Beware of Asymmetry – Causes, Consequences, Measurement and Control

Published by Sonel


  • Three-phase motors are overheating!
  • Overcurrent breakers are triggering without a reason!
  • Energy bills are higher than expected!
Undesirable Asymmetry

The economic benefits of energy suppliers and their users are strongly dependent on reliability, safety and efficiency of the power system. One of the phenomena that is strongly related to the efficiency of the power system is an asymmetry.

Current and voltage asymmetry degrades the efficiency of the power system. It reduces the efficiency of generation, transmission and distribution of electricity. Ultimately, this results in an increase in the price of electricity. The electricity consumer will also incur additional costs due to a decrease in the efficiency of electrical equipment with the appearance of voltage asymmetry.

Figure 1. Asymmetry in power network causes higher costs.

About Asymmetry

There are three types of asymmetry states in the power grid. It is the current asymmetry, voltage asymmetry and the simultaneous occurrence of both current and voltage asymmetry. 

With regard to three-phase systems, voltage asymmetry is defined as a state in which the effective values of the three phase voltages are not the same and/or the angles between them differ significantly from 120 ° as can be seen in figure 2b. Any three-phase system of voltage or current vectors can be decomposed into a sum consisting of three components: zero sequence, negative sequence and positive sequence component. Coefficients that are scaled to the positive sequence can be calculated and are used to describe the quantitatively phenomenon of voltage and current asymmetry.

Figure 2. Phasor graph in a) reflects perfect symmetry in 3 phase power system. All vectors corresponding to 3 phases have the same magnitude and there is 120° between two adjacent vectors. Phasor graph in b) reflects asymmetry in power system. The vectors have different length and the angular shifts are different than 120° between adjacent phases.

Sources of Asymmetry

Voltage asymmetry and current asymmetry are two different types of asymmetry in the power system. The source and nature of these asymmetries are different. Voltage unbalance results from the structural asymmetry of generators (variations in internal construction), transformers, and transmission and distribution lines. In addition, asymmetry can be caused by a voltage drop on the system impedance by asymmetrical currents. In turn, the main source of current unbalance is load imbalance, caused by a single phase load in the distribution system or a fault on the load side.

Voltage asymmetry can also cause asymmetry in the supply current. This is particularly evident in the current of induction motors supplied with asymmetric voltage. For example, a 1% asymmetry in the supply voltage can cause several times greater current unbalance in induction motors.

Negative Effect of Asymmetry

Asymmetry of the current, i.e. the occurrence of the asymmetrical component, causes the dissipation of energy in the elements of the power system in the form of heat. As a result, current asymmetry reduces performance when generating, transmitting and distributing electricity. Therefore, the distribution system cables and wires must be selected taking into account the level of asymmetry.

The negative voltage asymmetry component will contribute to the creation of a magnetic field with the opposite direction in induction motors. It’s like accelerating and braking at the same time. For example, the occurrence of voltage asymmetries of up to several percent is able to significantly increase the temperature of the motor winding and reduce the winding life by more than half. Therefore, the load on motors should be reduced accordingly to compensate heating losses resulting from asymmetry.

Figure 3. High asymmetry caused overheating windings of the engine and fire. 

Asymmetry also has a negative effect on three-phase rectifiers and inverters. Voltage unbalance causes asymmetry of the supply current, which increases the temperature of the rectifier diodes and disrupts the operation of the safety devices. Other negative effects occur during transient states mainly caused by faults in the power system.

Transient current asymmetry occurs, for example, due to phase-to-phase faults. In this case, extreme levels of current asymmetry will occur, which will last only for a few seconds. However, this may lead to instability and system failure if the causes are not eliminated on time.

Methods of Mitigating Asymmetry
  1. Adoption of appropriate standards regarding acceptable levels of current and voltage asymmetry and their control.
  2. Applying regulations and standards to the equipment and transmission line.
  3. Structural modifications of single-phase loads.
  4. Single-phase voltage regulators.
Parameters and Devices for Measuring the Asymmetry

The asymmetry is related to the presence of positive sequence and zero sequence components and parameters u0  and  u2 (equations shown in the table) are commonly used in measurements in power engineering:

u0=U0/U1 × 100%
u2=U2/U1 × 100%

where:
u0 –  zero sequence asymmetry parameter,
u2 – asymmetry of the opposite parameter,
U0 – zero sequence component,
U1 – positive sequence component,
U2 – negative sequence component.

Commonly used devices for measuring power network parameters, including asymmetry, are power quality analyzers. Series of devices named PQM is the series of power quality analyzers by Sonel. All analyzers in the PQM series have the ability to measure asymmetry parameters.

A Few Simple Measures to Perform the Measurement and Diagnostics of Asymmetry:
  1. Connect any PQM Sonel series analyzer according to the manufacturer’s instructions and set the voltage and/or current asymmetry measurement mode.
  2. After the appropriate measurement time, download the data to the computer and use the Sonel Analysis program to plot the time graph of the course of the asymmetry parameters.
  3. If the level of the asymmetry parameter exceeds the threshold of EN 50160 or other standards, take action to mitigate the adverse effects.

Figure 4. Electrician is configuring connected PQM for measurement of asymmetry.


Source: https://www.sonel.pl/en/knowledge-centre/press-articles/power-quality-analysis/beware-of-asymmetry-causes-consequences-measurement/

Revised IEC and IEEE Standards for PQ Measurements for Users of PQ Monitoring Equipment

New and revised Standards for Power Quality measurements from IEC and IEEE and their benefit to users of PQ monitoring equipment that is compliant with these new standards general information refer to the actual standard for additional details.


IEC 61000-4-30 Class A Edition 3

The IEC 61000-4-30 Class A standard defines the measurement methods, time aggregation, accuracy and evaluation, for each power quality parameter to obtain reliable, repeatable and comparable results between various brands and models of PQ instruments and systems.

IEC 61000-3-30 Class A Edition 2

IEC 6100-4-30 Class A Edition 2 standardizes the measurements of:

• Power frequency
• Supply voltage magnitude
• Flicker (by reference to IEC 61000-4-15)
• Voltage dips/sags and swells
• Voltage interruptions
• Supply voltage unbalance
• Voltage harmonics, and interharmonics (referenced to IEC 61000-4-7)
• Mains signaling voltage
• Rapid voltage changes
• Magnitude of current
• Current harmonics and interharmonics (referenced to IEC 61000-4-7)
• Current unbalance

IEC 61000-4-30 Edition 3 Introduced new measurements definitions and PQ parameters.

“This third edition cancels and replaces the second edition published in 2008. This edition constitutes a technical revision”.

• Rapid voltage changes
• Flicker class F1
• Magnitude of the current
• Current unbalance
• Current harmonics (by reference to IEC 61000-4-7)
• Current interharmonics (by reference to IEC 61000-4-7)

Additional changes in harmonic parameters from IEEE 519 2014
  • The number of harmonics to be evaluated. In many application, 50 harmonics are not enough and modern DC to AC inverters used in Wind and Solar generation have significate harmonic component up to the 100th.
  • Recording resolution – the latest edition of the IEEE 519 requires a daily and weekly harmonic evaluation of both voltage and current at 150/180 cycles (~3 sec) resolution per phase. An edition 3 compliant instrument must record this data and prepare a report from the instrument.
Why these revised standards are important to electric utilities?

1. Rapid Voltage Change (RVC) parameter captures voltage changes (sags) that can be disruptive to some loads without exceeding the standard of +/- 5% voltage change limit. An instrument that does not make RVC measurements will miss these events. So a utility may receive customer complaints (most common is light flickers) and not have any data to find the source of the complaint. (most common is large motor starts or other sudden load or distributed generation switching). (tripping)

2. The Edition 3 revision transfers the responsibility for measurement methods continue in this standard, but responsibility for influence quantities, performance, and test procedures are transferred to IEC 62586 -1 and -2.

Part 1, namely IEC 62586-1, was constructed to define a comprehensive PQ device product standard, coined within as PQIs. The standard outlines safety, electromagnetic compatibility (EMC), climatic, and mechanical requirements, and refers to IEC 62586-2 for functional aspects. These requirements serve to ensure the instrument’s robustness will be suitable for its installation within the severe environments of a power station or substation.

Part 2, IEC 62586-24, defines the functional tests cited in the first part of the series. These tests are intended to comprehensively verify the PQ measurement methods outlined in 4-30. This chapter was established to provide traceable and repeatable procedures to verify the compliance of each PQ metric outlined in 4-30. This firstly addresses the main shortcoming of 4-30 and ensures better method adherence between PQ meter manufacturers. Additionally, the standard allows regulatory laboratories adhering to ISO/IEC 170255 to issue conformance reports and certificates according to IEC 62586-1 or IEC 62586-2 (with compliance to IEC 62586-2 meaning compliance to IEC 61000-4-30). The latter provides PQ meter manufacturers a way to provide internationally recognized compliance for the entire scope of PQI requirements.

3. To help ensure accurate PQ metrics in the harsh installation environment of a power station or substation, a number of electromagnetic compatibility (EMC) and influence quantity tests were also added to the scope of the IEC 62586 series.

“IEC 62586-2:2013 specifies functional tests and uncertainty requirements for instruments whose functions include measuring, recording, and possibly monitoring power quality parameters in power supply systems, and whose measuring methods (class A or class S) are defined in IEC 61000-4-30. This standard applies to power quality instruments complying with IEC 62586-1. This standard may also be referred to by other product standards (e.g. digital fault recorders, revenue meters, MV or HV protection relays) specifying devices embedding class A or class S power quality functions according to IEC 61000-4-30. These requirements are applicable in single, dual- (split phase) and 3-phase a.c. power supply systems at 50 Hz or 60 Hz.”

