Published by Electrotek Concepts, Inc., PQSoft Case Study: Power Factor Correction, Document ID: PQS0312, Date: April 16, 2003.
Abstract: Low power factor because it means that you are using the facility’s electrical system inefficiently. It can also cause equipment overloads, low voltage conditions, and greater line losses. Most importantly, low power factor can increase total demand charges and cost per kWh, resulting in higher monthly electric bills. This document provides an overview of the concept of power factor, including impacts on the electrical distribution system, effects on power quality, benefits of improvements, and estimating financial savings.
This case presents the applications of low voltage power factor correction capacitors to improve poor power factor.
PROBLEM STATEMENT
A large plastics plant is paying a significant power factor penalty each month. The utility has informed the plant that correcting the overall plant power factor to 95% will eliminate the penalty.
A summary of previous utility bills is provided in Table 1.
Month
kVA
kW
kVAr
Power Factor
Feb 1991
5880
4080
4234
0.694
Mar 1991
5700
3900
4157
0.684
etc.
Dec 1991
6120
4200
4451
0.686
etc.
Average
6079
4185
4408
0.689
Table 1 – Previous Utility Bills
PRINCIPLES OF POWER FACTOR CORRECTION
Why Improve the Power Factor
The application of power factor correction capacitors is generally motivated by the desire to save money. Most often, this is a direct response to utility power factor penalties. However, there are several other reasons that a customer might decide to apply power factor correction capacitors.
Reduce electric utility bill
Release system capacity
Reduce current, (allowing additional load to be served)
Reduce I2R losses
Voltage control
While power factor correction alone is not a harmonic concern, it is nevertheless important to understand the relationship between capacitors and harmonic related problems.
Location for Power Factor Correction Capacitors
The benefits realized by installing power factor correction capacitors include the reduction of reactive power flow on the system. Therefore, for best results, power factor correction should be located as close to the load as possible. However, this may not be the most economical solution or event the best engineering solution, due to the interaction of harmonics and capacitors. Refer to Figure 1 for a oneline representation of possible placement options for power factor correction capacitors.
Often capacitors will be installed with large induction motors (C3). This allows the capacitor and motor to be switched as a unit. Large plants with extensive distribution systems often install capacitors at the primary voltage bus (C1) when utility billing encourages power factor correction. Many times however, power factor correction and harmonic distortion reduction must be accomplished with the same equipment. Location of larger harmonic filters on the distribution bus (C2) provides the required compensation and a low impedance path for harmonic currents to flow.
Figure 1 – Location of Power Factor Correction Capacitors
Evaluating the Effectiveness of a Capacitor Application
Several simple equations can be used to determine the effectiveness of power factor correction. The voltage improvement realized with the installation of capacitors is determined from:
Although capacitors raise a circuit’s voltage, it is rarely economical to apply them in industrial plants for that reason alone. The reduction in power system losses is determined from:
where:
%lossreduction = reduction in losses (percent) PForiginal = original power factor (per unit) PFcorrected = corrected power factor (per unit)
Financial return from conductor loss reduction alone is seldom sufficient to justify the installation of capacitors. It is an added benefit, especially in older plants with long distribution feeders. The optimum location of the power factor correction capacitors can be determined from a load flow analysis. However, it is important to remember that harmonic considerations are often more important than correction. Finally, the percent line current reduction can be approximated from:
where:
%ΔV = current reduction (percent) θbefore = power factor angle before correction (degrees) θafter = power factor angle after correction (degrees)
Displacement Power Factor vs. True Power Factor
The traditional method of power factor correction, both on the power system and within customer facilities has been the applications of shunt capacitor banks. This is based on the fact that most loads on the system draw a lagging current (partially inductive) at the fundamental frequency. Capacitors draw a leading current at the fundamental frequency and, therefore, can compensate for the current drawn by inductive loads (motors are the most important).
These characteristics of leading and lagging current are based on the assumption that loads on the system have linear voltage-current characteristics and that harmonic distortion of the voltage and current is not significant. With these assumptions, the power factor is equal to the displacement power factor (DPF). Calculation of the displacement power factor is completed using the traditional power factor triangle, and is summarized with the following relationship (shown in Figure 2):
Figure 2 – Displacement Power Factor Triangle
Harmonic distortion in the voltage and/or current caused by nonlinear loads on the system changes the way power factor must be calculated. True power factor (TPF) is defined as the ratio of real power to the total volt-amperes in the circuit.
This is a measure of the efficiency with which the real power is being used. Since capacitors only provide reactive power (VArs) at the fundamental frequency, they cannot correct true power factor when there are harmonics present. In fact, capacitors can make true power factor worse by creating resonance conditions which magnify the harmonic distortion in the voltage and current.
Adjustable-speed drives (ASDs) using pulse-width modulation (PWM) technology are a particularly important example of the difference between true power factor and displacement power factor. These drives use a diode bridge rectifier to convert the ac power to dc. As a result, these drives have a displacement power factor very close to unity. However, the harmonic distortion of the input current can be very high. This low true power factor cannot be improved with capacitors. Harmonic filtering is the most common way of improving power factor for this type of load.
Displacement power factor is still very important to most industrial customers because utility billing for power factor penalties is almost universally based on displacement power factor. Metering used to measure power factor is based on VAr meters that are only responsive to the fundamental frequency components of the voltage and current. Therefore, utilities do not currently penalize customers for the inefficiencies introduced by harmonics in their loads.
Typical Equipment Power Factors
The typical displacement power factor for individual equipment types is summarized in Table 2.
Table 2 – Typical Equipment Power Factor
Motor Power Factor Correction Example
The following example illustrates the correction of a 500 HP induction motor with an assumed power factor of 85%. The customer desires correction to 95%. The assumption of HP = kVA is used to determine the following:
Original power factor angle = cos-1(0.85) = 31.8° Desired power factor angle = cos-1(0.95) = 18.1°
Displacement vs. True Power Factor Example
The impact of harmonic distortion on power factor is illustrated using the PWM ASD current waveform shown in Figure 4.
Figure 4 – Typical PWM ASD Current
The rms current, for the drive waveform, is determined from the following equation:
Note: Harmonic spectrum data obtained from Fast Fourier Transform (FFT) on measured waveform
The total harmonic distortion (THD), and crest factor (CF) for the current waveform are determined from:
Note: Ipk obtained from measurement data. Note: Crest Factor for a single-frequency sinusoidal wave (no distortion) is 1.412
For the drive current illustrated, it is assumed that the fundamental components of the current and voltage are in phase – displacement power factor = 100%. Actual values for waveforms of this type range from 95-98%. If we assume that the voltage distortion is negligible, the real power consumed is:
P = V1 ∗ I1 * cosθ = (480 V) (1.63 A) (1.0) = 782.4 W
The true power factor can then be determined from:
TPF = P / (Vrms ∗ Irms) = 782.4 W / (480 V * 2.913 A) = 0.56 = 56%
INDUSTRIAL PLANT POWER FACTOR CORRCTION
Recalling, from Table 1, the plant’s previous utility bills. The average power factor is corrected to 95% using the following method:
After the installation of 3000kVAr of power factor correction, the average load is:
Average kW: 4185kW Average kVAr: 1408kVAr (4408-3000) Average kVA 4416kVA Average PF: 95.0%
SUMMARY
Power factor is a measurement of how efficiently a facility uses electrical energy. A high power factor means that electrical power is being utilized effectively, while a low power factor indicates poor utilization of electric power. Low power factor can cause equipment overloads, low voltage conditions, and greater line losses. Most importantly, low power factor can increase total demand charges and cost per kWh, resulting in higher monthly electric bills.
