Published by Tony Hoevenaars, PEng., MIRUS International Inc.














































Published by Tony Hoevenaars, PEng., MIRUS International Inc.














































Energy Platform® EP1 – Handheld Electrical Energy and Power Demand Analyzer
Dran-View 7 (DV7) Enterprise is a Windows based software package that enables power professionals to visualize and analyze power and energy monitoring data simply and quickly.
Harmonics
As the sensitivity of power electronics increases, equipment ranging from HVAC systems, personal computers to computerized process equipment and manufacturing systems are susceptible to harmonic pollution. In fact, harmonics can cause small, almost imperceptible variations in performance that aggregate to affect significant long-term damage. Current harmonics generated by a source can pollute the entire power system without being affected itself. The Energy Platform captures detailed harmonics, interharmonics, and subharmonics in accordance with IEC 61000-4-7 and IEEE 519 to effectively troubleshoot the complex problems caused by these events.
EP1 records the harmonics and DV7 provides the capability for the user to choose how they are displayed and additional calculation capability. All harmonic parameters are user selectable for Min/Max/Avg.

The harmonic calculations and display characteristics are user selectable

User can select harmonic magnitudes as % FND, %RMS, %Scale or absolute values or Voltage, Current and Watts. Harmonic calculation method is user selectable.

Symmetrical components can be displayed as % of positive FND or absolute values


Waveforms captured during the maximum load current and harmonics calculated from the waveforms for additional details voltage, current and power to the 125th.

Waveform stored by EP1 every 1-minute voltage and current Channel A and D for single phase. Could be all channels, single phase chosen for clarity of viewing.




EP1 recorded maximum load current in detail and DV7 EP1 calculated the harmonics in detail to the 125th.

EP1 records VTHD and VTID RSS, DV7 presents in RSS or allows user to choose % RMS, % Fundamental or % Scale.


Published by






























To do advanced harmonic analysis using the postprocessing capability of Dran-View 7 (DV7) Enterprise.

Note: Use the waveform capture on periodic basis to collect the most useful data but not necessary for normal PQ activity and reports.
The steps below give a few examples.
Step 1. Open the data file of the site of interest and select Voltage or current or both graphs. Change graph label for clarity.
Step 2. Select insert from the tool bar and the tables followed by Statistics.

Step 3. Double click on the statistics box. It will bring up the following selection box.

To adjust the time period for the statistics, simply zoom or unzoom the graph of the data and the statistics are reported on the time of the graph.
Step 4. Follow the instructions to move statistics box to the graph you want.


Step 5. Add data labels for clarity, save graph with camera icon
![]()
or report writer can automatically insert this graph in the report.
![]()
Published by Terry Chandler, A Power Quality Practitioner ™ for +30 years,
Director of Engineering Power Quality Thailand LTD/Power Quality Inc. USA,
Consultant for Dranetz Corporation USA (Asia business Unit General Manager)
Contact TerryC@powerquality.org
What is Power Quality (PQ)?
What is Quality of Supply (QOS)?
Power Quality Definition?
PQ problems (costs) vs Power passing thru a semiconductor switch

Semiconductor Sales vs PQ

Power Reliability vs Power Quality
Quality of Supply Parameters (Utility)
Source of most common voltage sag from utility distribution system or transmission or generation

A fault on transmission system

Voltage Sag Example (QOS)

Power Quality Parameters User Side
Source of the PQ issues?
In PQI’s 30 years of experience and data shows:
Power Quality is a constantly changing situation of varying loads, varying generation types, varying weather.
Influence on Power Quality due to drive for more energy efficient loads.
Today Power Quality is more about data/information. (SmartGrid)
Data Integrated by Power Quality Monitoring System at Con Edison

Energy Efficiency and Power Quality
Global Impact of Energy Efficiency

Electrical Energy Efficiency
Load Categories
Parameters of Electrical Usage
The Basics of Energy Savings
The Relationship Electricity usage to Power Quality Situations (parameters)

Computer Power Supplies (AC to DC)

Lighting (22%)



Lamp Efficiency Comparison and PQ Sensitivity
Light Dimmers
Solid State Lights (SSL)

Motors
High Efficiency Motors

Add VFD (VSD) to Motors
How a VFD or VSD works?

