Renewable Energy Collector Transformers

Published by 1. Waldemar ZIOMEK, 2. Krishnamurthy VIJAYAN, PTI Transformers LP, Winnipeg, MB, Canada ORCID: 1. 0000-0002-1216-6513


Abstract. The renewable energy collector transformer (RCT) in a solar station, or a wind farm, transforms the voltage from the collector system to the transmission level voltages. As the primary goal is stepping up the voltage, the RCT is similar in this function to a generator step-up (GSU) transformer, but there are design features and operational characteristics, which would make these units unique, such as typical winding configuration wye-wye-buried delta, the LV winding is typically grounded through the neutral grounding reactor. The design has to include a presence of harmonics in LV currents and voltages.

Streszczenie. Transformator główny stacji energii odnawialnej w stacji fotowoltaicznej lub farmie wiatrowej (stacji OZE) przekształca napięcie z układu zbiorczego na napięcia poziomu przesyłu. Ponieważ głównym celem jest podniesienie napięcia, RCT jest podobny w tej funkcji do transformatora GSU, ale istnieją cechy konstrukcyjne i właściwości operacyjne, które czynią te jednostki wyjątkowymi, takie jak typowa konfiguracja uzwojeń trójkąt – gwiazda-gwiazda, uzwojenie nn jest zazwyczaj uziemione poprzez neutralny dławik uziemiający. Konstrukcja musi uwzględniać obecność harmonicznych w prądach i napięciach nn. (Transformatory główne w stacjach OZE)

Keywords: power transformers, renewable energy station, overvoltage, harmonics.
Słowa kluczowe: transformatory mocy, stacja OZE, przepięcia, harmoniczne

Introduction

The renewable energy collector transformer (RCT), is a specialized power transformer which in a solar station or a wind farm, transforms the voltage from the station collector system, typically 34.5 kV, to the transmission voltage levels, typically ranging from 138 up to 345 kV or 500 kV. The location of RCT in a renewable energy station is shown in Figure 1. While the low-power transformers directly connected to the inverters are well described in the papers and standards [1, 2], the collector transformers are not well described in published references or standards. Therefore, the goal of this paper has been to fill in this gap.

Fig.1. Placement of the collector transformer between the collector bus and the transmission line; from ref. [1]

Most of renewable energy stations might use more than one collector transformer for different reasons, such as to limit their physical size, especially for transportation or due to site limitations, or utilize the features of a station design philosophy, such as distributing the loads, or transferring the loads between the sections of the station during faults, or emergency loading.

As the primary goal of an RCT is stepping up the voltage, the transformer is similar in this function to a generator step-up (GSU) transformer. However, there are numerous features and characteristics differentiating RCTs from GSUs, including: (i) typical winding configuration is wye-wye-buried delta, while GSU windings are connected wye-delta, (ii) the LV winding of RCT is typically grounded through the neutral grounding reactor (NGR), while HV is solidly grounded – the presence of NGR may impact the surge transfer from HV to LV side, sustaining the voltage oscillations [3], (iii) the RCT design has to include impact of a presence of harmonics in LV currents and voltages [4], (iv) these units are equipped with on-load tap changer (LTCs), located on LV side up to 100 MVA and on HV side for higher power ratings, (v) sizing of the unit MVA rating may be optimized, e.g. due to lack of electric power generation at night in a solar station, (vi) high ambient temperature may require an expanded cooling system to avoid an additional loss of insulation life, (vii) the fault calculations should include a realistic infeed from the LV side.

Emerging application of RCTs is Battery Energy Storage System (BESS) – see Figure 2 and 3. This seems to be a future solution for totally renewable green energy source without any dependence on other conventional source of energy generation [5, 6].

Fig.2. Simplified one-line diagram of a BESS in parallel with a solar PV facility connected to the grid through two RCTs and a common HV bus [5]

Modern Energy Storage Technologies include following storage methods: (i) pumped hydro-electric – most popular technology, used for decades, (ii) compressed air energy, (iii) flywheel energy, (iv) superconducting magnetic energy, (vi) conventional rechargeable batteries, (vii) flow batteries, typically using redox reaction between two liquids separated by membrane, (vii) supercapacitors, (viii) hydrogen and (ix) thermal energy (see Figure 3) [6].

Fig.3. Modern technologies employed in Energy Storage Systems showing their Discharge Duration vs Power Capacity [6]

Selected design features of RCT

Most HV transmission systems are designed to be effectively grounded [7, 13, 14]. To interconnect with such transmission systems, it is usually required that the wind or solar station provide a ground point to the transmission system on an HV side of a transformer. To avoid excessive temporary overvoltages, e.g., in the event of a ground fault on the LV collector system, or the surge transfer form HV side, it is usually necessary that the renewable energy collector transformer also provide a ground point at its LV side. A transformer winding connection that provides a ground point to both the HV and LV terminals is a grounded-wye (HV), grounded-wye (LV) with a delta tertiary (TV). This connection is used for most renewable energy plants in North America. The delta tertiary winding is needed to provide a path for zero-sequence currents and triplen harmonics to circulate, and this tertiary may not be loaded. Same comments refer to the BESS stations. One may note that the wye connected LV winding allows also for easy line-to-ground fault detection on LV side. Moreover, a relatively high LV voltage of 34.5 kV results in a smaller cable size and reduced load loss of the renewable energy station.

Based on a database of several dozens of units built at PTI Transformers LP, the following parameters are typical:

• the top power rating ranges from 50 to 350 MVA,

• the cooling designation is typically ONAN/ONAF/ONAF, with ONAN/ODAF/ODAF for larger power ratings,

• the LV voltage varies between 13.8-34.5 kV, with 34.5 kV in a vast majority of units,

• the HV voltage varies within 100-345 kV, with 230 kV in majority of units,

• majority (90%) of RCTs had a TV winding, most of them at 13.8 kV,

• the HV-LV impedance at base power rating varies from 4% to 15%, averaging at 9%.

Typical winding configuration of an RCT, counting from the core, is TV-LV-HV-LTC (see Figure 4).

Following additional comments can be made: (i) very often an electrostatic shield, a.k.a. core shield, is used on the core leg, (ii) the LTC winding position may change, depending on the transformer impedance and which circuit is regulated, i.e., HV or LV, (iii) the HV lead is typically connected to the axial center of the winding (becoming a center-fed design).

In case when the transformer impedance matching to existing transformer(s) is required, the position of windings can be changed to, e.g., TV-LTC-LV-HV layout.

Fig.4. Typical winding layout of RCT, i.e. TV-LV-HV-LTC with a center-fed HV winding

Operational characteristics of RCT

LV with Neutral Grounding Reactor – transferred surge voltages

The surges caused by lightnings or switching operations, can be transferred within and through the transformer from one winding system to another. The voltages transferred through the transformers are mainly fast-front, or slow-front overvoltages.

The transferred surge has usually both the capacitively and inductively transferred components which are superimposed on the power-frequency voltage. The capacitively transferred component is typically in the MHz range and is seen first in the transferred surge. The inductively transferred component is slower than the capacitive one and is seen later. Its shape and amplitude change in time, because the distribution of the voltage along the primary winding is time-dependent. The magnitude of the transferred voltages depends on the construction of the transformer, damping effect of the winding, capacitances of the transformer, winding turns (transformation), vector group, connection to the network, etc. In addition, the waveshape of the incoming surge has an important role [3, 8-11]. Often neglected factor is a neutral grounding method. Majority of RCTs are grounded through reactance with a purpose is to lower a ground fault current in the 34.5 kV system (typically single-phase underground cables), so that one can minimize the sizes of main conductors, concentric neutral and grounding wires in the collector system – those result in significant cost savings, as wind turbines can be up to 15 km away from a substation. Neutral Grounding Reactor (NGR) is typically easier to install and more durable than a neutral resistor. Typical NGR impedance is between 0.5-3.5 Ω. A presence of NGR in the neutral has impact on the transient response of a transformer. Grounding a transformer directly or with a resistor will result in lower internal overvoltages, than those appearing when an NGR is used. This characteristic – i.e., oscillatory response of a RCT grounded through reactance – was studied many times and typical results were presented at IEEE PES Transformers Committee [12]. The unit in this particular study was a 200 MVA windfarm collector transformer, 34.5Y-345Y kV with buried TV, with 1050/110 kV BIL HV and 200/200 kV BIL LV levels. The unit was analyzed for a transient response with LV neutral point: (i) grounded directly, (ii) grounded through resistance and (iii) grounded with reactance, NGR. The results on Chopped Wave application to LV terminals with different grounding methods are shown in Table 1.

From the results presented in Table1, one may see that while the LV voltage to ground does not change significantly with grounding method, the voltage from TV to ground and to LV is some 35-45% higher when the neutral is reactance grounded.

Table 1. Comparison of transient response (positive and negative magnitude) of LV and TV winding to LV CW of 220 kV, 3.5/50 ms, with different grounding type

.

Harmonics

The harmonic content is established by measurements of currents and voltages and performing the harmonic spectrum analysis. Next, (i) the UL K-factor, or (ii) IEEE harmonic loss factor FHL can be calculated (see Table 2). Using these factors, the stray loss increase from a fundamental frequency is calculated.

Table 2. Harmonic loss factor FHL (IEEE C57.110 [4]) and K-factor (UL UL1561 and 1562)

.

IEEE C57.110-2018 [4] defines harmonic loss factor FHL which is commonly used in HVDC, FACTS, and power applications, while UL1561-defined K-factor is used for distribution transformers connected to electronic equipment. The FHL factor is a function of the harmonic current spectrum and is independent of the relative magnitude. The UL K-factor is dependent on both the magnitude and the distribution of the harmonic current. For a new transformer with harmonic currents specified as per unit of the rated transformer secondary current, the K-factor and FHL factor have the same numerical values. The numerical value of the K-factor equals the numerical value of the harmonic loss factor only when the square root of the sum of the harmonic currents squared equals the rated secondary current of the transformer.

Voltage variation with LTC

Contrary to conventional GSU’s, RCTs are equipped with on-load tap changers (LTCs) to allow for the voltage variation under load. Typical voltage variation is: ±10% in ±8 steps, or ±10% in ±16 steps. Most often the high speed, resistor vacuum type, or high current reactor vacuum type (for LTC in LV circuit) are used. In majority of the RCTs, the LTC is provided on HV side for the HV voltage variation. Although the intention is for HV variation, most transmission voltages (specially rated 230 kV and higher) are very stable. Hence, the LTC is mostly used during initial commissioning to test the reactive performance of the wind or solar farm, by forcing the voltage changes, see e.g. [15].

In very few of the RCT units the LTC is required to vary the LV voltage, and then, depending on availability of LTC and cost consideration: (i) LTC is provided on LV side, or (ii) LTC is provided on HV side for LV variation (i.e., resulting in a variable core flux design).

Optimization of the MVA rating

Both solar and wind stations do not produce the rated power at all times, hence the power rating of a RCT could be accordingly adjusted, reducing size, weight and cost of transformer. However, the maximum power rating is often selected, as most of users want the RCT to match maximum output of the renewable energy station, and in addition the underloaded transformer insulation will last much longer than standard 20 years, meeting a long insulation life expectation of, say, 40-50 years.

Impact of high ambient temperature

Most solar stations are built in the areas of high exposure to the sunlight, having higher ambient temperatures, for momentary, daily and yearly average, different from those specified in standards. These higher ambient temperatures, together with solar irradiation increasing the oil temperature, need to be considered while designing and testing these transformers, resulting in higher winding and oil temperatures, and requiring the expanded cooling equipment.

Fault calculations with infeed from LV side

The power rating of solar or wind stations is constantly increasing, typically in several hundred MW range. The tertiary fault current will depend on infeed from the LV side. Therefore, a realistic infeed from LV side is required, to properly assess the short circuit current levels. The current of 25 kA or 40 kA is the typical system fault level on the LV side, limited by available circuit breakers’ rating.

Reverse Power Flow

In last 10-15 years the reverse power flow, resulting from the energy delivery by distributed energy sources, is affecting more and more transformers, especially these originally designed for a defined power flow direction (step-up, or step-down operation).

The operation of a transformer under reversed power flow needs to be evaluated for: tap changer’s range, voltage regulation, core overfluxing (higher core loss and temperature), load losses, etc. – see Fig.5.

This situation is especially complex for the dual LV units, supplying or receiving the power from different LV busses.

Fig.5. Transformer under Reverse Power Flow

Examples of RCTs design

The RCT unit, for wind, solar and BESS applications are characterized with expanded cooling system, HV-LV-TV bushing arrangements and employment of LTCs (Figure 6). The oil preservation system for these large power transformers is based on the oil expansion vessel with separation of the oil and air with the air bag and the breather.

Fig.6. Solar station RCT, 335 MVA, 230-34.5-(13.8) kV

Recently a trend of power ratings going up to 400 MVA range is emerging. With the limitation on the LV breaker capacity, dual LV units are being considered for larger units. There is also requirement of 500 kV class renewable energy units from some customers. The number of transformer deliveries for BESS application is steadily increasing. Some customers are also looking for flexibility of HV voltage, so that it can be used in two different systems, e.g., reconnectable units of 230 x 115 kV, or 345 x 230 kV voltage (see Figure 7, more details in [17]). In the nameplate one may see that the corner of a delta connected TV winding is brought out and grounded. If required, a winding insulation test or an applied voltage test can be performed. In the field, one may measure the TV winding insulation resistance, to verify there are no shorts to ground. If there were two corners brought out, the user can operate the transformer with open or closed delta TV [16]. The above aspects increase the complexity of designs and experience of transformer suppliers plays an important role in such cases.

Fig.7. External assembly of a dual LV / dual TV RCT unit, with 330-165-165 MVA, and voltages 345-34.5-34.5 kV

Conclusions

• With continuous development of large solar and wind distributed energy resources, the application of the renewable energy collector transformers (RCT’s) is increasing, with power rating up to 400 MVA, the voltage class up to 500kV.