Low power factor is generally solved by adding power factor correction capacitors to a facility’s electrical distribution system. Power factor correction capacitors supply the necessary reactive portion of power (kVAr) for inductive devices. The principle benefit is lower monthly electric bills.
REFERENCES
IEEE Recommended Practice for Electric Power Distribution for Industrial Plants (IEEE Red Book, Std 141-1986), October 1986, IEEE, ISBN: 0471856878
IEEE Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book, Std 399-1990), December 1990, IEEE, ISBN: 1559370440
IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems, March 1988, IEEE, ISBN: 0471853925
RELATED STANDARDS IEEE Standard 1036-1992
GLOSSARY AND ACRONYMS ASD: Adjustable-Speed Drive CF: Crest Factor DPF: Displacement Power Factor PWM: Pulse Width Modulation THD: Total Harmonic Distortion TPF: True Power Factor
ALEKSANDAR JANJIĆ, Department of renewable energy sources, R&D Center “Alfatec” Ltd. Bul. Nikole Tesle 63/5,18000 Niš, SERBIA, aleksandar.janjic@alfatec.rs
ZORAN P. STAJIĆ, Faculty of Electronic Engineering, University of Niš, Aleksandra Medvedeva 14, 18000 Niš, SERBIA, zoran.stajic@alfatec.rs
IVAN RADOVIĆ, ED “Elektrošumadija” Kragujevac, ED “Centar” d.o.o. Kragujevac, Slobode 7, 34000 Kragujevac, SERBIA, ivan.radovic@eskg.rs
Abstract: – The paper discusses power and especially voltage quality issues in the smart grid environment. New demands that are facing the distribution network, by introducing the concept of intelligent networks (Smart Grids), are presented. Some examples of non compliance of laws and practices in Serbia are presented as well, as the illustration of lack of strategic planning in the field. Through several case studies, a few typical problems regarding power quality, occurring in the electrical utilities in Serbia, which have to be solved in a new environment are presented. In the end, the conclusion and specific suggestions in regard with the importance of strategic planning and preparation for the customization to the expected changes are given.
Key-Words: – power quality, smart grids, power quality monitoring, harmonics, volt var control
1 Introduction
European Smart grid concept – The EU Smart Grids Technology Platform vision and strategy for Europe’s Electricity Networks of the Future was launched in 2006 [1]. The Smart Grid vision is aiming for “new products, processes and services, improving industrial efficiency and use of cleaner energy resources, while providing a competitive edge for Europe in the global marketplace”. The Smart Grid vision is highly important as a mean for support of the EU environmental as well as economical ambitions. Many of new technologies are involved, such as renewables, electric cars, and power flow control equipment, while an increased use of digital communication and control, including smart metering and advanced grid wide area real-time monitoring, can also be expected.
Principal functionality characteristics of Smart Grids are [2, 3]:
Active consumers participation;
Seamless accommodation of all generation and storage options;
Provision of new products and services, and opening of new markets;
Power quality (PQ) for the digital economy;
Optimization of asset utilization;
Anticipation and response to system disturbances (self-heal);
Resilience against attack and natural disaster (cyber security).
To fulfill these requirements, the evolution of existing grids is necessary, and it includes:
high use of renewables 20% – 35% by 2020,
bidirectional metering,
distributed storage,
smart meters that provide near-real time usage data, time of use and dynamic pricing,
smart appliances communicating with the grid, energy management systems in homes, and industrial facilities linked to the grid,
growing use of plug-in electric vehicles
networked sensors and automated controls throughout grid.
However, this evolution of existing grids will confront them with new challenges regarding power quality issues. Regarding distributed generation for instance, depending on applied technology (synchronous, single or doubly fed induction machines, or inverter technology) influence on power quality will be manifested through [4]:
magnitude of supply voltage,
increased unbalance,
transient overvoltages,
voltage sags, and
flickers.
Based on this facts, one can conclude that voltage quality is becoming increasingly important to customers for two reasons:
a) Voltage quality levels are affected by the increased use of distributed generation and different electronic devices (inverters, battery chargers, energy saving lamps).
b) Sensitive electronic devices are strongly affected by voltage quality.
Not only for consumers, but for all stakeholders involved in new, smart grid environment, power quality deserves particular attention. Thus, potential disturbance source may be found on both, generation and consumer side. From regulator point of view, it is important to asses what should be consider in establishing a regulatory framework for voltage quality in distribution networks.
The aim of this paper is to emphasize the need of improved and enhanced power quality monitoring, taking into account new requirements and new technologies of Smart grid. Finally, actions regarding power quality cannot be treated independently, without broad strategic planning frame.
In the following Section, the need for change of actual power quality policies and the need for integrated planning of all power aspects are presented through some examples of Serbian Power Industry.
In the Section 3, new smart grid functions addressing power quality aspects are presented. Through several study cases from Serbian Electrical Utilities, the need for integrated platform including power quality is presented.
Finally, conclusions are brought regarding the change in power quality treatment in the new environment.
2 Strategic planning regarding power quality in the new environment
Until now, the main focus of quality regulation has been on the reliability and commercial dimensions of quality. In contrast, there is far less experience with the issue of voltage quality regulation, especially in integrated, multi-functional and multicommunication platform like smart grid.
The proper approach to the smart grids and all matters related to this concept, and the issue of power quality, can be of a crucial importance for the countries that will be found in the way of its application.
If serious attention is not given to strategic planning and appropriate actions for preparing the system to move to a new concept are not taken, one can easily get into a situation that much greater financial resources are spent to remedy the consequences of damage, loss coverage, or on payment of fees and penalties. The only alternative is the timely planning and implementation of actions to predict and mitigate the occurrence of such losses and to optimize the adaptation to market conditions.
Disharmony between regulatory requirements and actual network level will be explained in the case of Serbian Electric Power Industry in the last decade. First example was the question of increasing the nominal voltage in low voltage distribution systems from 380 to 400 V.
Being aware of this change, many countries have made adequate preparations so the transition did not cause adverse effects. On the other hand, Serbia did not have an adequate attitude towards this issue, so the transition to a higher voltage level was carried out without any previous preparation. As a consequence, because motors in electrical drives were not replaced with new ones, designed for rated voltage of 400 V, a large increase of reactive power consumption appeared in the whole distribution system. This is especially contributed by the fact that, with the changes of rated power, the maximal allowed voltage in distribution networks in Serbia has increased even at 440 V. The second negative consequence was much larger number of failures in electrical drives.
Another example of poor strategic planning was the lack of high level incentives for customers to reduce their reactive power consumption. Without these incentives, consumers did not have any interest to invest in reactive power reduction. The problem could have been easily resolved by introduction of an appropriate tariff system. Since this was not done, after an increase of reactive power consumption in the system, Electric Power Industry of Serbia has invested in installation of reactive power compensation units in distribution networks, with the total installed capacity of 600 MVAr.
The previous examples show that due to lack of strategic planning and appropriate actions, the huge financial resources have been spent on unnecessary delays in manufacturing processes, repair of damaged equipment, insurance premiums, coverage of unnecessary energy losses and the investments in equipment that have not been necessary. All these actions have treated only the consequences, not the real causes of the problem.
By the introduction of the smart grid concept, the focus is changed, and new information and telecommunication infrastructure is required, as presented in figure 1. Power quality monitoring has to be included in this new infrastructure as well.