4. Environmental impact on the instrument from a laboratory environment. (25 Degrees C to a substation environment 40 Degrees C + ) is now part of the requirement of this standard.

5. Detailed measurement procedures for Harmonics including to the 100th are included.

6. Reporting of the harmonics to IEEE 519-2014 with harmonic limits specified for 1 and 1 week are included.

All of these issues can be defined as IEC 61000-4-30 Class A, Edition 3 compliant.

Application Guide for Solving Harmonic Problems

Published by MYRON ZUCKER INC. , Website: www.myronzucker.com


Definitions

Harmonics are multiples of the fundamental frequency of an electrical power system. If, for example, the fundamental frequency is 60 Hz, then the 5th harmonic is five times that frequency, or 300 Hz. Likewise, the 7th harmonic is seven times the fundamental, or 420 Hz, and so on for the higher-order harmonics. Harmonics can be discussed in terms of current or voltage. A 5th harmonic current is simply a current flowing at 300 Hz on a 60 Hz system. A 5th harmonic voltage occurs from the 5th harmonic current flowing through the impedances present. Sometimes the amount of harmonics is discussed as Total Harmonic Distortion (THD). The formula for calculating the THD for current is as follows:


If, for example…

I1 = current at 60 Hz = 250 Amps
I5 = current at 300 Hz = 50 Amps
I7 = current at 420 Hz = 35 Amps

then…


Sources

If these harmonic currents flow in a power system, then they cause what is known as poor “power quality” or “dirty power.” There are other causes of poor power quality, including transients such as voltage spikes, surges, sags and ringing. As shown in Figure 1, harmonics are considered a steady-state cause of poor power quality because they repeat every cycle. Figure 2 shows the resultant wave form from a 5th harmonic present in a 60 Hz system.

Figure 1 — Fundamental and 5th Harmonic

Figure 2 — Fundamental and 5th Harmonic Combined

Harmonics are caused by devices that draw non-sinusoidal currents when a sinusoidal voltage is applied. Many times these are devices which convert AC to DC. Some of the devices which cause harmonics are listed below:

◆ Adjustable Speed Drives (ASDs)
— DC Drives
— Variable Frequency Drives (VFDs)
◆ 6-pulse Converters
◆ Power Rectifiers (e.g., plating systems)
◆ Uninterruptible Power Supplies (UPSs)

The devices listed above use power electronics such as SCRs, diodes and thyristors. These devices have become a growing percentage of the load in industrial power systems. The majority use a 6-pulse converter similar to that in Figure 3.

Figure 3 — A Typical 6-pulse Converter

Loads which cause harmonics do so as a steady-state phenomenon. Therefore, if a load is suspected to be non-linear, then even an instantaneous reading of the load (while it is operating) can determine if it is harmonic producing.

Each type of load would typically exhibit a specific harmonic spectrum. For example, the most common industrial harmonic source is the 6-pulse converter. It exhibits a spectrum starting with the 5th harmonic and decreasing in amplitude throughout its spectrum. This spectrum is defined in the following formula and corresponding graph (Figure 4):

h = np ± 1

where

h = harmonic numbers of the spectrum
n = 1, 2, 3, . . .
p = 6 for a 6-pulse converter

Therefore h = 5, 7, 11, 13, 17, 19, 23, 25, . . .

Figure 4 — 6-pulse Converter Spectrum Graph

Another common spectrum is that of a switch-mode power supply used for personal computers. This is found in commercial applications and has a spectrum starting with the 3rd harmonic and continuing with the triplens as the most dominant.

h = 3, 9, 15, 21, 27, . . .

Large UPS (Uninterruptible Power Supply) systems exhibit yet another typical spectrum. They tend to use a 12-pulse converter and have the following spectrum:

h = np ± 1

where

h = harmonic numbers of the spectrum
n = 1, 2, 3, . . .
p = 12 for a 12-pulse converter

Therefore h = 11, 13, 23, 25, 35, 37, . . .

Problems Resulting from Harmonics

There are many problems that can arise from harmonic currents flowing in a power system. Some are easy to detect. Other problems may exist and persist because harmonics are not suspected as the cause. Harmonic currents cause higher RMS current and voltage in the system. This can result in any of the problems listed below:

  • Failed Power Factor Correction Capacitors
  • Blown Fuses (no apparent fault)
  • Tripped Circuit Breakers
  • Overheated Transformers
  • Overheated Conductors
  • Worn Conductor Insulation
  • Misfiring of AC and DC Drives

One of the larger problems is overheating transformers. In fact, a 10°C rise in operating temperature of transformers, motors or capacitors can cut equipment life by 50%. The harmonic currents are higher frequencies and tend to travel along the outside (skin effect) of the conductors, which results in insulation breakdown.

The need to address Harmonics

One of the two most common problems for industrial power users is striving to meet IEEE Std. 519-1992. IEEE 519 is a standard developed for utility companies and their customers in order to limit harmonic content and provide all users with better power quality. In the future, some utility companies may impose a penalty for users producing harmonics. Some key areas of the standard are as follows in Tables 1 and 2:

TABLE 1: Voltage Distortion Limits


TABLE 2: Current Distortion Limits for General Distribution Systems

(120 V through 69 000 V)


The other most common problem resulting from harmonics is power factor capacitor failures, or a need to correct power factor in a harmonic environment. In low-voltage systems (600 V or less), capacitors are typically the lowest impedance at harmonic frequencies. Therefore, they experience very high RMS currents and increased heat, which causes them to fail. So, even if meeting IEEE 519 is not the goal, dealing with harmonics may still be required.

When correcting power factor, there is the possibility of creating a resonant circuit. A resonant circuit occurs at the frequency when the impedance of the system (mostly the power transformer) and the impedance of the power factor capacitor are equal. This is called the resonant frequency.

The following formula can be used to find the resonant frequency in terms of harmonic number.

h = resonant frequency in terms of harmonic number
KVAsc = short-circuit capacity at the capacitor
KVAR = rated KVAR of the unswitched capacitance

If there are any sources of current at that frequency, they will be amplified. This will cause high distortion levels and could blow fuses or trip circuit breakers.

Locating the Source of Harmonics

When electric power users need to correct power factor, or they desire to meet IEEE 519, they must first locate the source of harmonics.

If the electrical power system is in the design phase, then the best approach is to gather as much information about any harmonics the non-linear loads will produce. A detailed one-line diagram including system voltages, transformer impedances, ASD Hp ratings, power rectifier KVA ratings, UPS KVA ratings and capacitor KVAR ratings is a good start to locating harmonics and the problems that may result. Myron Zucker, Inc. has produced a “Power Factor Correction & Harmonic Filter Questionnaire” which guides the user through a series of questions to obtain the data listed above and requests a one-line diagram.

The same approach should be used for an existing system. With an existing system, a harmonic study can be conducted to verify the system characteristics expected from the questionnaire or it can be done to determine the actual system characteristics. Myron Zucker, Inc. can provide assistance with both methods of locating harmonics.

Solving the Harmonic Problem

Harmonics can be “trapped” by the application of a Myron Zucker, Inc. tuned filter trap. The trap is an inductor capacitor (LC) filter which provides a low-impedance path for the harmonic currents. It “traps” the harmonics between itself and the harmonic source. As in correcting power factor problems at the source with capacitors, Myron Zucker, Inc. also recommends correcting harmonics problems at the source by using traps. For that reason, Myron Zucker, Inc. manufactures Caltrap™ brand harmonic filters from 10 to 100 KVAR, commonly tuned to the 5th harmonic, although other points are available. Myron Zucker, Inc. can also provide Caltrap™ brand harmonic filters with an integral line reactor to further isolate harmonics and provide other line reactor benefits such as reduced voltage notching from ASDs. Typical installations are shown in Figures 5 and 6 below.

Figure 5 — Caltrap™ Brand Harmonic Filter

Figure 6 — Caltrap™ With Line Reactor Brand Harmonic Filter

Although the best engineering practice is to trap the harmonics at the source, for economic reasons it may be better to use one trap for several harmonic sources. For example, a machine with several ASDs could be corrected with one trap at the machine control panel. In the same way, several small ASDs fed from one bus duct could have a trap at the beginning of the bus duct, giving the rest of the system better power quality.

In some cases, an even larger trap can be provided at the switchgear, feeding an entire low-voltage system. This would still trap the harmonics before the service transformer and could be used to reduce utility voltage harmonics.

Myron Zucker, Inc. manufactures Capacitrap® brand harmonic filters and automatically controlled Autocapacitrap® brand harmonic filters for these applications.Your local representative or Myron Zucker, Inc.’s Application Engineering Department can help determine what products are best for any application.

Myron Zucker, Inc. has successfully installed Caltrap™, Capacitrap® and Autocapacitrap® brand harmonic filters throughout the US and other countries. Our quality products and 50 years of experience in the power industry can be beneficial in any application

Harmonic Current and Voltage Distortion

Published by Michael Z. Lowenstein, President of Harmonics Ltd., Monroe, Conn. Nov 1st, 2002.


To obtain the effective voltage for a system in which voltages of several frequencies are present, you must add the voltages in an rms fashion.

Understanding the causes, similarities, and differences between current and voltage distortion will help you pinpoint most power quality problems.

When a writer or speaker mentions harmonic distortion in an article or presentation, they rarely distinguish between current and voltage distortion. This confuses the reader or listener and results in them passing on misinformation. So what’s the solution? Only when you truly understand the sources and properties of current and voltage distortion can you acknowledge their differences and realize how each affects a particular portion of the distribution system and the loads powered by that system.

