(RMS)% factor, respectively for point P2 (fig. 1)

Fig.4. Weekly trends of changes in the THDU(RMS)% factor, respectively for point P3 (fig. 1)

Fig.2,3,4 presents three waveforms of changes in the THDU(RMS)% coefficient, successively for points P1, P2 and P3 (Fig. 1). Approximate values of the range of changes of this indicator are listed in Table 1.

Table 1. Approximate ranges of coefficient changes THDu(rms)% for points P1, P2 i P3 (fig. 1)

.

In turn, Figure 5,6,7 presents three spectra of voltage harmonics for points P1, P2 and P3, respectively.

Fig.5. Spectrum of voltage harmonics respectively for point P1 (fig. 1)

Fig.6. Spectrum of voltage harmonics respectively for point P2 (fig. 1)

Fig.7. Spectrum of voltage harmonics respectively for point P3 (fig. 1)

The analysis of the presented waveforms allows to conclude that:

• the range of changes and values of the voltage distortion coefficient are the greatest for the supply network at the low voltage level, and decrease with increasing network voltage; it follows that the main source of voltage harmonics are non-linear low voltage receivers,

• in the 110 kV network harmonics of the 3rd, 5th and 7th order dominate, while at lower voltage levels the share of other harmonics is much larger; a kind of surprise is the higher harmonic level of the 3rd order in the 110 kV network than in the 10 kV network, despite the fact that the medium voltage winding of the T1 transformer is delta connected; it follows that the source of such a high level of the 3rd harmonic in the 110 kV network is not the loads in the 10 kV network, but the source is in the 110 kV network, e.g. it may result from earth current resulting from load asymmetry,

• the source of harmonics 5 and 7, clearly distinguishable in measurements at 10 kV voltage, is the converter station supplying the tram network, connected to this substation,

• characteristic daily changes of the coefficient are visible on all waveforms, however they differ depending on the voltage level; these differences are mainly due to the local nature of the supplied loads, which may be the subject of a separate, detailed analysis; the regularity of daily changes and the symmetry of the load of individual phases along with the decrease of the rated voltage of the network are characteristic; the minima of the runs fall on the night and late-afternoon hours, while the maxima on the evening and morning hours; these changes are related to daily load changes,

• the values of all measured parameters are within the acceptable levels specified in [3] and [4], except for the voltage of the 15th harmonic at point P3, which exceeded the permissible level of 0.5% and was 0.8%.

Summary

It is possible to observe the presence of higher harmonics in the presented waveforms, which distort the signal from the sine wave. With the exception of one harmonic, all parameters met the requirements of the standard. The reason for this is mainly converter devices, such as computer power supplies located in the building, as well as LED light sources that have replaced traditional light bulbs and are present in all rooms. Their construction is based on semiconductor elements such as thyristors, diodes, etc. whose task is to adjust the network parameters to such that the devices work properly, i.e. converting alternating voltage to constant and reducing its value in order to properly power supply. Another type of equipment causing visible interference is the high-powered motors installed to drive elevators that facilitate the movement of the building.

In order to eliminate poor quality electricity faster, a good solution is to use, among others:

• System for monitoring electricity quality parameters.

• Enabling the collection of statistical information about disturbances that occur in the plant. Each disruption entails greater or lesser financial losses.

• Recording and cost analysis of poor quality electricity – faster dispute and complaint resolution process.

• Application of more stringent requirements specified in the PN EN 50160 standard, in particular for two parameters, i.e. voltage dips and swells. Reducing or completely eliminating the problem of poor quality electricity should consist in:

• continuous measurement and analysis of electricity quality parameters – more measurement points,

• eliminating sources interfering with the operation of the system, e.g. by separating the circuit, adding receivers with high short-circuit power, applying good engineering practice,

• the use of appropriate devices for the designed conditions aimed at increasing the resistance of receivers to disturbances, e.g. by using input filters,

• limiting the impact of interference source emission by using passive or active filters, react

REFERENCES

[1] Kowalski.Z.: Power quality. Monographs of the Lodz University of Technologyj. Łódź 2007.
[2] Fuchs E., Masoum M.: Power Quality in Power Systems and Electrical Machines. Elsevier Inc., 2008. 205
[3] Z. Hanzelka, Quality of electricity supply, Krakow: Publisher AGH Krakow, 2013
[4] A.Klajn, M.Bątkiwicz-Pantuła, Application Note – Standard EN 50 160: Voltage characteristics of electricity supp
[5] EN 50160:2010. Voltage characteristics of electricity supplied by public electricity networks.
[6] Regulation of the Minister of Economy of Poland dated. May 4, 2007 on detailed conditions of functioning of the power system (Journal of Laws of 29 May 2007, item 623).
[7] Biernacik T., Skliński R. Negative impact of non-linear receivers on the power supply network and its reduction using passive filters of higher harmonics, Wiadomości Elektrotechniczne, 2020, R. 88, nr 11, 3-6
[8] Baggini A., Hanzelka Z., Voltage and Current Harmonic, Handbook of Power Quality, Whiley, 2008, 200-236
[9] Kamuda K., Klepacki D., Kuryło K., Sabat W. Statistical analysis of influence of the low-power non-linear loads on deformation of supply voltage, Przegląd Elektrotechniczny, R. 91 Nr 8/2015, 19-22
[10] Kuśmierek Z.: Harmonics in power systems, Przegląd Elektrotechniczny, 82 (2006), nr 6, 8-19
[11]PN-EN 61000-3-11:2020-01 Electromagnetic compatibility (EMC) – Part 3-11: Limits – Limitation of voltage variations, voltage fluctuations and flicker in public low-voltage power
supply networks – Equipment with a nominal current < or = 75 A subject to conditional connection
[12] PN-EN IEC 61000-3-2:2019 Electromagnetic compatibility (EMC) – Part 3-2: Limits – Limits for harmonic current emissions (phase supply current of the receiver ≤ 16 A)


Authors: dr inż. Marta Bątkiewicz-Pantuła, Wrocław University of Science and Technology, Faculty of Electrical Engineering, Power Electrical Department, ul. Wybrzeże Wyspiańskiego 27, 50-370 Wrocław, e-mail: marta.batkiewicz-pantula@pwr.edu.pl


Source & Publisher Item Identifier: PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 101 NR 1/2025. doi:10.15199/48.2025.01.52

Impact of Climatic Factors on the Restoration Time of MV Power Lines

Published by1. Kornelia A. BANASIK, 2. Andrzej Ł. CHOJNACKI, Kielce University of Technology, Chair of Power Engineering, Power Electronics and Electrical Machines
ORCID: 1. 0000-0002-6629-8650, 2. 0000-0002-9227-7538


Abstract. The duration of outages (restoration time) is a fundamental parameter characterizing the extent of failures, as well as the quality of organisation during their elimination. Its understanding allows for estimating the costs incurred by consumers and electric energy distributors. Besides technical and organizational factors, the weather conditions during repair works also influence its value. This paper presents a statistical analysis of the impact of weather conditions, represented by air temperature, wind speed, and daily precipitation, on the failure (restoration) time of medium voltage power lines. The econometric modelling method was used for this purpose.

Streszczenie. Czas trwania awarii (odnowy) jest podstawowym parametrem charakteryzującym rozległość awarii, a także jakość organizacji prac przy jej usuwaniu. Jego znajomość pozwala na oszacowanie kosztów ponoszonych przez odbiorców oraz dystrybutorów energii elektrycznej. Poza czynnikami technicznymi i organizacyjnymi na jego wartość mają wpływ także warunki atmosferyczne występujące w czasie wykonywania prac naprawczych. W referacie przedstawiona została analiza statystyczna wpływu warunków atmosferycznych, reprezentowanych przez temperaturę powietrza, prędkość wiatru oraz dobową sumę opadów, na czas trwania awarii (odnowy) linii elektroenergetycznych średniego napięcia. Wykorzystana została w tym celu metoda modelowania ekonometrycznego. (Wpływ czynników klimatycznych na czas odnowy linii elektroenergetycznych SN)

Keywords: electrical distribution networks, MV power lines, failures, failure duration, wind, precipitation, air temperature

Słowa kluczowe: elektroenergetyczne sieci dystrybucyjne, linie elektroenergetyczne SN, awarie, czas awarii, wiatr, opady atmosferyczne, temperatura powietrza

Introduction

The problem of ensuring continuity of electricity supply to consumers is a primary and most important issue for distribution companies. However, there are many phenomena and factors that contribute to the occurrence of failure states. These factors include primarily storms with atmospheric discharges, winds, soot, activities of third parties, and improper or incorrectly conducted operation. The presented factors belong to the group of external factors. In many cases, the factors causing failures are phenomena occurring within the power grid. These are the so-called internal factors. Among them are: switching surges and earth failures in networks with an isolated neutral point, fatigue phenomena (mechanical and electrical), aging phenomena, manufacturing and assembly defects, etc. [4, 5, 8, 9, 12].

The unreliability of power equipment results in losses incurred by consumers and electricity distributors. These are called reliability losses. Losses for industrial consumers mainly result from production not being carried out or being delayed, as well as from the destruction of raw materials used in production. In the case of municipal consumers, these losses include: losses due to forced inactivity (waste of time), material destruction losses (mainly food), and losses caused by deteriorating sanitary and health conditions. Losses for energy distributors result from the need to remove the occurred failure and the loss of profit for the duration of its occurrence [3, 9, 13].

The primary parameter determining the extent of a failure is the failure (restoration) duration ta. It is defined as the time from the moment the device failure occurs until its repair or replacement is completed, with the simultaneous restoration of the device’s power supply capability [9, 11, 13]. This parameter primarily provides a statistical picture of the quality of the failure removal organization and the extent of the damage.

Another parameter characterizing the reliability of power systems is the outage duration for consumers tp. This time is defined as the time from the moment the consumers lose power until it is restored with the simultaneous capability to provide the required power [13].

The device outage time due to a failure twa is the time from the moment the device is switched off (either automatically or by operation) due to its failure until the power is restored by the device after its repair. This time is not equivalent to the failure duration time because after the main cause of the failure is removed, the device may be energized despite still being in a failure state, provided that it can perform its functions completely or to a limited extent and does not pose a risk to operation. The final failure removal work is performed under voltage. During this time, even though the failure has not yet been removed, the device is no longer in a failure state. Furthermore, not every failure causes automatic device shutdown. In this case, the device in a failure state is not in an emergency shutdown state.