Drivers for Change in PQ and Efficiency
Conclusions

Published by
21st International Conference on Electricity Distribution, Frankfurt, 6-9 June 2011 (Paper 0917)
Abstract
The measurement of harmonic currents and voltages is a key issue e.g. for the assessment of voltage quality or the compliance verification for generating installations. Except for voltage measurements in LV networks the adaption of the primary signal to the input ranges of the power quality instrument needs instrument transformers. The accuracy of these transformers above the nominal frequency is usually not known and not defined by the appropriate standards up to now.
The main intention of the paper is to present the accuracy of conventional instrument transformers at higher frequencies for voltage levels up to 330kV and to attract attention of network operators, equipment manufacturers and regulators to possible influences on the harmonic measurements.
A short introduction is followed by a description of the measurement system and methodology. Next the measurements of the frequency dependent transformer ratio and frequency dependent phase angle difference for about 100 voltage transformers (VTs) are discussed in detail. For all analyses the frequency ranges from 50Hz up to 5kHz is considered. A final summary of the results should give first guidance to all interested parties on how to treat with voltage harmonic measurement accuracy in MV, HV and EHV networks.
Introduction
The number of sources of low as well as high order harmonics in distribution and transmission grids increases continuously (e.g. wind parks, HVDC links, …). It is very important that all involved parties know the current situation on the system. Hence network operators, customers and regulators carry out more and more power quality measurements including harmonics in all voltage levels from LV to EHV. IEC 61000-4-30 defines methods
and accuracies for the measurement instruments itself, but explicitly excludes the accuracy of instrument transformers. It is therefore not possible to specify an overall accuracy for such harmonic measurements. First research of the authors was focused on the frequency dependent behavior of instrument transformer ratio for MV voltage transformers [1]. A few publications exist for VTs for higher voltage levels [e.g. 2]. The factors with influence to the frequency behavior of instrument transformers, namely VTs, are detailed discussed in [1]. In general, these influences can be divided into 3 categories:
1. construction-specific (e.g. rated primary value)
2. operational-specific (e.g. burden)
3. test signal-specific (e.g. test-waveform)
The construction-specific characteristics have the most significant influence on the frequency behavior of VTs. It mainly defines the capacitances and inductances, which are responsible for the resonance effects within the instrument transformer. The following design-specific characteristics are discussed and analyzed in the paper:
1. voltage level
2. basic design (cast resin, gas insulated, or oil insulated, capacitive)
3. single or combined transformer
It should be pointed out that VTs with nearly same properties may still vary in their frequency characteristics due to different designs of constructions, housings and other parameters, like rated power or number of secondary windings. Due to its importance for power quality assessment according to standards and it’s more critical behavior the paper is focused on VTs (single-pole). First results for MVCTs and HV-CTs show no significant resonance effects in the frequency range up to 5 kHz.
Measurement System
In conclusion of the results from former research the measurement system was adapted to handle not only MVVTs but also VTs built for voltage levels up to 400 kV. Several test setups where discussed in [1]. For an extensive test setup a multi-frequent test signal consisting of a fundamental sine component at rated primary voltage and a second, swept sine component of smaller amplitude was used. A simplified setup using only a swept single frequent sine of small amplitude showed only insignificant differences compared to the extensive setup (cf. to [1] for more details). Therefore the simplified setup as shown in Fig. 1 is used for the measurements. Its main advantage compared to the extensive setup is its mobility, which was mandatory for the project, especially for the measurement of HV and EHV voltage transformers. The test signal is provided by a single-phase voltage source at voltages up to 280V (RMS) and frequencies up to 5 kHz. The voltage source is controlled by an external signal generator. For data acquisition an ADC-board with simultaneous sampling channels at sampling rates up to 2MS/s is used.