An electrical system supplies power to loads by delivering current at the fundamental frequency. Only fundamental frequency current can provide real power. Current delivered at harmonic frequencies doesn’t deliver any real power to the load. When current of a single frequency is present in a system, you can use the measured values in Ohm’s Law and power calculations (see Sidebar below). However, when currents of more than one frequency are present, direct addition of the current values leads to a summed value that doesn’t correctly represent the total effect of the multiple currents. Instead, you need to add the currents in a manner known as the “root mean square” summation. The equation for the rms addition of currents is as follows:


So if a system carries 70A of fundamental current, 18A of 5th harmonic current, 14A of 7th harmonic current, and 11A of 11th harmonic current, the effective current would be 74.3A rms, not the arithmetic sum of 113A. This 74.3A rms value would be the correct value to use in all power calculations.

The same is true for harmonic voltages. To obtain the effective voltage for a system in which voltages of several frequencies are present, you must add the voltages in an rms fashion.

Fig. 1 Current measurement with harmonics

Current measurement with harmonics. Fig. 1 illustrates the measurement of current drawn by a nonlinear load. The rms current contains both the fundamental and harmonics. Note that the value of current at each harmonic as well as that for the rms current are the same at each measuring point, just as in a system containing only fundamental current. The term “distortion rms” is used to denote the rms value of harmonic current with the fundamental left out of the summation. The rms current is basically the total effective load current. Calculate total harmonic distortion (THD) by using the value of distortion rms current in the following equation:


The current THD is the same at each measuring point.

Fig. 2 Voltage measurement with harmonics

Voltage measurement with harmonics. Fig. 2 at right illustrates the measurement of voltage in a system powering a nonlinear load. The voltage contains both the fundamental and harmonics. The farther you measure from the source, the higher the harmonic voltage generated. The increased impedance, through which the harmonic current must flow, results in higher harmonic voltage generation. This is the opposite effect of impedance on the fundamental voltage, whereas fundamental voltage causes fundamental current flow, and harmonic current flow causes harmonic voltage.

Looking at Fig. 2 again, we see that although the fundamental voltage has dropped from 480V at Point 1 to 465V at Point 3, the increase in harmonic voltage causes the rms voltage to be higher at each measuring point than the fundamental voltage alone. Distortion rms is the rms value of the harmonic voltage with the fundamental left out of the summation, and it increases the farther away you measure from the source. Calculate THD using the same equation used for current distortion.

Effects of current distortion. Since operation of nonlinear loads causes the distorted current, which is path dependent, the effect of current distortion on loads within a facility is minimal. Therefore, harmonic currents can’t flow into equipment other than the nonlinear loads that caused them. However, the effect of current distortion on distribution systems can be serious, primarily because of the increased current flowing in the system.

All distribution systems are rms current-limited. In a system powering 3-phase loads, for example, a 1,000kVA, 480V transformer is rated to deliver 1,200A rms. But the more harmonic current this transformer has to supply, the less fundamental current it can provide for powering loads. In other words, because the harmonic current doesn’t deliver any power, its presence simply uses up system capacity and reduces the number of loads that can be powered.

Harmonic currents also increase I2Z heat losses in transformers and wiring. Since transformer impedance is frequency dependent, increasing with harmonic number, the impedance at the 5th harmonic is five times that of the fundamental frequency. So each ampere of 5th harmonic current causes five times as much heating as an ampere of fundamental current.

In a system powering phase-to-neutral connected loads, detrimental effects are again due to the harmonic currents using up system capacity and reducing the number of useful loads that can be powered. Third harmonic currents cause a further detriment, because they’re additive in the neutral conductor. When many computers, which are nonlinear loads, are connected, the neutral current — primarily 3rd harmonic — can be larger than any of the phase currents. These 3rd harmonic currents circulate in the primary (delta) of the distribution transformer that serves the portion of the system powering the computers and are dissipated as heat.

Effects of voltage distortion. Besides overheating, the other major effect of current distortion on an electrical system is the creation of voltage distortion. This distortion will have minimal effect on a distribution system, but unlike current distortion, it isn’t path dependent. So harmonic voltages generated in one part of a facility will appear on common buses within that facility. As we see in Fig. 2, high-voltage distortion at the terminals of a nonlinear load doesn’t mean high distortion will be present throughout the system. In fact, the voltage distortion becomes lower the closer a bus is located to the service transformer. However, if excessive voltage distortion does exist at the transformer, it can pass through the unit and appear in facilities distant from the origin.

The effect on loads within the facility could be detrimental in certain cases. For example, extreme voltage distortion can cause multiple zero crossings for the voltage wave. For equipment where proper sequencing of operations depends on a zero crossing for timing, voltage distortion can cause misoperation. Most modern electrical equipment uses an internal clock for timing sequencing so it’s unaffected by multiple zero crossings.

Voltage distortion appears to have little effect on operation of nonlinear loads connected either phase-to-phase or phase-to-neutral.

On the other hand, 5th harmonic voltage distortion can cause serious problems for 3-phase motors. The 5th harmonic is a negative sequence harmonic, and when supplied to an induction motor it produces a negative torque. In other words, it attempts to drive the motor in a reverse direction and slows down its rotation. So the motor draws more 60-Hz current to offset the reverse torque and regain its normal operating speed. The result is overcurrent in the motor, which either causes protective devices to open or the motor to overheat and fail. For this reason, removing 5th harmonic current from systems powering 3-phase loads is often a high priority in industrial facilities.

IEEE 519 “Harmonic Current and Voltage Limits.” This document outlines limits on voltage and current harmonic distortion measured at the point of common coupling (PCC), which is usually defined as the place where the consumer connects to the power supplier. Without going into a thorough analysis, here are several aspects of IEEE 519 that are particularly relevant.

  • IEEE 519 isn’t an individual standard — it’s a system standard. So any attempt to apply its limits to an individual piece of equipment or a particular location within a facility is a misuse.
  • The reason for limiting current distortion at the PCC is to ensure a consumer won’t draw so much harmonic current from the utility through the unity impedance that the utility voltage distortion will be excessive.
  • Limiting this voltage distortion prevents it from spreading to other facilities.

IEEE 519 is designed to protect the voltage integrity of the utility grid system, and shouldn’t be applied to operations within a particular facility. For example, using the system shown in Fig. 2, the presence of 18.7% voltage distortion at the load does not violate the 5% voltage distortion limit of IEEE 519, since the terminals of the nonlinear load are far removed from the PCC.

Thinking about the possible detrimental effects of a large amount of voltage distortion on this nonlinear load, you have to remember that the load itself causes this distortion. Voltage distortion caused by normal operation isn’t detrimental to operation of the load.

In another example, imagine the nonlinear load illustrated in Fig. 1 is an adjustable speed drive (ASD) or a nonlinear load connected to a 1,000kVA, 480V transformer. Current distortion is 25A, or 35.7%, for this drive. But as a percentage of the transformer capacity, the load is negligible. So the effect of powering this drive on the transformer, or on the generation of voltage distortion at the PCC, is insignificant.

Voltage and harmonic distortion levels can vary drastically, depending on the configuration of your system. Your job is to find them, diagnose the cause, and eliminate it before it has a chance to damage your equipment.

Sidebar: Current, Voltage, and Impedance Before studying the effect of harmonics on an electrical distribution system, you must understand the relationships between current, voltage and impedance. Ohm’s Law governs these relationships. This basic electrical tenet states that voltage equals current times resistance. For alternating current (AC) circuits, resistance is replaced by impedance, but the unit of measure (the ohm) remains the same. Using Ohm’s Law, you can calculate the voltage losses due to current flow through the impedance of a system. Once you know the impedance, you can find the power dissipated by this current flow.

Current measurement

Fig. A (below) illustrates the principles of current measurement. Laws of physics state that the current into a point must equal the current out of a point. If the current path shown is the only current path, the current measurements at Points 1, 2, and 3 must all be the same. Since the load is linear, all current flows at 60 Hz.

Fig A. Current measurement

Voltage measurement

Voltage measurement is different. Fig. B (below) illustrates the principles of voltage measurement. Measuring in the direction of current flow, the voltage measured at any point is reduced from the voltage measured at a previous point by the product of the current and the impedance (I×Z.) The voltage drop across the system impedance reduces the voltage measured at Point 2. The voltage drop across the relatively high impedance of the line reactor further reduces the voltage measured at Point 3. As you can see, the farther you measure from the source, the more the voltage is lowered.

Fig. B Voltage measurement

Power losses and power delivery

If the voltage measured at Point 3 is lower than that measured at Point 2, and the current is the same, then some power was lost in the line between the two points. This power is often called the I2Z loss. To ensure that you supply loads with enough voltage for them to operate properly, or to reduce I2Z losses, you must use larger conductor sizes for long electrical runs. This reduces the line impedance and, therefore, the voltage and power losses.

Sidebar: Sample Power Loss Calculation

Using the system shown in Fig. 2 above, it’s easy to calculate the power loss due to the voltage drop across system impedance. The data to the right illustrates this calculation. Calculate the power loss for the 60 Hz or fundamental current and then do the same for the rms current. As you can see, the presence of harmonic currents results in increased power losses. In this example, the harmonic currents increase power loss by 132W, or 12.6%. In many cases, removing harmonic currents can result in energy savings.

Fig C. Power Loss Calculation

Measurements on electrical distribution systems powering nonlinear loads usually disclose the presence of both current and voltage harmonics.