In the event of a failure, the losses incurred by consumers depend on the outage duration, while the losses incurred by distributors depend on the failure duration [3, 7]. Therefore, the distribution company should aim to minimize the outage duration for consumers by using backup or emergency power supplies and to minimize the failure duration through proper failure removal organization.

Factors that significantly hinder or even prevent failure removal (restoration) are weather conditions. Among the most significant are high and low air temperatures, high wind speeds, large daily rainfall totals, and lightning strikes [1, 2, 6].

In the event of lightning, storms, or hail, regulations prohibit work on electrical equipment. A similar situation occurs when wind speeds exceed 10 m/s. In such cases, all work at heights on power lines should be suspended [10]. Another factor preventing work on overhead lines is dense fog. The problem also arises when weather conditions are not clearly assessable. In such cases, it is best to refrain from unnecessary work until the weather conditions improve. In situations of urgent work that should be carried out immediately, the decision to start or refrain from work is made by the person leading the team or the foreman, after prior assessment of whether the work can be safely conducted in the existing weather conditions and in accordance with applicable regulations.

In this article, the authors presented the results of analyses regarding the impact of weather conditions, represented by air temperature, wind speed, and precipitation, on the duration of restoration (failure duration) of medium-voltage power lines. The method of modelling the relationship between failure duration of power system components and various environmental factors was discussed. The results obtained during many years of research for overhead power lines with bare conductors, overhead lines with partially insulated conductors, and underground cables, operated in national electricity distribution networks, were presented.

All the analyses were carried out at the level of significance α = 0.05.

The analyses presented in the article were based on data on failures that occurred over a period of 15 years in two electricity distribution companies in the country.

Modelling the Impact of air temperature, wind speed, and daily precipitation on the restoration time of medium-voltage power lines

Weather conditions in Poland and around the world are constantly changing. The range of temperatures occurring on Earth is very large. The maximum air temperature in the shade in an open space is around 60°C (the highest recorded is 56.7°C in Death Valley, USA). The lowest temperatures, on the other hand, can reach nearly -90°C (the lowest recorded is -89.2°C in Antarctica). The range of temperatures observed is obviously dependent on geographic latitude. The record temperatures recorded in Poland are -41.0°C (Siedlce) and 40.2°C (Prószków near Opole). Also, the range of wind speeds observed on Earth is very large. The maximum measured wind speed in a gust was over 110 m/s (113.33 m/s – Barrow Island, Australia). The highest officially recorded wind speed in a gust in Poland was 95.83 m/s (Meteorological station on Śnieżka). However, these are not record values. Much higher wind speeds are reached in tornadoes. The highest value on Earth, recorded by Doppler radar, was over 133.33 m/s (Oklahoma, USA), while in Poland, it was 102.50 m/s (near Lublin). The average annual wind speed in Poland is around 3-4 m/s. The highest wind speeds occur in late autumn, winter, and early spring. During these times, they are often accompanied by sub-zero air temperatures and heavy precipitation. Environmental conditions such as these are unfavourable and contribute to the occurrence of failures in electrical equipment (particularly overhead lines) as well as complicate the restoration process.

The world record for the highest daily precipitation was observed in Réunion, amounting to 1825 mm. In Poland, the record daily precipitation was observed at Hala Gąsiennicowa, reaching 300 mm.

It is important to note that various values of individual weather factors occur in different combinations with values of other weather factors. In many situations, it is the specific combination of these values that negatively or positively impacts electrical facilities and their operation. To determine the outage duration as a function of air temperature, wind speed, and daily precipitation t̅α = f (T, W, O) it is necessary to calculate the average values t̅αi = (Ti, Wi, Oi) for successive combinations of air temperature intervals Ti , wind speed Wi , and daily precipitation Oi .

Determining the empirical functions t̅α = f (T, W, O) does not fully address the problem of investigating the dependency of the restoration time on the considered atmospheric factors. It is also important to determine the functional form of these dependencies, i.e., to implement mathematical models.

Knowing the discrete values of the failure duration t̅α and the values of the environmental factors present during the restoration of electrical lines allows for the creation of a general multiple regression equation in the form:

.

where: T – air temperature value [°C], W – wind speed value [m/s], O – daily precipitation sum value [mm], a, b, c, d, e, f, g, h, i, j, k, l, m – coefficients of the approximating function.

Preliminary studies have shown that the dependency of outage duration on individual environmental stressors can be approximated by a fourth-order polynomial. Since, in all cases, the coefficients of the approximation function obtained for an order higher than the fourth are close to zero, it was decided to approximate these dependencies with a polynomial of at most the fourth order. Therefore, the final general regression equation was adopted in the form (1).

To implement the above mathematical model, the econometric modelling method was used. For the individual medium-voltage lines, the functional form of the failure time was determined, and the theoretical models obtained were verified by assessing their conformity with empirical data. In the considered models, the intervals of climatic factors were analysed on the principle that each interval of a given factor was combined with each interval of every other factor. In total, 393,984 intervals were created. The number of combinations of intervals in which failures occurred, and thus non-zero values of the average failure (restoration) time, for the respective lines is as follows: bare overhead medium-voltage lines – 890 observations (over 15 years), semi-insulated overhead medium-voltage lines – 21 observations (over 13 years), and medium-voltage cable lines – 465 observations (over 15 years).

The failure time of bare overhead medium-voltage lines is determined by an econometric model given by:

.

To determine the quality of the model fit to empirical data, the following measures were used: multiple correlation coefficient, coefficient of determination, convergence coefficient, standard error of estimation, and the coefficient of random variability. Additionally, the F Fisher-Snedecor test was conducted. The results of this verification are shown in Table 1. As indicated by equation (2), the factor that most strongly influences the restoration time of bare overhead medium-voltage lines is wind speed.

The duration of restoration is proportional to the square of the wind speed. A slightly lesser influence is attributed to the daily sum of precipitation. In this case, it is a relationship in the first power. The influence of other atmospheric factors is so weak that they were rejected in the procedure of creating the econometric model. The theoretical variability of the failure duration for bare overhead medium-voltage lines is shown in Figure 1.

The duration of failure of medium-voltage overhead lines with partially insulated conductors is determined by an econometric model in the following form:

.

The results of the model verification are presented in Table 2.

As indicated by the relation (3), the factors that most strongly influence the duration of failure of medium-voltage lines with partially insulated conductors are precipitation and wind. The duration of failure (restoration) of these lines depends on the daily precipitation in the second power and the wind speed in the fourth power. The influence of other atmospheric factors is so weak that they were rejected in the procedure of creating the econometric model. The theoretical variability of the failure duration for overhead lines with partially insulated conductors is shown in Figure 2.

Fig.1. Theoretical durations of failures of bare overhead lines depending on wind speed and daily precipitation sum

Fig.2. Theoretical durations of failures of overhead lines with partially insulated conductors depending on wind speed and daily precipitation sum

The duration of failure of MV cable lines is determined by an econometric model in the following form:

.

The results of the model verification are presented in Table 3.

As stated in equation (4), the factors that most strongly influence the restoration time of high-voltage cable lines are precipitation and ambient temperature. In this case, we observe a very strong influence of daily precipitation, on which the duration of recovery depends in the power of the fourth. The effect of ambient temperature in the first power is much smaller, but clearly noticeable. The influence of other atmospheric factors is so weak that they were rejected in the procedure of creating the econometric model. The theoretical variability of the duration of failure of MV cable lines is presented in Figure 3.

Fig.3. Theoretical durations of failures of MV cable lines depending on daily precipitation and ambient temperature

Conclusions

The article presents the results of an analysis regarding the influence of weather conditions, represented by air temperature, wind speed, and daily precipitation sum, on the restoration (failure) time of medium-voltage power lines. The analysis considered the independent effects of weather on uninsulated overhead lines, partially insulated overhead lines, and underground cable lines. As indicated by the relationships (2), (3), and (4), the factors that most strongly affect the restoration time of overhead lines are wind speed and daily precipitation sum, while for underground cables, it is the daily precipitation sum and air temperature. The influence of air temperature on the restoration time of overhead lines and wind speed on the restoration time of underground cables is relatively weak, leading to their exclusion during the econometric model creation process. The most significant factors affecting the restoration time of lines are: for uninsulated (bare) overhead lines – wind speed, and for partially insulated overhead lines and underground cable lines – the daily precipitation sum.

The developed mathematical models enable the calculation of the expected restoration time for medium-voltage power lines in the event of simultaneous influence of multiple atmospheric factors. As the analyses have shown, these models are quite simple to apply, and the results obtained using them largely correspond with the statistical data from electricity distribution companies. These models can be used in further reliability studies of power lines. The authors have already made initial attempts to use them in simulation algorithms based on Petri nets.

Table 1. Verification of the model of duration of failure of overhead lines with bare conductors

.

Table 2. Verification of the model of duration of failure of overhead lines with partially insulated conductors

.

Table 3. Verification of the model of duration of failure of cable lines

.

REFERENCES

[1] Banasik K., Chojnacki A. Ł., Gębczyk K., Grąkowski Ł., Influence of wind speed on the reliability of low-voltage overhead power lines, Progress in Applied Electrical Engineering (PAEE) – IEEE, czerwiec 2019
[2] Banasik . K. A., Analiza wpływu warunków atmosferycznych na niezawodność eksploatacji urządzeń i obiektów w elektroenergetycznych sieciach dystrybucyjnych. Praca doktorska. Kielce 2023
[3] Chojnacki A. Ł., Analiza skutków gospodarczych niedostarczenia energii elektrycznej do odbiorców indywidualnych. Wiadomości elektrotechniczne Nr 09/2009, s. 3-9
[4] Chojnacki A. Ł., Analysis of Seasonality and Causes of Equipment and Facility Failures in Electric Power Distribution Networks,. Przegląd elektrotechniczny, Nr 1/2023, s. 157 – 163
[5] Chojnacki A. Ł., Impact of ambient temperature on the failure intensity of overhead MV power lines. Przegląd elektrotechniczny Nr 10/2022, s. 307 – 311
[6] Chojnacki A. Ł., Kaźmierczyk A., Wpływ temperatury otoczenia na intensywność awarii stacji transformatoroworozdzielczych SN/nN, Logistyka Nr 6/2014, s. 2610-2618
[7] Chojnacki A. Ł., Świercz ewski Z. : Koszty strat u dystrybutorów energii elektrycznej spowodowane zawodnością stacji elektroenergetycznych SN/nN. Energetyka Nr 03/2010, s. 149-157
[8] Chojnacki A.Ł., Sezonowość oraz przyczyny uszkodzeń elektroenergetycznych sieci dystrybucyjnych. Elektro Info Nr 03/2023, s. 90 – 94
[9] Kowalski Z., Niezawodność zasilania odbiorców energii elektrycznej. Wydawnictwa Politechniki Łódzkiej, Łódź, 1992
[10]Rozporządzenie Ministra Infrastruktury z dnia 6 lutego 2003 r. w sprawie bezpieczeństwa i higieny pracy podczas wykonywania robót budowlanych (Dz.U. 2003 nr 47 poz. 401)
[11]Sozański J., Niezawodność i jakość pracy systemu elektroenergetycznego. WNT, Warszawa, 1990
[12]Sozański J., Niezawodność urządzeń i układów elektroenergetycznych, PWN, Warszawa 1974
[13]Sozański J., Niezawodność zasilania energią elektryczną. WNT, Warszawa, 1982