Basic schema of measurement system.
Figure 1
Measurement Methodology
As mentioned before a single-frequent sweep of sine signals of different frequency is used for the measurements. Each sweep starts at a predefined frequency. The frequency is stepwise increased up to 5 kHz. The step size changes adaptively. By this adaptive step control even small resonances are measured with a sufficient frequency resolution while measurement time is optimized (about 2-3 minutes per VT). Minimum step size is 5Hz. For each frequency primary voltage Upri (green plot in Fig.2) and secondary voltage Usec (red plot in Fig. 2) are measured simultaneously. Finally, the normalized transformer ratio is calculated (blue plot in Fig. 2) that allows better comparison between different transformers:

The calculation of the phase angle difference is based on the following equation:
![]()
ϕpri is always 0° due to the synchronization of the measurement to the positive zero crossing of primary voltage Upri.

Figure 2
Depending on the value of the ratio nr(f) three different ranges (I, II, III – cf. Fig. 2) have to be distinguished.

Evaluation Methodology
Fig. 3 shows the plots of normalized ratio nr(f) for 3 different VTs, namely a 66-kV-VT (green), a 110-kV combined transformer (blue) and a 220-kV-VT (red). All VTs are inductive, oil-paper insulated and for outdoor use. Fig. 4 shows the corresponding phase angle difference Δϕ(f) respectively. All measurements were carried out without burden. Based on the figures the behavior of frequency dependency can be discussed in more detail:
1. Resonance frequency and resonant rise of the first resonance differ significantly due to the diverse design of VTs.
2. For frequencies higher than the first resonance accurate measurements are very difficult. A correction based on the transfer characteristic is not easily possible due to the high sensitivity of the characteristic in this range from lots of influencing factors (cf. [1]).
3. Characterizing the frequency response of a VT based on the resonance frequency only is not sufficient, because deviation from rated transformer ratio at nominal frequency starts usually at much lower frequencies.
4. Depending on the design the first resonance can be a parallel one (Maximum) or a series one (Minimum). Therefore both cases (conservative or critical) according to Tab. 1 may be possible below the first resonance.
5. Large phase angle differences are always related to the resonances. The higher the resonant rise, the higher the phase angle difference. For narrow resonances with high resonance rise (larger than 3) the phase angle difference can significantly exceed 90°.
6. For resonance conditions where a maximum is followed by a minimum (case II acc. to Tab. 1) phase angle difference becomes positive. If minimum is followed by a maximum, the phase angle difference becomes negative.

Figure 3

Figure 4
As an appropriate way to quantify the accuracy of a VT the paper uses different thresholds for transformer ratio accuracy and phase angle accuracy.

For each of the thresholds the corresponding critical frequency (fcrit) is calculated. In order to compensate possible differences that may result from the low excitation, in this paper the difference |nr(f)-nr(fN)| is related to the measured ratio at nominal frequency instead of the rated (name plate) transformer ratio. Fig. 5 shows exemplarily the plot of transformer ratio accuracy Δnr(f) with marked thresholds.

Figure 5
Measurement Results
The critical frequencies fcrit for transformer ratio accuracy Δnr(f) = 1 % are shown in Fig. 6. While rated primary voltage can be read from the figure directly, the different design of the transformer is highlighted by a symbol acc. to table 3.