• These units are equipped with LTCs, typically on HV side.

• The HV and LV windings are wye-connected and grounded, with buried delta TV windings.

• LV winding neutral point is typically grounded with a reactor, hence increasing the electric stresses within and between the windings due to the voltage transients produced by lightning or switching impulses, or system faults.

• Presence of inverters in the renewable energy stations introduces the voltage and current harmonics, which need to be considered for the RCT design, resulting in higher load losses and typically leading to expanded cooling system.

• Often higher ambient temperatures and solar irradiation also lead to expanded cooling system design.

REFERENCES

[1] IEEE Std C57.159-2016 IEEE Guide on Transformers for Application in Distributed Photovoltaic (DPV) Power Generation Systems
[2] IEC/IEEE 60076-16:2018 Power transformers – Part 16: Transformers for wind turbine applications
[3] IEEE Std C57.142 – IEEE Draft Guide for to Describe the Occurrence and Mitigation of Switching Transients Induced by Transformers, Switching Device, and System Interaction
[4] IEEE Std C57.110-2018 IEEE Recommended Practice for Establishing Liquid Immersed and Dry-Type Power and Distribution Transformer Capability when Supplying Nonsinusoidal Load Currents
[5] Zhang Z., Mode for reducing wind curtailment based on battery transportation, J. Mod. Power Syst. Clean Energy, 2018
[6] Refaat S.S., Ellabban O., Bayhan S., Abu-Rub H., Blaabjerg F., Begovic M.M, Smart Grid and Enabling Technologies, First Edition, John Wiley & Sons Ltd, 2021
[7] Ackermann T., (editor) Wind Power in Power Systems, Second Edition, John Wiley & Sons Ltd, 2012
[8] IEC 60072-2: Insulation coordination, Part 2 Application Guide
[9] IEEE Std 142 Recommended Practice for Grounding of Industrial and Commercial Power Systems, 1991 (revised in 2007)
[10] Tian C, et al, Lightning Transient Characteristics of a 500 kV Substation Grounding Grid, 7th Asia Pacific International Conference on Lightning, November 1 4, 2011, Chengdu, China
[11] Saied M., Effect of Transformer Sizes and Neutral Treatments on the Electromagnetic Transients in Transformer Substations, IEEE Trans. On Industry Appl., VOL. 31, NO. 2, Mar-Apr 1995
[12]https://grouper.ieee.org/groups/transformers/subcommittees/performance/C57.142/F17ImpactOfDifferentNeutralGroundingMethods-Ziomek.pdf
[13] IEEE Std C57.12.00-2021, IEEE Standard for General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers, 2021
[14] CSA Std C88-16, Power transformers and reactors, 2016
[15] WECC Generating Facility, Testing and Model Validation Requirements, 2020
[16] IEEE Std C57.158-2017 – IEEE Guide for the Application of Tertiary and Stabilizing Windings in Power Transformers
[17] Ziomek W., Vijayan K., Ho A., Design and Operation of Renewable Energy Collector Transformers, 2023 CIGRE Canada Conference & Exhibition, Vancouver, BC, Sept.25 –28, 2023


Authors: Dr. Waldemar Ziomek, P.Eng., PTI Transformers LP, Winnipeg, MB, Canada, e-mail: wziomek@ptitransformers.com; Kroshnamurthy Vijayan, MSc, PTI Transformers LP, Winnipeg, MB, Canada


Source & Publisher Item Identifier: PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 100 NR 11/2024. doi:10.15199/48.2024.11.39

Practical 400 Hz use Cases for Aviation Teams

Published by Dranetz Technologies, Inc.


Below are three situations aviation teams often face, and how the HDPQ Xplorer 400 helps resolve them.

Jetway keeps resetting when an aircraft connects

What’s happening: During bridge movement or aircraft power-up, the 400 Hz supply dips. Sometimes it is a brief sag, other times a fast transient that trips protection.

How the HDPQ helps: The analyzer locks to 400 Hz and records synchronized waveforms, RMS trends, and an event list with timestamps. You see whether the disturbance is a sag, swell, interruption, or inrush, and how deep and long it lasted.

Outcome: Maintenance can point to a specific root cause, such as a voltage sag to 86 percent for 6 cycles during bridge travel, instead of a generic “power issue.” Fixes are targeted and repeat calls drop.

Disputes about parked aircraft energy usage at the gate

What’s happening: Finance wants real numbers for billing or cost allocation, but estimates vary by aircraft type and turn length.

How the HDPQ helps: You get true 400 Hz measurements for kW, kWh, power factor, and demand across a full turn. Results can be grouped by aircraft family and dwell time, with easy-to -read charts.

Outcome: Contract discussions shift from estimates to measured profiles. One hub used profiles to update agreements and reduced variance between billed and actual significantly.

Proving savings after upgrades to support systems

What’s happening: A facilities project replaces conveyors with higher efficiency equipment, and wants to document the manufacturer’s  energy savings claim.

How the HDPQ helps: Comparable pre- and post-data sets confirm changes in kW, kWh, demand peaks, and power factor. High-speed capture also shows if inrush or switching transients improved, which affects nuisance trips.

Outcome: Engineering delivers a simple before-versus-after story. The project team validates the savings and identifies additional tweaks, like adjusting start sequences to lower demand spikes.

Why these teams choose the HDPQ Xplorer 400

• Correct 400 Hz synchronization for trustworthy frequency, RMS, and timing
• High-speed event capture that surfaces short sags, transients, and inrush
• Remote viewing from phones, tablets, PCs, and Macs so supervisors can monitor without crowding the gate

Automatic setups and dashboards that keep field work moving and make results easy to share

Dranetz HDPQ® Xplorer 400 Plus

Dranetz Products: Dranetz HDPQ® Plus & SP Family

Website: Dranetz.com , Call 1-800-372-6832 (US and Canada) or +1-732-287-3680 (International)

The Importance of Diagnostics of Electrical Equipment at Thermal Power Plants for Ensuring the Reliability of Power Systems

Published by Elshad Safiyev1, Sona RZAYEVA2, Rashida KARIMOVA3, Azerbaijan State Oil and Industry University (1, 2, 3) ORCID: 1. 0009-0005-4971-1721; 2.0000-0001-7086-9519


Abstract. This article discusses the importance of diagnostics of electrical equipment in thermal power plants to ensure the reliability of power systems. Electrical equipment is a key component in the production and transmission of electricity, and its reliable operation is essential to prevent emergency situations and ensure stable operation of power systems. The article discusses diagnostic methods and technologies used to assess the condition of electrical equipment, as well as identify potential problems. The importance of regular maintenance and monitoring of electrical equipment is emphasized to prevent failures and increase the reliability of power systems.

Streszczenie. W artykule omówiono znaczenie diagnostyki urządzeń elektrycznych w elektrowniach cieplnych dla zapewnienia niezawodności systemów elektroenergetycznych. Urządzenia elektryczne są kluczowym elementem wytwarzania i przesyłu energii elektrycznej, a ich niezawodne działanie jest niezbędne, aby zapobiec sytuacjom awaryjnym i zapewnić stabilną pracę systemów elektroenergetycznych. W artykule omówiono metody i technologie diagnostyczne stosowane do oceny stanu urządzeń elektrycznych, a także identyfikacji potencjalnych problemów. Podkreśla się znaczenie regularnej konserwacji i monitorowania urządzeń elektrycznych dla zapobiegania awariom i zwiększania niezawodności systemów elektroenergetycznych. (Znaczenie diagnostyki urządzeń elektrycznych w elektrowniach cieplnych dla zapewnienia niezawodności systemów energetycznych)

Keywords: infrared thermography, ultrasound diagnostics, thermal imagers, monitoring system, diagnostics.
Słowa kluczowe: termowizja w podczerwieni, diagnostyka ultradźwiękowa, kamery termowizyjne, system monitorowania, diagnostyka.

Introduction

Electrical equipment plays a key role in the operation of thermal power plants, providing power supply, process automation, safety and equipment control. It is used to supply electricity to all components of the installation, including security, control and monitoring systems. Automation of processes such as fuel regulation, temperature and pressure control is carried out using electrical systems. Electrical equipment also plays a role in ensuring plant safety through emergency shutdown, fire extinguishing and equipment condition monitoring systems [1]. In modern installations, energy-saving technologies and electrical-based energy management systems help reduce energy consumption and improve overall system efficiency. Thus, electrical equipment is an integral part of thermal power plants, ensuring their stable, safe and efficient operation.

Equipment failures in thermal power plants can have a serious impact on production processes and safety. Firstly, they can lead to a decrease in productivity or a complete shutdown of the installation, which in turn can cause losses in energy production and a decrease in the efficiency of the entire system. This can result in increased downtime, lost revenue, and increased equipment recovery costs.

The impact of equipment failures on safety is also extremely serious. Failures can disrupt the normal functioning of safety systems such as fire extinguishing systems, emergency lighting, gas leak prevention systems, etc. This creates potential dangers for workers, the environment and society as a whole. In some cases, equipment failures may be associated with emergency situations, such as accidents with the release of harmful substances or fires, which threaten not only the safety of personnel, but also the surrounding area and population.

Thus, equipment failures in thermal power plants have serious consequences for both production processes and safety, and require careful monitoring, maintenance and updating of equipment to prevent negative consequences [2-5].

Problem setting

Visual methods for checking equipment condition.

Visual methods are indispensable for maintaining equipment functionality and ensuring operational safety in various industries. Engineers rely on these techniques to visually inspect equipment for signs of wear, damage, or irregularities, while also considering environmental factors. For instance, they meticulously scrutinize surfaces for cracks, corrosion, leaks, or other indicators of potential issues.

Moreover, comparing the current state of equipment to established standards is another vital aspect of visual inspection. Engineers assess characteristics like color, shape, size, and position, aligning them with prescribed safety and efficacy criteria. For instance, in examining a piping system, engineers meticulously look for signs of play, cracks, or leaks, comparing them against predetermined thresholds.

Incorporating specialized equipment, such as infrared thermal cameras or ultrasonic flaw detectors, further enhances visual inspection capabilities. These tools enable the detection of latent problems that may elude normal visual scrutiny. By swiftly pinpointing potential malfunctions, engineers can intervene preemptively, mitigating the risk of serious incidents or accidents.

Using Thermal Imaging Cameras to Detect Overheating.

Thermal imaging cameras serve as invaluable tools for detecting overheating in various systems, including thermal power plants. These cameras utilize infrared radiation to visualize temperature variations across object surfaces. Overheating often signals underlying issues like poor connections, overload, component wear, or cooling system inefficiencies.

Engineers leverage thermal imaging cameras to swiftly scan equipment, pinpointing areas of elevated temperature that may signify trouble. For instance, heightened temperatures at electrical connections could indicate overloads or inadequate contacts, while overheating on pipe surfaces might signal heat transfer or cooling system issues. By promptly detecting such anomalies, engineers can proactively address potential problems, averting serious damage or accidents.

In essence, the use of thermal imaging cameras for overheating detection proves highly effective in diagnosing equipment conditions within thermal power plants. This proactive approach enables the timely identification of potential issues, thereby preempting adverse consequences and ensuring operational integrity.

Application of ultrasonic flaw detectors to detect cracks and defects.

Ultrasonic flaw detectors play a pivotal role in identifying cracks and flaws within diverse materials and structures, including equipment found in thermal power plants. These devices harness ultrasonic waves to penetrate materials, gauging the time taken for wave reflections from internal imperfections. By utilizing ultrasonic flaw detectors, even minuscule cracks and defects, alongside inclusions, pores, or density alterations, can be detected.

In the realm of thermal power plants, these flaw detectors are deployed to assess the integrity of materials utilized in crucial components like boilers, piping, and tanks. They excel in identifying imperfections that may escape visual detection, swiftly highlighting potential issues such as fatigue cracks, corrosion, or structural alterations.

Ultrasonic flaw detectors offer several advantages, including heightened sensitivity across a spectrum of defects, the capability to conduct in-depth examinations, and their non-intrusive nature, ensuring equipment integrity and safety. Incorporating such defect detection methodologies into maintenance protocols is vital, fostering prolonged service life and secure operation of equipment within thermal power plants.

Monitoring and diagnostic systems based on IoT (Internet of Things) and data collection.

Monitoring and diagnostic systems leveraging IoT (Internet of Things) technology and data collection are pivotal in enhancing the efficiency, reliability, and safety standards of thermal power plants. By employing sensors, data acquisition devices, and interconnected networks, these systems ensure continuous monitoring of equipment performance and environmental conditions.

IoT systems enable real-time data collection and transmission to remote servers for analysis and processing. This facilitates prompt responses to fluctuations in equipment condition, enabling the timely identification of potential issues and accident prevention. For instance, IoT systems can monitor parameters like temperature, pressure, vibration, and substance levels in cooling systems or fuel tanks.

Moreover, IoT-based monitoring and diagnostic systems harness machine learning algorithms and big data analysis to predict equipment conditions. This proactive approach optimizes maintenance schedules, offers early fault warnings, and minimizes plant downtime.

Examples of practical application

Diagnostics of turbines, generators and transformers.

Diagnostics of turbines, generators and transformers in thermal power plants is an important maintenance step and ensures the reliable operation of these key components. For turbines, such diagnostics include checking the condition of the blades, rotor, casing, seals and bearings to identify wear, damage or other problems that may affect their operation and efficiency. For generators, it is important to diagnose the stator and rotor windings, insulation, cooling system, bearings and other key components to identify potential problems such as short circuits, insulation defects or wear. And for transformers, diagnostics include checking the condition of the windings, insulation, cooling system, oil level and other parameters to identify problems such as short circuits, oil leaks or thermal anomalies.

Various methods and technologies can be used to diagnose these components, including visual inspection, temperature measurement, oil analysis, ultrasonic testing, vibration analysis, thermal imaging and others. For example, thermal imaging can be used to detect overheating in the internal components of turbines, generators and transformers, while ultrasonic testing can detect hidden defects in windings or bearings [6-8].