Authors: Dr. Eng. Kornelia Agnieszka Banasik, Dr. hab. Eng. Andrzej Ł. Chojnacki, prof. at PŚk, Kielce University of Technology, Faculty of Electrical Engineering, Automation and Computer Science, Department of Power Engineering, Energoelectronics and Electrical Machines, Aleja Tysiąclecia Państwa Polskiego 7, 25-314 Kielce, e-mail: k.banasik@tu.kielce.pl, a.chojnacki@tu.kielce.pl


Source & Publisher Item Identifier: PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 101 NR 2/2025. doi:10.15199/48.2025.02.57

Interference Present in the Electrical Installation with Special Consideration of Higher Harmonics

Published by Marta BĄTKIEWICZ-PANTUŁA, Wrocław University of Science and Technology. ORCID: 0000-0002-1628-1818


Abstract. Converter devices, i.e. computer power supplies prevalent in buildings, as well as LED light sources, which have replaced traditional light bulbs due to their widespread use and characteristics, are the most common cause of poor power quality. The construction of the devices is based on semiconductor elements such as thyristors, diodes, etc. whose task is to adjust the network parameters so that the devices work properly, i.e. converting the alternating voltage into direct current and reducing its value in order to provide proper power supply. The share of receivers in the overall balance of power installed at a single consumer increased to the level that phenomena such as higher harmonics appeared in the supply voltage. The article presents the assessment of electricity quality parameters based on measurements carried out at consumers. The assessment was based on the Regulation of the Minister of Economy of. May 4, 2007. On the detailed conditions for the operation of the power system and the PN-EN 50160: 2010 standard – Parameters of the supply voltage in public power networks. The analysis was carried out on the example of real measurements of power quality parameters. The assessment of power quality parameters was carried out on the basis of the analyzes discussed.

Streszczenie. Urządzenia przekształtnikowe, czyli przeważające w budynkach zasilacze komputerowe, jak i LED-owe źródła światła, które wyparły tradycyjne żarówki ze względu na swoje powszechne zastosowanie i charakterystykę są najczęstszą przyczyna złej jakości energii elektrycznej. Budowa urządzeń opiera się na elementach półprzewodnikowych takich jak, tyrystory, diody itp. których zadaniem jest dostosowanie parametrów sieciowych do takich, aby urządzenia pracowały poprawnie, czyli zamiana napięcia przemiennego na stałe i zmniejszenie jego wartości, w celu poprawnego zasilania. Udział odbiorników w ogólnym bilansie mocy zainstalowanej u pojedynczego odbiorcy wzrósł do poziomu, że w napięciu zasilającym pojawiły się zjawiska takiej jak wyższe harmoniczne. W artykule zaprezentowano ocenę parametrów jakości energii elektrycznej pozyskiwaną od odbiorców. Ocena została oparta na Rozporządzeniu Ministra Gospodarki z dnia. 4 maja 2007 r. W sprawie szczegółowych warunków funkcjonowania systemu elektroenergetycznego i normy PN-EN 50160: 2010 – Parametry napięcia zasilającego w publicznych sieciach elektroenergetycznych . Analiza została przeprowadzona na przykładzie rzeczywistych pomiarów parametrów jakości energii elektrycznej. Ocena parametrów jakości energii elektrycznej została przeprowadzona na podstawie omówionych analiz. (Zakłócenia występujące w instalacji elektrycznej ze szczególnym uwzględnieniem wyższych harmonicznych)

Keywords: power quality, harmonic, negative impact on the electricity grid.
Słowa kluczowe: jakość energii elektrycznej, harmoniczne, negatywny wpływ na sieć

Introduction

Power quality is a set of parameters describing the properties of the process of supplying energy to the user under normal operating conditions. These parameters determine the continuity of the power supply and characterize the supply voltages. In practice, the power quality is perceived as satisfactory when deviations from nominal values do not have a significant impact on the stable and effective operation of devices and the system. Currently, the most accurate description of power quality is the definition proposed by the Advisory Committee on Electromagnetic Compatibility IEC, which says that power quality are parameters that describe the properties of electricity supplied to the recipient when operating under normal conditions. These parameters determine the continuity of the power supply, i.e. short and long interruptions in the power supply, and describe the supply voltage, namely its value, asymmetry, frequency and waveform. [1]

The discussed power quality does not depend only on the power supply conditions, but also on the electronic equipment used, which may be more or less susceptible to electromagnetic interference, as well as generating and feeding into the network itself. [2]

Higher Harmonics

Even harmonics occur the least in the power supply network, the reason for this is that few devices that are currently used generate this harmonic in large quantities. The receivers characterized by even harmonics include mainly arc furnaces. The course of the current consumed by them is random, due to the arc discharge conditions, which depend on the melting phase, the largest deformations occur in the melting phase.

Odd harmonics are part of the distorted signal whose frequencies, as the name suggests, are an odd number of integer multiples of the fundamental component of the waveform. These types of harmonics are most commonly found in power lines. They are further divided into triple and non-triple. Triple harmonics are characterized by the fact that their number, in addition to being an odd number, is also a multiple of the digit 3. They are particularly dangerous for the neutral wire of the network, because in each phase the triple harmonics have the same phase shift. As a consequence, they add up in the neutral wire, and the value of the current flowing through the neutral wire can sometimes be higher than in the phase wire.

The main cause of these harmonics are single-phase receivers, discharge light sources, and transformers, which are characterized by the 3rd harmonic. In the case of transformers, it mainly depends on the operating point at which they are located and the magnetization characteristics, which are strongly non-linear. Generally, these devices are designed in such a way that the magnetization current does not exceed 1-2% of the rated current. Thanks to this, the transformer’s operating point is located on the linear part of the magnetization characteristic, and the generation of higher harmonics is small. However, the situation changes in the case of even a slight increase in the supply voltage, the ferromagnetic core becomes saturated, the operating point moves to the nonlinear part of the characteristic and the magnetization current increases. Then transformers become a significant source of 3rd harmonics. One way to eliminate this effect is to connect the windings in D/y, which gives a low-impedance circuit for the 3rd harmonic in the delta-connected windings. [3]

The occurrence of non-triple harmonics is characteristic of converter devices such as power supplies, especially 6- pulse ones. This is due to the nature of their work, where a constant voltage is obtained at the output by appropriately switching on the thyristors. This keying has a significant impact on the distortion of the voltage supplying the rectifier, mainly 5th and 7th harmonics occur. This group of receivers also includes engines. Most motor windings have 5 or 7 grooves for each pole, which results in the appearance of the 5th or 7th harmonic, which, despite being much smaller than in converters, becomes noticeable when the power of such a machine is high or their number is greater. [3]

The occurrence of higher harmonics causes many problems. In the case of receivers such as generators, motors and transformers, the losses generated in the windings increase, which is also associated with an increase in temperature that must be discharged to the environment, as a result of which the life of the device is shortened, the insulation of the wires is subjected to high thermal stress and deteriorates faster its properties. Additionally, the noise of such devices increases significantly, and in the case of moving machines, uneven operation may also occur. It should also be remembered that starting engines may be difficult due to increased slip due to the occurrence of higher harmonics.

Other effects of this phenomenon include a reduction in the switching capacity of circuit breakers, where the occurrence of higher harmonics may increase the value of the current derivative di/dt during zero crossing, which significantly worsens the process of interrupting load currents. Although converter devices are the main cause of harmonics in the power supply network, they are also susceptible to their effects. Synchronization errors resulting from false zero crossing of voltage or damage to system components caused by an increase in the maximum voltage value.

Measuring instruments are also exposed to higher harmonics. They are usually tuned to measure sinusoidally variable values, and due to the appearance of harmonics, the measured signal may significantly deviate from the ideal sinusoidal shape, which consequently results in an incorrect measurement of a given value. This was of great importance in the case of power meters, which were equipped with a motor that, due to harmonics, could incorrectly count the consumed electricity. With the digital meters currently used, the situation looks better.

Thermal hazard also occurs in electrical cables, which accelerates the aging of insulation. Two mechanisms influence this. The first of them is the so-called skin effect, which is characterized by the displacement of current streams from adjacent wires. This effect leads to an increase in the resistance of the power lines, which is proportional to the higher harmonic frequency. The second one is related to the neutral wire and the triple harmonic current flowing in it (3, 9, 15…), which in each phase have the same phase shift and due to summation in the neutral wire, the current value is significant, and due to the fact that it is not designed for high current values may be damaged due to overheating. [3]

Higher Harmonics Filtration Methods

In order to reduce the negative effects of higher harmonics in current and voltage waveforms, various methods are used to reduce their occurrence. Such methods include:

• active and passive higher harmonic filters
• appropriate connection of transformer windings
• reduction of higher harmonic values in the receiver current.

Higher harmonic filters are the most commonly used solution to improve the quality of electrical energy and eliminate distortions of current and voltage waveforms. They fulfill two basic roles: firstly, they provide reactive power at the fundamental frequency, and secondly, they relieve the network from the flow of harmonic currents. They can be divided into series, parallel, series-parallel, first, second and third order, but basically there are two types of filters: active and passive.

Passive filters consist of passive LC power electronic elements, the values of which are selected individually for a given object or receiver. Most often, they are connected as a shunt to the receiver’s power supply system. Their principle of operation is to select LC elements so that the resonant frequency of the resulting series circuit is equal to the value of the higher harmonic frequency that is to be eliminated. This creates a low-impedance path for the filtered frequencies. These filters are most often constructed as a single, separate branch filtering a specific harmonic. If the receiver generates harmonics of higher orders, e.g. above 17, a broadband filter is additionally used. Note that when designing LC filters, it is necessary to start with the lowest order harmonic, even when it is not dominant. This is due to the impedance characteristics of the filter system. A big advantage is that the use of an active filter eliminates not only the higher harmonics generated by the non-linear receiver, but also the harmonics already present in the power supply network. However, passive filters also have disadvantages, including: [3]:

• the effectiveness of filters depends on the impedance of the power supply system at the point of connection, which is usually unknown and changes during changes made to the network configuration,

• already at the stage of filter design, special attention should be paid to the frequency characteristics to avoid resonance phenomena that could lead to amplification of the harmonic signal,

• filters become detuned due to frequency changes,

• usually only characteristic harmonics are filtered, although other harmonics also occur, • they cause teletransmission interference.