Figure 1. Smart grid overview
3 New Smart grid functions and power quality
The effective realization of smart grid concept is not possible without advanced distribution network automation. This automation introduces advanced distribution network operation as well, through the set of advanced distribution functions. The key aspect of electricity supply quality in a power system is the optimal application of voltage levels to all transmission and distribution networks. With significant penetration of distributed generation, the distribution network has become an active system with power flows and voltages determined by the generation as well as by the loads. Growing customer expectations and using of sophisticated electrical equipment are putting an additional responsibility upon the network operator to ensure that the delivered level and quality of supply are maintained within the parameters previously set by the regulatory bodies, while the maximal amount of distributed generation to be installed and operated is permitted at the same time. Some of innovative solution in that field are elaborated in [5, 6, 7, 8].
Integrated Volt/Var control is an important and one of the most desirable functions of a modern Distribution Automation (DA) system, as an integral part of Smart Grids. This function deals with the complexity of voltage and reactive power control in distribution systems. This complexity usually limits the capabilities of local automatic controllers which conventionally control Load Changing Transformers (LTCS) or Voltage Regulators (VRS) on the bases of local voltage measurements, and, Capacitor (CAP) banks on the bases of temperature or voltage changes.
Performing the Volt/Var control in an integrated manner provides a flat voltage profile over the feeder and at the same time minimizes the power loss in the system. In addition, a coordinated operation of VRS and CAP banks permits avoiding of an excessive and unnecessary tripping of these devices.
Centralized voltage and reactive power control is typically considered the most cost effective function of real-time DA. Rule based Centralized Capacitor Control with an objective of unity power factor has a relatively long history of real-time implementation. With development of a more reliable real-time Power Flow, the power flow based on Optimal Volt/VAr control attracts more and more attention.
Optimal Volt/VAr control allows a wider choice of objectives which can be achieved with higher mathematical accuracy. The objective of operating the distribution network within voltage and loading constraints serves as the primary objective, where other objectives – power losses, demand, etc. – serve as secondary. In addition, more and more distribution utilities are investing in remotely controlled capacitors and step voltage regulators as part of their distribution automation strategy. This offers the opportunity for periodic closed loop Volt/VAR control, which determines the optimal set of control actions and executes them immediately.
Fault Location, Isolation, and Restoration applications in a DA environment have also recently increased in importance. The trend for these applications is going towards more intelligent solutions that react to fault events and assist the operator in clearing and restoring the fault or taking action without any operator interaction at all. Fault location programs evaluate the SCADA information of breaker trip events and faults.
However, the proper introduction of these function is not possible without advanced monitoring of all important values in the power network, including the monitoring of voltage quality. In other words, power quality monitoring, together with the proper information and telecommunication techniques, is becoming the back bone of fully implemented smart grid.
A few of the case studies taken from authors experiences in Serbian power network will demonstrate the need of advanced and integrated measurement and data analysis.
3.1 Case Study 1
The first case study represents the common problem of voltage reduction in the transmission system. Due to some problem of unbalance between production and consumption, transmission network operators are commonly performing the short term (1 – 2h) voltage reduction (of the order of 5 – 10%). This reduction is leading to the short term demand reduction, but after few hours, the demand is continuing to grow, because of the „pay back effect“. Consequently, the problem is the drastic decrease of voltage quality for many customers, affected by this wide area voltage reduction.
Figure 2 is representing voltages measured in one TS 10/0,4 kV, at the low voltage bus bars. The voltage magnitude decrease is of order of 10%, registered after 10 a.m. in total duration of 1 hour and 30 minutes.
Figure 2.Voltages measured at the low voltage bus bars in TS 10/0.4 kV „Kadinjača“ 31.01.2011.
The distribution company has not been warned, so the situation represented in figure 1 had as the result, many customers complaints of the low voltage in their households.
Figure 3 represents diagrams of active and reactive power from the TS 400/110 kV „Petrovac“ at one 110 kV transformer bay, which supplies, through one intermediate TS 110/35 kV „Ilićevo“ and one TS 35/10 kV „21. oktobar“, the TS 10/0.4 kV „Kadinjača“, represented in figure 2.
The measurement information system (MIS) in the TS “Kadinjača”, recorded data with 12 s time resolution. The architecture of measurement information system installed in TS 10/0,4 kV to record the parameters of voltage quality in power distribution networks is presented in figure 4.
Figure 3.Active and reactive power in the supply TS station 400/110 kV „Petrovac“ 31.01.2011.
The measurement system which measured the active and reactive power at 400/110 kV “Petrovac” recorded the data at 900 s (15 min), and forms of change shown in the diagram would not faithfully convey.
Figure 4. MIS architecture
The presented example aims to demonstrate the need of measuring information system with adequately allocated measuring units, and analysis software that allows the analysis of recorded data (for instance, data recorded from other distribution utilities which are equipped with similar devices). Figures 5 and 6 show the diagrams of voltage changes in two other TS 10/0,4 kV in other areas supplied by the same TS 400/110 kV.
Figure 5.Voltages measured at the low voltage bus bars in TS 10/0.4 kV “Vranje” 31.01.2011.
Figure 6.Voltages measured at the low voltage bus bars in TS 10/0.4 kV “Pirot” 31.01.2011.
It is shown that without data recorded by measuring information systems and proper analysis software, many phenomena affecting the quality of voltage in electricity distribution network, when their causes are out of the site of measurement (and even outside the territory covered by the entire company for distribution) often can not be explain.
3.2 Case Study 2
Above was already stated that performing the Volt/Var control in an integrated manner provides a flat voltage profile over the feeder while minimizing the power loss on the system. In addition, a coordinated operation of VRS and CAP banks permits avoiding of an excessive and unnecessary tripping of these devices. The simplified layout of one distribution feeder is represented in figure 7.
Figure 7. Simplified model of distribution feeder
The load connected to the main bus bars, presented in figure 7, represents one wood processing facility. Voltage variation is represented in figure 8. The problem in this particular case was the excessive operation of On Line Tap Changer (OLTC) in distribution transformer station. Only after installation of power quality measurement device and, what is more important, introduction of these measurement in the central data warehouse, the problem is solved by proper settings of OLTC in supply transformer station.
Figure 8. Voltages measured at the low voltage bus bars in TS 10/0.4 kV at consumer side
The same problem was registered in another TS 110/10 kV station, which supplied one TS 10/0,4 kV with voltage variations represented on figure 9.
Figure 9.Voltages measured at the low voltage bus bars in TS 10/0.4 kV in ED Nis at consumer side
Only after detection of sources of voltage variations at the lower level, the proper setting of OLTC in supplying station were possible.
3.3 Case Study 3
The final case study is dedicated to the problem of harmonics. The following is the example of electricity customer who injected into the network a large content of higher harmonics and caused unauthorized voltage drops of other electricity customers in the region. Figure 10 represents the active, reactive, and apparent powers of the consumer.
Figure 10. Active, reactive, and apparent powers of the consumer
Figure 11.THD factors of the consumer’s phase voltages
Figure 12. Corresponding phase power factors
Fig. 11 presents the high level of THDu (greater than 12%), while Figure 12 presents the corresponding power factor. Checking the technical requirements for the connection, the conclusion was that are connected to the network without their fulfillment.
4 Conclusion
The paper points out that the problem of monitoring power quality parameters in Serbia should be given far more serious attention in order to adopt laws and standards in the EU, and to fulfill requirements regarding EU Smart Grid technology platform.