When checking electric motors, you need to pay maximum attention to the following elements:

• bearings – assess their defectiveness by temperature;
• ventilation ducts – check their permeability;
• windings – make sure that there are no turn short circuits.

An example of a thermogram of electric motors is shown in Figure 1.

Fig.1. Example of thermogram of electric motors

Inspecting a generator using a thermal imager involves several key steps to ensure thorough evaluation:

1. Checking Stator Steel for Defects: The thermal imager is used to examine the stator steel for any irregularities or defects that may affect performance or safety.

2. Determining Device Temperature and Identifying Abnormal Heating Zones: By measuring temperatures across the device, abnormal heating zones can be identified, which may indicate potential issues such as overload or insulation breakdown.

3. Assessing Solder Insulation Surface Temperature: The thermal imager is utilized to determine the temperature of the solder insulation surface, helping to detect any areas of overheating or degradation.

4. Measuring Brush Heating Temperature: Brush heating temperature is determined using the thermal imager, allowing for the identification of any excessive heat generation that could lead to brush wear or malfunction.

5. Evaluating Thermal State of Excitation System Devices: The thermal imager is employed to assess the thermal condition of excitation system devices, helping to detect any abnormalities or overheating that may affect performance or reliability.

By following these steps and utilizing thermal imaging technology, engineers can effectively inspect generators, identify potential issues, and take preventive measures to ensure optimal performance and safety [9-12].

Detection and analysis of defects in electrical circuits and connections.

Detection and analysis of defects in electrical circuits and connections within thermal power plants are crucial for maintaining equipment safety and reliability. These defects, including overheating, corrosion, insulation faults, breaks, and short circuits, can arise from factors like improper installation, material degradation, or environmental exposure.

A variety of methods and technologies are employed for defect detection and analysis. These encompass visual inspections, resistance measurements, thermographic and thermal imaging assessments, ultrasonic testing, insulation testing, among others. For instance, thermal imaging cameras are effective in identifying overheating in connections or circuit components, indicating potential issues like improper contact or overload. Ultrasonic inspection can detect hidden defects such as cracks or corrosion that may elude visual inspection.

Innovative solutions like DJI’s thermal imaging drones are increasingly utilized worldwide to enhance productivity and safety in defect detection (Figure 2). These drones are equipped with specialized thermal imaging cameras featuring lenses that capture infrared frequencies. The thermal sensor and image processor within the camera, housed protectively, detect infrared wavelengths and convert them into electronic signals. The resulting thermographic image, or thermogram, displays a color map representing various temperature values, aiding in defect identification and analysis [13-16].

By leveraging these advanced technologies, thermal power plants can effectively detect and analyze defects in electrical circuits and connections, ensuring enhanced safety and reliability of equipment operations.

The temperature sensor, also known as a microbolometer, plays a critical role in thermal imaging technology. Its intricate structure enables it to absorb infrared energy and subsequently generate a thermogram based on its measurements.

Analyzing the data acquired through diagnostics of electrical circuits and connections enables the identification of problematic areas, the assessment of their severity, and the implementation of corrective measures. Regular diagnostics and maintenance of these components are imperative to prevent accidents, ensure personnel safety, and uphold the reliable operation of thermal power plants.

Monitoring the insulation and thermal conditions of equipment stands as a pivotal aspect of maintenance and safety protocols in thermal power plants. Adequate insulation of electrical systems is essential for averting short circuits and potential accidents. Additionally, thermal control of equipment aids in preventing overheating and damage to components, thus safeguarding the integrity and efficiency of plant operations.

Fig.2. Drones with thermal imaging from DJMonitoring of insulation and thermal conditions of equipment

Insulation monitoring is typically conducted through regular measurements of insulation resistance using specialized testers. This practice enables the detection of potential insulation defects such as damage, moisture ingress, or contamination, which can lead to current leaks and safety hazards. By promptly identifying such issues, corrective actions such as replacing damaged insulation sections can be taken.

Equipment thermal monitoring involves continuous measurement and analysis of temperatures in critical system components and assemblies. Thermal imaging cameras, thermocouples, thermistors, and other temperature measurement tools are utilized for this purpose. Continuous thermal monitoring facilitates the early detection of potential problems such as overheating, inadequate cooling, or thermal imbalances, allowing for appropriate interventions such as optimizing cooling systems or adjusting equipment operating modes.

Overall, monitoring insulation and thermal conditions in thermal power plant equipment is vital for accident prevention, ensuring personnel safety, and maintaining operational reliability. Preventing emergencies and mitigating risks in thermal power plants relies on a multifaceted approach:

1. Monitoring and diagnostic systems, including IoT systems, thermal imaging cameras, and ultrasonic flaw detectors, enable the swift identification of potential issues before they escalate into emergencies. Regular maintenance and diagnostics allow for the early detection and resolution of problems, preventing further escalation.

2. Adherence to strict safety regulations and standards, alongside comprehensive safety protocols, forms the foundation for accident prevention. This entails providing regular training to staff on equipment safety procedures and maintaining workplace safety protocols.

3. Utilizing modern technologies and equipment that adhere to high safety standards and ensure reliable operation is crucial. Regular equipment updates and modernization efforts help minimize the risk of emergencies and uphold safety levels in thermal power plants.

By integrating these approaches, thermal power plants can effectively mitigate risks, prevent accidents, and ensure the safety and reliability of their operations

Conclusions

Increasing the service life of equipment and reducing maintenance costs are crucial objectives for ensuring the efficient and reliable operation of thermal power plants. Achieving these goals involves employing various strategies and methods:

Regular Maintenance and Preventive Maintenance: Conducting regular inspections, replacing worn parts, lubricating, and adjusting mechanisms help prevent premature wear and prolong the service life of equipment.

Utilization of Modern Technologies: Implementing innovative solutions such as IoT-based monitoring and diagnostic systems enables quick identification and resolution of potential problems, thus extending equipment service life and reducing maintenance costs.

Personnel Training and Compliance with Operating and Safety Regulations: Ensuring personnel are well-trained and adhering to safety protocols minimizes equipment damage and reduces the likelihood of accidents, ultimately increasing equipment service life and reducing maintenance costs.

Optimizing Production Processes and Improving Energy System Efficiency: Enhancing economic efficiency and competitiveness in thermal power plants involve various strategies:

Introduction of Modern Control and Automation Systems: Optimizing production processes, managing equipment operating modes, and maximizing resource utilization through automation reduces energy, raw material, and labor costs while improving process accuracy and reliability.

Utilization of Modern Technologies and Equipment: Incorporating renewable energy sources such as cogeneration units, solar panels, and wind generators increases energy efficiency, reduces dependence on traditional energy sources, and lowers energy costs while mitigating environmental impact.

Implementation of Advanced Management and Production Planning Methods: Optimizing production processes and enhancing power system efficiency through data analysis and modern management techniques identify opportunities for process improvement and cost reduction, thereby enhancing productivity and competitiveness in the energy market.

In summary, increasing equipment service life and reducing maintenance costs in thermal power plants are achieved through a combination of regular maintenance, utilization of modern technologies, personnel training, and adherence to safety regulations. Similarly, optimizing production processes and improving energy system efficiency involve leveraging modern technologies, automation, renewable energy sources, and advanced management methods to enhance productivity, efficiency, and competitiveness in the energy sector.

REFERENCES

[1]. Lina Y, Lia C, Yanga Y, Qina JF, Sub X, Zhanga H, Zhangao W, “Automatic Display Temperature Range Adjustment for Electrical Equipment Infrared Thermal Images”, The 4th International Conference on Power and Energy Systems Engineering 2017, CPESE 2017, 454-459, Berlin, Germany, 25-29 September 2017.
[2]. Afonin AV, Newport RK, Polyakov VS, et al., “Fundamentals of Infrared Thermography”, Mining Science and Technology, p. 240, Moscow, Russia, 2004.
[3]. S.A. Bazhanov, “Infrared Diagnostics of Electrical Equipment of Switchgears”, Mining Science and Technology, p. 76, Moscow, Russia, 2000.
[4]. Y. Luo, Zh. Li, H. Wang, “A Review of Online Partial Discharge Measurement of Large Generators”, MDPI Energies, Issue 10, Vol. 11, No. 1694, pp. 1-32. Basel, Switzerland, October 2017.
[5]. M. Sasic, C. Chan, “Using Measurement Results to Diagnose the Condition of High-Voltage Rotating Machines Part 1 and 2”, Industry Topics, Iris Power, pp. 1-9, Canada, 2019
[6]. Mohamed ES. Development and analysis of a variable position thermostat for smart cooling system of a light duty diesel vehicles and engine emissions assessment during NEDC. Applied Thermal Engineering 2016; 99: 358–372. https://doi.org/10.1016/j.applthermaleng.2015.12.099
[7]. Rzayeva SV, Ganiyeva NA, Piriyeva NM. Modern methods of diagnostics of electric power equipment. The 19th International Conference on” Technical and Physical Problems of Engineering 2023; Т. 31. 105-110.
[8]. S.V. Rzayeva, N.A. Ganiyeva, N.M. Piriyeva Modern approaches to electrical equipment diagnostics. International Journal on “Technical and Physical Problems of Engineering” (IJTPE), Issue 58, Volume 16, Number 1, March 2024, pp.182-189
[9]. Rahimli I, Bakhtiyarov A, Abdullayeva G, Rzaeva S, Application Of Optical Current Sensors In Electric Substations Przeglad Elektrotechniczny 2024; 2, pp. 132-134 DOI: 10.15199/48.2024.02.26
[10]. Rahimli NI, Rzayeva SV, Aliev HZ. Diagnostics and monitoring of power transformers. Universum: technical sciences 2022; (11-6 (104)): 32-35.
[11]. Alimamedova S.J. Some issues in diagnostics of electric motors. Vestnik nauki 2024; 4.1(70): 528-535. DOI 10.24412/2712-8849-2024-170-528-535
[12]. Mammadov N. Analysis of systems and methods of emergency braking of wind turbines. International Science Journal of Engineering & Agriculture 2023; 2(2): 147-152/ doi: 10.46299/j.isjea.20230202.14
[13]. Pirieva NM, Guseinov ZH. Fault Analysis in Power Transformers. Vestnik nauki 2023; T4, 7(64), 297-304. DOI 10.24412/2712-8849-2023-764-297-304
[14]. Mamedova GV, Pirieva NM, Shirinova MCh Diagnostics of power transformers. Internauka: electron. scientific magazine 2023; 6(276), 31-34 DOI:10.32743/26870142.2023.6.276.352720
[15]. Walentynowicz J, Krakowski R. Modeling of the higher pressure cooling system for transport vehicles engines. Transport Problems 2010; 5(4): 39-47. https://doi.org/10.20858/tp.2010.5.4.5.
[16]. Agarwal N, Chiara F, Canova M. Control-Oriented Modeling of an Automotive Thermal Management System. 2012 Workshop on Engine and Powertrain Control, Simulation and Modeling. The International Federation of Automatic Control RueilMalmaison 2012; 23-25: 392-399. https://doi.org/10.3182/20121023-3-FR-4025.00051


Source & Publisher Item Identifier: PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 100 NR 9/2024. doi:10.15199/48.2024.09.23

Research of Lightning Protection Systems for Wind Electric Installations

Published by Nijat Mammadov1, Najiba Piriyeva2, Shukufa Ismayilova3, Azerbaijan State Oil and Industry University ORCID: 1. 0000-0001-6555-3632; 2. 0000-0002-8990-1803


Abstract. The purpose of this study is to analyze the lightning protection systems of wind turbines. One of the main causes of damage to wind electric installations is lightning strikes. In order to reduce the likelihood of damage to these installations, it is necessary to improve the performance that is associated with lightning protection. Early shutdown of a wind turbine to protect against lightning damage can result in a reduction in utilization that must be prevented. Therefore, in order to improve the lightning protection characteristics of wind power installations, it is necessary to study the mechanism of lightning strikes. In this article, two main systems are considered for the analysis of lightning protection systems for wind turbines. This is a grounding system and a system for detecting thunderclouds near wind turbines. This article provides some grounding measures that include modifying the receptor, laying an insulated cable on the down conductor to increase the likelihood of a lightning strike on the receptor. The article also presents a scheme of the formation of thunderstorm leaders and response leaders emanating from the wind turbine blade receptors. The characteristics of wind rotation speed during normal operation, before and after a lightning strike are given. The main types of lightning detection devices are considered. The article presents modern methods and technologies for lightning protection of wind turbines.

Streszczenie. Celem pracy jest analiza systemów ochrony odgromowej turbin wiatrowych. Jedną z głównych przyczyn uszkodzeń instalacji wiatrowych są uderzenia piorunów. Aby zmniejszyć prawdopodobieństwo uszkodzenia tych instalacji, należy poprawić wydajność związaną z ochroną odgromową. Wcześniejsze wyłączenie turbiny wiatrowej w celu ochrony przed uszkodzeniami spowodowanymi przez wyładowania atmosferyczne może skutkować zmniejszeniem wykorzystania, któremu należy zapobiegać. Dlatego w celu poprawy właściwości odgromowych instalacji wiatrowych konieczne jest zbadanie mechanizmu uderzeń pioruna. W tym artykule rozważono dwa główne systemy do analizy systemów ochrony odgromowej turbin wiatrowych. Jest to system uziemiający oraz system wykrywania chmur burzowych w pobliżu turbin wiatrowych. W tym artykule opisano pewne środki uziemiające, które obejmują modyfikację receptora i ułożenie izolowanego kabla na przewodzie odprowadzającym, aby zwiększyć prawdopodobieństwo uderzenia pioruna w receptor. W artykule przedstawiono także schemat powstawania liderów burzowych i liderów reakcji pochodzących z receptorów łopatek turbiny wiatrowej. Podano charakterystykę prędkości wirowania wiatru w czasie normalnej pracy, przed i po uderzeniu pioruna. Rozważono główne typy urządzeń do wykrywania wyładowań atmosferycznych. W artykule przedstawiono nowoczesne metody i technologie ochrony odgromowej turbin wiatrowych. (Badania systemów ochrony odgromowej instalacji wiatrowych)

Keywords: wind electric installation, lighting strike, thunderstorm, receptor, wind rotation speed, grounding system, overvoltage
Słowa kluczowe: instalacja elektryczna wiatrowa, uderzenie pioruna, burza, odbiornik, prędkość wiatru, instalacja uziemiająca, przepięcie

1. Introduction

Wind turbines on the horizon hold the potential not only for clean energy production, but also for possible lightning related risks. Providing effective lightning protection for wind turbines becomes a prerequisite to ensure the safety, reliability and long life of these economic activity systems. A thunderstorm is a dynamic meteorological process involving various atmospheric phenomena such as strong winds, rain and lightning. During a thunderstorm, intense movements of air masses occur, accompanied by the formation of clouds and precipitation. However, one of the most exciting and dangerous aspects of a thunderstorm is the lightning. Lightning is a phenomenon associated with electrical discharges in the atmosphere. It occurs as a result of the accumulation and discharge of electrical charge between clouds or between a cloud and the ground. Within the thunderstorm region, various charge zones are formed, where negative and positive charges accumulate in the upper and lower layers of the atmosphere, respectively.