Source: https://www.ecmweb.com/content/article/20887165/harmonic-current-and-voltage-distortion

Standard EN 50160 – Voltage Characteristics of Public Distribution Systems

Published by Henryk Markiewicz, Email: henryk.markiewicz@pwr.wroc.pl, & Antoni Klajn, Email: antoni.klajn@pwr.wroc.pl, Wroclaw University of Technology, July 2004. Website: www.pwr.wroc.pl

Source: Leonardo Power Quality Initiative (LPQI) Power Quality Application Guide Voltage Disturbances 5.4.2 Standard EN 50160


Introduction

Electrical energy is a product and, like any other product, should satisfy the proper quality requirements. If electrical equipment is to operate correctly, it requires electrical energy to be supplied at a voltage that is within a specified range around the rated value. A significant part of the equipment in use today, especially electronic and computer devices, requires good power quality (PQ). However, the same equipment often causes distortion of the voltage supply in the installation, because of its non-linear characteristics, i.e. it draws a non-sinusoidal current with a sinusoidal supply voltage (see Section 3.1 of this Guide). Thus, maintaining satisfactory PQ is a joint responsibility for the supplier and the electricity user. According to standard EN 50160 [1] the supplier is the party who provides electricity via a public distribution system, and the user or customer is the purchaser of electricity from a supplier. The user is entitled to receive a suitable quality of power from the supplier. In practice the level of PQ is a compromise between user and supplier. Where the available PQ is not sufficient for the user’s needs, PQ improvement measures will be needed and will be the subject of a cost-benefit analysis (see Section 2.5 of this Guide). However, the cost of poor PQ usually exceeds the cost of measures required for improvement – it is estimated that losses caused by poor power quality cost EU industry and commerce about € 10 billion per annum (see Section 2.1 of this Guide).

However, electrical energy is a very specific product. The possibility for storing electricity in any significant quantity is very limited so it is consumed at the instant it is generated. Measurement and evaluation of the quality of the supplied power has to be made at the instant of its consumption. The measurement of PQ is complex, since the supplier and user, whose sensitive electrical equipment is also a source of disturbances, have different perspectives.

Standard IEC 038 [2] distinguishes two different voltages in electrical networks and installations:

  • supply voltage, which is the line-to-line or line-to-neutral voltage at the point of common coupling, i.e. main supplying point of installation
  • utility voltage, which is the line-to-line or line-to-neutral voltage at the plug or terminal of the electrical device.

The main document dealing with requirements concerning the supplier’s side is standard EN 50160, which characterises voltage parameters of electrical energy in public distribution systems. This is a European standard but it is supplemented in some regions or countries by other supplemental standards, such as [3] in Germany, or [4] in Poland. Many regional codes, such as the German TAB [3] apply to an individual utility, but these are being unified as part of the liberalisation of the German electricity market. According to IEC 038, both standard EN 50160 and rules [3,4] concern the supply voltage, i.e. that measured at the point of common coupling.

On the user’s side, it is the quality of power available to the user’s equipment that is important. Correct equipment operation requires the level of electromagnetic influence on equipment to be maintained below certain limits. Equipment is influenced by disturbances on the supply and by other equipment in the installation, as well as itself influencing the supply. These problems are summarised in the EN 61000 series of EMC standards, in which limits of conducted disturbances are characterised. Equipment sensitivity to utility voltage quality, as well as mitigation measures, are presented in Section 3 (Harmonics) and Section 5 (Voltage Disturbances) of this Guide.

The subject of this section is a detailed presentation of standard EN 50160 and an analysis of its requirements according to the operation of chosen equipment. Methods of measuring supply voltage parameters are also presented.

Basic definitions of voltage parameters

In standard EN 50160 several voltage parameters are defined. The most important are:

Supply voltage – the rms value of the voltage at a given moment at the point of common coupling, measured over a given time interval.

Nominal voltage of the system (Un) – the voltage by which a system is designated or identified and to which certain operating characteristics are referred.

Declared supply voltage (Uc) – is normally the nominal voltage Un of the system. If, by agreement between the supplier and the user, a voltage different from the nominal voltage is applied to the terminal, then this voltage is the declared supply voltage Uc.

Normal operating condition – the condition of meeting load demand, system switching and clearing faults by automatic system protection in the absence of exceptional conditions due to external influences or major events.

Voltage variation – is an increase or decrease of voltage, due to variation of the total load of the distribution system or a part of it.

Flicker – impression of unsteadiness of visual sensation induced by a light stimulus, the luminance or spectral distribution of which fluctuates with time.

Flicker severity – intensity of flicker annoyance defined by the UIE-IEC flicker measuring method and evaluated by the following quantities:

  • Short term severity (Pst) measured over a period of ten minutes
  • Long term severity (Plt) calculated from a sequence of 12 Pst – values over a two-hour interval, according to the following expression:

Supply voltage dip – a sudden reduction of the supply voltage to a value between 90% and 1% of the declared voltage Uc, followed by a voltage recovery after a short period of time. Conventionally the duration of a voltage dip is between 10 ms and 1 minute. The depth of a voltage dip is defined as the difference between the minimum rms voltage during the voltage dip and the declared voltage. Voltage changes which do not reduce the supply voltage to less than 90% of the declared voltage Uc are not considered to be dips.

Supply interruption – is a condition in which the voltage at the supply terminals is lower than 1% of the declared voltage Uc. A supply interruption is classified as:

  • prearranged in order to allow the execution of scheduled works on the distribution system, when consumers are informed in advance
  • accidental, caused by permanent (a long interruption) or transient (a short interruption) faults, mostly related to external events, equipment failures or interference.

Temporary power frequency overvoltages – have relatively long duration, usually of a few power frequency periods, and originate mainly from switching operations or faults, e.g. sudden load reduction, or disconnection of short circuits.

Transient overvoltages – are oscillatory or non-oscillatory, highly damped, short overvoltages with a duration of a few milliseconds or less, originating from lightning or some switching operations, for example at switch-off of an inductive current.

Harmonic voltage – a sinusoidal voltage with a frequency equal to an integer multiple of the fundamental frequency of the supply voltage. Harmonic voltages can be evaluated:

  • individually by their relative amplitude Uh related to the fundamental voltage U1, where h is the order of the harmonic
  • globally, usually by the total harmonic distortion factor THDU, calculated using the following expression:

Interharmonic voltage – is a sinusoidal voltage with frequency between the harmonics, i.e. the frequency is not an integer multiple of the fundamental.

Voltage unbalance – is a condition where the rms value of the phase voltages or the phase angles between consecutive phases in a three-phase system are not equal.

Main requirements of EN 50160

EN 50160 gives the main voltage parameters and their permissible deviation ranges at the customer’s point of common coupling in public low voltage (LV) and medium voltage (MV) electricity distribution systems, under normal operating conditions. In this context, LV means that the phase to phase nominal rms voltage does not exceed 1000 V and MV means that the phase-to-phase nominal rms value is between 1 kV and 35 kV.

The comparison of the EN 50160 requirements with those of the EMC standards EN 61000, listed in Tables 1 and 2, show significant differences in various parameters. There are two main reasons for these differences:

◆ The EMC standards concern the utility voltage, according to IEC 038, while EN 50160 deals with the supply voltage. The differences between these voltages are due to voltage drops in the installation and disturbances originating from the network and from other equipment supplied from the installation. Because of this, in many standards of the EN 61000 series the equipment current is an important parameter, while the load current is not relevant to EN 50160.

◆ EN 50160 gives only general limits, which are technically and economically possible for the supplier to maintain in public distribution systems. When more rigorous conditions are required, a separate, detailed agreement between supplier and consumer must be negotiated. Measures for improving PQ imply additional cost and equipment and are considered in other parts of this Guide.

◆ EN 50160 has additional limitations. It does not apply under abnormal operating conditions, including the following:

  • conditions arising as a result of a fault or a temporary supply condition
  • in the event of the failure of a customer’s installation or equipment to comply with the relevant standards or with the technical requirements for the connection of loads
  • in the event of the failure of a generator installation to comply with relevant standards or with the technical requirements for interconnection with an electricity distribution system
  • in exceptional situations outside the electricity supplier’s control, in particular:
    • exceptional weather conditions and other natural disasters
    • third party interference
    • actions of public authorities
    • industrial action (subject to legal requirements)
    • force majeure
    • power shortages resulting from external events.

As the analysis of parameters presented in Table 1 shows, these requirements are not particularly rigorous for the supplier. The numerous situations in which the standard does not apply can excuse the majority of outages and voltage disturbance events that occur in practice. Thus, many suppliers interpret the requirements of EN 50160 as principally informative and accept no responsibility when the limits are exceeded.

Table 1 – Comparison of supply voltage requirements according to EN 50160 and the EMC standards EN 61000

On the other hand, the consumer’s point of view is usually totally different – they regard the limits given in EN 50160 as requirements that must be guaranteed by the supplier. However, as mentioned before, for many consumers, even fulfilling the requirements given in EN 50160 does not assure a satisfactory level of PQ. In such cases the level of PQ required must be defined in a separate agreement between supplier and consumer.

Table 2 – Values of individual harmonic voltages at the supply terminals for orders up to 25, given in percent of Un

Figure 1 – Illustration of a voltage dip and a short supply interruption, classified according to EN 50160; Un – nominal voltage of the supply system (rms), UA – amplitude of the supply voltage, U(rms) – the actual rms value of the supply voltage

Operation of equipment and requirements of EN 50160

The correct operation of electrical equipment requires a supply voltage that is as close as possible to the rated voltage. Even relatively small deviations from the rated value can cause sub-optimal operation of equipment, e.g. operation at reduced efficiency, or higher power consumption with additional losses and shorter service life. Sometimes prolonged deviations can cause operation of protection devices, resulting in outages. Of course, the correct operation of equipment also depends on many other factors, such as environmental conditions and proper selection and installation.

Investigation of the independent influence of each supply voltage parameter on equipment operation is easily performed, but when parameters vary simultaneously the situation is much more complex. In some cases, after detailed analysis of the effects of each of the different voltage parameters, results can be superimposed in order to estimate the total influence of many parameters. The influence of a particular voltage parameter on equipment operation is made based on mathematical formulae describing analysed physical phenomena. Two simple examples, concerning lighting and motors, follow.