It is shown that solutions for problems described above should not be sought independently but as part of the development concept of intelligent networks (smart grids).
Moreover, power quality problem can be one of additional “driving factors” for the implementation of Intelligent network in Serbia.
Finally, it is shown that only the elaboration of an integrated information platform is required for resolving of power quality issues in a satisfactory manner.
Acknowledgement: The work presented here was supported by the Serbian Ministry of Education and Science (project III44006).
References:
[1] Toward Smart Power Networks, Lessons learned from European research FP5 projects, European Commission, 2005. [2] Strategic Research Agenda for Europe Electricity Networks of the Future European Technology Platform, European Commission, April 2007. [3] Strategic Deployment Document for Europe Electricity Networks of the Future European Technology Platform, European Commission, April 2010. [4] T. Degner, J. Schmidt, P. Strauss, Dispower, Distributed Generation with High Penetration of Renewable Energy Sources, Final Public Report, iSET, Kassel, 2005. [5] M. H. J. Bollen, J. Zhong et all. Power Quality aspects of Smart Grids International Conference on Renewable Energies and Power Quality (ICREPQ’10) Granada (Spain), 23th to 25th March, 2010. [6] H. Spaack et all. Intelligent Transformer Substations in Modern Medium Voltage Networks as Part of “Smart Grid” 7th Mediterranean Conference and Exhibition on Power Generation, Transmission, Distribution and Energy Conversion7-10 November 2010, Agia Napa, Cyprus (Paper No. MED10/240). [7] J. Kester et all. A smart MV/LV station that improves power quality, reliability and substation load profile, 20th International Conference on Electricity Distribution Prague, 8-11 June 2009. [8] J. Heckel, Smart substation and feeder automation for a smart distribution grid, 20th International Conference on Electricity Distribution Prague, 8-11 June 2009.
Published by Electrotek Concepts, Inc., PQSoft Case Study: General Reference – Power Factor Correction, Document ID: PQS0311, Date: April 16, 2003.
Abstract: Simply stated, power factor is a measurement of how efficiently a facility uses electrical energy. A high power factor means that electrical power is being utilized effectively, while a low power factor indicates poor utilization of electric power.
Low power factor because it means that you are using the facility’s electrical system inefficiently. It can also cause equipment overloads, low voltage conditions, and greater line losses. Most importantly, low power factor can increase total demand charges and cost per kWh, resulting in higher monthly electric bills. This document provides an overview of the concept of power factor, including impacts on the electrical distribution system, effects on power quality, benefits of improvements, and estimating financial savings.
INTRODUCTION TO POWER FACTOR
A large number of customer loads in a modern electrical system are inductive, which means that they require an electromagnetic field to operate. Inductive loads, such as motors, require two kinds of electric power:
Active Power (also known as “working power”) – powers equipment and performs useful work, such as creating heat, light, motion, etc.
Reactive (magnetizing) Power – sustains an electromagnetic field (flux necessary to operate an inductive device).
Power factor involves the relationship between these two types of power. Active Power is measured in kilowatts (kW) and Reactive Power is measured in kilovolt-amperes-reactive (kVAr). Active power and reactive power together make up Apparent Power, which is measured in kilovolt-amperes (kVA). This relationship is often illustrated using the familiar “power” triangle (Figure 1):
Figure 1 – Illustration of Power Factor Triangle
Power factor measures how effectively electrical power is being used. Power factor is the ratio between active power (kW) and apparent power (kVA). Active power does work and reactive power produces an electromagnetic field for inductive loads. Using the values in the power triangle example, the facility is operating at 400 kW (Active Power) with an 80% power factor, resulting in a total load of 500 kVA.
Low power factor means that you are using a facility’s electrical system inefficiently. It can also cause equipment overloads, low voltage conditions, and greater line losses. Most importantly, low power factor can increase total demand charges and cost per kWh, resulting in higher monthly electric bills.
Effect of Load on Power Factor
Lightly-loaded or varying-load inductive equipment such as HVAC systems, induction furnaces, molding equipment, presses, etc. One of the worst offenders is a lightly loaded induction motor. Examples of equipment with:
85% power factor or better – incandescent lighting, diode rectifiers (small adjustable-speed drives (ASDs)), electronic ballasts, most electronic power supplies (personal computers, and office equipment).
70% – 85% power factor – induction motors (air conditioners, pumps, grinders, fans, and blowers).
70% power factor or worse – dc-drives (printing presses, elevators), single-strike presses, automated machine tools, finish grinders, and welders.
Benefits of Improving Power Factor
The principle benefit is lower monthly electric bills. Additional benefits include:
More efficient use of the electrical system
Improved voltage regulation due to reduced line voltage drop
Increased load carrying capabilities in existing circuits
Possible reduction in size of transformers, cables, and switchgear for new installations
Reduced power system losses
Most Common Method for Improving Power Factor?
Low power factor is generally solved by adding power factor correction capacitors to a facility’s electrical distribution system. Power factor correction capacitors supply the necessary reactive portion of power (kVAr) for inductive devices. By supplying its own source of reactive power, a facility frees the utility from having to supply it. This generally results in a reduction in total customer demand and energy charges.
Power factor correction capacitors are rated in electrical terms called “VArs”. One VAr is equivalent to one volt-amp of reactor power. Since reactive power is generally measured in thousands of vars, the letter “k” (abbreviation for kilo) proceeds the Var creating the more familiar “kVAr” term. Therefore, a capacitor kVAr rating indicates how much reactive power the capacitor will supply.
The amount of power factor correction that is required to correct a facility to a target power factor level is the difference between the amount of kVAr in the uncorrected system (required by loads) and the amount of kVAr in the corrected system. A capacitor application is illustrated in the following power triangle (Figure 2):
Figure 2 – Power Factor Correction Application
The location that provides the maximum benefits of power factor correction is at the load. Capacitors work from the point of installation back to the generating source. However, individual load (e.g. motor – shown in Figure 3) correction is not always practical and ongoing maintenance may become an issue as well. Sometimes it is more effective to connect larger capacitor banks to the main distribution bus, or to install automatic systems at the incoming service in conjunction with fixed capacitors at distributed loads.
Figure 3 – Motor Terminal Power Factor Correction
IMPACT OF POWER FACTOR ON POWER QUALITY
A properly designed capacitor application should not have an adverse affect on equipment or power quality. However, despite the significant benefits that can be realized using power factor correction capacitors, there are a number of power quality-related concerns that should be considered if you install capacitors. Potential problems include increased harmonic distortion and transient overvoltages.
Harmonic Issues
Harmonic distortion on power systems can best be described as noise that distorts the sinusoidal wave shape. Harmonics are caused by nonlinear loads (e.g. ASDs, compact fluorescent lighting, induction furnaces, etc.) connected to the power system. These loads draw nonsinusoidal currents (on a 60 Hz system, the 5th harmonic is equal to 300 Hz), which in turn react with the system impedance to produce voltage distortion. Generally, the harmonic impedances are low enough that excessive distortion levels do not occur. However, power factor correction capacitors can significantly alter this impedance and create what is known as a “resonance” condition. High voltage distortion can occur if the resonant frequency is near one of the harmonic currents produced by the nonlinear loads. A method for estimating the resonance point (hresonance) is shown in the following example:
Resonance point, hresonance
Indications that a harmonic resonance exists include device overheating, frequent circuit breaker tripping, unexplained fuse operation, capacitor failures, and electronic equipment malfunction. Ways to avoid excessive distortion levels include altering (or moving) the capacitor size to avoid a harmful resonance point (e.g. 5th, 7th), altering the size (or moving) of the nonlinear load(s), or adding reactors to the power factor correction capacitors to configure them as harmonic filters.