Active filters are an alternative to passive filters and, compared to them, they have numerous advantages, including high operational stability, accuracy, ease of frequency tuning, lack of attenuation of the useful signal, and can even be used to amplify such a signal. They are also devoid of induction elements, which are very expensive. Another big advantage of this system is its flexibility in the case of expansion of a given installation, the filter can be easily adjusted to the current requirements, as well as the possibility of reactive power compensation.

Active filters work in follow-up mode, i.e. they automatically adjust to the receiver current. When using active filters, the distorting current components are closed in the filter-receiver circuit, without causing additional losses in the network supplying the given receiver, which generates interference. [4]

Most often, these types of filters are used in [5]:

• low-voltage networks with a large number of frequency converters,

• modern converter drives, with high harmonic feedback, but with low demand for reactive power,

• low voltage networks with mainly 3rd order harmonics and a large number of single-phase receivers. Such networks are characterized by relatively high current values in the neutral wire, which should not occur with a symmetrical distribution of loads on individual phases. As a result of the electronic load, in addition to possible asymmetries of resistive loads, harmonic currents accumulate in the neutral conductor, which may result in a higher current in the neutral conductor than in the phase conductor, leading to its overload, which is not intended for this purpose. In addition to the above higher harmonic filtering methods, there are other solutions used by manufacturers of equipment with non-linear characteristics. Such methods include, for example, input chokes in AC and DC circuits. They significantly contribute to reducing the THD value. Another element is the use of multi-pulse power supply systems. A larger number of pulses visibly reduces the distortion of the converter current, thus eliminating the negative effects of higher harmonics in the power supply network.

Actual measurements of higher harmonics

The measurements of electricity quality parameters presented in the article were carried out in a public building. There are electrical devices in the building which, through their operation, shape the final shape of current and voltage waveforms in the internal power supply network, and also influence the type of disturbances occurring in it. The main elements include elevator circuits, lighting and computer workstations. Overall, the installed load capacity is around 140 kW. However, please remember that the above devices will not all work together, at the same time, and in the case of engines with the same power, which depends on its load. When assuming a simultaneous operation factor of 0.6, the maximum instantaneous power consumed from the network is approximately 84 kW.

When analyzing the occurrence of higher harmonics in the network of a public building (Fig. 1), the 7th and 11th harmonics dominate, and to a lesser extent the 5th, 9th, 13th and 17th harmonics. A similar situation occurs in the current waveform (Fig. 2). Mainly there are harmonics of odd orders, up to the 19th harmonic. The next ones have a negligible impact on the voltage and current distortion.

Fig.1. Spectrum of higher voltage harmonics
Fig.2. Spectrum of higher current harmonics

After isolating the 5th harmonic (Fig. 3), an increase in values can be observed during the weekend, when most of the installed devices are turned off. The reason for this phenomenon may be the loads which, normally working on working days, additionally compensate for the 5th harmonic, or on these two days equipment was used whose characteristic harmonic is the 5th harmonic..

Fig.3. Waveforms of the 5th harmonic voltage in 3 phases

Another deviation is the occurrence of harmonic number 21 mainly in the L3 phase (Fig. 4 – blue). It means that single-phase devices are installed, which generate this harmonic characteristic.

Fig.4. Waveforms of the 21st harmonic voltage in 3 phases

Forecasting of higher harmonics occurrence

To predict the behavior of higher harmonics, one type of statistical series, which is a time series, can be used. It can be defined as a sequence of observations of a phenomenon in subsequent units of time, e.g. years, quarters, months.[14-17] The phenomenon under consideration may be subject to certain regularities, the detection and description of which is the purpose of time series analysis.[16]

The basic functions of time series include::

The regression function described by the formula:

.

The difference between empirical and model values described by the formula:

.

Seasonality index described by the formula:

.

Determination of modified theoretical values taking into account seasonality, described by the formula:

.

Forecasting described by the formula:

.

Based on the observations of harmonic variability, the type of seasonality can be identified. In the example discussed, it has an additive character.

The figures below show example charts of the seasonality function for a public building (Fig. 5).

Fig.5. An example chart of the seasonality function for a public building

Analyzing the charts (Fig. 5), it can be observed that the seasonality function has a positive trend. The measure of model fit is low. This is most likely due to the nature of the coefficient changes.

By determining the basic functions of time series in accordance with the relationship (1) and (5), the regression function and forecasting take the form:

.

The forecast increase in the occurrence of harmonics for a period of 24 months is 1.67.

Summary

The analysis of electricity quality parameters did not reveal any exceedances. It can be noticed that in both current and voltage waveforms there are higher harmonics that distort the signal. Odd harmonics predominate to the greatest extent, the 5th, 7th, 11th and 13th harmonics are characteristic of the voltage signal, and to a lesser extent the 3rd, 9th, 13th and 17th harmonics. The current waveform mainly contains the 5th and 7th harmonics. It can therefore be concluded that these are characteristic harmonics (5 and 7) of devices located in the building, such as:

• converter devices, i.e. computer power supplies prevailing in the building, as well as LED light sources. Their construction is based on semiconductor elements such as thyristors, diodes, etc. whose task is to adjust the network parameters so that the devices work properly, i.e. converting the alternating voltage into direct current and reducing its value for proper power supply,

• as well as high-power motors used in elevator drives.

When taking into account the type of facility that is a public building, the best solution would be to use an active filter to reduce the number of higher harmonics. This is justified by the positive seasonality trend. The work system in the analyzed facility proves that the building is continuously equipped with the latest equipment containing converter elements,

REFERENCES

[1] Kowalski.Z.: Power quality. Monographs of the Lodz University of Technologyj. Łódź 2007.
[2] Fuchs E., Masoum M.: Power Quality in Power Systems and Electrical Machines. Elsevier Inc., 2008. 205
[3] Z. Hanzelka, Quality of electricity supply, Krakow: Publisher
AGH Krakow, 2013
[4] K. Kuczyński, J. Szymański,Harmonic compensation – introduction to active filters, elektro.info 12/2020
[5] https://jeanmueller.pl/filtry-aktywne-wyzszych-harmonicznych/
[6] A.Klajn, M.Bątkiwicz-Pantuła, Application Note – Standard EN 50 160: Voltage characteristics of electricity supp
[7] EN 50160:2010. Voltage characteristics of electricity supplied by public electricity networks.
[8] Decree of the Minister of Climate and Environment of March 22, 2023 on detailed conditions for the operation of the electricity system (Dz. U. 2023 r., 819).
[9] Heping P., Wenxiong M,. Yong W., Le L., Zhong X. Identification method for power quality disturbances in distribution network based on transfer learning, Archives of Electrical Engineering , 2022 , vol. 71 , No 3 , 731-754
[10] Baggini A., Hanzelka Z., Voltage and Current Harmonic, Handbook of Power Quality, Whiley, 2008, 200-236
[11] EN 61000-4-30:2015 Electromagnetic compatibility (EMC) – Part 4-30: Testing and measurement techniques – Power quality measurement methods
[12] Chojnacki A. Ł., Kończak Z., Seasonality and causes of damage to power distribution networks, Elektro.info 7-8/2023, 2023
[13] Golkhandan, N.H.; Ali Chamanian, M.; Tahami, F. A New Control Method for Elimination of Current THD under Extremely Polluted Grid Conditions Applied on a Three Phase PWM Rectifier. In Proceedings of the INTELEC, International Telecommunications Energy Conference (Proceedings), Turino, Italy, 7–11 October 2018
[14] Kot S., Jakubowski J., Sokołowski A., Statistics, Difin, Warszawa 2011
[15] Sokołowski A., Time series analysis and forecasting, Statistics in research and teaching statistics, Statsoft, Kraków 2010
[16] Ręklewski M. Descriptive statistics. Theory and examples. State Vocational University in Włocławek, Włocławek 2020
[17] IEA,Management Seasonal and Interannual Variability of Renewables , IEA, Paryż https://www.iea.org/reports/managing-seasonal-andinterannual-variability-of-renewables, Licencja: CC BY 4.0, 2023
[18] Kuśmierek Z.: Harmonics in power systems, Przegląd Elektrotechniczny, 82 (2006), nr 6, 8-19
[19] PN-EN 61000-3-11:2020-01 Electromagnetic compatibility (EMC) – Part 3-11: Limits – Limitation of voltage variations, voltage fluctuations and flicker in public low-voltage power
supply networks – Equipment with a nominal current < or = 75 A subject to conditional connection
[20] PN-EN IEC 61000-3-2:2019 Electromagnetic compatibility (EMC) – Part 3-2: Limits – Limits for harmonic current emissions (phase supply current of the receiver ≤ 16 A)


Authors: dr inż. Marta Bątkiewicz-Pantuła, Wrocław University of Science and Technology, Faculty of Electrical Engineering, Power Electrical Department, ul. Wybrzeże Wyspiańskiego 27, 50-370 Wrocław, e-mail: marta.batkiewicz-pantula@pwr.edu.pl


Source & Publisher Item Identifier: PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 101 NR 2/2025. doi:10.15199/48.2025.02.52

Analysis of Power Quality Parameters at Facilities Connected to the Municipal Electricity Grid

Published by 1. Aleksander CHUDY1, 2. Paweł MAZUREK1, 3. Korneliusz PAWLAK2, Lublin University of Technology (1), Ball Packaging Europe Lublin Sp. z o.o. (2) ORCID: 1. 0000-0002-3183-8450, 2. 0000-0002-7098-2084


Abstract. In the present study, power quality parameters across two residential blocks, a single-family house, and an industrial facility were studied and evaluated. Compliance was generally satisfactory, with occasional voltage harmonic exceedances in residential and industrial areas and exceedances in THDV and long-term flicker perceptibility in the industrial setting, highlighting the need for continued monitoring and potential mitigation strategies.