It is important to understand that intense vertical air movements occur inside a thundercloud. Rising currents of warm, moist air can collide with falling currents of cold air, which contributes to the formation and strengthening of an electrical charge. This process leads to further formation of lightning discharges within the cloud and between the cloud and the ground. Sharp objects, such as tall buildings, trees, or mountain peaks, can greatly amplify the electric field and attract lightning. When lightning strikes such objects, energy is rapidly released, which can cause fires, destruction or injury. Modern technologies make it possible to develop structures that are resistant to lightning strikes, such as wind turbines. Manufacturers use a variety of methods to minimize the risk of lightning damage, including conductive mesh, lightning rods, and special grounding systems. However, lightning remains a powerful and unpredictable phenomenon, and the risk of a lightning strike cannot be completely eliminated. It is important to take appropriate precautions during thunderstorms to minimize the risk of injury and damage from lightning [1, 2, 6].

Lightning protection for wind turbines is an important aspect of their safety. Wind turbines taller than 30 meters are more susceptible to lightning strikes because they protrude above the surrounding area and attract lightning strikes. Here are a few precautions and lightning protection systems that can be applied to wind turbines:

1) Grounding: The grounding system is the basis of lightning protection. Wind turbines must have reliable grounding, including deeply driven ground electrodes connected to the main structures of the wind turbine.

2) Lightning rods: Installation of lightning rods helps to attract lightning and discharges past the very structure of the wind turbine. Lightning rods may consist of metal rods or conductors installed at a height and near the wind turbine.

3) Surge protection system: In addition to lightning rods, wind turbines must have surge protection systems to prevent damage to electrical equipment in the event of a direct lightning strike.

4) Lightning protection management: Wind turbines must be equipped with lightning protection management systems that can detect the presence of lightning in the vicinity and take appropriate action, such as shutting down electrical equipment or switching to backup power.

5) Regular maintenance: It is important to carry out regular maintenance of lightning protection systems, including checking the grounding, lightning rods and control systems, to ensure that they are working properly.

Let’s consider the general lightning protection system for wind turbines. The electronic systems in the nacelle body are sensitive to voltage surges or current pulses. Therefore, the body of the gondola, if conductive, can be used as a Faraday cage that protects electronic systems. If the material of the gondola is non-conductive, to create a Faraday cage, it is necessary to use metal meshes from a metal that has a high electrical conductivity. Distribution cabinets, control cabinets and connecting cables located in the nacelle must also be shielded.

Fig.1. Scheme of the formation of thunderstorm leaders and response leaders emanating from the wind turbine blade receptors

Receptors are receivers that are used to protect the blades of a wind turbine, located at the end of the blades of a wind turbine (Fig.1). The lightning current that enters the receptor is diverted through the descending wire in the blade, gondola, tower and through the grounding system goes into the ground. The blade rarely suffers serious damage if lightning hits the receiver, but the receptor is likely to be damaged if the lightning current is high. For such cases, receivers made of materials with high thermal conductivity have been developed. Not all lightning strikes in wind turbines rush to the receptor. There are cases when lightning penetrates the blade and the discharge reaches the descending conductor inside the blade. This discharge method damages the surface of the blade and, in some cases, can shatter it, resulting in damage to the wind turbine caused by parts of the delaminated blade. Therefore, a lightning protection system for the blades is needed to minimize the possibility of such damage. Some lightning strikes the surface of the blade and directly penetrates the downward conductor inside the blade, resulting in severe damage to the blade. In addition, it has been recorded that lightning strikes to wind turbines are concentrated in areas located approximately 5 mm from the end of the blade. To avoid this, all metal parts are treated with an insulating coating. Some blade manufacturers have developed blades that use insulated wires as down conductors internally. This reduces the likelihood of a lightning strike in the area near the receptor [5, 8-11].

Wind turbine operation before and after a lightning strike. The performance of a wind turbine before and after a lightning strike can vary significantly depending on the damage caused to the structure and its components. Before a lightning strike, the wind turbine operates within normal operating parameters. The blades rotate under the influence of the wind, driving a generator to produce electricity. Control systems monitor wind speed and automatically adjust turbine operation for optimal operation under design conditions. After a lightning strike, the condition of a wind turbine can change significantly. Damage can affect a variety of components, including the blades, electrical system, control equipment, and other parts of the turbine. If the damage was minimal and limited to mechanical components only, the wind turbine can continue to operate with relatively few changes. However, if the electrical system or control components are damaged, the operation of the wind turbine may be impaired. In some cases, the turbine may be disabled to prevent further damage or to ensure the safety of maintenance personnel. After a lightning strike, a thorough inspection and damage assessment must be carried out to determine the extent of the restoration work and ensure the continued operation of the wind turbine is safe [3, 4, 7]. Figure 2 shows the characteristics of wind rotation speed on normal operation, before lightning strike and after lightning strike.

Fig.2. Characteristics of wind rotation speed on normal operation, before lightning strike and after lightning strike

2. Materials and Methods

Grounding system. The grounding system of a wind turbine (Fig.3) plays a key role in ensuring safety and protecting the equipment from lightning strikes and surges. It consists of a series of grounding conductors and electrodes that direct electrical current from structures and equipment to the ground. When lightning strikes a receiver, such as a wind turbine blade, the grounding system provides an efficient path for the lightning current, directing it to the ground. This prevents equipment damage and minimizes the risk of fire or electrical shock.

Fig.3. Grounding system for wind electric installations

Key components of a grounding system include grounding fixtures at the base of the tower or pole, as well as additional grounding devices, such as ring or deep electrodes, that are installed in the ground around the base of the structure. This creates a low ground resistance, which allows lightning current to be effectively discharged and prevents the rise of ground potential around the wind farm. Additionally, the wind turbine grounding system may include monitoring equipment to monitor the condition of the grounding. This allows any grounding problems to be quickly identified and corrective action taken, thereby reducing the likelihood of equipment damage and ensuring personnel safety. Moreover, wind farm design engineers take into account factors such as local climate conditions and geological features when designing the grounding system. This allows you to adapt the design and location of grounding elements to specific operating conditions, providing optimal protection against lightning and surges.

Overall, a wind turbine’s grounding system is an essential component for ensuring safe and reliable operation during thunderstorms and lightning, and its effectiveness has a direct impact on the protection of equipment, personnel and the environment [12-15].

Lightning detection devices. There are four main types of lightning detection devices:

1) Solenoid coil tower type.
2) Rogowski coil, tower type.
3) Rogowski coil (for ground wire).
4) Rogowski coil (for downstream conductor).


These devices use current sensors that measure lightning current and detect when a wind turbine has been struck by lightning.

Tower type solenoid coil. It is usually installed in a lightning detection device. When lightning strikes a wind turbine, the equipment detects a transient magnetic field created by the lightning current flowing through the installation tower. Due to the low cost and ease of installation, this type of device is the most popular, but it has its drawbacks. If lightning does not hit the wind turbine itself, but in the areas surrounding it, then a voltage appears between the output terminals of the solenoid coil. This voltage may exceed the detection threshold, the device may incorrectly detect both wind blow and installation blow. Manufacturers of this type of equipment have raised the detection threshold to reduce the number of such errors, but the problem still persists.

Coil Rogowski tower type. The coil is placed around the tower and is used as a sensor that detects the lightning current flowing through the tower. The sensor does not respond to lightning strikes in the areas adjacent to the wind turbine, which means it allows you to more accurately determine the presence of a lightning strike in the wind turbine. Due to the wide frequency band from 0.1 Hz to 0.96 MHz, the coil can collect lightning current parameters related to turbine damage, such as the maximum lightning current and electric charge. This type of device is expensive. In recent years, functional limitations have been introduced, so its price has come down [16-18].

Rogowski coil (for ground wire). The coil is installed on the ground wire of the grounding system and detects the shunt current when lightning strikes the wind turbine, thereby revealing that the turbine has been struck. Before using the equipment, it is necessary to determine the relationship between the lightning current flowing through the wind turbine and the shunt current flowing through the ground wire on which the coil is installed. Based on this dependence, the detection threshold is set. It must be taken into account that the wind turbine has power electronics and other devices that create noise and in many places constant noise is superimposed on the ground line. Therefore, it is not advisable to use this type of equipment when the noise current exceeds the current threshold.

Rogowski coil (for descending conductor). The coils are attached to the descending (from the receptors) conductors in the blades. When lightning strikes, a current is detected in the wind turbine and it is possible to determine which blade was struck. There are, however, some drawbacks. First, the sensors are installed in the rotating section of the wind turbine, which means that the measuring equipment is required to be attached to the blade conductor inside and fixed at the hub. Secondly, in some wind turbines, the hubs and blades are sealed, so it is necessary to develop a way to communicate between the transmitters installed in them and the receiver located in the nacelle [19-22].

Systems for detecting thunderclouds near wind turbines. Storm cloud detection systems near wind turbines are critical to ensuring the safety of personnel and equipment. Here are some of the main components and methods that can be used in such systems:

1. Lightning detection radar systems: Installation of specialized radar systems that detect lightning near wind turbines. These systems can accurately determine the location of lightning and its proximity to an installation.

2. Meteorological sensors: Placement of meteorological sensors on wind turbines to continuously monitor atmospheric parameters such as pressure, humidity, temperature and wind speed. This data can be used to detect approaching thunderclouds.

3. Equipment condition monitoring systems: Using equipment condition monitoring systems that can detect electromagnetic interference caused by lightning and automatically take measures to protect the equipment.

4. Automated control systems: Development of automated control systems that can automatically adjust the operation of wind turbines in the event of lightning activity, for example, reducing the speed of rotation of the blades or temporarily stopping the operation of the installation [23-25].

There are two main approaches to detecting thunderclouds near wind turbines. The first approach is based on measuring the electrostatic field around the turbine. As a thunderstorm approaches, this field increases. Research has shown that there is a relationship between this electrostatic field and the likelihood of lightning striking a turbine, and in 85% of cases the plant can be shut down before a lightning strike if the field threshold is determined accurately. However, reducing the threshold value may reduce the likelihood of lightning striking the turbine, but will lead to increased downtime and reduced turbine utilization. The second approach is based on a lightning location system. This system monitors lightning strikes near wind turbines and detects approaching thunderclouds. This method can detect thunderstorms that originate far from the turbines, giving more time to decide whether to shut down the plant. However, for winter thunderstorms, which rarely result in lightning strikes but can develop quickly near turbines, the first method, based on measuring localized electrostatic fields, may be more effective [26-28]. The purpose of these systems is to ensure reliable operation of wind turbines in lightning conditions, minimize risks and increase the safety of personnel and equipment.

3. Conclusion.

In the absence of a lightning protection system for a wind turbine, a lightning discharge may result in damage to control systems, electrical systems, blades, and other mechanical parts. Therefore, when designing wind turbines, it is necessary to carefully consider and identify potential risks and pay special attention to the lightning protection system. For this purpose, an efficient system has been developed using numerical analysis of the electromagnetic field in the grounding structure. In addition, an automatic detection system is proposed that accurately detects lightning strikes, determines the level of damage from the strike, and tells whether the turbine needs to be repaired, whether it is able to continue working. Studies have been carried out to detect the approach of thunderclouds, to determine the probability of impact in wind turbines. The proposed measures make it possible to improve the performance of protection of wind turbines from lightning.