Figure 6
a) Main general findings:
1. The critical frequency up to the point where accurate measurements are possible decreases with voltage level.
2. Even for VTs with same primary voltage the critical frequency fcrit can vary in wide ranges due to the different design. The specification of a single fcrit only per voltage level is not adequate.
b) Some specific findings:
1. Block-design VTs (+) are usually used up to 35kV. The critical frequency varies in a wide range from fcrit ≈ 3500Hz for 10-kV-VTs down to fcrit ≈ 600Hz for 35-kV-VTs.
2. The accuracy of capacitive VTs (*) is guaranteed within a very small frequency range around the nominal frequency only. These VTs are not suitable for harmonic measurements in standard cases.
3. For 66-kV-GIS VTs () the critical frequency is about 500Hz higher compared to the inductive outdoor VTs (O) of same voltage level.
4. 110-kV combined transformers (x) show in most cases a better performance compared to the inductive outdoor VTs (O) for same voltage level.
5. No significant difference exists between inductive outdoor type (O) for 110kV and 220kV. Both are suitable for measurements up to the fcrit ≈ 500Hz (10th harmonic).
In the new 3rd edition of EN 50160 (ratified in 03/2010) the application range is extended from MV networks (Un ≤ 35 kV) to HV networks (Un ≤ 150 kV). Fig. 6 shows that harmonics up to the 25th order can be measured with sufficient accuracy in MV networks up to 20 kV. Only THD accuracy may fail under certain circumstances. Fig. 7 shows that the situation is much more difficult for HV networks. Only the 66-kV-GIS-VTs fulfill all requirements acc. to EN 50160 at a 1-%-transformer ratio accuracy. Measurements in 110-kV-networks may already have an unacceptable error at 9th harmonic. With 110-kVcombined transformers in most cases the error doesn’t exceed 5%. Most international standards related to harmonics in MV, HV and EHV networks (e.g. IEC 61000-3-6 or IEC 61000-2-12) cover the frequency range up to 2.5kHz (50th harmonic) for individual harmonics as well as THD. This requirement is also included in Fig. 7. Fig. 8 shows the transformer ratio accuracy and phase angle accuracy for all analyzed 110-kV-VTs in one diagram. For the chosen phase angle accuracy thresholds the critical frequency fcrit for the transformer ratio accuracy is in virtually all cases lower than fcrit for phase angle accuracy. This means if a certain VT has transformer ratio accuracy better than 1 % its phase angle accuracy is always better than 1° and so on.

Figure 7

Figure 8
Conclusion
The paper is a contribution to the discussion on the accuracy of harmonic measurements using standard VTs, especially at higher voltage levels. It should be defined reasonable accuracy classes for HV and EHV voltage transformers. The influence of transformer ratio accuracy on the harmonic measurements according to actual standards (e.g. EN 50160) was verified. It shows that attention has to be taken to the interpretation of such measurements, especially at voltage levels above 20kV. This is of special importance if regulatory rules should be introduced in future dealing with harmonics. Only instrument transformers of two different manufacturers were analyzed in the project. Due to the high sensitivity of the frequency dependent behavior from transformer design the results may be different to other manufacturers.
Finally, the paper should give impulses for the ongoing standardization work. Adding requirements for frequency dependent behavior of instrument transformers to future standards can improve the quality of harmonic measurements significantly in long-term. As short-term solution for the network distributors that carry out measurements in HV and EHV networks at least the frequency dependent transformer ratio of the used VTs should be known.
Reference
[1] M. Klatt, J. Meyer, M. Elst, P. Schegner, 2010, “Frequency Responses of MV voltage transformers in the range of 50 Hz to 10 kHz”, International Conference on Harmonics and Quality of Power (ICHQP), IEEE, Bergamo (Italy) [2] H. Seljeseth, E.A. Saethre, T. Ohnstad, I. Lien, 1998, “Voltage transformer frequency response. Measuring harmonics in Norwegian 300kV and 132kV power systems” Proceedings 8th International Conference on Harmonics and Quality of Power, p. 820 – 824, vol. 2.