Streszczenie. W badaniu dokonano oceny parametrów jakości energii elektrycznej w dwóch blokach mieszkalnych, domu jednorodzinnym oraz obiekcie przemysłowym. Zgodność była zadowalająca, choć sporadyczne przekroczenia harmonicznych w obszarach mieszkalnych oraz krótkotrwałe przekroczenia THDV i współczynnika długotrwałego migotania światła obiekcie przemysłowym podkreślają konieczność ciągłego monitorowania i potencjalnych strategii łagodzących. (Analiza parametrów jakości energii w obiektach przyłączonych do miejskiej sieci elektroenergetycznej)

Keywords: power quality, residential power supply, industrial power supply, harmonic distortion
Słowa kluczowe: jakość energii, zasilanie budynków mieszkalnych, dystrybucja energii dla przemysłu, zniekształcenia harmoniczne

Introduction

Nowadays, the necessity for reliable and high-quality power is vital across various sectors, ranging from residential to industrial settings. Ensuring the stability and efficiency of power supply networks is essential to satisfy the demands of occupants and sustain the productivity of industrial facilities [1, 2]. With this necessity in mind, this study gives an analysis of power quality parameters in networks providing apartment blocks, a single-family house, and an industrial facility.

For apartment blocks, the primary concern often revolves around managing diverse and fluctuating loads from multiple units within the same building. Issues such as harmonic distortion, voltage fluctuations, and power factor imbalance can arise due to the collective impact of various appliances and equipment used by residents [3].

In single-family houses, while the scale may be smaller compared to apartment blocks, similar concerns regarding load diversity and quality persist. Additionally, factors such as renewable energy integration, electric vehicle charging, and smart home technologies further complicate the energy quality landscape. Addressing these complexities requires tailored approaches to monitoring, analysis, and mitigation strategies [4].

Industrial facilities present a distinct set of challenges, often characterized by high-power loads, sensitive equipment, and stringent reliability requirements. Energy quality issues such as voltage sags, transients, and power interruptions can have significant operational and financial implications for these establishments. Therefore, comprehensive analysis of power quality parameters Is essential to minimize downtime, enhance productivity, and ensure regulatory compliance.

Furthermore, advancements in technology and regulatory frameworks play a crucial role in shaping the landscape of power quality management. The recent changes in Polish regulations regarding power quality parameters limits were introduced in Regulation of the Minister of Climate and Environment of 22 March 2023 on detailed conditions for the operation of the power system [5] partially based on the PN-EN 50160 standard. These updates replaced the previous regulation from 2007, reflecting ongoing efforts to ensure the effectiveness and relevance of standards within the power distribution sector. From this point forward in the article, the term regulation will refer to the 2023 regulation. Integration of renewable energy sources, deployment of smart grid technologies, and adherence to stringent quality standards are integral components of modern power supply networks.

The study [6] monitored and analysed various power quality parameters in a typical commercial building with non-linear loads like computers, printers, and compact fluorescent lamps. The proliferation of non-linear loads their harmonic current injections was identified as the root cause behind most of the major power quality issues observed.

In [3] issues such as voltage/current unbalance, harmonics, and power factor in residential loads (lights, fans, AC/DC drives) and a real-time system with multiple single-phase AC servo motors were analysed. Experimental results showed significant voltage unbalance, current total harmonic distortion (THDi) reaching 120%, and poor power factors ranging from 0.25 to 0.75 due to the non-linear nature of the loads. The authors highlighted the need for mitigation techniques like active power filters to reduce harmonics and improve power quality when operating multiple non-linear household/industrial loads.

The study [4] presents one-minute resolution measurements of voltage, THDi, active/apparent power, and power factor for 17 common household appliances like lights, fans, AC units, washing machines. Key results include maximum THDi reaching 120%, THDV up to 3%, and poor power factors from 0.25 to 0.8 across different residential loads.

Methodology

Measurements of power quality parameters were carried out using different devices and lengths of averaging time for each kind of location.

a) Residential Blocks

Power quality measurements were undertaken utilizing the Sonel PQM-711 power quality analyser equipped with F-5A current clamps. The measurements encompassed a distribution transformer serving two residential blocks in lubelskie voivodeship, each comprising 77 flats. Opting for a measurement duration of 2 days, an averaging time of 3 seconds was implemented to enable the analysis of current harmonics in compliance with the IEEE 519-2022 standard.

b) Single-Family House

The power quality measurements were conducted using the Chauvin Arnoux 8336 power quality analyser paired with MA193 current clamps. Given the lower complexity of the load profile, the measurements were conducted for a duration of 4 hours. The averaging time for measurements was set to 1 minute to achieve a balance between obtaining detailed data and decreasing measurement duration.

c) Industrial Facility:

The power quality measurements were conducted within an industrial facility located in Lublin, part of the city’s economic zone. The facility, established in 2008, initially intended to produce food cans but later shifted its focus to manufacturing aluminium lids. The production process is highly automated. High-tech components such as PLC controllers, frequency converters, servo drives, and realtime plant visualization systems are integral to the production modules.

The measurements were performed using the Sonel PQM-711 power quality analyser. Due to the higher complexity of the industrial load and the need for comprehensive data collection, the measurements were conducted over a two-week period. The averaging time for measurements was set to 10 minutes.

During the first week, the measurements were exclusively performed at substation R4, while in the second week, attention shifted to substation R2. Substation R4 serves critical functions, including powering machinery supporting the third production module and supplying compressor with a capacity of 200 kW. Additionally, it provides power to another substation, responsible for one of the production modules. On the other hand, substation R2 is tasked with powering essential systems for facility maintenance, such as internal and external lighting, server rooms, UPS emergency power supplies, cooling for production presses, heaters, ventilation, waste disposal presses, and other 2 compressors each with a capacity of 200 kW.

The Sonel PQM-711 analyser adheres to the IEC 61000-4-30 Class A standard, while the Chauvin Arnoux 8336 analyser complies with the IEC 61000-4-30 Class B standard.

These specific measurement setups and durations enabled for complete investigation of power quality parameters in varied circumstances, guaranteeing reliable data collection and valuable insights into the functioning of the individual power supply networks.

Results

a) Phase voltage profile and voltage unbalance The voltage profile diagram (Fig. 1.) shows the RMS voltage values for the three phases (UL1, UL2, and UL3) over a two-day period concerning residential blocks. The red lines in the diagram represent the voltage limits specified by the PN-EN 50160 standard, which allows for a ±10% deviation from the nominal voltage of 230V. Based on the diagram, the voltage values for all three phases remain within the upper and lower limit, indicating that the voltage magnitudes comply with the PN-EN 50160 standard requirements.

In each graph presented within this article, the red line serves as a clear indicator of the permissible values defined in the PN-EN 50160 standard.

The RMS voltage profile measured at a switchboard in a single-family house over a 4-hour period is presented in Figure 2. The highest peaks are around 235–237 V for all three phases (maximum value: 237.6 V, phase L2) which is still within the PN-EN 50160 standard limit. The lowest measured voltage value was 232.9 V for phase L2.

Figure 3 illustrates voltage fluctuations measured in distribution substations R4 and R2. The cyan line demarcates the division between measurements from substations R4 and R2. For distribution substation R4, the RMS voltage fluctuates between a minimum of 232 V and a maximum of 242 V meeting regulatory requirements. In the case of distribution substation R2, the RMS voltage ranges from a minimum of 235 V to a maximum of 246 V.

The 95th percentile of voltage unbalance factor was found to be 0.29%, 0.33%, and 0.31%/0.31% for the residential blocks, single-family house, and industrial facility (R4/R2), respectively. This indicates that the measured voltage unbalance falls well within the limits established by the PN-EN 50160 standard.

Fig.1. RMS Voltage Profile (two residential blocks)
Fig.2. RMS Voltage Profile (single-family house)
Fig.3. RMS Voltage Profile (industrial facility)

b) Total harmonic distortion of voltage

The 95th percentile values for phases L1, L2, and L3 were obtained for the distribution substation supplying two residential blocks and the switchboard at a single-family house. Additionally, diagrams illustrating THDV levels were provided for the industrial facility.

At the distribution substation supplying two residential blocks, THDV levels were within acceptable limits according to limit established by PN-EN 51060 standard. The 95th percentile values for phases L1, L2, and L3 were 2.86%, 2.66%, and 2.95%, respectively. Similarly, the THDV measurements at the switchboard of the single-family house indicated relatively low levels of harmonic distortion, with 95th percentile values of 2.2%, 2.1%, and 2.0% for phases L1, L2, and L3, respectively.

For the industrial facility, analysis of THDV revealed noteworthy findings. At substation R4, THDV values ranged from a minimum of 2.75% to a maximum of 5%. The values of 95th percentile were 4.23%, 4.34%, 4.32% for phases L1, L2 and L3, respectively. Well within the criteria specified in the previously mentioned standard (8%). Conversely, substation R2 exhibited significantly higher THDV values, the values of 95th percentile were 7,28%, 7,77%, 7,68%. Disturbances introduced by frequency converters and electric motors were observed in substation R4, while anomalies from energy-efficient LED lighting throughout the facility were noted in substation R2.

Figure 4 presents THDV levels at the distribution substations at the industrial facility.

Fig.4. Total harmonic distortion of voltage variation (industrial facility)

c) Voltage harmonics

One significant change introduced by the 2023 regulation [5] is the requirement to analyse voltage harmonics up to the 50th harmonic order, doubling the previous scope of analysis which only extended to the 25th harmonic. This expanded scope reflects advancements in power system monitoring and the recognition of the impact of higher-order harmonics on system performance and equipment operation.

By extending the analysis to the 50th harmonic order, a more comprehensive assessment of voltage harmonics can be achieved, enabling a deeper understanding of potential harmonic distortion effects on the power supply network. This enhanced analysis is essential for ensuring compliance with regulatory standards, optimizing power system performance, and mitigating risks associated with harmonic distortion.

At a distribution substation supplying two residential blocks it was observed that the 15th harmonic order for phase L3 exceeded the prescribed limit of 0.5%. The measurements revealed 95th percentile values of 0.5%, 0.41%, and 0.55% for phases L1, L2, and L3, respectively. The examination revealed no additional exceedances beyond the 15th harmonic order, with the 5th and 7th harmonics emerging as the most prominent. Figure 5 depicts voltage harmonic values from the 2nd to the 25th order. Harmonic values from the 26th to the 50th order were negligible, warranting their exclusion from further analysis.