Harmonic Filter Applications
In general, both harmonic problems and switching transient problems can be solved by configuring power factor correction capacitors as a “tuned bank”. This involves adding a series reactor (Xf) to the capacitor bank to form a tuned circuit (resulting in low impedance at a specific frequency).
It is common to tune the filter below the 5th harmonic (e.g. 4.7th) for most industrial facilities. It is important to note that the addition of a series reactor results in a voltage rise on the capacitor, which often means that capacitors with a higher voltage rating are required. Figure 4 illustrates a tuned filter bank using 300 kVAr capacitors rated 600 volts.
Figure 4 – Typical Low Voltage Harmonic Filter Configuration
Transient Overvoltage Issues
Transient overvoltages can be caused by a number of power system switching events, however, utility capacitor switching often receives special attention due to the impact on customer equipment. Each time a utility switches a capacitor bank a transient overvoltage occurs. Generally, these overvoltages are low enough that they do not affect the customer’s system. However, high overvoltages can occur when customers have power factor correction capacitors. This phenomenon is often referred to as “voltage magnification”. Magnification occurs when the transient oscillation initiated by the utility capacitor switching excites a resonance (refer to previous definition) formed by the step-down transformer and low voltage power factor correction capacitors. Magnified overvoltages can be quite severe and the energy associated with these events can be damaging to power electronic equipment and surge protective devices (e.g. transient voltage surge suppressor – TVSS). ASDs have been found to be especially susceptible to these transients and nuisance tripping can result even when overvoltage levels are not severe.
Ways to avoid excessive voltage levels due to utility capacitor switching include altering (or moving) the capacitor size to avoid a harmful resonance point, adding high-energy low-voltage arresters (metal-oxide varistors – MOVs), or adding reactors to power factor correction capacitors to configure them as harmonic filters. The probability of nuisance tripping of ASDs can be significantly reduced by adding reactors (also known as “chokes”) to the drives.
Before investing in power factor correction capacitors, it is prudent to have the electrical system carefully analyzed to avoid potential problems with excessive transient voltages and harmonic distortion levels.
Estimating Financial Savings
A monthly electric bill will include an additional surcharge if the rate schedule has a “power factor penalty” and the power factor is below a specific level (such as 95%). This penalty can be reduced or completely eliminated with the proper application of power factor correction capacitors. The savings realized needs to be weighed against the equipment costs to determine if the payback period is acceptable. Payback times can vary significantly due to wide range of low voltage capacitor costs (e.g. approximately $15/kVAr for fixed capacitors to $75/kVAr for adjustable filter banks).
Example Illustrating Capacitor Sizing and Payback Estimation:
Consider the following example data. Please note that this example is provided to illustrate one possible method for determining a power factor correction capacitor size and payback period. You will need to utilize your billing and rate schedule data for an accurate calculation
Example Data: Energy Rate: $0.05/kWh Demand Charge: $9.00/kW Month: June Number of Days: 30 Energy Use: 325000kWh Demand: 800kW Power Factor: 80% Assumed Low Voltage Power Factor Correction Capacitor Cost: $20/kVAr
Step 1: Determine Energy and Demand Components of the Monthly Bill:
Energy Use (kWh) * Energy Rate ($/kWh) 325,000 kWh * $0.05/kWh = $16,250
$(Total Energy and Demand Components) * (95 – Power Factor) * 0.0025 $23,450 * (95 – 80) * 0.0025 = $879
Step 3: Determine Average Active Load (kW):
Energy Use (kWh) / (Number of Days * 24hours/day) 325,000 kWh / (30 * 24) = 451 kW
Step 4: Determine Capacitor Rating to Correct Power Factor to 95%:
kVAr95% = (Average Active Load) * [TAN(COS-1(Power Factor)) – TAN(COS-1(0.95))] 451 kW * [TAN(COS-1(0.80)) – TAN(COS-1(0.95))] 190 kVAr (will purchase a 200 kVAr, 480 volt capacitor bank)
Step 5: Estimate Equipment and Installation Cost:
Capacitor Bank Cost = 200 kVAr * $20/kVAr = $4,000 Estimated Installation Cost = $1,000 Total Cost = $5,000
Step 6: Determine Payback Period:
Payback (in months) = Total Cost / Monthly Power Factor Penalty $5,000 / $879 = 5.7 months
Note that this analysis only illustrates a simple payback and does not include operating and maintenance costs (generally low for low-voltage fixed capacitor banks), the cost of capital, or interest rates.
SUMMARY
Power factor is a measurement of how efficiently a facility uses electrical energy. A high power factor means that electrical power is being utilized effectively, while a low power factor indicates poor utilization of electric power.
Low power factor can cause equipment overloads, low voltage conditions, and greater line losses. Most importantly, low power factor can increase total demand charges and cost per kWh, resulting in higher monthly electric bills.
Low power factor is generally solved by adding power factor correction capacitors to a facility’s electrical distribution system. Power factor correction capacitors supply the necessary reactive portion of power (kVAr) for inductive devices. The principle benefit is lower monthly electric bills.
REFERENCES
IEEE Recommended Practice for Electric Power Distribution for Industrial Plants (IEEE Red Book, Std 141-1986), October 1986, IEEE, ISBN: 0471856878
IEEE Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book, Std 399-1990), December 1990, IEEE, ISBN: 1559370440
IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems, March 1988, IEEE, ISBN: 0471853925
Industrial and Commercial Power Systems Handbook, F. S. Prabhakara, Robert L. Smith, Ray P. Stratford, November 1995, McGraw Hill Text, ISBN: 0070506248
RELATED STANDARDS IEEE Standard 519-1992 IEEE Standard 18-1992 IEEE Standard 1036-1992
GLOSSARY AND ACRONYMS ASD: Adjustable-Speed Drive HVAC: High-Voltage Air Conditioning MOV: Metal Oxide Varistor PF: Power Factor PWM: Pulse Width Modulation TVSS: Transient Voltage Surge Suppressors
Published by World Nuclear News (WNN), 24th February 2022. Website: world-nuclear-news.org
With the attention of the world focused on events in Ukraine, one of the questions people are asking is about the country’s nuclear power industry. Here is a brief overview.
The location of nuclear power plants in Ukraine (Image: World Nuclear Association)
How big is Ukraine’s nuclear power industry?
Ukraine is heavily dependent on nuclear energy, with 15 reactors generating about half of its electricity. All its current reactors are Russian-designed VVER types.
What is the history of nuclear power in Ukraine?
Nuclear development started in 1970, when Ukraine was part of what was then the Soviet Union, with the construction of the Chernobyl power plant. The first unit was commissioned in 1977 with unit 4 coming online in 1983. Following the accident in 1986, units 5 and 6 were cancelled in 1989.
The industry remained relatively stable during the years when the country became independent of the former Soviet Union. At the end of 1995 Zaporozhe 6 was connected to the grid making Zaporozhe the largest nuclear power station in Europe, with a net capacity of 5700 MWe. (The second largest station operating is Gravelines, near Dunkerque in France, with a net capacity of 5460 MWe.)