Application note for the Dranetz automatic characterizer in HDPQ portable instruments.
Overview
The RMS variation characterizer analyzes cyclic records saved in the database and determines which of those records constitute an event based on a selected criterion. The result is a database record that contains the description of the event, detail of the event, and indices to the cyclic records in the database.
Characterizer Types
IEEE 1159 characterizer
RMS variations are characterized based on the IEEE 1159 Categories and Typical Characteristics of Power System Electromagnetic Phenomena. The table below summarizes the relationships between categories, duration, and magnitude:
| Category | Typical duration | Typical Voltage Magnitude |
| Short Duration Variations | ||
| Instantaneous | ||
| Sag | 0.5 – 30 cycles | 0.1 – 0.9 pu |
| Swell | 0.5 – 30 cycles | 1.1 – 1.8 pu |
| Momentary | ||
| Interruption | 0.5 cycles – 3 sec | < 0.1 pu |
| Sag | 30 cycles – 3 sec | 0.1 – 0.9 pu |
| Swell | 30 cycles – 3 sec | 1.1 – 1.4 pu |
| Temporary | ||
| Interruption | 3 sec – 1 min | < 0.1 pu |
| Sag | 3 sec – 1 min | 0.1 – 0.9 pu |
| Swell | 3 sec – 1 min | 1.1 – 1.2 pu |
| Long Duration Variations | ||
| Interruption, Sustained | > 1 minute | 0.0 pu |
| Undervoltages | > 1 minute | 0.8 – 0.9 pu |
| Overvoltages | > 1 minute | 1.1 – 1.2 pu |
IEC 61000-4-30 characterizer
RMS variations are characterized based on the IEC 61000-4-30 standard. Unlike the IEEE 1159 standard, the requirement does not consider the relationship between the magnitude and duration. The table below summarizes the requirement of the standard.
| Category | Typical duration | Typical Voltage Magnitude |
| Interruption | >=1 cycle | 0.01 pu |
| Dip | >=1 cycle | 0.9 pu |
| Swell | >=1 cycle | 1.1 pu |
Generic characterizer
Contiguous cycles recorded in the database are grouped together and called a data aggregate. Min and max values are calculated through the group and saved with the record. This mode is used when the selected preset is inrush or fault recorder.
Characterizer Engine
The RMS variation characterizer goes through the database periodically to analyze newly acquired data for events. It runs in the background routine where the other housekeeping routines are located. Whenever the instrument is idle, the 5-second ISR sets a flag to signal the characterizer to run. Once the flag is set, the characterizer will start from the last database index from the previous run up to the last index in the database.
Aggregated Events
The characterizer was intuitively designed to allow data characterization in groups. Aggregating channels in an event illustrates a fault as a system instead of independently treating each phase in a multi-phase system as a separate entity.
Channels are grouped according to the selected circuit type. In a three-phase circuit for instance, channels Va, Vb, and Vc are grouped together. A fault on more than one phase will result an aggregate event. For example, a sag occurred on phases A and B. The sag on phase A lasted for 30 cycles, 50 cycles for phase B. The result will be an aggregated event that has a total duration of 50 cycles.
An event starts when any channels in the group is out of limit and ends until all channels in the group are in limit. The group mask simply indicates which phases are grouped together. Split phase for example has two groups. Volts A and B (0x0003), and Amps A and B (0x0030).
When an event is in progress, the state of any channels in the group might change that will alter the category where the event should fall in. A sag for example might become an interruption. When this occurs, the characterizer will save the sag event, reset the start indices and counters, and wait for the interruption to come back in limit.
There are priorities when determining the state of an aggregated event based on severity. The highest is interruption, next is sag, then swell. Take for example an event on three-phase system that has a swell on derived channels A and B, and a sag on channel C. The aggregator will characterize the event as sag because of its priority, and the phenomena that the sag caused an unbalance to the system pulling the neutral that caused a swell on the other phases. Another example is an interruption on one phase and sag on the other phases. The characterizer will characterize the aggregated event as interruption because of priority through severity.
After finding an event, the characterizer will pass the search result to the categorizer. From the raw result, the categorizer will populate the necessary details of the event.
The IEEE and IEC characterizer use the same categorizer. Parameters that are not required by the IEC standard are still populated. The display screen decides whether the extra information is displayed based on the selected characterizer mode.
Brief Overview of the transient characterizer
Type – type of transient. Can be one of the following:
Duration – In case of multiple hits, the width of the disturbance is measured from the start of the first to the end of the last. The reported notch width is the worst case. Duration can be any of the following:
Severity – Describes the severity of the transient based on the amplitude of the peak. Severity can be mild, moderate or severe.
Input – The input where the transient was detected.
Summary DB Record – Points to the related summary record in the database.
First Impulse Direction – Describes the direction of the transient, either positive or negative. Positive direction adds energy to the wave, that is, it heads away from the zero crossing. Negative on the other hand, subtracts energy from the wave. It heads towards the zero crossing.
Start Offset – Offset to be added to the timestamp for location of the start of the transient.
Point on Wave in Degrees – Phase degrees that corresponds to the main timestamp – the start of the wave sample set.
Microseconds per degree – Period in microseconds per degree in the waveform.
Width – Width of the entire transient in microseconds.
Offset to 50% – Offset to start of impulse at 50% width.
Width at 50% – Width of impulse at 50% width.
Amplitude at 50% – Actual signed amplitude at 50% width.
Offset to 10% – Offset to start of impulse where it exceeds 10%.
Rise time from 10% to 90% – Rise time in microseconds.
Amplitude at 10% – Actual signed amplitude at 10%.
Amplitude at 90% – Actual signed amplitude at 90%.
Offset to max peak – offset in microseconds.
Peak Value – Signed peak value in the whole run.
Peak Value Adjacent – uses adjacent peaks.
Worst peak-to-peak Value – worst peak-to-peak deviation in the whole run.
Zero Crossing Oscillating frequency – measured oscillating frequency in hertz.
Peak Oscillating Frequency – highest measured oscillating frequency in hertz.
The transient characterizer produces a record that contains the above information. High frequency and low frequency transients use the same database record. Some parameters are not populated for the low frequency, depending on the classification of the event.
Contact: info@powerquality.co.th
Published by Phongphat Waraphok, Provincial Electricity Authority (PEA), Thailand.


