For incandescent light sources, supply voltage is the most significant influence on the luminous flux, as illustrated in Figure 2 and formula (3). The permissible supply voltage variations according to EN 50160 can thus cause significant changes of the flux. EN 50160 allows, for example, that the supply voltage can be equal to Un-10 % or Un+10% for a long period, thus an incandescent lamp will deliver as little as 70%, or as much as 140%, of its nominal luminous flux respectively. Furthermore, at Un +10%, the service life of these lamps is reduced to about 25% of the nominal value (Figure 3), i.e. about 250 hours instead of the typical life of 1 000 hours. (Note that the durability of fluorescent and discharge lamps depends mainly on the number of turn-on cycles. The effect of supply variations is small.) The values shown in Figures 2 and 3 are calculated for steady state operation voltage at the given value.

Figure 2 – Relative value of luminous flux F of an incandescent and discharge lamp as a function of the supply voltage according to formula (3)

Figure 3 – Relative value of the service life (durability) of an incandescent lamp as a function of the supply voltage according to formula (4)

In practice the voltage value changes continuously according to the operation and load conditions in the network, as for example shown in Figure 4. The mathematical description of characteristics shown in Figures 2 and 3 are:


where:

  • F = luminous flux
  • U = supply voltage
  • Fn = luminous flux at nominal value of supply voltage Un
  • b = factor equal 3.6 for incandescent lamps and 1.8 for discharge lamps

where:

  • D = service life (durability) of the incandescent lamp
  • Dn = durability at nominal value of supply voltage Un.

Figure 4 – Examples of voltage dips (rms phase to neutral voltage); oscillograms showing the supply voltage (upper trace) and frequency changes (lower trace) at the PCC of a small factory

One can see that the requirements concerning voltage changes in EN 50160 are not very rigorous. Even keeping voltage variations in the permissible limit ±10%, can cause under performance of lighting sources In practice, these variations should be limited to about ±(3-4)%, in order to avoid negative consequences in lighting.

The voltage fluctuations shown in Figure 4 illustrate the voltage influence on the flicker severity, which can be measured and calculated according to formula (1). Measurement of flicker is considered in another section of the Guide.

For electric motors the most significant factor is the fluctuation of torque, which depends on the square of the supply voltage value. Problems could occur during start-up of heavy loads, because the inrush current causes an additional voltage drop within the installation (Figure 5). In practice, for the majority of three phase electric motors, start-up occurs normally at or above 85% of nominal voltage for heavy starting loads and at or above 70% for light starting loads. Thus, the EN 50160 voltage fluctuation requirements are satisfactory here. However prolonged operation of the motor at an rms voltage value of –10% or +10 % of Un can cause other negative consequences: overloading and operation of the thermal protection in the first case, or operation at excessive power and protection tripping in the second case. All voltage dips can cause nuisance tripping of the motor protection.

Figure 5 – Example of supply voltage changes (upper trace) at start-up of an asynchronous motor; lower trace – load current in the supplied installation of a small factory; the peak at the end of current flow is the inrush process

The influence of the load current on the supply voltage in the installation depends on the impedance of the supply grid. The utilization voltage at the equipment depends on the impedance of the supply grid and that of the customer’s installation. An illustration of the influence of load current on the supply voltage is shown in Figure 6.

Figure 6 – Illustration of the load current influence on the supply voltage dips in the electrical installation

Other important problems for the motors are voltage harmonics in and unbalance of the supply voltage. Voltage unbalance in a three-phase system causes an opposing torque, proportional to the negative sequence voltage component. Each voltage harmonic produces a respective harmonic current and its own torque, which can be coherent or opposite to the main torque, for various slip values. The most important here are the 5th and 7th harmonics. Figure 7 illustrates a case in which the 7th harmonic torque can cause problems during motor start-up, where the characteristic torque and the braking torque curves cross.

Figure 7 – Influence of asynchronous torque produced by harmonics on the main torque characteristic of an asynchronous motor

For other electrical equipment the relationship between supply voltage and its power or efficiency may be significant. For the majority of equipment, voltage changes in the range (0.9 – 1.1) Un do not cause any negative consequences, especially for common heating devices. For equipment with a higher sensitivity to the supply voltage proper protection should be installed.

Measuring methods

Measurement and testing of supply voltage quality, according to EN 50160, requires specialised apparatus and measuring methods (see Sections 3.2 and 5.2 of this Guide). This arrangement enables continuous monitoring, over 7 days, of the following parameters:

  • voltage in three phases
  • frequency
  • total harmonic distortion factor THDU
  • voltage unbalance factor, which is a multiple of positive and negative sequence voltage components
  • fast and slow voltage variations, which are defined as short term (Pst) and long term (Pst) flicker severity factors (equation 1).

This type of equipment also enables measurement of voltage dips and outages, its frequency and duration.

The measured parameters are processed and recorded as 10 minute time-segments (1008 segments over 7 days). For each segment the mean value of the measured parameter is calculated. After the 7-day recording period a so-called “ordered diagram” is produced, which shows the sum of the duration of a given distortion level in the observed time period. (For frequency measurement, the duration of each single segment is 10 seconds).

An example of an ordered diagram is shown in Figure 8. It clearly shows whether the measured voltage parameters have been maintained at the permissible level for 95% of the tested time. (Table 1).

Figure 8 – Example of the ordered diagram of the total harmonic distortion factor measured in substations supplying low voltage industrial (1 and 3) and municipal (2) networks

Country perspectives

As mentioned above, while EN 50160 gives general limits for public supply networks, various European countries have additional rules governing supply conditions. Many of these national regulations cover areas not included in EN 50160, such as the maximum permissible harmonic load to be connected to the PCC.

The German national standard VDE 0100 states that the voltage parameters defined in DIN EN 50160 reflect extreme situations in the network and are not representative of typical conditions. In planning networks, the recommendations of VDE 0100 should be followed. One of the TABs [3] gives maximum values (per unit) for phase-angle controlled resistive loads (1 700 VA single-phase, 3 300 VA two-phase and 5 000 VA balanced three-phase) and for uncontrolled rectifier loads with capacitive smoothing (300 VA single-phase, 600 VA two-phase and 1000 VA balanced three-phase). The equipment standard VDE 0838 (EN 60555) is also quoted.

In Poland, the rules of electrical energy distribution established by the government [4] give the fundamental parameters of the supply voltage (Table 3) and do not refer to EN 50160. Additionally, consumers are divided into six groups, for which separate, permissible total annual outage times are defined. The document also deals in detail with various economic aspects of the energy market, principles of settlement between network and distribution companies etc.

Table 3 – Requirements concerning PQ of supply voltage in Polish distribution network, according to [4]

In Italy there is an important document dealing with the continuity of supplied supply [8]. The Italian Regulatory Authority for Electricity and Gas (AEEG) has in fact set out a uniform system of service continuity indicators and has put in place a system of incentives and penalties in order to progressively bring continuity levels up to meet European standards. The Authority has divided the national territory into 230 geographical zones, sub-divided by areas of population density and has set improvement targets for each area on the basis of the previous year’s performance. Utilities that succeed in improving by more than the required rate can recover the higher costs sustained. Conversely, companies have to pay a penalty if they fail to meet the improvement target. Interruptions due to acts of God, or those caused by third parties, are not included in the calculation. The overall performance target is to bring continuity levels up to national benchmark levels based on European standards: 30 minutes of interruptions overall per user per year in large cities (high density); 45 minutes in medium-sized towns (medium density): and 60 minutes in rural areas (low density). Other countries have similar regimes imposed by the regulatory authorities.

The UK has a number of documents making up the distribution code. One of the most important is G5/4, discussed elsewhere in this Guide, which regulates the connection of harmonic loads to the point of common coupling. Measures to encourage the improvement of continuity are the responsibility of the Office of Gas and Electricity Markets (OFGEM).

Conclusions

The requirements of EN 50160 are not difficult for electricity suppliers to fulfil. The parameters of the supply voltage shall be within the specified range (Table 1) during 95% of the test period, while the permitted deviations in the remaining 5% of the period are much greater. For example, the mean value during 95% of the time shall be between 90% and 110% of the nominal voltage. This means that, in an extreme case, customers could be supplied at 90% of nominal voltage continuously while, for 5% of the time, the voltage could be much lower. If, in such a boundary situation, other parameters are also at the extremes permitted in the standard, for example harmonic voltages or voltage unbalance, then equipment mal-operation is likely.

The standard could be improved. For example, requiring the mean values of measured voltage parameters, over the whole of the test period within ±5% would guarantee that the supply voltage could not be maintained at the lower or upper boundary value for a prolonged period.

The number of voltage dips permitted (up to 1 000 during the year) and the number of short and long outages are rather high from the customer’s point of view. Voltage dips to below 30% of the nominal voltage with duration longer than 0.3 s can cause low voltage protection to trip or contactors in the motor circuits to drop out. Thus, the real number of process interruptions will be much greater than the number that would be expected to result from voltage interruptions.

EN 50160 should be understood as representing a compromise between supplier and customer. It requires that the supplier provide, as a minimum, a barely adequate quality supply. Most suppliers routinely exceed these requirements by a large margin, but do not guarantee to do so. If the customer has higher requirements, mitigation measures should be provided or a separate agreement for a higher quality supply must be negotiated. However, the important advantage of the standard is:

  • definition of the voltage parameters important for power quality
  • uantitative determination of the values, which are a reference point in evaluation of the power quality.

It is the task of the electricity regulator to set a level of quality that requires best practice from the supplier, while not setting the level too high so that the price of electricity increases for everybody.