In August and October 2004 Khmelnitski 2 and Rovno 4 respectively were connected to the grid, bringing their long and interrupted construction to an end and adding 1900 MWe to replace that lost by closure of Chernobyl units 1 and 3 in 1996 and 2000 respectively.
What plans has Ukraine had for new nuclear capacity?
The original design lifetime of the Russian reactors was 30 years, but work has taken place to allow a series of lifetime extensions.
In September 2021 the Ukrainian state-owned nuclear power firm Energoatom signed an agreement with the US-based firm Westinghouse to build four AP1000 reactors at established sites in the country. Since then Energoatom has outlined plans for further reactors – including exploring the possibility of deploying small modular reactors from US firm NuScale – as part of its goal of 24GWe of nuclear capacity by 2040.
What about Ukraine’s nuclear fuel?
Ukraine has access to two fuel suppliers: Russia’s TVEL and Westinghouse. Most fuel in Ukraine’s reactors is manufactured by TVEL, but the country has had an ongoing project in recent years to diversify its fuel sources
As of mid-2021, six of Ukraine’s 15 reactors were operating using fuel manufactured by Westinghouse, fabricated at its plant in Västerås in Sweden.
What Energoatom said ahead of the latest events
Earlier this month Energoatom’s CEO Petro Kotin said that: “According to the protocol, the plants will not work in case, for example, of bombing attack. In such a case, the plant is shut down and unloaded until the threat is eliminated.
“In the event of loss of the external power supply at the nuclear power plant, the autonomous power supply system starts working by means of powerful diesel generators. Ukrainian nuclear power plants are ready for such a mode of operation: the stock of diesel fuel located at nuclear power plants significantly exceeds the established standards.
“In addition, Ukrainian power units are ready even for an aircraft crash, because the containment and the reactor vessel designed to withstand corresponding risks.”
He added that two years’ worth of nuclear fuel had been stockpiled in case of interruption of supply.
The latest updates on the situation in Ukraine
The State Nuclear Regulatory Inspectorate of Ukraine has said that all four of the country’s nuclear power plants have been operating normally, with nine out of the 15 units connected to the grid as of Monday 28 February.
Ukraine’s nuclear power company Energoatom issued a statement on Tuesday 1 March saying that all the power plants were continuing to operate normally, and said its CEO Petro Kotin had asked the International Atomic Energy Agency (IAEA) to intervene to help keep the area around nuclear power plants free from military action.
The Russian Ministry of Defence’s spokesman Major General Igor Konashenkov was quoted by Russian media as saying, on the morning of 28 February, that Russian forces “have complete control and are protecting the territory” around the Zaporozhe plant, with its staff “working to maintain the facility and control the nuclear environment”.
In its update on 28 February the IAEA said that it had been told that Russian forces were “operational near the site but had not entered” Zaporozhe (also known as Zaporizhzhia) nuclear power plant in eastern Ukraine at that time.
The IAEA statement also said that Ukraine had informed them the previous week that “Russian forces had taken control of the facilities of the State Specialised Enterprise Chernobyl NPP, located within the Exclusion Zone set up after the 1986 accident. The regulator said that the shift supervisor at the site had not been replaced since 24 February but that he continued to perform his duties.
“SNRIU also provided radiation readings from the site which the IAEA assessed as low and in line with near background levels.”
The condition of Chernobyl nuclear facilities and other facilities was unchanged, it said.
IAEA Director General Rafael Mariano Grossi said the IAEAwas monitoring developments in Ukraine “very closely and with grave concern” and with a special focus on the safety and security of its nuclear power plants and other nuclear-related facilities.
He stressed that the IAEA General Conference adopted a decision in 2009 that “any armed attack on and threat against nuclear facilities devoted to peaceful purposes constitutes a violation of the principles of the United Nations Charter, international law and the Statute of the Agency”.
Published by Pacific Crest Transformers, 300 West Antelope Road – Medford, Oregon 97503 Tel : (541) 826 – 2113 Fax : (541) 826 – 8847. March, 2015.
Transformers serving heavy nonlinear loads are subject to increased winding temperatures due to the harmonic currents generated by those loads. This overheating can result in a shortened service life for the transformer. For example, operating a transformer at 10 degrees C above its insulation rated class will cause approximately a 50% reduction in the life of the transformer. If the over temperature gets high enough or lasts long enough, the insulation with fail which in turn will result in a transformer failure. K-factor rated transformers are designed to compensate for the presence of harmonic loading thereby preventing excess heating.
The definition for the K-factor as provided by the IEE Std. C57.110-2008 (IEEE Recommended Practice for Establishing Transformer Capacity When Supplying Nonsinusoidal Load Currents) states:
“A rating optionally applied to a transformer indicating its suitability for use with loads that draw non-sinusoidal currents.
where
Ih(pu) = the rms current at harmonic “h” (per unit of rated rms load current); h = the harmonic order.”
Confused? – The object of this paper is to demystify the subject thereby providing a basic understanding as to the impact of K-factor on transformer design and operation.
Although transformers are inherently very efficient, there are losses associated with their design and loading. These losses are made up of core, winding (I2R), and eddy currents. Although core loss and winding loss values are largely constant and directly dependent on the quality and amount of material used, eddy currents can vary depending on load profiles.
In a transformer, the primary windings induce voltage in the secondary windings through an expanding and contracting magnetic field. Eddy currents are stray currents of electricity that are created by induction in conductors. These counter-electromotive forces (emf) are induced in opposition to the original field thereby creating opposition to current flow (resistance) which translates to losses.
Eddy current losses are expressed as a percentage of the transformer’s normal winding (I2R) as determined by Ohms law. They are a phenomena that increase in severity as the frequency of the current increases.
In an electrical power system, harmonics are current and voltage with frequencies that are integer multiples of the fundamental power frequency. That is, in a power system with a fundamental frequency of 60Hz, the second harmonic is 120Hz, the third harmonic is 180Hz, and so on. Harmonics have no useful purpose, yet contribute to losses and lower system efficiency. Harmonics return over the neutral and are dissipated as heat in connecting cables and transformers. These frequencies are referred to as non-sinusoidal loads. The presence of non-sinusoidal harmonic content in the current waveform will have the effect of increasing eddy current losses in the transformer leading to “harmonic distortion” of the fundamental power frequency waveform.
In the image to the right “A” depicts a single 60Hz cycle waveform (fundamental power frequency). “B” represents a 3rd harmonic (180Hz) waveform. The resultant waveform as shown in “C” provides an example as to the impact that the harmonic load may have on the fundamental waveform. Although the example depicts an unlikely 3rd harmonic magnitude, it provides a graphic depiction as to the impact that non-sinusoidal content can have on the fundamental waveform. The magnitude of the distortion is dependent on the number and magnitude of the total harmonic load profile.
The table to the right provides an example of environments in which various K-factor rated transformers would be used. A transformer “K-factor” rating conveys its ability to manage varying degrees of nonlinear loads without exceeding the rated temperature rise limits. For any given nonlinear load, if the harmonic current components are known, the K-factor can be calculated and compared to the transformer’s nameplate K-factor. As long as the load K-factor is equal to or less than the transformer’s rated K-factor, the transformer does not need to be de-rated. The higher the K-factor, the more non-linear loads the transformer can handle. The actual formula to determine K-factor takes into account the frequency and current intensity of each individual harmonic.