Published by Terry Chandler, A Power Quality Practitioner ™ for 30 years, Director of Engineering Power Quality Thailand LTD/Power Quality Inc. USA,Consultant for Dranetz Corporation USA (Asia business unit General manager)

Harmonics defined by multiple standards around the world.
Why do we need to measure harmonics?
Measurement techniques are documented in detail by IEC 61000-4-30 class A Edition 3
Harmonic Current Flow


Harmonic Load Current

Impedance:
The AC circuit equivalent of resistance in DC circuits. Impedance is the opposition to AC current flow made up of the available circuit elements of resistance, capacitive reactance, and inductive reactance. Each AC current frequency (harmonic) may be subject to a different impedance in the circuit. – Mike Lowenstein is president of Harmonics Ltd., Monroe, Conn.

Voltage Distortion (result of current)

Note : the distorted current is constant the voltage distortion changes based on the Measurement point.
Harmonic Flow on Feeders
Normal path:

Figure 5: Harmonic currents tend to flow from the harmonic source (nonlinear load) into the utility source because it is the lowest impedance.
Flow Path Altered by Capacitor – II

Monitoring for Harmonic Studies
Monitoring Duration
How many simultaneous monitoring points? It depends on the situation and loads.

Is voltage distortion from the voltage or the current?


The variations are useful time is in seconds!!
Harmonic Power Flow
Harmonic current flow?
Measuring Harmonic Power Flow Low Voltage (Direct Connection)
– Frequency response
– Low current accuracy (typical 10% to 90% rated)
CT’s – TR2510A


Measuring Harmonic Power Flow (in a transmission or distribution system)
Typical PQ meter Voltage Accuracy

PQ meter Current Accuracy (voltage input without I to V transducer)


Medium Voltage or HV Voltage and Current Transducers
Voltage Transducers (PT or VT)



Frequency Response Transformer Type PT (Typical?)

Transducer Output Value at Harmonic Frequencies
Example:
Assume 50% of the THD is the 5th harmonic (1% 5th harmonic) 1 % of 110kV = 1.1kV of the 5th harmonic (250 hertz) / PT ratio 110kV to 100V divide by 1000.
Actual 5th harmonic voltage presented to instrument is 1.1 volt.
If 7th Voltage harmonic is 0.1% then 110/1000 = 0.1VAC is presented to voltage channel.
If 9th voltage harmonic is 0.01% .010 VAC is presented to the voltage channel.
Voltage channels are typically specified from 1 or 10vrms to 600v or 1000vrms.
VT Errors at Range of Frequencies

Errors in Inductive Voltage Transformers PTs

HV/MV Inductive Current Transducers

Secondary Current Transducer



Is it possible to identify the harmonic source on distribution substation buss? YES! But it’s not easy and it is expensive.
Conclusions
Contact the author TerryC@powerquality.co.th
If you can’t explain it to a 6th grader, you don’t understand it yourself ~ Albert Einstein
Published by Danaisak Tangsakha, Provincial Electricity Authority (PEA), Thailand.































Have a WordPress.com account? Log in now.