References and Bibliography

[1] EN 50160, Voltage characteristics of electricity supplied by public distribution systems, 1999

[2] IEC 038, IEC standard voltages, 1999

[3] Technische Anschlussbedingungen (Technical requirements of connection), VDEW

[4] Rozporzadzenie Ministra Gospodarki z dnia 25 wrzesnia 2000, w sprawie szczególowych warunków przylaczania podmiotów do sieci elektroenergetycznych, obrotu energia elektryczna, swiadczenia uslug przesylowych, ruchu sieciowego i eksploatacji sieci oraz standardów jakosciowych obslugi odbiorców. Dziennik Ustaw Nr 85, poz. 957 (Rules of detailed conditions of connection of consumers to the electrical power network and quality requirements in Poland).

[5] Baranecki A et al, Poprawa jakosci zasilania w sieciach NN i SN. (Improvement of supply quality in LV and MV networks), Elektronizacja 1-2/2001

[6] Seipp G G, Elektrische Installationstechnik, Berlin – München, Siemens AG, 1993

[7] DIN VDE 0100-100 (VDE 0100 part 100): 2002-08

[8] Decision 128/1999: Definizione di obblighi di registrazione delle interruzioni del servizio di distribuzione dell’energia elettrica e di indicatori di continuità del servizio

[9] Decision 144/00: Determinazione dei livelli effettivi base e dei livelli tendenziali di continuità del servizio per ogni ambito territoriale e per ogni anno del periodo 2000-2003 ai sensi dell’articolo 7 della deliberazione dell’Autorità per l’energia elettrica e il gas 28 dicembre 1999, n. 202/99 e per la determinazione della media nazionale dei livelli tendenziali di continuità del servizio per l’anno 2004, ai sensi dell’articolo 9, comma 9.4, della medesima deliberazione.

Harmonics Mitigation and Power Quality Improvement in Grid Connected Wind Power Plant Using STATCOM

Published by Nasiru B. Kadandani, Department of Electrical Engineering, Bayero University, Kano, Nigeria. Email: nbkadandani.ele@buk.edu.ng.

Published in: The Proceedings of Second International Conference on Electrical and Electronics Engineering, Clean Energy and Green Computing, Konya, Turkey, 2015.


Abstract

Grid integration of intermittent renewable energy sources like wind and solar is usually associated with power quality disturbance especially when the penetration level is high. This paper investigates the power quality issues associated with grid connected wind power plant (WPP) and how to overcome such problems using static synchronous compensator (STATCOM) – a member of Flexible A.C Transmission System (FACTS) devices. The major power quality issue investigated in the paper is harmonic distortions. Other power quality parameters such as voltage dip, voltage swell, flicker, transient, short and long interruptions were also briefly introduced. The entire system including the STATCOM control scheme is simulated in Simulink environment of MATLAB. Simulation results show that the harmonic contents at the output of the system with unfiltered linear loads are quite high, thus showing power quality deterioration. Fast Fourier Transform (FFT) analysis on the voltage and current waveforms of the system show that the STATCOM control scheme is capable of cancelling out the reactive and harmonic parts of the load current thereby restoring the smooth sinusoidal waveform of the voltage and current at the wind point of interconnection (POI), or point of common coupling (PCC) which signifies power quality improvement.

Keywords—power quality; STATCOM; THD; FFT; WPP.

I. INTRODCUTION

Power quality is a term used by engineers to refer to the problems associated with voltage, current or frequency deviation that result in failure or equipment malfunction. It is usually related to maintaining a smooth sinusoidal waveform of bus voltage, current and frequency [1]. Thus, a perfect power supply is one that is highly available within prescribed voltage and frequency tolerances, with smooth sinusoidal wave form and also enables equipment work properly. On the other hand, any disturbance in the magnitude, frequency or purity from the balanced three phase sinusoidal wave form can lead to deterioration of the power quality. Power quality is of great concern to consumers, utilities and equipment manufacturers. It becomes especially important with the insertion of sophisticated devices, whose performance is very sensitive to the quality of power supply [2]. Power quality study is gaining much emphasis due to the increased proliferation of sensitive equipment and the need of maintaining excellence in electrical power generation [3]. Increased research in grid integration of wind turbine and the actual project development makes power quality issues more and more important both in theory and practice.

Among all forms of power quality issues in grid connected wind power plants (WPP), harmonic distortion is more common since any deviation from a perfect sinusoidal wave shape in voltage, current or frequency is an indication of the presence of harmonics in the power system. Due to the wide-spread use of power electronic devices in residential, commercial and industrial loads, electric utilities have experienced an increase in the level of harmonic frequencies on their electrical delivery systems. Hence, the potential harmonic effects on power equipment and system operation are becoming a concern for the utilities.

In response to the aforementioned challenges, some utility operators and wind farm vendors usually assess the quality of power supplied to major customers through measurement and analysis to ascertain whether the harmonic levels are within allowable limits as recommended by regulating bodies like IEC and IEEE. Fortunately, intensive research in power electronics has lead to the development of flexible a.c transmission system (FACTS) devices for power quality improvement. Such devices are capable of mitigating power quality disturbances with respect to grid codes and provide power system stability by controlling the power flow in a transmission network using power electronic controlled devices [4]. FACTS devices are categorized into two, namely; Thyristor-based FACTS controllers and GTO based FACTS controllers. Members of the first category include Static VAR Compensator (SVC), Thyristor Controlled Series Capacitor (TCSC), Thyristor Controlled Phase Angle Regulator (TCPAR), e.t.c. The second category includes static synchronous compensator (STATCOM), Static Synchronous Series Compensator (SSS), Unified Power Flow Controller (UPFC), e.t.c.

II. POWER QUALITY PARAMETERS AND THEIR CONSEQUENCES

A. Harmonic Distortions

Harmonic distortion refers to the periodic deviation of voltage (or current) sine wave from a smooth sinusoidal shape and usually occurs when frequencies of the multiple integers of the fundamental frequency are added to the pure sinusoidal waveform of the voltage (or current). Harmonics are therefore integer multiples of the fundamental frequency. Total harmonic distortion (THD) is a measure of all the values of the waveform that are distorted.

At the generation end, harmonics are usually caused by power electronic converters used in variable speed wind turbine, while at the receiving (consumer) end, harmonics are caused by non-linear loads (equipment’s that do not use voltage or current in normal sinusoidal shape) such as computers, television, arc furnace, arc welders, mercury lamps, electronic ballasts, battery charger, variable speed drives, medical diagnostic equipment and fluorescent lamps [5]. Other causes of harmonics include resonance phenomena, transformer saturation, light dimmers and switch mode power supplies.

Harmonics can cause significant damage to transmission and distribution network as well as to consumer equipment. The most notable effects of harmonic distortion are; overload operation of electric motor, nuisance tripping of circuit breaker, misbehaved operation of fuses, tripping of variable speed drives, overheating of electric motors and transformers, incorrect power measurement and failure or damage to electrical equipment’s like contactors and power factor correction capacitors.

Harmonic distortions can be mitigated by application of active conditioners, input chokes, passive filters, isolation transformers, and equipment’s with build-in power factor correction capability such as FACTS devices like STATCOM, DVR, SVC.

• Harmonic Distortion in Bus Voltages

The total harmonic distortion of bus voltage, 𝑉𝑇𝐻𝐷 is defined as the ratio of the square root of the sum of squares of the rms value of the harmonic component, 𝑉𝑛 to the rms value of the fundamental component, 𝑉1 [6].


For 132kV, the voltage THD limit is <3% [7].

• Harmonic Distortion in Line Currents

The total harmonic distortion of line current, 𝐼𝑇𝐻𝐷 is defined as the ratio of the square root of the sum of squares of the rms value of the harmonic component, 𝐼𝑛 to the rms value of the fundamental component, 𝐼1 [6].


For 132kV, the current THD limit is <2.5% [7].

It can be seen from equations 1 and 2 that THD is the rms value of the waveform when the fundamental is removed. The fundamental of a smooth sinusoidal voltage (or current) waveform is the system frequency (50Hz in some countries and 60Hz in others).

B. Flicker

Flicker is a term used to relate the short lived voltage variation that is associated with annoying changes in the luminance of lamps. It is usually caused by the two modes of operations of the WPP, namely; switching operations and continuous operations. Flicker from switching operation usually occurs as a result of start-up and shut down of the wind turbines (WTs). Continuous operations like blade pitching, wind turbulence, tower shadow, wind shear, and yaw misalignment can also cause flicker. Furthermore, industrial loads such as welding machine, electric boilers and electric arc furnaces also cause flicker [8].

The long term flicker, 𝑃𝑙𝑡, which is usually evaluated over 2 hours period is expressed in [9] as:


Where

𝑆𝑛= Rated apparent power of the WT,
𝑆𝑘= Short circuit apparent power of the grid,
𝜑= Phase shift and
𝐶= Flicker coefficient

The limiting value for flicker coefficient is ≤ 0.4 for average value of 2 hours [10].

The main effect of flicker is the annoying and noticeable changes in lightning levels. Flicker can be mitigated by controlling the power factor angle; controlling the voltage at PCC and by application of FACTS devices like STATCOM, SVC and UPFC.

C. Voltage Dip / Voltage Sag

A voltage dip (or voltage sag) is defined as a sudden reduction of the voltage to a value between 1% and 90% of its nominal value followed by a voltage recovery after a short period of time, conventionally 1 millisecond to 1 minute. In other word, it refers to the sudden reduction in the potential of electric grid usually between 10% and 90% of its nominal value followed by a rapid return to its normal value for duration of 0.5 cycles to 1 minute [11].