Fig.5. Voltage harmonic spectrum (95th percentile; two residential blocks)

In the single-family house, values of voltage harmonics across phases were below standard thresholds. For instance, the 3rd harmonic showed values of 1%, 0.6%, and 0.6% across phases L1, L2, and L3, respectively, below the limit of 5%. Similarly, the 5th harmonic displayed values of 1.5%, 1.6%, and 1.6%, below the limit of 6%. Harmonics like the 7th, 9th, and 11th also stayed within acceptable limits, with slight variations across phases. Voltage harmonics values beyond the 15th order up to the 50th were negligible, indicating minimal impact on power quality.

At substation R2, the 95th percentile values for the 5th harmonic across phases L1, L2, and L3 were 6.09%, 6.56%, and 6.38%, respectively, exceeding the specified limit of 6%. This indicates a potential issue with power quality at the substation that warrants further investigation and mitigation measures. However, at substation R4, the corresponding values were 3.67%, 3.84%, and 3.81%. Further analysis identified the most dominant voltage harmonics observed, including the 5th, 7th, 9th, 11th, 13th, 17th, 19th, 23rd, and 25th harmonics. Despite variations in their magnitudes, all of these harmonics remained within the specified limits, indicating satisfactory power quality conditions at the industrial facility.

d) Long-term flicker perceptibility

At the distribution substation supplying two residential blocks, the 95th percentile PLT values for phases L1, L2, and L3 were 0.6, 0.31, and 0.3 respectively, all falling within the limit (1) of PN-EN 50160 standard.

At a single-family house switchboard, the 95th percentile PLT values for the same phases were observed to be 0.82, 0.88, and 0.81, also adhering to the standard. At this point, the PLT calculation was updated in a two-hour window every 10 minutes due to the short duration of measurement, with most values falling within the range of 0.3 to 0.45.

In the industrial facility, the PLT values fluctuated mostly within the range of 0.3 to 0.45 phases L1, L2, and L3, respectively. However, it is worth mentioning that two events occurred where the PLT value exceeded 1, with one event recorded at substation R4 (1.34 – phase L2) and another at substation R2 (1.39 – phase L3). Nevertheless, it did not cause non-compliance with the PN-EN 50160 standard.

e) Power frequency

In all points of measurement – the values of power frequency were well within the acceptable limits with a significant margin of the limit (50 Hz ± 1%). Therefore, further consideration of this parameter is deemed unnecessary for the analysis in this article. The 99.5th percentiles for frequency were measured as 50.03 Hz, 50.04 Hz, and 50.03 Hz for residential blocks, single-family house, and industrial facility, respectively, reaffirming the stability of the parameter.

f) Current harmonics

In the assessment conducted for the case involving two residential blocks, an analysis of current harmonics was undertaken. While the PN-EN 50160 standard and the regulation do not explicitly address current harmonics, the requirements outlined in IEEE 519-2022 were employed.

The analysis was divided into two separate periods of 24 hours each to analyse variations in load profiles. The daily limits specified for the short-circuit current (ISC) to the maximum demand load current (IL) ratio less than 20 were considered (99th percentiles values; very short time, 3 s, harmonic currents). The maximum demand load current was determined as the highest average fundamental current across all recorded current channels during the measurement period (103.1 A). The values of the 99th percentiles of current harmonics for the 3rd harmonic were recorded as 7.69 A, 7 A, and 7.07 A for phases L1, L2, and L3, respectively.

These values were compared against the IEEE 519-2022 limit of 8.25 A, which corresponds to 8% of IL. These measurements approached the limit, particularly in the case of phase L1, indicating a potential proximity to the threshold for acceptable harmonic distortion. Further examination revealed that the remaining values of 99th percentiles across the harmonic spectrum were lower, with significant decreases observed, especially in the 26th to 50th order region.

Figure 6 presents the 99th percentile values of current harmonics recorded during the first 24 hours of measurements.

Fig.6. Current harmonic spectrum (99th percentile; two residential blocks)
Conclusions

In summary, the power quality assessment across residential blocks, the single-family house, and the industrial facility reveals satisfactory compliance in most parameters. However, the presence of the 15th voltage harmonic exceedance in residential blocks and the 5th voltage harmonic in the industrial facility, as well as occasional short exceedances in THDV and long-term flicker perceptibility in the industrial facility, warrant further attention. Table 1 presents the compliance status of each parameter, emphasizing the need for ongoing monitoring and potential mitigation strategies to ensure sustained power quality.

Table 1. Power quality parameters assessment (results by location)

.

This work was supported by Lublin University of Technology grant no. FD-20/EE-2/403.

REFERENCES

[1] Chudy A., Mazurek P., Electromobility – the Importance ofPower Quality and Environmental Sustainability, Journal of Ecological Engineering, 20 (2019), No. 10
[2] Chudy A., Hołyszko P., Mazurek P., Fast Charging of an Electric Bus Fleet and Its Impact on the Power Quality Based on On-Site Measurements, Energies, 15 (2022), Nr 15, p. 5555
[3] Thentral T. T., Palanisamy R., Usha S., Bajaj M., Zawbaa H. M., Kamel S., Analysis of Power Quality issues of different types of household applications, Energy Reports, 8 (2022), 5370-5386
[4] Garabitos Lara E., Electrical dataset of household appliances in operation in one apartment, Data in Brief, 51 (2023)
[5] Minister of Climate and Environment. Regulation of the Minister of Climate and Environment of 22 March 2023 on detailed conditions for the operation of the power system, 2023
[6] Ojo A., Awodele K., Sebitosi A., Power Quality Monitoring and Assessment of a Typical Commercial Building. In: 2019 IEEE AFRICON; IEEE, 92019, 1-6


Author: dr inż. Aleksander Chudy, dr inż. Paweł Mazurek, Department of Electrical Engineering and Smart Technologies, Lublin University of Technology, Nadbystrzycka Street 38A, 20-618 Lublin, e-mail: a.chudy@pollub.pl, p.mazurek@pollub.pl; mgr inż. Korneliusz Pawlak, Ball Packaging Europe Lublin Sp. z o


Source & Publisher Item Identifier: PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 101 NR 2/2025. PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 101 NR 2/2025

Recommendation for a Structure and Fuzzy Logic Control of a Common Storage System between Autonomous Photovoltaic Systems

Published by 1. Ali Boukerche1, 2. Salima Lekhchine1, 3. Tahar Bahi2, Department of Mechanical Engineering, Faculty of technology, University of 20 August 1955, LGMM Laboratory, Skikda, Algeria (1), Department of Electrical Engineering,Faculty of technology, Badji Mokhtar University, Laboratory (LASA) , Annaba, Algeria (2) E-mail: a.boukerche@univ-skikda.dz


Abstract. At present, energy saving and renewable energies represent one of the most important axes of sientific research. One of these renewable energies is solar energy, which has two aspects: solar thermic and solar photovoltaic; this energy is highly coveted due to its availability, but the cost of this energy remains very high, specially for autonomous installations where there are storage batteries. the aim of this work is to minimise the invisible cost of storage and to promote energy saving using a connected network energy management system controlled by fuzzy logic.. There are several types of storage batteries, including batteries that are less expensive in terms of storage capacity and price (Wh/Price), such as OPZS batteries, but they cannot be used for a single consumer because their capacity is very large. In our work, we propose a collective storage structure between multiple variable loads, and each load is equipped with a photovoltaic generator that supplies the same storage bus. Fuzzy logic is used to collect information on the behaviour of loads, in other words the consumers, their compliance with the consumption instructions set in advance, as well as the degree of contribution to recharging the collective storage bus. Using mathlab simulink, we have performed a simulation of the proposed system. The result is that the program classifies the consumers and gives them a quantity of energy from the storage bus according to their class, a quantity that can be estimated using fuzzy logic. This approach can be used in a number of different ways, either by the electricity network distributors by installing collective storage buses in each utility, with multiple benefits such as the use of the storage bus as a back-up source in the event of a network failure to ensure continuity of service, energy savings, because consumers will try to save as much energy as possible in order to have a good rating and benefit from more energy in unfavourable weather conditions. It will also enable the electricity distributor to have a more smart and better-controlled grid, because consumers will respect hourly power consumption thresholds to have a better rating at all times instead of varying consumption rates on an hourly basis, as many suppliers do, to avoid consumption peaks that cause problems on the electricity network, such as voltage drops. Or co-location in a collective storage bus for off-grid installations to minimise the investment cost of the storage bus and be more respectful of the environment.

Streszczenie. Obecnie oszczędzanie energii i odnawialne źródła energii stanowią jedną z najważniejszych osi badań naukowych. Jedną z tych odnawialnych energii jest energia słoneczna, która ma dwa aspekty: słoneczną energię cieplną i słoneczną energię fotowoltaiczną; energia ta jest bardzo pożądana ze względu na jej dostępność, ale koszt tej energii pozostaje bardzo wysoki, szczególnie w przypadku autonomicznych instalacji, w których znajdują się akumulatory. Celem tej pracy jest zminimalizowanie niewidocznych kosztów magazynowania i promowanie oszczędzania energii przy użyciu połączonego sieciowego systemu zarządzania energią kontrolowanego przez logikę rozmytą. Istnieje kilka rodzajów akumulatorów, w tym akumulatory, które są tańsze pod względem pojemności i ceny (Wh / Cena), takie jak akumulatory OPZS, ale nie można ich używać dla pojedynczego konsumenta, ponieważ ich pojemność jest bardzo duża. W naszej pracy proponujemy zbiorczą strukturę magazynowania między wieloma zmiennymi obciążeniami, a każde obciążenie jest wyposażone w generator fotowoltaiczny, który zasila tę samą magistralę magazynową. Logika rozmyta jest wykorzystywana do zbierania informacji na temat zachowania obciążeń, innymi słowy konsumentów, ich zgodności z instrukcjami zużycia ustalonymi z wyprzedzeniem, a także stopnia wkładu w ładowanie zbiorczej magistrali magazynowej. Korzystając z programu Mathlab Simulink, przeprowadziliśmy symulację proponowanego systemu. W rezultacie program klasyfikuje konsumentów i daje im ilość energii z magistrali magazynowej zgodnie z ich klasą, ilość, którą można oszacować (Zalecenia dotyczące struktury i sterowania rozmytego wspólnego systemu magazynowania pomiędzy autonomicznymi systemami fotowoltaicznymi)

Keywords: Photovoltaic,MPPT,Storage,Battery,Fuzzy logic,Energy management.
Słowa kluczowe: Fotowoltaika, MPPT, magazynowanie, akumulator, logika rozmyta, zarządzanie energią.

Introduction

Nowadays, the ever-increasing need for electrical energy throughout the world requires an increase in the production of electrical energy in order to satisfy this need and therefore requires the establishment of a significant number of power stations.