REFERENCES

[1]. Mammadov N., Mukhtarova K. “ANALYSIS OF THE SMART GRID SYSTEM FOR RENEWABLE ENERGY SOURCES”, Journal «Universum: technical sciences”, № 2 (107), pp. 64-67, 2023
[2]. Nijat Mammadov, “Analysis of systems and methods of emergency braking of wind turbines”. International Science Journal of Engineering & Agriculture, Vol. 2, № 2, pp. 147-152, Ukraine, April 2023
[3]. Mammadov N.S., Rzayeva S.V., Ganiyeva N.A., “Analisys of synchronized asynchronous generator for a wind electric installation”, Przegląd Elektrotechniczny, №5, 2023, pp.37-40, doi:10.15199/48.2023.05.07
[4]. Mammadov N.S., “Vibration research in wind turbines”, XV International Scientific and Practical Conference «The main directions of the development of scientific research», Helsinki, Finland, 2023, pp. 345-346
[5]. Csanyi E. “Lightning and surge protection of multi-megawatt wind turbines” // EEP — Electrical Engineering Portal, 2014 –pp. 35-38
[6]. Fisher F. A., Plumer J. A., Perala R. A. “Lightning protection of Aircraft”, 2 edition. Lightning Technologies Inc, 2000 – pp.45-54
[7]. Radicevic B. M., Savic M. S. “Experimental research on the influence of wind turbine blade rotation on the characteristics of atmospheric discharges” // IEEE Transactions on Energy Conversion. 2011 – Vol. 26. – pp. 1100–1190.
[8]. Gao L. “Characteristics of Streamer Discharges in Air and along Insulating Surfaces”/ Institute of High Voltage Research, Uppsala University, Sweden, PhD thesis, 2000 – pp.145-146
[9]. Ayub A. S., Siew W. H., MacGregor S. J. “Lightning protection of wind turbine blades-an alternative approach” // AsiaPacific International Conference on Lightning. 2011 – pp. 925–946.
[10]. Yokoyama S., Honjo N., Yasuda Y. “Causes of wind turbine blade damages due to lightning and future research target to get better protection measures” // Intern. Conference on Lightning Protection. 2014- pp. 800–830
[11]. Yamamoto K., Honjo N. Latest trends in technologies for sound operation of wind turbines against lightning // Electr Eng Jpn., 2018
[12]. Glushakow B. Effective lightning protection for wind turbine generators // IEEE Transactions on Energy Conversion. 2007 – Vol. 22. – pp. 200–222.
[13]. Mammadov N.S. “Methods for improving the energy efficiency of wind turbines at low wind speeds”, Vestnik Nauki journal, 2023 – No 4 (61) – T.2 – pp. 230-233
[14]. Mammadov N.S., Aliyeva G.A. “Energy efficiency improving of a wind electric installation using a thyristor switching system for the stator winding of a two-speed asynchronous generator”, IJTPE, Issue 55, Volume 55, Number 2 , pp. 285-290, June 2023
[15]. Rzayeva S.V., Mammadov N.S., Ganiyeva N.A. “Overvoltages during Single-Phase Earth Fault in Neutral-Isolated Networks (10÷ 35) kV”, Journal of Energy Research and Reviews 2023 -13 (1) – pp.7-13
[16]. Rzayeva S.V., Mammadov N.S., Ganiyeva N.A. “Neutral grounding mode in the 6-35 kv network through an arcing reactor and organization of relay protection against singlephase ground faults”, Deutsche Internationale Zeitschrift für Zeitgenössische Wissenschaft, 2023 – №42
[17]. Pastromas, S.; Pyrgioti, E. Protection Measures on Wind Turbines against Lightning Strikes. In Proceedings of the International Conference on Renewable Energies and Power Quality (ICREPQ’17), Malaga, Spain, April 2017 – №4–6 – pp.388–393.
[18]. Kalair, A.; Abas, N.; Khan, N. Lightning interactions with humans and lifelines. J. Light. Res. 2013 – №5 – pp. 11–28.
[19]. Nasiri, M.J.; Homaee, O.; Najafi, A.; Jasinski, M.; Leonowicz, Z. Analyzing the Effect of Lightning Channel Impedance on the Induced Overvoltages in Wind Turbines. In Proceedings of the 2022 IEEE International Conference on Environment and Electrical Engineering and 2022 IEEE Industrial and Commercial Power Systems Europe (EEEIC / I&CPS Europe), Prague, Czech Republic, 28 June–1 July 2022 – pp. 1–6.
[20]. Ilkin Marufov, Aynura Allahverdiyeva, Nijat Mammadov, “Study of application characteristics of cylindrical structure induction levitator in general and vertical axis wind turbines”, PRZEGLĄD ELEKTROTECHNICZNY, R. 99 NR 10/2023, pp.196-199
[21]. Nijat Mammadov, Ilkin Marufov, Saadat Shikhaliyeva, Gulnara Aliyeva, Saida Kerimova, “Research of methods power control of wind turbines”, PRZEGLAD ELEKTROTECHNICZNY, R.100 NR 5/2024, pp. 236-239
[22]. N.M.Pirieva, S.V.Rzaeva, S.N.Talibov “Analysis of overvoltage protection devices in electrical networks” “Internauka”: scientific journal – No. 43 (266). Part 3. Moscow, 2022. pp. 14-17.
[23]. N.M.Piriyeva, S.V.Rzayeva, E.M,.Mustafazadeh. “Evaluation of the application of various methods and equipment for protection from emergency voltage in 6-10 kv electric networks of oil production facilities.” , Internauka, 2022. № 39(262). c.40-44
[24]. Safiev E.S., Piriyeva N.M., Baqırov Q.T.“Analysis of the application of active lightning rods in lightning protection objects.” Interscience: electron. scientific magazine 2023. No.6(276). Pp 14-17
[25]. Ilkin Marufov, Najiba Piriyeva, Nijat Mammadov, Shukufa Ismayilova, “Calculation of induction levitation vertical axis wind generator-turbine system parameters, levitation and influence loop” Przegląd elektrotechniczny – 2024 – No.2 – pp.135-139
[26]. I.M. Marufov, N.S. Mammadov, K.M. Mukhtarova, N.A. Ganiyeva, G.A. Aliyeva “Calculation of main parameters of induction levitation device used in vertical axis wind generators”. International Journal on technical and Physical Problems of Engineering” (IJTPE), Issue 54, Volume 15, Number 1, pp. 184-189, March 2023
[27]. Piriyeva N.M, Kerimzade G.S., “Mathematical model for the calculation of electrical devices based on induction levitators”, IJ TPE Journal, ISSUE 55. Volume 15 . Number 2, (Serial № 0055-1502- 0623), IJTPE – june 2023. p.274-280.
[28]. Piriyeva N.M, Kerimzade G.S. “Electromagnetic efficiency in induction levitators and ways to improve it“ Przeglad Elektrotechniczny. R.99 NR 06/2023, Poland, pp.204-207


Source & Publisher Item Identifier: PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 100 NR 9/2024. doi:10.15199/48.2024.09.38

Power Quality Measurements from the Spain – Portugal Blackout

Published by Mr. Thomas Ottosson, Managing Director, Unipower AB, Sweden. Email: thomas.ottosson@unipower.se . Website: unipower.se


.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

Source URL: https://pqsynergy.com/assets/files/Power-QualityMeasurementsfromtheSpainPortugalBlackout.pdf

UNIPOWER IEC 61000-4-30 Ed. 4

Published by Mr. Jonny Carlsson, Research Manager, Unipower AB, Sweden. Email: jonny.carlsson@unipower.se . Website: unipower.se


.
.
.
.
.
.
.
.
.
.
.

Source URL: https://pqsynergy.com/assets/files/UNIPOWER-IEC61000-4-30Ed.4InprogressstateFDISMemberofWG9.pdf

Protection of DC Microgrid using ΔCB

Published by 1. Marwan R. Abed, 2. Oday A. Ahmed, 3. Ghassan A. Bilal, University of Technology Iraq, Baghdad, ORCID: 1. 0000-0002-1257-2810; 2. 0000-0001-7214-3412; 3. 0000-0002-5090-103X


Abstract. When implementing a DC distribution network, it is much easier to integrate distributed energy sources than it is with an ac grid. Furthermore, the efficiency and reliability of DC distribution networks outperform those of AC systems. The protection of the DC distribution networks, particularly the interruption and isolation of short-circuit fault currents, is still a major problem. Traditional mechanical and hybrid circuitbreakers for DC fault protection have the disadvantage of being sluggish to operate, necessitating the use of high-power equipment. The Solid-State Circuit Breaker is the best choice for quick fault interruption. Since they employ thyristors, Impedance-Source Circuit Breakers are among those that provide automated fault detection and clearing. In this work, a new DC circuit breaker based Δ-impedance source configuration is proposed for medium and low voltage DC distribution networks to provide the bidirectional operation which has also become the general requirement for the modern power system. The proposed topology uses three-coupled windings with one capacitor and four SCR thyristors to facilitate the bidirectional operation. MATLAB/Simulink environment is used to analyze and evaluate the performance of the proposed DC circuit breaker to protect the 240V DC microgrid configuration with different fault conditions and locations. The results obtained prove that the proposed DC circuit breaker has a good performance in protecting the DC distribution networks.

Streszczenie. Wdrażając sieć dystrybucyjną prądu stałego, znacznie łatwiej jest zintegrować rozproszone źródła energii niż z siecią prądu przemiennego. Ponadto wydajność i niezawodność sieci dystrybucyjnych prądu stałego przewyższa sieci prądu przemiennego. Ochrona sieci dystrybucyjnych prądu stałego, w szczególności przerywanie i izolowanie prądów zwarciowych, nadal stanowi poważny problem. Tradycyjne mechaniczne i hybrydowe wyłączniki automatyczne do ochrony przed zwarciami prądu stałego mają tę wadę, że działają wolno, co wymaga użycia sprzętu o dużej mocy. Wyłącznik półprzewodnikowy to najlepszy wybór do szybkiego przerywania zwarć. Ponieważ wykorzystują tyrystory, wyłączniki źródła impedancji należą do tych, które zapewniają automatyczne wykrywanie i usuwanie usterek. W tej pracy zaproponowano nową konfigurację źródła Δ-impedancji opartą na wyłączniku prądu stałego dla sieci dystrybucyjnych prądu stałego średniego i niskiego napięcia, aby zapewnić dwukierunkową pracę, która stała się również ogólnym wymogiem dla nowoczesnego systemu elektroenergetycznego. Proponowana topologia wykorzystuje trzy sprzężone uzwojenia z jednym kondensatorem i czterema tyrystorami SCR, aby ułatwić pracę dwukierunkową. Środowisko MATLAB/Simulink jest wykorzystywane do analizy i oceny wydajności proponowanego wyłącznika prądu stałego w celu ochrony konfiguracji mikrosieci 240 V DC z różnymi warunkami i lokalizacjami uszkodzeń. Uzyskane wyniki dowodzą, że proponowany wyłącznik prądu stałego ma dobrą skuteczność w zabezpieczaniu sieci dystrybucyjnych prądu stałego. (Zabezpieczenie mikrosieci DC za pomocą ΔCB)

Keywords: DC microgrid protection; Coupled inductor; DC circuit breaker; Bidirectional operation; Impedance source circuit breaker
Słowa kluczowe: ochrona mikrosieci prądu stałego; cewka sprzężona; wyłącznik prądu stałego; Działanie dwukierunkowe

Introduction

The twentieth century began with a critical discussion over the form of energy supply and its essential elements. When Nikola Tesla with George Westinghouse argued for Alternating Current (AC) while Thomas Edison argued for Direct Current (DC). It was evident that the generation of DC power was restricted to a low voltage, and the voltage drop was a key concern. As a result, Edison’s power plants had to be used locally, which meant that loads had to be near the generating stations. The success of this fundamental milestone in the history of electricity notably ushered in the era of central power generation (power plants) and the global spread of AC transmission and distribution systems. In addition, power plants fuelled by fossil fuels (gas and coal) have risen to prominence as a source of electricity. To this time, AC power systems have lasted for even more than a century, and AC loads have ruled the market. However, high energy prices, as well as a lack of funds to build new big power stations with long-distance transmission networks, are some of the limitations to meet rising energy demand. Furthermore, ageing power system infrastructures, global warming, increased awareness of restricted power generation resources, higher power consumption requirements, and growth in the use of DC loads due to improvements in power electronics all indicate that transformation of the existing energy system is unavoidable [1, 2].

DC sources have been subjected to many developments causing an increment in the efficiency and live time of these sources, also the use of various DC loads, and the use of energy storage devices have led the way to use the of DC microgrids (DC MG). Harmonic, Ferranti, and skin effects are essentially non-existent in the DC-MG. As a consequence, DC MG will be better suited for new power systems than AC MG. The DC-MG idea may be viewed as a master foundation for using Smart Grid (SG) technologies [3]. The main problem in these DC MG is that the zerocrossing point is not present, so modern protection devices are needed to limit and interrupt the high fault current rapidly without producing sparks [4, 5].

The traditional mechanical DCCBs have many disadvantages such as Low current interruption abilities, slow response time, and low durability [5, 6], so a faster solid-state DCCBs have been suggested, these breakers provide a higher reliability and longer lifetime. The main disadvantage of such types of DCCBs are the demand for an additional forced commutation and sensing elements, which cause an increase in the circuit complexity and cost and also the high on-resistance (Ro) of the semiconductor switches [4-9].

The Impedance source DCCB is suggested as a faster response that isolates faults in microseconds and has an automatic turn-off because of its natural commutation principle [5, 10, 11].

In [11] produced the first unidirectional impedance source DCCB, consisting of one thyristor (SCR) and two capacitors and inductors which had been arranged as a cross shape. The absence of a common ground in the cross DCCB is solved by introducing the series ZCB in [10, 12]. Other research is done to reduce the reflecting current to zero and reduce the size and response time using coupled inductors in DCCBs as in [13]. In [14, 15] producing a symmetrical bidirectional ZCB with coupled-inductors. In [16, 17], a unidirectional Gamma DCCB (ГCB) was present. Also, in [18-22] presented the T-shape DCCBs (TCB). In [23-25] introduced a Y-shape DCCB (YCB), which consisted of a single capacitor and three coupled-inductors. The most important advantage of this configuration is the higher reflected current gain which produced by the secondary windings, as well as the three inductors’ turn ratios.

In this paper, a new symmetrical bi-directional with delta-shape coupled-inductors (ΔCB) is used in the protection of a DC MG, the following sections will introduce the new circuit breaker and test the protection of a 240V DC MG.

Configuration of the suggested ΔCB

A new circuit breaker with three coupled inductors configuration, in which the inductors are connected in a delta shape, is introduced as a new impedance source CB. It also consists of a single capacitor and four SCRs arranged in two back-to-back switch pairs, as shown in Fig.1. The direction of power flow in the ΔCB is selected by the two switches in the gate circuit S1 and S2 as shown in Table.1.

Fig.1. The suggested ΔCB configuration

Table.1. Switches states of Gate circuit

.

Table.2. The values of the parameters of the proposed ΔCB

.
Operation principle of the ΔCB

During steady state, the power flows from V1 to V2 through T1, L1, L2, L3, and T3, as shown in Fig.2. While the power flows from V2 to V1 through T4, L1, L2, L3, and T2 during opposite power flow direction, as illustrated in Fig.3. In the event of a transient situation, such as a short circuit fault or under sudden load change, the capacitor will act as the source that fed the transient current through the three delta-coupled inductors.