Voltage dip, Δ𝑈𝑑, at the wind point of common coupling (PCC), or point of interconnection (POI) can be expressed as a function of rated apparent power of the WT, 𝑆𝑛, Short circuit apparent power of the grid, 𝑆𝑘, voltage change factor, 𝐾𝑢(𝜑𝑘), and Phase shift, 𝜑 [12].


The acceptable voltage dip limiting value is ≤ 3% [13].

In grid connected WPP, voltage dip is usually said to occurs when large wind turbines are started up together – in which case, the current drawn from the electric grid will rise to a high value for duration of milliseconds. It can also occur as a result of the start up of large motors or when there is grid short circuit [14]. Other sources of voltage dip in power system include power line switching, lightning stroke, utility and facility faults, balanced or unbalanced faults, large load changes and starting of heavy electrical loads.

The main consequences of voltage dip include loss of data, shutdown (system halts), fail function of equipment and disconnection of sensitive loads. Other effects of voltage dip include light flicker, failure of transformers and motors, overload operation of motors, tripping of variable speed drives and loss of computer or controller memory.

In complex systems like grid connected WPP, a severe voltage dip can leads to cascading failures as result of disconnection of the wind generators that can further results in loss of generation; which will consequently affects the stability of the net power system [5]. Furthermore, the fault clearance is usually followed by high inrush current during the recovery process. The WT is required to be able to “ride through” a severe voltage dip and other power quality disturbance by remaining in operation and connected to the grid during the fault. Hence, voltage dip should be given more attention in order to avoid cascading failures in complex power system.

Depending on the condition and location in the power system, voltage dip can be mitigated by installing devices such as ferroresonant transformer, sag proofing transformer, uninterruptible power supply (UPS), coil-hold in devices, flywheel and motor-generator (MG), and FACTS devices like STATCOM, SVC and DVR.

D. Voltage Swell

Voltage swell is a term used to refer to the increase in the rms value of a voltage or current at power frequency from 1.1p.u to 1.8p.u for duration of 30 to 60 seconds [15]. Voltage swell at the PCC is given as a function of the turbine’s maximum apparent power, 𝑆𝑚𝑎𝑥, grid impedance (Resistance, 𝑅, and Reactance, 𝑋) and the phase shift, 𝜑 [16]:


The limiting voltage rise value is < 2% [17].

In grid connected WPP, voltage swell is usually caused by large load changes such as starting up and shutting down of large capacity WTs as well as by power-line switching. Other origins of voltage swell include sudden drop of loads, open neutral connection, unsymmetrical faults, and energizing a large bank of capacitor.

The main consequences of voltage swell include equipment malfunction, insulation breakdown, disconnection of equipment, failure or damage on power factor correction capacitor, damage to electric contactor, light flicker and tripping of variable speed drives.

Mitigation of voltage swell can be achieved by the use of transformer with tap changing, connection of large load at the PCC, application of soft starter, – a device capable of providing smooth connection and by installing FACTS devices like STATCOM.

E. Voltage Transient

Voltage transients are sudden and significant deviations from normal levels usually of short durations (microseconds or milliseconds) and vary greatly in magnitude [18]. They are usually caused by lightning, electrostatic discharges, or load switching. Transient disturbances are sometimes called surges.

The frequency of the transient is defined in [19] by the following expression:


Where

𝑓= Frequency of the supply
𝐿= Inductance
𝐶= Capacitance of the grid


In grid connected WPPs, transient can occur when some WTs are suddenly switched on or off, or when there is lightning discharge. Similarly, the inrush current that arises due to the connection or disconnection of induction generator can also give rise to voltage transient. Transient disturbances can also occur when mechanical switches are used to switch power factor correction devices (such as reactive power compensation capacitors). Other sources of transients include, load switching, utility fault clearing and facility faults.

The main consequences of voltage transients are insulation failure, loss of data, equipment damage, overheating of equipment, and reduced lifetime of transformers and motors. Other effects include errors on microprocessor controlled equipment, computer system data alterations, tripping of variable speed drives, misbehaved fuse operation and damage to electrical contactors and other electronic equipment.

Voltage transients can be mitigated by installing equipment’s with build-in power factor correction capability like STATCOM, DVR and SVC.

F. Short Interruptions

This is a term used to refer to the total interruptions of electrical power supply for a duration ranging from few milliseconds to one or two seconds. It is usually caused by the opening and automatic re-closure of protection devices. The main impacts of short interruption are; tripping of protection devices and stoppage of sensitive equipment like computer.

G. Long Interruptions

When the total interruption of electrical power supply exceeds two seconds, then, it is referred to as long interruptions. It is usually caused by failure of protection devices or equipment failure in the power system.

III. STATIC SYNCHRONOUS COMPENSATOR (STATCOM)

A. Basic Configuration

STATCOM is a member of GTO based FACTS family. It is a shunt connected reactive power compensation device that can regulate bus voltage at the wind POI. Depending on the condition, a STATCOM can control the electric power system parameters by generating or absorbing reactive power. STATCOM is a shunt connected FACTS device whose output current (inductive or capacitive) can be controlled independently of the a.c system voltage [20]. It is capable of helping WPP to stabilize after disturbances.

Basically, STATCOM consists of two-level voltage source converter (VSC) with d.c energy storage; a coupling transformer connected in shunt with the a.c system and control devices (Fig. 1). The VSC converts the d.c voltage across the d.c energy storage device into a set of three phase a.c output voltage. The three phase voltages are in phase with the a.c voltage and are coupled with the a.c system through the reactance of the coupling transformer. Active and reactive power control can be achieved by varying the magnitude and phase angle of the STATCOM. Thus, when fed from an energy source or energy storage device, a STATCOM can generate or absorb independently controllable real and reactive power at its output terminals. In other words, it can provide a.c power when connected to a source.

STATCOM is analogous to an ideal synchronous machine, in which case, it can generate a balanced three phase sinusoidal voltage at fundamental frequency with controllable amplitude and phase angle. Hence, it can regulate the voltage profile of the bus to which it is connected.

Fig. 1. Basic Configuration of a STATCOM.

B. STATCOM Topology for Power Quality Improvement in Grid Connected WPP

The STATCOM control scheme is connected with the interface of an induction generator and some linear loads at the PCC with the grid network (Fig. 2). In order to maintain the power quality of the grid network, the output of the STATCOM is varied in accordance with the control strategy. The STATCOM used here is IGBT based and is capable of providing the reactive power support to the induction generator and the nonlinear load in the grid network. Specifically, the STATCOM is used to provide the reactive power support to the grid connected WPP. The design is made in such a way as to provide the required reactive power to the WPP under normal operation and also to operate as reactive power source when the wind is below the cut-in (i.e. the minimum wind speed required to starts the turbine).

Fig. 2. STATCOM in a Grid Connected WPP for Power Quality Improvement.

The a.c voltage difference across the transformer leakage reactance results in an exchange of reactive power between the STATCOM and the power system in such a way that the a.c system bus voltage can be regulated to improve the voltage profile of the system. The VSC generates a controllable a.c voltage source behind the transformer leakage reactance. The VSC voltage is compared with the system a.c bus voltage. If the voltage magnitudes are equal, the reactive power exchange is zero. When the system a.c bus voltage is greater than the VSC voltage, the a.c system sees the STATCOM as an inductance connected to its terminals. If however the system a.c bus voltage is lower than the VSC voltage, the system sees the STATCOM as a capacitance connected to its terminals.

C. Advantages of STATCOM over other FACTS Device

In this paper, STATCOM is used as the FACTS device for power quality improvement because of the following advantages that it offers over other FACTS family:

• It provides harmonic filtering
• It provides power factor correction
• It is faster in terms of voltage control and reactive power support
• It provides both capacitive and inductive compensation
• It has the capability of controlling output current over the rated maximum capacitive or inductive range independent of the a.c system voltage
• It has increased transient rating in both capacitive and inductive operating regions
• It can maintain full compensating current at depressed line voltage
• It can control output power and provide power oscillation damping by self generation and or absorption of reactive power
• The reactive power provision is independent from the actual voltage on the point of interconnection with the grid network
• It can produce full capacitive output current at low system voltage

IV. SIMULATION RESULTS AND DISCUSSION

A wind energy system is simulated in Simulink environment of MATLAB and connected to a simulated grid network having a non-linear load as shown in Fig. 3.

Fig. 3. Proposed Grid Connected WPP with STATCOM Controller.

A. Simulation Results Without STATCOM Controller

The STATCOM controller is first switched off and a simulation is run. Result obtained (Fig. 4) shows how the wind penetration and the non-linear load contributes in deteriorating the voltage and current wave forms from being of smooth sinusoidal shape, thereby deteriorating the power quality of the system.

Fig. 4a. 3-Phase Voltage at the Wind POI without a STATCOM Controller.

Fig. 4b. 3-Phase Current at the wind POI without a STATCOM Controller.

FFT analysis on the above voltage and current waveforms of Fig. 4 gives THD level of 1.40% and 3.20% respectively which are high enough to deteriorate the power quality of the system as shown in Fig. 5.

Fig. 5a. FFT Analysis of Voltage Waveform at the Wind POI without STATCOM Controller.

Fig. 5b. FFT Analysis of Current Waveform at the Wind POI without STATCOM Controller.

B. Simulation Results With STATCOM Controller

The simulation is re-run with the STATCOM controller switched on and all other load parameters intact. The result shows how the STATCOM control scheme mitigates the harmonic current and provides the necessary harmonic compensation thereby cancelling the voltage and frequency variations on the system (Fig. 6). The power quality of the system is thus improved.

Fig. 6a. 3-phase Voltage at the Wind POI with a STATCOM Controller.

Fig. 6b. 3-phase Current at the Wnd POI with a STATCOM Controller.