The identification, measurement, and determination of the presence of non-sinusoidal frequency loads is essential in determining the impact on a transformer load. ANSI/IEEE C57.110, is the guide for determining the heating effects of nonlinear loads. It developed an equation for calculating these heating effects. By squaring the frequency and the per-unit current and multiplying them together, the guide arrived at a number without a designation. Originally it was going to be called C for “constant”, but was decided against because of possible confusion with “centigrade”. The letter K for “Konstant” was selected and Underwriters Laboratory used this designation in the original submission of a low voltage dry type transformer. K since became the standard measure of the ability of a transformer to withstand nonlinear loads.
The K-factor is a number derived from a numerical calculation based on the summation of harmonic currents generated by the non-linear load. The higher the K-factor, the more significant the harmonic current content.
Standard K-factor transformers come in K-factors of 4, 9, 13, 20, 30, 40, and 50. After K-factor load calculations are made, a transformer rated equal to or higher than the result is specified. It is more economical to purchase a K- factor transformer than to use a de-rated oversized transformer.
As a “rule of thumb”:
0% electronic, 100% electrical – standard (K-1 rated) transformer
“electronic” = Nonlinear Loads “electrical” = Inductive and Resistive Loads
K-factor rated transformers are preferred over oversized (de-rated) conventional transformers because they are designed to supply nonlinear loads, are equipped with 200% rated neutral bus, and are likely to be smaller and less expensive. Disadvantages of an over-sized standard transformer may include the requirement for a higher short-circuit rating on circuit breakers and a higher inrush current. De-rating a standard transformer is only a temporary fix that often translates into lower efficiency operation.
To calculate the K-factor, multiply the square of the percentage of harmonic current by the square of the harmonic order and add the results. For example, if a load is 60% of the fundamental, 65% of the third harmonic, 30% of the fifth harmonic, and 35% of the seventh harmonic, the resulting K-factor would be 12.3
In this example, a transformer with a K-factor of 13 should be specified. The K-factor rating defines the transformer’s ability to withstand odd-harmonic currents while operating within its insulation class. When the K-factor is unknown, a transformer may be selected by using the above “Examples…” table as a guide.
For existing installations, one can validate the K-factor load by using a 3 phase analyzer such as pictured below.
3-phase power analyzer
Such a device can also be used to check the impact of adding additional load devices on K-factor loading so as to insure that the existing transformer can be used.
So, what changes must be made to a transformer design in order to accommodate the additional losses caused by non-sinusoidal loads? The most notable is that the capacity of the transformer neutral is increased a minimum of 200% of the transformer kva rating. This is to accommodate the presence of triplen harmonics. The triplen harmonics are defined as the odd multiples of the 3rd harmonic (ex. 3rd, 9th, 15th, 21st etc.). Triplen harmonics are of particular concern because they are zero sequence harmonics, unlike the fundamental, which is positive sequence. The consequence of this fact is that the magnitude of these currents on the 3 phases are additive in the neutral which if not accommodated for, can lead to significant heating.
For K-factor rated transformers, PCT routinely utilizes round coil construction with cruciform cores which allow for 360 degree cooling ducts. This approach minimizes the potential for localized heating within the coils since the cooling fluid flows freely throughout the core/coil assembly.
With the additional loss requirements identified via the K-factor rating, additional cooling radiators may be added to insure that while delivering nameplate capacity, the temperature limit will not be exceeded. In extreme cases (K-20 and above), winding conductor current densities and/or core material flux densities may be adjusted.
Pacific Crest Transformers: Providing innovative solutions for today’s complex challenges
Published by Electrotek Concepts, Inc., PQSoft Case Study: Electric Arc Furnace Flicker and Harmonic Control, Document ID: PQS0314, Date: April 16, 2003.
Abstract: A steel manufacturer plans to construct an electric arc furnace-based steel making facility using a thin slab casting machine directly coupled to a hot strip rolling mill. The planned melt shop contains two dc electric arc furnaces (EAF) and will supply two ladle metallurgy furnaces (LMF) which will feed two thin slab casting machines. Concerns are raised with regards to voltage flicker and harmonic distortion levels associated with the proposed steel plant. The main objectives of this study are to evaluate the need for a Static-var Compensator (SVC) to control voltage fluctuations and to develop a minimum harmonic filter design that will provide required reactive compensation for the plant loads and will control harmonic levels to meet IEEE Std. 519 limits.
INTRODUCTION
This case study presents the results of an engineering study evaluating concerns for flicker and harmonic distortion levels associated with a proposed steel plant. The steel manufacturer plans to construct an electric arc furnace-based steel making facility using a thin slab casting machine directly coupled to a hot strip rolling mill. The planned melt shop contains two dc electric arc furnaces (EAF) and will supply two ladle metallurgy furnaces (LMF) which will feed two thin slab casting machines.
The steel plant will be supplied by a utility from its 500kV transmission system. The available short-circuit capacity from the utility will be 25,000A, 21,600 MVA; 19233A, 16,648 MVA; and 12,940A, 11,205 MVA respectively under different utility operation conditions. The steel plant’s electric power system will consist of a 500kV to 34.5kV substation. The substation 34.5kV bus is sectionalized. Sections 1 and 2 supply the melt shop, each has an 80 MW dual electrode dc arc furnace (EAF) and a 15 MW ac ladle furnace (LMF). Section 3 of the 34.5kV bus supplies a distribution system for the rolling mill. The auxiliary system of the steel plant will contain various types of air compressors, water pumps, ac drives and cycloconverters. A diagram of the overall facility represented for the study is provided in Figure 1. For simplicity, details of the system connection have not been shown. Multi-stage harmonic filters on each of the 34.5kV buses are indicated using a single filter symbol.
The steel manufacturer intends to operate this system with a minimum installation of reactive power compensation and harmonic filtering. The major concerns associated with operating the steel plant, as far as utility power quality is concerned, are harmonic distortion, flicker (voltage fluctuations), and transients caused by switching on the utility system or by switching a filter bank in the steel plant.
Operation of electric arc furnaces introduces random variations in the demand of the real and reactive power from the utility supply system. Due to the nonlinear characteristics of an electric arc furnace, the furnace current will be rich with harmonics. An installation of a static var compensator (SVC) at the steel plant will help to reduce the level of the system voltage fluctuations. However, the SVC operation can also generate harmonics. In addition to the arc furnaces, adjustable speed drives and cycloconverters used in the plant will also generate harmonics. The combined effects of all these harmonic producing loads will determine the levels of voltage and current distortion at the point of common coupling (PCC) between the utility and the steel plant. The filter designs developed in this study are based on the combined impacts of all the nonlinear loads in the facility.
The main objectives of this study are to evaluate the need for an SVC to control voltage fluctuations and to develop a minimum harmonic filter design that will provide required reactive compensation for the plant loads and will control harmonic levels to meet IEEE Std. 519 limits at the 500kV PCC.
Approach
Electrotek developed a complete steel manufacturer power supply system model for the evaluation using the Electromagnetic Transient Program (EMTP). The model includes all important system components from the 500kV utility power supply to the 480V steel plant power systems. The model is used to characterize the harmonics generated by the nonlinear loads in the facility (arc furnaces, ladle furnace, cycloconverter, ac drives, etc.). The model also includes a dynamic representation of the arc characteristics to permit evaluation of voltage fluctuations at the PCC with the utility supply system.
Circuit components such as power transformers, arc furnaces, cycloconverters, ac drives, SVC system as well as capacitor or harmonic filter banks are represented in the system model using data modules developed by Electrotek. If future evaluations are needed or if there are any system changes, this modularized approach for the model implementation will make additional simulations much easier.