Fig.2. Power flow direction in case of steady state (V1 to V2)

Fig.3. Power flow direction in case of a steady state (V2 to V1)

Fig.4. Transient current direction during a fault condition

As shown in Fig.4, these inductors also act as a channel for the reflected current. If this reverse current is equal to a certain value of the forward current, it will force the thyristors to turn off immediately, causing an interruption to the source current.

Input-to-output current response

By driving the current transfer relation of the ΔCB from the three loop equations, So the input-to-output current relation is shown in Eq.(1):

I1/I2=−𝑠(𝐿3−𝑀13+𝑀23)(𝐿3−𝑀31+𝑀32)+(𝐿1+𝐿2+𝐿3−𝑀12−𝑀13−𝑀21+𝑀23−𝑀31+𝑀32)(𝑠𝐿3+𝑅𝐿+𝑍𝑐)𝑠(𝐿2−𝑀12+𝑀32)(𝐿3−𝑀31+𝑀32)−(𝐿1+𝐿2+𝐿3−𝑀12−𝑀13−𝑀21+𝑀23−𝑀31+𝑀32)(𝑠𝑀32−𝑍𝑐)………Eq.(1)

Where: Zc: The total impedance of the capacitor By using the parameters in Table.2 to plot the bode plot of this relation, as shown in Fig.5:

Fig.5. Input-to-output Frequency response of ΔCB

The figure shows a negative amplitude and higher value than the amplitude in low frequencies (steady state) with 180⁰ in phase. This reverse current will cause in a decrement in the first thyristor current making it lower than latching current, so the thyristor will turn-off causing in an interruption in the circuit breaker.

Simulation Results

The ΔCB should be used to protect a DC microgrid (DCMG) from a short circuit fault. A MATLAB tool is used in this test. The simulation type is discrete of 5µs sampling time. A hybrid power supply system is constructed from three power sources: a connected AC grid, wind energy, and solar panels. The battery bank is 24v and used for transient cases during the changing from source to source and in an emergency. Every single source of the three power sources is regulated by a controller in order to provide a continuous supply to the load [26]. The sequence of the power source work in this simulation:

1. AC grid: From 0s to 1.5s.
2. Solar panel: From 1.5s to 3s.
3. Wind turbine: From 3s to 4s.

The schematic diagram of the used DCMG is shown in Fig.6. The bus voltage of the DCMG is 250V and the load consists of four parallel loads 30Ω, 20Ω, 20Ω, and 30Ω (the total load is equal to 6Ω), the load is connected to the DC bus.

Fig.6. Schematic diagram of the selected DCMG

Check the System Protection Under Fault in Parallel to Load

a) The CB is in series with the load

The system is tested under normal operation and records the voltage and current of each power source, bus voltage, and load current (Ibus=ILoad). The simulation time is 5s. The steady-state results are obtained Fig.7.

Fig.7. The steady-state waveforms of the IBus, VBus, PBus, VGrid, irradiation, wind speed, and battery SOC.

Three different fault cases will be tested, as follows:

The first fault case: By inserting the fault after one second from a run during the period of the AC grid supply source, The AC is converted to DC through the rectifier and the inductive filter, and the load current shows the isolation of the breaker in about 10µs as shown in Fig.8 (Ibus=ILoad), and the other results are obtained as shown in Fig.9.

The second case: By inserting the fault after two seconds from the simulation run during the PV panel (solar panel) supply source period, Also, the load current shows the isolation of the breaker in about 10µs as shown in Fig.10, and the results are obtained as shown in Fig.11.

Fig.8. The load current of the DCMG during the first case (normal and zoomed figure).

Fig.9. The first case waveforms of the ILoad, VLoad, VGrid, PV irradiation, wind speed, and battery SOC

Fig.10. The load current of the DCMG during the second case (normal and zoomed figure)

Fig.11. The Second case waveforms of the ILoad, VLoad, VGrid, PV irradiation, wind speed, and battery SOC

Fig.12. The load current of the DCMG during the third case (normal and zoomed figure)

Fig.13. The third case waveforms of the ILoad, VLoad, VGrid, PV irradiation, wind speed, and battery SOC

The third case: By inserting the fault after three seconds from a run during the period of the wind turbine and its rectifier as a supply source, the load current shows the isolation of the breaker in about 10µs as shown in Fig.12, and the results are obtained as shown in Fig.13.

b) The CB is in series with the rectifier of the AC Grid

The ΔCB is connected in series with the filter of the AC grid, as shown in Fig.14. The fault occurs after 0.5 seconds, and the source current of the ΔCB interrupted after 4.1ms with an overshoot during transient, as shown in Fig.15. The delay in isolation time and the increment in the current overshoot are because of the ripple in the rectified power and the effect of the inductor used as a filter.

Fig.14. The schematic diagram of the selected DCMG with ΔCB

Fig.15. The source current waveform of the AC-grid rectified under fault

Adding a capacitor in parallel with the input of this ΔCB of 220µF will illuminate the overshoot problem, and the isolation time will be reduced to 35µs, as shown in Fig.16.

Fig.16. The source current waveform of the AC-grid rectified under fault by adding an input capacitor

Fig.17. The source current of ΔCB in case of step load change

Conclusion

MATLAB/Simulink environment is used to analyze and evaluate the performance of the proposed DC circuit breaker to protect the 240V DC microgrid configuration with different fault conditions and locations. The results prove that the proposed DC circuit breaker is well at protecting the DC distribution networks. It shows a faster isolation time of 10µs and no negative part in the source current. That makes it the better choice for protecting DC microgrids. Finally, the result shows that ΔCB could distinguish between fault and step load change.

REFERENCES

[1] D. Kumar, F. Zare, and A. Ghosh, “DC microgrid technology: system architectures, AC grid interfaces, grounding schemes, power quality, communication networks, applications, and standardizations aspects,” Ieee Access, vol. 5, pp. 12230-12256, 2017.
[2] J. J. Justo, F. Mwasilu, J. Lee, and J.-W. Jung, “AC-microgrids versus DC-microgrids with distributed energy resources: A review,” Renewable and sustainable energy reviews, vol. 24, pp. 387-405, 2013.
[3] K. Nandini, N. Jayalakshmi, and V. K. Jadoun, “An overview of DC Microgrid with DC distribution system for DC loads,” Materials Today: Proceedings, 2021.
[4] W. Li, Y. Wang, X. Wu, and X. Zhang, “A novel solid-state circuit breaker for on-board DC microgrid system,” IEEE Transactions on Industrial Electronics, vol. 66, no. 7, pp. 5715-5723, 2018.
[5] S. S. Lumen, R. Kannan, and N. Z. Yahaya, “DC Circuit Breaker: A Comprehensive Review of Solid State Topologies,” in 2020 IEEE International Conference on Power and Energy (PECon), 2020: IEEE, pp. 1-6.
[6] S. Bhatta, R. Fu, and Y. Zhang, “A New Design of Z-Source Capacitors to Ensure SCR’s Turn-Off for the Practical Applications of ZCBs in Realistic DC Network Protection,” IEEE Transactions on Power Electronics, vol. 36, no. 9, pp. 10089-10096, 2021.
[7] S. Bhatta, “Specification, Control, and Applications of Z-Source Circuit Breakers for the Protection of DC Power Networks,” 2021.
[8] V. Raghavendra, S. N. Banavath, and S. Thamballa, “Modified z-source dc circuit breaker with enhanced performance during commissioning and reclosing,” IEEE Transactions on Power Electronics, vol. 37, no. 1, pp. 910-919, 2021.
[9] L. L. Qi, A. Antoniazzi, L. Raciti, and D. Leoni, “Design of solidstate circuit breaker-based protection for DC shipboard power systems,” IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 5, no. 1, pp. 260-268, 2016.
[10] A. H. Chang, B. R. Sennett, A.-T. Avestruz, S. B. Leeb, and J. L. Kirtley, “Analysis and design of DC system protection using Z-source circuit breaker,” IEEE Transactions on Power Electronics, vol. 31, no. 2, pp. 1036-1049, 2015.
[11] K. A. Corzine and R. W. Ashton, “A new Z-source DC circuit breaker,” IEEE Transactions on Power Electronics, vol. 27, no.6, pp. 2796-2804, 2011.
[12] A. H. Chang, A.-T. Avestruz, S. B. Leeb, and J. L. Kirtley, “Design of dc system protection,” in 2013 IEEE Electric Ship Technologies Symposium (ESTS), 2013: IEEE, pp. 500-508.
[13] A. Maqsood and K. Corzine, “Z-source Dc circuit breakers with coupled inductors,” in 2015 IEEE Energy Conversion Congress and Exposition (ECCE), 2015: IEEE, pp. 1905-1909.
[14] S. G. Savaliya and B. G. Fernandes, “Modified bi-directional Zsource breaker with reclosing and rebreaking capabilities,” in 2018 IEEE Applied Power Electronics Conference and Exposition (APEC), 2018: IEEE, pp. 3497-3504.
[15] S. G. Savaliya and B. G. Fernandes, “Performance Evaluation of a Modified Bidirectional Z-Source Breaker,” IEEE Transactions on Industrial Electronics, vol. 68, no. 8, pp. 7137-7145, 2020.
[16] H. Al-khafaf and J. Asumadu, “Γ-Z-source DC circuit breaker operation with variable coupling coefficient k,” in 2017 IEEE International Conference on Electro Information Technology (EIT), 2017: IEEE, pp. 492-496.
[17] X. Diao, F. Liu, Y. Song, M. X. Y. Zhuang, and X. Zha, “Topology Simplification and Parameter Design of Z/T/CSource Circuit Breakers,” IEEE Journal of Emerging and Selected Topics in Power Electronics, 2021.
[18] C. Li, Z. Nie, H. Li, and Y. Zhang, “A novel solid-state protection scheme for DC system,” in 2016 IEEE 8th International Power Electronics and Motion Control Conference (IPEMC-ECCE Asia), 2016: IEEE, pp. 2039-2042.
[19] Y. Song, Y. Yu, S. Wang, Q. Liu, and X. Li, “A Novel Efficient Bidirectional T-source Circuit Breaker for Low Voltage DC Distribution Network,” in 2021 IEEE 12th International Symposium on Power Electronics for Distributed Generation Systems (PEDG), 2021: IEEE, pp. 1-5.
[20] X. Diao, F. Liu, Y. Song, M. Xu, Y. Zhuang, and X. Zha, “An Integral Fault Location Algorithm Based on a Modified T-source Circuit Breaker for Flexible DC Distribution Networks,” IEEE Transactions on Power Delivery, 2020.
[21] S. Sapkota, K. Pokharel, Y. Wang, W. Li, and H. Wang, “Modified T-Source Circuit Breaker for Bidirectional Operation in MVDC,” in 2020 IEEE Sustainable Power and Energy Conference (iSPEC), 2020: IEEE, pp. 813-818.
[22] X. Diao, F. Liu, Y. Song, M. X. Y. Zhuang, W. Zhu, and X. Zha, “A New Efficient Bidirectional T-source Circuit Breaker for Flexible DC Distribution Networks,” IEEE Journal of Emerging and Selected Topics in Power Electronics, 2020.
[23] H. Al-Khafaf and J. Asumadu, “Bi-directional Y-Source DC Circuit Breaker Design and Analysis Under Different Conditions of Coupling,” in 2018 9th IEEE International Symposium on Power Electronics for Distributed Generation Systems (PEDG), 2018: IEEE, pp. 1-6.
[24] H. Al-khafaf and J. Asumadu, “Efficient Protection Scheme Based on Y-Source Circuit Breaker in Bi-Directional Zones for MVDC Micro-Grids,” Inventions, vol. 6, no. 1, p. 18, 2021.
[25] H. Al-khafaf and J. Asumadu, “Y-source bi-directional dc circuit breaker,” in 2018 International Power Electronics Conference (IPEC-Niigata 2018-ECCE Asia), 2018: IEEE, pp. i-v.
[26] D. SHAH. “DESIGN OF DC MICROGRID.” MathWorks. https://www.mathworks.com/matlabcentral/fileexchange/104120-design-of-dc-microgrid (accessed March 4, 2023).


Source & Publisher Item Identifier: PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 99 NR 11/2023. doi:10.15199/48.2023.11.25

Manage Your Energy Expenses

Published by Dranetz Technologies, Inc., Case Study


Utility energy and demand costs have a direct impact on a company’s bottom line. In fact, a typical commercial or industrial facility can save from 10% to as much as 35% annually on energy costs by implementing a comprehensive energy management plan. And while each facility will require an organized approach to recognize those savings, facilities first need to understand their power consumption, location of major loads, electric demand usage patterns, and associated costs.

.

The cost of energy is one of the most commonly mismanaged expenses, regardless of a company’s size or the industry represented. Often, energy is purchased in one department, consumed in another, with energy management systems operated and maintained by still another. Since each facility’s energy situation is dynamic and interdependent, it requires continuous monitoring and management action to avoid escalating costs. The web-based Signature System™ enables users to continuously monitor and store power consumption and quality information in real time-to capture those savings and improve profitability. Customers use the System for:

Power cost management: By looking at time of day, peak load and aggregated energy usage, customers can reduce their costs by rescheduling loads, making sure unneeded equipment is shut off when not in use, or installing energy-efficient equipment. Historical load profile data can be used to develop price/risk curves for evaluating energy purchase agreements.

Power factor: Many customers pay a penalty to the utility for inefficient use of energy, or the ratio of power consumed to power delivered. Monitoring is a necessary tool for understanding the processes within a facility that impact power factor, to improve energy efficiency and reduce or eliminate any surcharges.

Curtailment Rate Structure: Many customers have agreed to reduce (curtail) load at the request of their utility supplier in exchange for lower energy rates. Plus, non-essential loads can be shed or distributed generation brought on line to reduce consumption and/or participate in utility-sponsored demand reduction programs. Monitoring can help determine which loads on which circuits can be curtailed, as well as to certify compliance with curtailment requests.