FFT analysis on the voltage and current waveforms of Fig. 6 gives THD level of 0.13% and 0.38% respectively. These low values of THD signify improvement on the power quality of the system as shown in Fig. 7.

Fig. 7a. FFT Analysis of Voltage Waveform at the Wind POI with STATCOM Controller.

Fig. 7b. FFT Analysis of Current Waveform at the Wind POI with a STATCOM Controller.

V. CONCLUSION

The paper has presented power quality parameters related to an electrical power system with large wind power penetration. Specifically, emphasis is given on harmonic distortion due to the increased use of nonlinear loads by consumers. The paper have also presented a STATCOM control scheme for power quality improvement in a grid connected WPP consisting of non-linear load and waveform analysis using FFT. Simulation results show that the harmonic contents at the output of the system with unfiltered linear loads are quite high. FFT analysis on the voltage and current waveforms of the system show that the STATCOM control scheme is an excellent means of cancelling out the reactive and harmonic parts of the load current thereby restoring the smooth sinusoidal waveform of the voltage and current at the wind POI, which signifies power quality improvement.

References

[1] V. Kumbha, and N. Sumathi, “Power Quality Improvement of Distribution Lines Using DSTATCOM Under Various Loading Conditions”, Int. Journal of Modern Engineering Research, Vol. 2, Issue 5, September – October 2012, pp 3451 – 3457.
[2] J. Sridevi, J. Amarnath, and G. Govinda Rao, “Zonal Power Quality Improvement Using Static VAR Compensator for an Indian Utility System”, Int. Journal of Engineering Research and Application, Vol. 2, Issue 3, May – June 2012, pp 1320-1325
[3] M.R. Sayed, M.A.M. Hassan, and A.A. Hassan, “Power System Quality Improvement Using Flexible A.C Transmission Systems Based on Adaptive Neuro-Fuzzy Interface System”, WSEAS Transactions on Power Systems, Vol. 8, Issue 2, April 2013, pp 656-73
[4] B. Singh, “Introduction to FACTS Controllers in Wind Power Farm – A Technological Review”, Int. Journal of Renewable Energy Research, Vol. 2, No. 2, 2012, pp 166-212
[5] T.R. Ayodele, A.A. Jimoh, J.L. Munda, and J.T. Agee, “Challenges of Grid Integration of Wind Power on Power Systems Grid Integrity: A Review”, Int. Journal of Renewable Energy Research, Vol. 2, No. 4, 2012, pp 618 – 626
[6] K. Ravichandrudu, P.S.P. Kumar, and V.E. Sowjanya, “Mitigation of Harmonics and Power Quality Improvement for Grid Connected Wind Energy System Using UPFC”, Int. Journal of Application or Innovation in Engineering and Management”, Vol. 2, Issue 10, October 2013, pp. 141 – 156.
[7] D. Srinivas, and M.R.S. Reddy, “Power Quality Improvement in Grid Connected Wind Energy Systems Using FACTS Devices and PID Controller”, IOSR Journal of Engineering, Vol. 2, Issue 11, November 2011, pp 19-26
[8] J.N. Barothu, and A. Arif, “Method for Enhancement of Power Quality at Point of Common Coupling of Wind Energy System”, American Journal of Engineering, Vol. 1, Issue 1, March 2013, pp. 11 -21
[9] S.W. Mohod, and M.V. Aware, “Power Quality Issues and its Improvement in Wind Energy Generation Interface to Grid System”, MIT Int. Journal of Electrical and Instrumentation Engineering, Vol. 1, No. 2, August 2011, pp 116-122
[10] S. Shakil, K.K. Srivastava, and A.V. Pandey, “Power Quality Enhancement and Sag Mitigation by Dynamic Voltage Restorer”, Int. Journal of Scientific and Engineering Research, Vol. 4, Issue-6, June 2013, pp. 999 – 1009
[11] Y.I Nakhoda, and A. Lomi, “Implementation of Dynamic Voltage Restorer and Distribution Static Compensator for Power Quality Improvement”, Journal of Selected Areas in Renewable and Sustainable Energy, May 2012, pp 1 – 7
[12] T. Ackermann, “Wind Power in Power Systems”, John Wiley and Sons Limited, Stockholm, 2005
[13] A.K Chourasia, A. Mishra, and D. Sharma, “A Simulation of a STATCOM Control for Grid Connected Wind Energy System for Power Quality Improvement”, Int. Journal of Engineering Research and Applications, Vol. 3, Issue 4, August 2013, pp. 1207 – 1214
[14] S.A Mohammed, M.A. Abdel-Moamen, and B. Hasanin, “Analysis, Modeling and Simulation of Dynamic Voltage Restorer for Compensation of Voltage Quality Disturbances”, Int. Journal of Control, Automation and System, Vol. 1, No. 2, 2013, pp 23 -29
[15] C. Tajavoth, M. Trishulapani, V.K.R. Mohan-Rao, and Y. Yambabu, “Power Quality Improvement for Grid Connected Wind Energy System Using STATCOM Control Scheme”, IOSR Journal of Engineering, Vol. 3, Issue 7, 2013, pp. 51 – 57
[16] S. N. Deepa, and Yuvaraj, “Improving Grid Power Quality with FACTS Devices on Integration of Wind Energy Systems”, Students Pulse Academic Journal of Anna University of Technology, Coimbatore, Vol. 3, Issue 4, April 2011, pp 1-8
[17] V.A. Reddy, P.H. Reddy, and M.S. Basu, “Power Quality Improvement in Wind Energy System by Using STATCOM on Integration to the Grid”, International Journal of Modern Engineering Research, Vol. 2, Issue 5, September – October 2012, pp 3637 – 3640.
[18] M.R.S. Reddy, and M.V. Kumar, “Power Quality Improvement in DFIG Based Wind Energy Conversion System Using UPFC”, IOSR Journal of Engineering, Vol. 3, Issue 1, January 2013, pp 46 – 54
[19] J. Earnest, T. Wizelius, “Wind Power Plants and Project Development”, PHI Learning Private Limited, New Delhi, 2011
[20] A. Vijayan, and S. Padma, “Maintaining Voltage Stability in Power System Using FACTS Devices”, Int. Journal of Engineering Science Invention, Vol. 2, Issue 2, February 2013, pp 20 – 25

PQ Analysis: Power Quality Reports

Published by testguy, November 23, 2019. Website: testguy.net


Power Quality Reports

A power quality meter can plot the voltage and current waveforms as functions of time, this is called an oscillogram. Data can be extracted from the power quality recorder and analyzed to determine the overall condition of the power system using various timeplots and tables.

The actual data analysis is usually performed by an electrical engineer, who will generate a report that provides a summary of the various power conditions, a list of events that occurred during the analysis, and any corrective action or recommendations that should be considered.

Photo: Dranetz BMI Dranview

Figure 1. Data can be extracted from the power quality recorder and analyzed to determine the overall condition of the power system using specialized computer software.

Power Quality Meters are capable of calculating a large number of power measurements at extremely high speeds. These measurements may include minimum, average, and maximum values for parameters such as:

  • current and voltage RMS
  • phase relationship between waveforms
  • power factor and frequency
  • Active power (kW), reactive power (kVAr), apparent power (kVA)
  • active energy (kWh), reactive energy (kVArh) and apparent energy (kVAh)
  • Harmonic spectrum, THD, TDD
Photo: Fluke PowerLog.

Figure 2. Power Quality Meters are capable of calculating a large number of power measurements at extremely high speeds.


Source:https://testguy.net/content/361-Power-Quality-Analysis-Basic-Theory-and-Applications-Explained#reports

PQ Analysis: How Power Quality is Measured

Published by testguy, November 23, 2019. Website: testguy.net


How Power Quality is Measured?

Several types of instruments are available for power quality measurement, each serving their own unique purpose. Power quality analyzers are the most commonly used tools to observe real-time readings and also collect data at high speeds for downloading to computers for analysis, opposed to a power recorder or “data logger” which is mainly used for simple voltage and current measurements.

Often times power interruptions are unpredictable and of short duration, which can only be captured using a power quality meter (PQM) installed over a period of days, weeks or months. Each phase in the system has a voltage probe and current sensor applied to monitor the magnitude and polarity of each channel over the specified period.

Photo: Fluke Corporation

Image#1: Several types of instruments are available for power quality measurement, each serving their own unique purpose.

The place where the PQM is connected is called the measurement plane, everything to the right of the plane is considered part of the load and everything to its left is considered the source. The measurement plane can be any point within the power system, not necessarily at the incoming service.

A cycle is the time that the waveform takes to travel from the zero line up to its positive peak, back down to its negative peak, and then back to zero. Power quality meters can be extremely high speed devices designed to capture events down to the sub-cycle level.

In an ideal 60Hz system, one cycle takes 16.7 milliseconds, or 0.0167 seconds. This is called the period of the wave, and is represented by the letter T. Frequency is equal to the inverse of the period, f = 1/0.0167 = 60Hz.

Photo: Fluke Corporation

Image#2: Power Quality Analyzer Connection Example.

The type of meter to install will depend on the data to be captured. For example, a simple ampere load evaluation or utility bill audit would require a far less sophisticated meter than trying to pinpoint the cause of a nuisance trip or other power interruption.

The most important factor to consider when performing power quality analysis is safety. Often times meters are applied live with equipment in service which can be an extremely dangerous task.

This type of work should only be performed by qualified personnel while observing all appropriate safety precautions. A local power outage at the monitoring location is always the safest way to install and remove a power quality meter.

Photo: Fluke Corporation

Image#3: The most important factor to consider when performing power quality analysis is safety.


Source: https://testguy.net/content/361-Power-Quality-Analysis-Basic-Theory-and-Applications-Explained#measurements