Indeed, to satisfy the growing demand for electrical energy, several types of conventional power plants are installed [1-3]. These stations use as raw material the fossil energies which are known as not-renewable, they are polluting and have a negative impact on the environment, and are also being depleted [4,5]. This goes against the current standards and issues defined for the environment. To overcome these problems, governments have adopted as an indispensable solution the promotion of electric energy production facilities based on renewable resources such as solar energy, wind energy, biomass etc…[6-8]. However, solar energy is the most used because of its wide availability. It is divided into two types, the first type being solar thermal, a partly chemical process generally used in high power plants (thermo-solar power station) and the second type is the photovoltaic solar energy which can be used for large as well as for small powers [9,10].

In this work we are interested to design an optimal structure and to propose the power management of solar photovoltaic installations not connected to the distribution network (autonomous) equipped with a common storage system. The storage system consists of a set of lithium batteries with deep discharge of voltage 2V particularly batteries OPZS: O: Ortsfest (stationary), PZ : PanZerplatte (tubular plate) and S : Flüssig (flooded) which are designed on the basis of an electrical energy storage technology particularly adapted to photovoltaic solar systems [11]. These batteries are made of positive and negative lead plates, separated by separators and immersed in a liquid electrolyte. In contrast to other types of batteries, OPZS batteries have the advantage of being transparent, which makes it easy to see the condition of the plates and electrolyte [12]. They have a relatively long life, which makes them an interesting choice for applications requiring long-term storage of the renewable energy produced. However, to obtain 24V or 48V storage bus, several of these batteries are needed, which is appropriate for large load. They are used as an intermediary to all production facilities in order to optimize the investment on storage bus and promote the saving of electrical energy. Nevertheless, to ensure their optimal use, a large load or several medium loads are required. This is the subject of our work as well as the promotion of economy of electrical energy.

Structure and modeling

Structure In this work a new structure of an electrical network consisting of a collective storage bus between several isolated sites with a photovoltaic generator each one is proposed. The charging and discharging system of each installation is based on a Buck-boost converter and a proportional integral (PI) controller. The systems will be interconnected using a control system based on fuzzy logic that will take into consideration the energy delivered by each system to the storage bus as well as the consumption mode of each system in order to incite the users to better consume and respect the energy consumption thresholds.

Using MatLab/Simulink software, we have developed a system composed of 4 photovoltaic generators two of them composed of five of 215Wp panels which are the GPV1 and GPV4, 4 panels of the same type for GPV2 and 3 panels for GPV3 all equipped with a Boost converter with a Maximal Power Point Tracking (MPPT) incremental control, each one of them powering a variable load with different variations for each load, the set of loads connected to storage bus 120Ah- 24V controlled by a controller based on fuzzy logic as shown in the Fig.1.

Fig.1. Global diagram of the chain
Modeling Photovoltaic cell model

The photovoltaic cell is the basic element of a solar panel and consists of a current generator and a diode, as well as two resistors – one in series (Rs) and one in parallel (Rsh). The equivalent electrical circuit of this cell is shown in the Fig.2.and considered this figure we can deduce the expression of the current [13-15]:

Fig.2. Equivalent model of photovoltaic cell
.

Where, I0 (A): diode saturation current; K: constant of Boltzmann (1, 380649×10-23 m2 kg s-2 K-1); q: charge of the electron; T: temperature; n: factor of diode junction; IL (A): short-circuit current; ID (A): current through the diode; IRsh (A) : current through the shunt resistor.

DC-DC converters

A DC/DC converter is an electronic device that converts a DC voltage from one power source to another DC voltage of a different level, usually using a pulse width modulation (PWM) technique [16,17]. There are several types of DC/DC converters, each with different characteristics and advantages, such as Buck converters it converts a high input voltage to a lower output voltage, Boost Converter: it converts a lower input voltage to a higher output voltage, and the Buck-Boost Converters it can convert a high input voltage to a lower output voltage or convert a lower input voltage to a higher output voltage. The table 1 shows the most frequently used DC/DC converter models [18-20].

Table 1. Converters DC/DC

.
Boost converter model

The mathematical model of the boost converter is derived by applying Kirchhoff’s laws to the basic schematic of the converter, as shown in Fig.3 and taking into account the mode of operation and the state of the S-switch. In other words, the principles of conservation of energy and electrical load are used to describe the behavior of the boost converter under different operating conditions as a function of parameters such as input voltage, connected load, and the switching frequency of the S switch [21].

Fig.3. Equivalent model of Boost converter
.

The dynamic equations of the boost converter are derived for the current in the inductor and the voltage across the capacitor in the continuous conduction regime, where IL is the current in the inductor L, E is the input voltage, Vdc is the output voltage, and U is the control. For x1 =IL and x= Vdc then the equations of state become:

.

The equation of state of the boost converter thus becomes:

.
Buck-boost converter model

To present the functioning of a converter of this type in the form of mathematical equations, it is necessary to consider the state of the switch S, as shown in the Fig.4 When the switch is in the ON position, the time Ton during which it is conducting is equal to α times the switching period Ts. During this phase, the energy stored in the circuit inductor increases. On the other hand, when the switch is OFF, the time Toff during which it is not conducting is equal to (1-α) times the switching period Ts. During this phase, the energy stored in the inductor is transferred to the capacitance and the load connected to the converter [22].

Fig.4. Equivalent model of Buck-Boost converter
.

The equation of state of the buck boost converter gives:

.
Incremental MPPT technique

This technique requires the use of two sensors to measure the output voltage and current [23-25]. It uses the derivative of current with respect to voltage (dI/dV) to estimate the derivative of power with respect to voltage (dP/dV). When dI/dV equals (-I/V), the algorithm detects that the maximum power point (MPP) has been reached, and it then stops to return the appropriate operating voltage value for the Maximum power point. Figure 5 shows the algorithm for the incremental technique to track the maximum power bridge.

Fig.5. Flowchart of the incremental MPPT
Charge controller

The voltage control system is a technique commonly used in photovoltaic systems to charge the batteries by imposing a voltage set point. Using a Buck-Boost DC/DC converter, this technique is very efficient because it allows to maintain the battery voltage at an optimal level according to the state of charge or discharge, which prolongs its life [26].The operation of the imposed voltage charge controller is simple the system follows the imposed voltage set point and adjusts the current according to the load requirements. In other words, the current is adapted in real time to meet the requirements of the load and the availability of the energy delivered by the PV array.

Figure 6 illustrates this process the voltage is controlled to remain constant, while the current varies according to the demands of the load. This technique maximizes the battery’s charging efficiency while protecting it from over- or under-charging, thereby significantly extending its life.

Fig.6. Control diagram of the storage system

2.2.5. fuzzy logic controller

Fuzzy logic is a method of information treatment that makes it possible to model complex systems by using fuzzy sets and variables that can take gradual values. This technique is largely used in electrical engineering for the control of control systems, the control of electric motors, robotics and image and signal processing systems [27-29]. Several fuzzy logic source management projects have been proposed by classification, as in [30] In our case we are going to use it to manage the quantity of energy delivered by the storage batteries according to the acquired data of the system, the input parameters of our fuzzy controller are the using factor that varies from 0 to 20 from very good user to very bad user and the second parameter and the giving factor that varies from 0 to 100% of the delivered energy according to the rules mentioned in the Table 2. To assure the good functioning and the longevity of the battery the energy that is delivered between the four systems will be limited to a threshold of 30% of the battery autonomy to avoid the deep discharge harmful to the battery, the rules established for the fuzzy system are as in Table 2.

Table 2. Fuzzy log

.

We will have the amount of energy to be delivered for each user at night or in bad weather and even in the case of pane. Figure 7 shows the conversion of the numerical input variables into linguistic variables. The abbreviations used for the using factor (UF) are VGU,GU,MGU,MU,MBU,BU and VBU are relative to very good user, good user, middle good user, middle bad user, bad user and very bad user this variable of between vary sell the respect of the consumer to the consumptions instructions.

.

With the condition If t=0 UFn=Cn else UFn= Cn/t

For the second input variable delivering factor (DF) we have VLD, LD, MLD, MHD, HD and VHD for very low deliverer, low deliverer, middle low deliverer, middle high deliverer, high deliverer and very high deliverer this parameter varies according to the ratio between the energy delivered by a GPVn system to the storage bus and some of the energy delivered to the storage bus by all the photovoltaic generators.

.

For t ∈ [(𝐸≥𝐸𝑥);(𝐸<𝐸𝑥)]

Fig.7. Fuzzy input/output variables

We note that Ex is the irradiation sufficient for the availability of photovoltaic energy in our case we have taken 100w/m², the data processing is done according to the program in Fig.8.

Fig.8. Fuzzy controller program

The system operates according to the flow diagram in the figure Fig.9 at time t≥t(Ex) for t(Ex) is the time when the photovoltaic system receives a large enough irradiation to develop a considerable power in our case we took E=100w/m² the data calculation is done during the period t ∈ ]𝑡(𝐸≥𝐸𝑥); 𝑡(𝐸<𝐸𝑥)] equivalent to one day of production to then deliver the energy from the storage bus at period t ∈ [𝑡(𝐸<𝐸𝑥); t (𝐸≥𝐸𝑥)] according to the giving factor estimated by the fuzzy algorithm at the end of the cycle the acquired data Uf and Df will be deleted to make place for the new data. Figure 9 shows the detailed operation of the controller for a simulation period relating to a normal day.

Fig.9. Fuzzy Logic control chart
Simulation result and discussion

The proposed structure and control was developed in Matlab/Simulink to analyze the performance of our approach and its validation under different operating profiles inspired by real cases considering a constant temperature of 25°C and a variable irradiation profile as shown in the Fig.10.

The time of data collection is from t=4.2s corresponding to an ‘irradiation E≥100W/m² which is proportional to the dawn and the distribution of stored energy is done from the moment t=17.5 or the irradiation E<100W/m² which is proportional to the twilight two simulation phase one with the fuzzy controller deactivated in second with the fuzzy controller activated.

Fig.10. Irradiation and temperature of the system

However, under the effect of climatic profiles (constant temperature and variable irradiation) of the figure 10, the evolution of the recommended power as well as the powers actually consumed by each load as a function of time, respectively shown by the dashed lines and the solid lines of the Figure 11.