Allocate Costs and Perform Activity-based Costing: Track energy-related costs by department, tenant or process. Use the Signature System’s Energy Usage and Expense Reporting AnswerModule® to track, compare and document those costs against scheduled rates, and from one time period to another.

Load profiling: Adding or upgrading equipment, computers and processes will impact the power requirements of a facility. Monitoring the existing load on circuits lets you know the impact of those changes and how much new load can be added to an existing circuit or facility.

Lost power costs: Improper load balance grounding may not always be obvious. By monitoring, lost energy can be identified and minimized.

.

Source URL: https://www.dranetz.com/technical-support-request/case-studies/case-study-manage-energy-expenses/

Dranetz Products: Dranetz HDPQ® Plus & SP Family

Website: Dranetz.com , Call 1-800-372-6832 (US and Canada) or +1-732-287-3680 (International)

Investigating Blinky Lights

Published by Dranetz Technologies, Inc., Technical Documents


he HDPQ Family of products have a number of trigger mechanisms for capturing different types of power quality phenomena.   Most users are familiar with settings for sags and swells, but those typical limits usually don’t capture the “blinky lights” problems.   While the Pst (perceptibility short term) parameter will indicate whether the voltage supply is likely to produce light flicker when the Pst is close or above 1, it doesn’t help determine where it comes from or what the source is since it is a ten-minute journal value. The graph below illustrates such.

.

The voltage and current plots show that it is an increase in current over 100A that results in the voltage decreasing by 5-8V every 15 minutes. The rms variation limit for sags is set to 90% of the nominal 120V or 108V, so no sag was reported.   In above example, the red dotted line is that sag limit. Yet the residents complained of “blinky lights” while the Pst does increase to 0.8 each time, not over 1.

The rms deviation transient trigger is one method to capture such as an event. However, there is a parameter that is included in the IEC and IEEE standards that was defined just for such disturbances.   It is the RVC or Rapid Voltage Change.   It looks for a sudden change in the voltage from one steady state value, waits for stability in any continued variations until stable at another steady state voltage value for 1 second or more.   The delta change limit is typically set to 2-3%. Since the variation shown in the data above was 4-7%, this mechanism was ideal for capturing and reporting each time that it happened. An example at 22:189:54 is shown below.   The rms deviations and wave shape triggers also captured the event, but they also triggered on other disturbances that weren’t part of the investigation, which produced extra data to sort through.

#39 10/03/2017 22:02:05.297 AV Misc at 0.8 Deg
#40 10/03/2017 22:02:05.297 BV Misc at -179.1 Deg
#41 10/03/2017 22:02:05.306 AVRmsDev Normal To High
#42 10/03/2017 22:02:05.306 BVRmsDev Normal To High
#44 10/03/2017 22:02:05.323 AVRmsDev High To Normal
#45 10/03/2017 22:02:05.323 BVRmsDev High To Normal
#48 10/03/2017 22:18:54.874 AV Misc at 0.7 Deg
#49 10/03/2017 22:18:54.874 BV Misc at -179.0 Deg
#50 10/03/2017 22:18:54.874 AVRmsDev Normal To High
#51 10/03/2017 22:18:54.874 BVRmsDev Normal To High
#52 10/03/2017 22:18:54.883 A Delta V RVC Rapid Voltage Change 0.175 Sec.
#53 10/03/2017 22:18:54.883 B Delta V RVC Rapid Voltage Change 0.259 Sec.

The right tool for the right job has always been a wise adage. Setting the right tool up with the right limits on the right parameters to help solve the customer’s problems is an extension of that idea that can help get the answer quickly and clearly.   By the way, the answer here was a common answer for such problems.   The HVAC unit was causing the blinky lights.


Source URL: https://www.dranetz.com/technical-support-request/technical-documents/investigating-blinky-lights/

Dranetz Products: Dranetz HDPQ® Plus & SP Family

Website: Dranetz.com , Call 1-800-372-6832 (US and Canada) or +1-732-287-3680 (International)

Modelling of Passive Cooling Systems for Solar Panels

Publised by Oleh HOLOVKO1, Adam KONIECZKA2, Adam DĄBROWSKI3, Politechnika Poznańska, Wydział Automatyki, Robotyki i Elektrotechniki (1, 2, 3)
ORCID: 2. 0000-0002-0362-3006; 3. 0000-0002-9385-6080O


Abstract. This paper proposes a method for evaluating the efficiency of passive cooling systems of solar panels in a type of radiator using CFD simulations. The movement of air through the cooling system and the dependence of the thermal state of the radiator on its shape, wind speed, and ambient temperature were analyzed. A mathematical analysis was made that takes into account the average temperature drop of a solar panel connected to a ribbed heat sink. Experimental measurements of the temperature of the solar panel were performed.

Streszczenie. W artykule zaproponowano metodę oceny wydajności pasywnych układów chłodzenia paneli fotowoltaicznych bazujących na radiatorach z wykorzystaniem symulacji CFD. Przeanalizowano ruch powietrza w układzie chłodzącym oraz zależność temperatury radiatora od jego kształtu, prędkości wiatru i temperatury otoczenia. Przeprowadzono analizę matematyczną uwzględniającą spadek średniej temperatury panelu fotowoltaicznego połączonego z żebrowym radiatorem. Wykonano eksperymentalne pomiary temperatury panelu fotowoltaicznego. (Modelowanie systemów chłodzenia pasywnego paneli fotowoltaicznych).

Słowa kluczowe: panel solarny; wydajność paneli solarnych; radiator; symulacje CFD.
Keywords: solar panel; efficiency of solar panels; heat sink; CFD simulations.

1. Introduction

According to [1], an increase in the installed capacity of photovoltaics in Poland amounted in 2021 to 3.7 GW. Data from the end of the first quarter of 2022 indicates the installed power of 9.4 GW. The global success of the solar industry is due to many factors but reduction of the cost of the generated electricity is crucial: according to [2] (Fig. 1), the cost of solar energy over the past 10 years has fallen 7.5 times.

Fig.1. Cost of solar energy (USD/MWh) compared to other energy sources in 2009‒2020 [2]

The second reason is versatility: from small housing systems to large enterprises. In addition, unlike fossil-fuel electricity generation, solar energy causes no environment damage.

The main task with the use of solar radiation is to increase the efficiency of solar panels. The efficiency of commonly used photovoltaic panels is between 17 and 24% [3]. Most commonly used solar cells use wavelength range of 250 to 1100 nm to generate electricity. The remaining radiation is reflected or absorbed by the cells as heat. The temperature of the solar panel is influenced by external climatic variables such as wind speed, humidity, atmospheric temperature and concentrated dust [4]. The heat emission from the roof surface also plays an important role. The absorbed heat may raise the panel temperature even up to 70‒80°C. The result is a significant decrease in the output power.

The amount of energy loss of photovoltaic modules as a result of overheating shall be determined during the production tests. The thermal power loss in different models of silicon-crystalline batteries (according to the manufacturers’ catalog data) is on average within the limits of 0.45 to 0.50%/°C. Thin-film (amorphous) solar panels are more resistant to temperatures. Their thermal loss performance is about 0.2–0.3%/°C [5]. A way to improve the performance of solar panels is to keep their temperature within the optimum range. This method will not only increase electricity generation but also extend the life of the modules, which currently stands at 25 years.

There are many ways to cool solar panels:

1) Active cooling is carried out by forced air or liquid in both the area of the panel itself and the heat exchangers installed on the panels [6]. Problems with the use of active systems are mainly related to: additional equipment, which, as a rule, is not agreed upon with the manufacturer and additional costs of calculations, installation, maintenance. When using liquid-cooled systems, there is a problem of maintaining the installation in the winter to avoid damage.

2) Passive methods include panel cooling using phase conversion materials, heat pipes and radiators: conventional and micro-channel heat exchangers, nanofluids, spectral filters, and thermoelectric, evaporative and radiation cooling [6].

The method of natural cooling has great potential, does not require energy supply and is reliable and simple. In [7], based on the modeling results, the area of an additional surface needed to compensate for the heating of a solar panel was calculated. The size of the additional surface area should be 5‒5.5 times the size of the solar cell. However, the performed calculations do not take the shape of the cooling surface and the relative direction of the wind into account.

According to [8‒11], the use of a passive cooling system in the form of a radiator (aluminum or copper fins mounted on the back of the solar panel) allows the average temperature of the solar panel to be reduced by 2 to 7°C, thus raise its efficiency by 2‒4%.

In [12, 13] the efficiency of a radiator with perforated ribs was considered, and in [14‒17], a study of inclined and complex-shaped ribs was carried out. Depending on the geometry of the structure and wind speed, the temperature of the solar panel decreases by 4‒12 degrees. It should be noted that the measurements and calculations in the mentioned works were carried out for specific locations of solar panels and cannot be applied to other places and conditions.

The degree of the temperature drop depends on the characteristics and location of the panel, stochastic climatic conditions, the design used and the material of the cooling system. In order to estimate the magnitude of the temperature drop of a photovoltaic panel achieved with a heat sink, a full detailed analysis of the airflow shall be carried out, taking the effect of gravity into account, the design of the heat sink, the position and orientation of the panel and other objects near the panel.

CFD (Computational Fluid Dynamics) method can be used for modeling active and passive cooling systems. This method needs numerical analysis to analyze and solve fluid flow problems. In papers [18–21] thermal analysis of the heat sink in the conditions of air convection was considered. In [19] the CFD simulation results were compared with experimental results. Heat transfer tests were carried out for various shapes of radiators (solid pin fins, perforated pin fins, solid flat plate, and perforated flat plate). The achieved results show that the base temperature for experiment is typically 6.05% to 9.52% higher than the base temperature of the CFD simulation. Therefore, the use of CFD software for modeling parameters of heat transfer in passive cooling of solar panels in real conditions can be reasonable.

Section 2 presents the methodology for estimating and theoretical calculations of the temperature drop of a solar panel with a passive cooling system depending on the type of heat sink and external conditions (wind direction and speed). For this purpose the CFD modeling software Solidworks Flow Simulation was used. It allows for performing a simulation of fluid flow, advanced thermal analysis, and study of heat exchange between the designed components and the predefined medium.

Section 3 presents experimental verification of the temperature dependence of a photovoltaic panel without cooling and with a passive cooling system in the form of a rib radiator on external climatic conditions. A thermal imaging camera was used for experimental testing.

A brief summary and conclusions are provided in Section 4.

Table 1. Selected theoretical and statistical models to determine the temperature of a photovoltaic cell

.
2. Calculation of solar panel temperature and evaluation of effect of radiator shape on heat exchange efficiency

When calculating the temperature of the solar panel, the most influential factors are usually taken into account: the power of the solar radiation falling on the surface of the module, the ambient temperature and the wind speed. To determine the T୮ (temperature of the photovoltaic cell), various theoretical and statistical models have been proposed, determining the appearance, respectively [22‒28]. Table 1 shows commonly used T୮ calculation equations. However (according to [29]) depending on the chosen thermal model, the average error between the calculations and the measured value of the solar panel temperature can reach more than 30 percent.

The choice of a model and appropriate coefficients depends on the type of the panel and the conditions under which the panel is located. It can be determined from experimental data [30].

To analyze radiator performance, various ribbed radiators were modeled in Solidworks 3D CAD (2017), assuming that they are made of 5052-type aluminum alloy (thermal conductivity 140 W/mK (T=273K), density ‒ 2680 kg/m3 , specific heat ‒ 921 J/kg·K) [31].

During modeling, the following parameters were determined:

• P [W] ‒ total heat transfer capacity,
• Q [W/m2] ‒ the amount of heat distributed by the radiator surface unit,
• T [°C] ‒ initial temperature of the front surface of the heat sink,
• Tm [°C] ‒ average temperature of the heat sink,
• Tmin [°C] ‒ m

An example of the simulation obtained for a rib radiator is shown in Fig. 2.

Fig.2. Simulation of air flow and temperature distribution for a radiator measuring 35×75×100 mm (s=0.063 m2). Rib thickness 1 mm. Initial temperature of the front surface of the module T=60°C, ambient temperature Ta = 20°C. Wind direction along the Z axis. Wind speed v=5 m/s

Geometric dimensions of the heat sink affect the amount of dissipated heat. The purpose of the prepared tests is to perform a comparative analysis of heat exchange efficiency for the rib-type radiators with different rib heights ‒ L [mm].

Figure 3 summarizes the heat transfer efficiency of radiators of different shapes. The wind speed varied within 0‒ 20 m/s, the direction of air flow was perpendicular to the ribs at the rear, overheating of the front of the module in relation to the environment is 40°C.

Analysis of the dependence of the heat dissipation power on the surface of the radiator shows that under certain conditions the most efficient are radiators with a rib height of 20‒35 mm, providing a decrease in the module temperature on average from 5.74 to 11.8°C.

Compared to a flat plate of 5052-type aluminum alloy, the average heat dissipation power of the radiator increases 3.13 and 3.30 times, respectively. No further increase in the dimensions is recommended, since a significant part of the radiator does not participate in heat exchange with the environment.

Fig.3. Dependence of the size of the heat transfer capacity P [W] on the module surface for radiators with different rib heights L mm. Front panel temperature T=60°C, ambient temperature ‒ Ta =20°C, wind speed v=0‒20 m/s, wind direction along the Z axis

Further tests shall aim to determine the optimum position of the radiator relative to the wind direction at different initial temperatures of the front panel.

Analysis of the heat dissipation efficiency of an unshielded radiator Q [W/m2] (Fig. 4) shows that the most efficient system is one in which the flows are directed perpendicular to the radiator from the ribs (100%) or along the ribs (99%). Changing the wind direction – from the front of the photo module (direction Z) or perpendicular to the ribs (direction X) – causes a decrease in efficiency by 55% and 40%, respectively.

Fig.4. Dependence of the heat flux Q [W/m2] through the radiator surface 35×75×100 mm (s=0,063 m2) on the wind speed v [m/s], direction of the wind along the Z, Y, X axis). Initial temperature of the front surface T=40°C, T=60°C

The reason for such a decrease in the efficiency of the radiator as a cooling system is a significant decrease in wind speed in the area of the ribs. Figure 5 shows an example of the temperature distribution on the surface of the radiator and wind speed values in the radiator area.

In the next step, the dependences of the average temperature of the heat sink on the temperature difference between the heat sink and the surrounding air, wind speed and direction at the location of the panel were analyzed.

Figure 6 shows an illustrative calculation of the average heat sink temperature Tm[°C] for a radiator of dimensions 35×75×100 mm (s=0,063 m2) as a function of the initial temperature of the front surface T[°C] of the solar panel and wind speed. The influence of the thermal resistance between the solar panel and the radiator has not been taken into account.

Fig.5. Temperature distribution on the surface of the radiator and wind speed values in the radiator area of 35×75×100 mm (s=0.063 m2), initial wind speed v=5 m/s, wind direction along the X axis. Initial temperature of the front surface T=60°C

Fig.6. Dependence of the average temperature Tm [°C] of the module on the temperature T [°C] of the initial front surface and the wind speed v [m/s], (wind direction along the Z axis)

The magnitude of the decrease in the average temperature of the radiator can be described using a mathematical function. Considering the above simulation, the decrease in the average temperature dTm[°C] at different temperatures T[°C] of the initial front surfaces can be described using the proposed mathematical expression

.

where σ, τ [°C ∙ s/m], λ[s/m] , m, n are determined using nonlinear regression of CFD simulation results.

Fig.7. Proposed mathematical expression and simulation dependence of the decrease of the average temperature dT [°C] for a radiator of dimensions 35×75×100 mm (s=0,063 m2) on the wind speed v (wind direction along the Z axis).

For example, when using a radiator with the rib thickness of 1 mm, the rib height of 35 mm, the distance between the ribs of 7.5 mm and the wind direction perpendicular to the radiator from the side of the ribs, the coefficients have the following values:

.

Figure 7 for a radiator (35×75×100 mm s=0.063 m2) shows the simulation dependence and proposed mathematical expression of the decrease in the average temperature of the dT[°C] on the wind speed, the temperature T[°C] of the initial front surface.

3. Experimental verification of the temperature dependence of a solar panel with passive cooling system on external climatic conditions

The Sandia thermal model [23] was used to calculate the theoretical temperature, which corresponds to experimental data for a SYP-S05V5W solar panel used in research [31].

.

The corresponding coefficients for a panel with a polymer substrate are: ε = 1 [K∙m2/W], a = -3.56, b = -0.075 s/m [23].

For an unshielded photovoltaic panel installed at an angle of 45°, taking into account the average wind direction in the Wielkopolska ‒ region south-west (at an angle of 45° at the rear of the solar panel), the coefficients in equation (1) (according to the next Solidworks Flow Simulation) determining the temperature decrease have the following values:

.

The use of an additional cooling module reduces the average temperature of the entire system (panel and heatsink). In this work a proportional dependence of the change in the average temperature of the solar panel with the cooling system on the temperature of the illuminated side it is assumed. This change can be recorded with a thermal imaging camera.

An experimental verification of the temperature dependence of a photovoltaic panel without heat sink and with a passive cooling system on external climatic conditions was carried out on 17th January 2022 in a place with coordinates 52.4028 and 16.9537 [31].

A radiator with dimensions of (35×75×100 mm) was vertically placed on the right hand side of the solar panel type SYP-S05V5w, the angle of inclination of the panel was 40°, the wind speed during the day varied within the limits (6‒12 m/s). The temperature during the day varied between +2 and +11°C, with an average of +8°C. Information about the level of solar radiation, ambient temperature, and wind speed comes from the internet weather service [32] and additionally from the NASA MERRA-2 model [33].

A detailed temperature measurement of the panel and radiator was performed using the Seek Thermal ShotPRO thermal imaging device. Figures 8 and 9 show a photo of the solar panel taken with a thermal imaging camera.

Fig.8. Experimental verification of the temperature dependence of the solar panel with a passive cooling system (on the right side) and without them (on the left side) on external conditions ‒ front view

Fig. 9. Experimental verification of the temperature dependence of the solar panel ‒ rear view

The reduction of the mean temperature of the solar panel was calculated according to model (1) for the uncovered ribbed radiator (2).

Figure 10 shows theoretical calculations of the temperature of the panel without cooling and with a passive cooling system during the day and experimental measurements of the temperature of the solar panel using the above thermal imaging camera. Analysis of this chart shows a good match between the theoretical calculations and the experimental data.

Fig.10. Experimental verification of the temperature dependence of the solar panel with the passive cooling system on external conditions

The average temperature of the module during the day without a cooling system is 12.3°C, while with the cooling system the theoretical temperature is 11.0°C and the experimental temperature is 10.2°C.

4. Summary and conclusions

The use of Solidworks Flow Simulation to CFD modeling of solar panels allows one to evaluate the thermal state of photovoltaic panels and the effectiveness of a passive cooling system of any material, size and shape.

The coefficients σ, τ,λ, m, n in expression (1) determining the temperature drop using a radiator are depending on its design, the angle of inclination of the solar panel, the direction of the wind at the location of the panel, the distance to the limiting planes (other panels) and can be determined on the basis of the performed simulation.

Application of the proposed method for estimation of the thermal state of solar panels with a passive cooling system enables estimation of the energy production of solar panels installed in any location at a defined time.

The research was financed by a research grant 0211/SBAD/0223.

REFERENCES

[1] Rynek Fotowoltaiki w Polsce 2022 (Photovoltaic market in Poland 2022), https://ieo.pl/pl/raport-pv 2022, access: 15.03.2022.
[2] SolarPower Europe, Global Market Outlook for Solar Power 2021‒2025, https://www.solarpowereurope.org/global-marketoutlook-2021-2025/, access: 20.7.2021.
[3] Photovoltaic Energy Factsheet, Center for Sustainable Systems, University of Michigan. 2022, Pub. No. CSS07-08.
[4] Siecker J., A review of solar photovoltaic systems cooling technologies, Renew. Sustain. Energy Rev. 79 (2017) 192-203.
[5] Sayigh A., Comprehensive Renewable Energy, Photovoltaic Solar Energy, Volume One, Elsevier Ltd, 2012, P.746.
[6] Sato D., Yamada N., Review of photovoltaic module cooling methods and performance evaluation of the radiative cooling method, Renew. Sustain. Energy Rev. 104 (January) (2019), 151-166.
[7] Асанов М.М., Бекиров Э.А., Воскресенская С.Н., Снижение влияния нагрева поверхности фотоэлемента на эффективность его работы (Reducing the effect of solar cell surface heating on its efficiency), Строительство итехногенная безопасность, No 51. (2014), pp. 92-96.
[8] Parkunam N., Pandiyan L., Navaneethakrishnan G., Arul S., Vijayan V., Experimental analysis on passive cooling of flat photovoltaic panel with heat sink and wick structure, Energy Sources, Part A Recovery, Util. Environ. Eff. (2019), https://doi.org/10.1080/15567036.2019.1588429.
[9] Firoozzadeh M., Shiravi A.H., Shafiee M., An experimental study on cooling the photovoltaic modules by fins to improve power generation: economic assessment, Iranian (iranica), Journal of Energy and Environment 10(2) (2019) 80-84, https://doi.org/10.5829/ijee.2019.10.02.02.
[10] El Mays A., et al., Improving photovoltaic panel using finned plate of aluminum, Energy Procedia, 119 (2017) 812-817.
[11] Chen H., Chen X., Li S., Ding H., Comparative study on the performance improvement of photovoltaic panel with passive cooling under natural ventilation, Int. J. Smart Grid Clean Energy, (2014), https://doi.org/10.12720/sgce.3.4.374-379.
[12] Arifin Z., Danardono Dwi Prija Tjahjana D., Hadi S., et. al., Numerical and experimental investigation of air cooling for photovoltaic panels using aluminum heat sinks, Int. J. Photoenergy (2020), 1574274, https://doi.org/10.1155/2020/1574274.
[13] Gotmare J.A., Borkar D.S., Hatwar P.R., Experimental investigation of PV panel with fin cooling under natural convection, Int. J. Adv. Technol. Eng. Sci., 03 (02) (2015) (February).
[14] Bayrak F., Oztop H.F., Selimefendigil F., Effects of different fin parameters on temperature and efficiency for cooling of photovoltaic panels under natural convection, Sol. Energy, 188 (2019) 484-494.
[15] Hernandez-Perez J.G., Carrillo J.G., et. al., Thermal performance of a discontinuous finned heatsink profile for PV passive cooling, Applied Thermal Engineering, 184 (2021) 116238, https://doi.org/10.1016/j.applthermaleng.2020.116238.
[16] Popovic C.G., Hudis teanu S.V., Mateescu T.D., Chereches N.- C., Efficiency Improvement of Photovoltaic Panels by Using Air Cooled Heat Sinks, Energy Procedia, 85 (2016) 425-432.
[17]Jobair H., Improving of photovoltaic cell performance by cooling using two different types of fins, International Journal of Computer Applications (0975–8887), Volume 157 – No 5, (2017) (January)
[18] Freegah B., Hussain A.A., Falih A.H., Towsyfyan H., CFD analysis of heat transfer enhancement in plate-fin heat sinks with fillet profile: Investigation of new designs, Therm. Sci. Eng.Prog., 17 (December) (2019), p. 2020, DOI: 10.1016/j.tsep.2019.100458.
[19] Tijani A.S., Jaffri N.B., Thermal analysis of perforated pin-fins heat sink under forced convection condition, Procedia Manuf., 24 (2018), pp. 290-298, DOI: 10.1016/j.promfg.2018.06.025.
[20] Pal V., Modeling and thermal analysis of heat sink with scales on fins cooled by natural convection, Int. J. of Research in Eng. and Technology, 03(06), 2014, pp. 359-362, DOI: 10.15623/ijret.2014.0306067.
[21] Parihar S., Randa R., Thermal Analysis of Heat Sink Using Solidworks, J. of Emerging Technologies and Innovative Research (JETIR), 8 (10), 2021, pp. 167-175.
[22] Jakhrani A.Q., Othman A.K., Rigit A.R.H., Samo S.R., Comparison of Solar Photovoltaic Module Temperature, ModelsWorld Applied Sciences Journal, 14:1-8.
[23] Website of Sandia National Laboratory (SNL), To Improve PV Performance ModelingCollaborative (PVPMC1), https://pvpmc. sandia.gov/modeling-steps/2-dc-moduleiv/module-temperature/sandia-module-temperature-model/, access: 11.08.2016.
[24] Faiman D., Assessing the outdoor operating temperature of photovoltaic modules, Prog. Photovolt. Res., Appl. 16 (2008) 307-315, http://dx.doi.org/10.1002/pip.
[25] Obuchow S., Plotnikow I., Model symulacyjny trybów pracy autonomicznej stacji fotowoltaicznej z uwzględnieniem rzeczywistych warunków pracy, Wiadomości z Tomskiego Uniwersytetu Politechnicznego. Inżynieria geodezyjna, 2017. T. 328. No 6., 38-51.
[26] Muzathik A.M., Photovoltaic Modules Operating Temperature Estimation Using a Simple Correlation, International Journal of Energy Engineering, Aug. 2014, vol. 4, Iss. 4, 151-158.
[27] Akhsassi. M., El Fathi A., Erraissi N., et. al., Experimental investigation and modeling of the thermal behavior of a solar PV module, Sol. Energy Mater. Sol. Cells, 2018, 180, 271-279.
[28] Skoplaki E., Boudouvis A.G., Palyvos J.A., A simple correlation for the operating temperature of photovoltaic modules of arbitrary mounting, Sol. Energ. Mat. Sol. C., 2008, 92:1393-1402.
[29]Yang R., Tiepolo G.,Tonolo E.,Junior J.,Souza M., Photovoltaic Cell Temperature Estimation for a Grid-Connect Photovoltaic Systems in Curitiba, Brazilian Archives of Biology and Technology. Vol.62 no.spe: e19190016, 2019 http://www.scielo.br/babt
[30] Oh J., Pavgi A., Tamizhmani G., Determination of Empirical Coefficients and ΔT for Sandia Thermal Model: Dependence on Backsheet Type, proc. of 7th World Conference on Photovoltaic Energy Conversion (WCPEC-7), 2018, pp. 442-446.
[31] Holovko O., Badanie efektywności energetycznej systemu pasywnego chłodzenia paneli słonecznych w klimatycznych warunkach regionu Kujawsko-Pomorskiego (Research on the energy efficiency of a passive cooling system for solar panels in the climatic conditions of the Kuyavian-Pomeranian region). master thesis, Wyższa Szkoła Gospodarki w Bydgoszczy, 2022.
[32] MSN Weather, https://www.msn.com/pl-pl/pogoda/prognoza/inPoznan, access: 17.01.2022.
[33] ArcGIS World Geocoding Service, Prediction Of Worldwide Energy Resource, POWER | Data Access Viewer, https://power.larc.nasa.gov/data-access-viewer/, access: 17.03.2022.


Authors: M.Sc. Oleh Holovko, Poznan University of Technology, Institute of Automatic Control and Robotics, 3a Piotrowo Street, 61- 138 Poznań, E-mail: oleh.holovko@put.poznan.pl; PhD Eng. Adam Konieczka, Poznan University of Technology, Institute of Automatic Control and Robotics, 3a Piotrowo Street, 61-138 Poznań, E-mail: adam.konieczka@put.poznan.pl; prof. dr hab. Eng. Adam Dąbrowski, Poznan University of Technology, Institute of Automatic Control and Robotics, 3a Piotrowo Street, 61-138 Poznań, E-mail: adam.dabrowski@put.poznan.pl.


Source & Publisher Item Identifier: PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 99 NR 10/2023. doi:10.15199/48.2023.10.54