Fig.11. Loads behaviors

With the knowledge of the evolution of the powers consumed by the various loads as well as the set point of consumption according to the laws of calculation establishes the factor of use Uf and the factor of donation Df which reflect respectively the respect of each load with regard to the set point of consumption and the quantity of energy delivered to the bus of storage by each system compared to the totality of the energy received by the bus of storage, the Figures 12 and 13 illustrate these two factors

Fig.12. Using Factor (UF)
Fig.13. Delivering Factor (DF)

Figure 14 shows the energy delivered by the photovoltaic generator, the consumption of the loads and the energy delivered to the storage bus of the four systems respectively. Figure 15 shows the state of charge of the battery (soc) its current and voltage without application of the fuzzy controller, We notice that the battery was charged from t=11s to t=16s the period where there was an excess of energy production. We also notice that the GPV 02 and 03 are the most implied in terms of charge of the battery having a good factor of Delivering (Df) while respecting the consumption The GPVs 01 and 04 did not contribute practically to the battery charge, however, in terms of respecting the consumption set point, the load four is higher than the load 01 (Uf04>Uf01) as shown in figures 11 and 12.

Fig.14. Energy of the system without application of the Fuzzy controller

Fig.15. Battery states

Figure 16 shows the energy delivered by the PV array, the consumption of the l loads and the energy delivered to the storage bus of the four systems but this time applying the fuzzy logic controller. Figure 17 shows the thresholds set by the fuzzy system and the consumption of each load of the storage bus. It can be seen that load 01 has been excluded at t=19s because it has a bad Uf and Df factor and it requires a large current as shown in Fig.19.

Fig.16. Energy of the system with application of the Fuzzy controller

Fig.17. Limits controller

Fig.18. Switching states

Fig.19. Battery states

Conclusion

At the end of this work, it was proven that it is possible to make photovoltaic installations with storage, which are classified among the most expensive photovoltaic installations, more profitable by investing in a collective storage bus while inciting consumers to respect consumption thresholds to promote energy saving and ensure a good continuity of service whatever the climatic conditions to which the installations are solicited and also in the event of unexpected defect occurring in one of the installations. Furthermore, the proposed structure encourages users to save electrical energy and allows suppliers to better manage their facilities by prescribing energy consumption guidelines to users and can also be designed for a more complex system.

REFERENCES

1. MD. LEONARD, E.E.MICHAELIDES and D. MICHAELIDES, Energy storage needs for the substitution of fossil fuel power plants with renewables. Renewable Energy,145, pp. 951-962 (2020).doi: https://doi.org/10.1016/j.renene.2019.06.066
2. SO. AMROUCHE, D. REKIOUA, T. REKIOUA and al. Overview of energy storage in renewable energy systems. International journal of hydrogen energy, 41, 45, pp 20914-20927 (2016).doi: https://doi.org/10.1016/j.ijhydene.2016.06.243
3. M. UMAR, X. JI, D. KIRIKKALELI and al. The imperativeness of environmental quality in the United States transportation sector amidst biomass-fossil energy consumption and growth. Journal of Cleaner Production, 285, pp.124863 (2021).doi: https://doi.org/10.1016/j.jclepro.2020.124863
4. F. GUANG, Electrical energy efficiency of China and its influencing factors. Environmental Science and Pollution Research, 27, 26, pp. 32829-32841 (2020). doi: https://doi.org/10.1007/s11356-020-09486-6
5. Ayat Y., Badoud A.E., Mekhilef S., Gassab S. Energy management based on a fuzzy controller of a photovoltaic/fuel cell/Li-ion battery/supercapacitor for unpredictable, fluctuating, high-dynamic three-phase AC load. Electrical Engineering & Electromechanics, 2023, no. 3, pp. 66-75. doi: https://doi.org/10.20998/2074-272X.2023.3.10:
6. A. SHARIF, M. BHATTACHARYA, S. AFSHAN and al. Disaggregated renewable energy sources in mitigating CO2 emissions: new evidence from the USA using quantile regressions. Environmental Science and Pollution Research,28 ,41, pp.57582-57601 (2021). doi: https://doi.org/10.1007/s11356-021-13829-2
7. SK. BHATIA, AK. PALAI, A. KUMAR, and al. Trends in renewable energy production employing biomass-based biochar. Bioresource Technology,340, pp. 125644 ( 2021). doi: https://doi.org/10.1016/j.biortech.2021.125644
8. Ali Moussa M., Derrouazin A., Latroch M., Aillerie M. A hybrid renewable energy production system using a smart controller based on fuzzy logic. Electrical Engineering & Electromechanics, 2022, no. 3, pp. 46-50. doi: https://doi.org/10.20998/2074-272X.2022.3.07 PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 100 NR 6/2024 263
9. A. BORETTI, Integration of solar thermal and photovoltaic, wind, and battery energy storage through AI in NEOM city. Energy and AI, 3,pp.100038(2021). doi:https://doi.org/10.1016/j.egyai.2020.100038
10. U. EICKER, A. COLMENAR-SANTOS, L. TERAN and al. Economic evaluation of solar thermal and photovoltaic cooling systems through simulation in different climatic conditions: An analysis in three different cities in Europe. Energy and Buildings,70, pp. 207-223 (2014). doi: https://doi.org/10.1016/j.enbuild.2013.11.061
11. R. DUFO-LÓPEZ, T. CORTÉS-ARCOS, JS. ARTAL-SEVIL and al. Comparison of lead-acid and li-ion batteries lifetime prediction models in stand-alone photovoltaic systems. Applied Sciences,11, 3, pp. 1099 (2021). doi: https://doi.org/10.3390/app11031099
12. A. KARAFİL, H. ÖZBAY, Design of Stand-Alone PV System on a Farm House in Bilecik City, Turkey. El-Cezeri,5,3,pp.909-916 (2018). doi: https://doi.org/10.31202/ecjse.352826
13. Latreche S., Khenfer A., Khemliche M. Sensors placement for the faults detection and isolation based on bridge linked configuration of photovoltaic array. Electrical Engineering & Electromechanics, 2022, no. 5, pp. 41-46. doi: https://doi.org/10.20998/2074-272X.2022.5.07
14. AM. SHAHEEN, RA. EL-SEHEIMY, G. XIONG and al. Parameter identification of solar photovoltaic cell and module models via supply demand optimizer. Ain Shams Engineering Journal,13,4, pp. 101705 (2022). doi: https://doi.org/10.1016/j.asej.2022.101705
15. Y. MAHMOUD et E. EL-SAADANY, A photovoltaic model with reduced computational time. IEEE transactions on industrial electronics,62,6, pp. 3534-3544 (2014). doi: 10.1109/TIE.2014.2375275
16. S. KAPAT and P. KREIN. A tutorial and review discussion of modulation, control and tuning of high-performance dc-dc converters based on small-signal and large-signal approaches. IEEE Open Journal of Power Electronics, 1, pp. 339-371 (2020). doi: https://doi.org/10.1109/OJPEL.2020.3018311
17. H. TARZAMNI, F. ESMAEELNIA, F. TAHAMI and al, Reliability assessment of conventional isolated PWM DC-DC converters. IEEE Access,9, pp. 46191-46200 (2021). doi: https://doi.org/10.1109/ACCESS.2021.3067935
18. B. ZHU, HU, L. Shishi, Guanghui, and al, Low-voltage stress buck-boost converter with a high-voltage conversion gain. IEEE Access, 8, pp. 95188-95196 (2020). doi: 10.1109/ACCESS.2020.2995889
19. A. RAJAVEL and P. RATHINA, Fuzzy logic controller-based boost and buck-boost converter for maximum power point tracking in solar system. Transactions of the Institute of Measurement and Control,43, 4, pp. 945-957 (2021). doi: https://doi.org/10.1177/0142331220938211
20. B. CHANDRASEKAR, CH. NALLAPERUMAL, S. PADMANABAN and al, Non-isolated high-gain triple port DC– DC buck-boost converter with positive output voltage for photovoltaicapplications. IEEEAccess,8,pp.113649-113666, (2020). doi: 10.1109/ACCESS.2020.3003192
21. Tahar, Benaissa, Mahi Djillali, and Halbaoui Khaled. “Maximum Power Point Tracking under simplified sliding mode control based DC-DC boost converters.” Przeglad Elektrotechniczny 97.7 (2021). doi:10.15199/48.2021.07.12
22. N. OBEIDI, M. KERMADI, B. BELMADAN and al, A current sensorless control of buck-boost converter for maximum power point tracking in photovoltaic applications. Energies,15,20,pp. 7811 (2022). doi: https://doi.org/10.3390/en15207811
23. HAMOODI, Ali N., Safwan A. HAMOODI, and Farah I. HAMEEDI. “Enhancing the Solar PV Plant Based on Incremental Optimization Algorithm.” Przeglad Elektrotechniczny 2023.10 (2023).. doi:10.15199/48.2023.10.35
24. RB. BOLLIPO,S. MIKKILI and K. BONTHAGORLA, Hybrid, optimal, intelligent and classical PV MPPT techniques: A review. CSEE Journal of Power and Energy Systems,7,1, pp.9- 33 (2020). doi: 10.17775/CSEEJPES.2019.02720
25. I. OWUSU-NYARKO, MA.ELGENEDY, I. ABDELSALAM and al. Modified variable step-size incremental conductance MPPT technique for photovoltaic systems. Electronics,10,19,pp. 2331(2021). doi: https://doi.org/10.3390/electronics10192331
26. Jusoh, Mohd Afifi, Muhamad Zalani Daud, and Mohd Zamri Ibrahim. “Fuzzy logic-based control strategy for hourly power dispatch of grid-connected photovoltaic with hybrid energy storage.” Przeglad Elektrotechniczny 98.1 (2022). doi: https://doi.org/ 10.15199/48.2022.01.02
27. ZOUGGARET, Abdelhak, et al. “An Efficient Fuel Cell Maximum Power Point Tracker based on an Adaptive Neural Fuzzy Inference System.” Przeglad Elektrotechniczny 99.2 (2023). doi:10.15199/48.2023.02.23
28. M. KOTB, M. ELMORSHEDY, H. SALAMA and al. Enriching the stability of solar/wind DC microgrids using battery and superconducting magnetic energy storage based fuzzy logic control. Journal of Energy Storage,45, pp.103751 (2022). doi: https://doi.org/10.1016/j.est.2021.103751
29. Z. ROUMILA, D. REKIOUA, et T. REKIOUA, Energy management based fuzzy logic controller of hybrid system wind/photovoltaic/diesel with storage battery. International Journal of Hydrogen Energy,42,30, pp.19525-19535 (2017). doi: https://doi.org/10.3390/en16052286


Source & Publisher Item Identifier: PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 100 NR 6/2024. doi:10.15199/48.2024.06.54