The EMTP model is used directly for the evaluation of flicker concerns but it is inefficient for the many cases required for filter (each case requires many hours to run). Therefore, a steady state system representation is developed using Electrotek’s SuperHarm® program for harmonic evaluations. This SuperHarm model is used for the filter design task using frequency domain simulations. The program allows evaluation of response to the whole range of frequencies generated by the steel plant nonlinear loads (integer and non-integer harmonics).
VOLTAGE FLUCTUATION EVALUATION
There are two kinds of power changes associated with the melt shop operation. First, at each stage of the melt, the furnace demands different levels of active heating power. The furnace operating voltage and current settings are correspondingly changed during the heating cycle to meet with a designed furnace load profile. This type of change happens several times per melting cycle. Corresponding to each of these input power adjustments, disturbances in the system voltage occur. However, these power level adjustments do not result in the voltage flicker investigated here.
The voltage fluctuations of interest are those associated with uncontrollable variations of the dc arc length. These variations are highly random, and occur much more frequently than the power level adjustments described above. The greatest change in arc length occurs during initial scrap meltdown, with variations in equivalent arc resistance diminishing as the melt progresses. Different types of scrap exhibit different arc variation profiles.
The flicker study examines the following questions:
What flicker level can be expected on the 500kV PCC bus with no reactive compensation or other mitigation?
Does two-furnace operation double the flicker level of single-furnace operation? What is the worst case scenario?
Is a SVC necessary for flicker control? If yes, what is the minimum size needed to reduce 500kV flicker magnitude to an acceptable level?
Summary of Flicker Evaluation Cases
The source strength at the 500kV PCC varies with on-line generation. The multiple system configurations can be reduced to three approximate capacity levels, as shown below:
Table 1 – Possible Utility Supply System Strength at 500kV PCC Bus
Source Strength
Short-Circuit Strength (MVA) at 500kV PCC
Short-Circuit Isc (Amps) at 500kV PCC
Weak
11206
12940
Normal
16648
19223
Strong
21650
25000
Results of the EMTP voltage flicker simulations are summarized in Table 2 and Table 3.
As expected, comparing the first and fourth case in the table shows that a 100Mvar capacitor at the melt shop 34.5kV bus has only a slight impact on the voltage flicker at 34.5kV and basically no impact on flicker at 500kV. The reason is that, compared with the utility supply source, the current loop impedance of the compensation circuit is fairly high, especially at flicker frequencies. As a result, even with the local var supply, the major portion of the fluctuation in reactive power is delivered from the utility system. The capacitor compensation is mainly for melt shop power factor correction.
The table also summarizes flicker levels with an SVC consisting of a 100Mvar TCR and 95Mvar of fixed tuned filter banks. It is shown that the SVC effectively reduces flicker at both 34.5kV and 500kV.
Only a weak system was considered for single furnace operation. In all single furnace cases, the maximum instantaneous voltage flicker magnitude is less than 0.3% of system line-to-ground voltage. The dominant frequency of the flicker voltage is around 4 Hz. Voltage fluctuations at this level should not cause any problem.
Table 2 – Maximum Instantaneous Voltage Flicker for Single Furnace Operation
Case
Conditions
MW
Max ΔV/V at 34.5kV (1000*%)
Max ΔV/V at 500kV (1000*%)
80 MW
Weak Source, a single furnace, No compensation
80.3
2400
300
80CAP
Weak Source, a single furnace, With 95Mvar cap./filter
80.3
2500
300
80TCR
Weak Source, a single furnace, With 65 Mvar cap./filter and 100Mvar TCR
80.3
1350
200
For the two furnace cases, the maximum instantaneous voltage flicker at 34.5kV reached 5% and 500kV flicker reached 0.6% with two furnace operation on a weak source.
Table 3 – Maximum Instantaneous Voltage Flicker for Double-Furnace Operation
Case
Conditions
MW
Max ΔV/V at 34.5kV (1000*%)
Max ΔV/V at 500kV (1000*%)
2-80MW
Weak Source, two furnaces, no compensation
2*80.3
5000
600
2-80TCR
Weak Source, two furnaces, With 95Mvar cap./filter and 100Mvar TCR on each furnace bus
2*80.3
1500
300
2-80MW2
Normal Source, two furnaces, no compensation
2*80.3
4000
380
Typical Waveforms from Simulation
Simulations with normal source strength showed that an SVC is not needed to control flicker. It was not necessary to analyze the strong source condition, since flicker level would be even lower. However, the weak source condition was analyzed to obtain the worst case flicker level.
Two sets of flicker simulation waveforms are shown below. The first set shows single furnace operation on a weak system with the balancing control between two rectifiers activated. The second set two furnace operation on a normal system with fully independent rectifier operation (i.e., balancing control disabled). No reactive power compensation was assumed for these simulations.
Single Furnace, Weak Source Condition
This case simulated a single dual-electrode dc arc furnace operating on a weak supply with no reactive compensation. An average melting power of 80.3 MW was specified by setting the rectifier dc bus voltage reference to 535 V and the electrode dc current reference to 75 kA/electrode.
For this single furnace case, the maximum instantaneous flicker reached 2.5% at 34.5kV bus and 0.3% at the 500kV PCC. Flicker voltage frequency content ranged from 1 to 15 Hz, with great concentration at about 4 Hz.
Figure 2 shows the waveform and spectrum of the total current injection into the 34.5kV side of the 150 MVA melt shop supply transformer.
Figure 2 – Single Furnace 34.5kV Current Injection
Voltage variations at 34.5kV and at 500kV were evaluated, with flicker at 500kV being the more important with regard to the need for an SVC.
Line-ground voltage, instantaneous flicker voltage, and flicker voltage frequency content waveforms at 500kV and 34.5kV are shown in Figure 3.
Figure 3 – Single Furnace Voltage Waveforms and Spectrum
Two Furnaces, Normal Source Conditions
This case simulates two-furnace operation with normal source strength. The furnace melting power settings and other system conditions are the same as those given in Case 80 MW, but the balancing control circuit was disabled to obtain independent operation of the two six pulse rectifiers for each furnace. This is the normal procedure for the initial portion of the melt. Therefore, this case should represent worst case conditions with two furnaces operating in the initial melt period. Electrical quantities for this case are shown in Figure 4 and Figure 5.
Two furnace operation with normal source strength produced a maximum flicker of 3.8% at 34.5kV and 0.37% at 500kV. Flicker voltage frequency content was found to be different than that for single furnace operation. The dominant frequency in this case is close to 6 Hz with the spectrum spread from 2 to 12 Hz. In general, 500kV voltage flicker of this magnitude should not create problems for the other customers on the utility transmission system.
Figure 4 shows the waveform and spectrum of the total current injection into the 500kV transmission system.
Figure 4 – Double Furnace 500kV Current Injection
Voltage variations at 34.5kV and at 500kV were evaluated, with flicker at 500kV being the more important with regard to the need for an SVC.
Figure 5 – Double Furnace Voltage Waveforms and Spectrum
Harmonic Filter Design
Filter Options Evaluated
Four different filter options were considered and presented to the utility. The first option was a classic filter design with individual tuned branches at the 2nd, 3rd, 4th, 5th, 7th, and 11th harmonics (Sections 1 and 2). This results in a very expensive design because many branches require damping resistors to avoid high impedance parallel resonances that could excite non-integer harmonic components. Options 2 and 3 both involve the third order filter tuned to the fifth harmonic with a damping resistor to prevent resonance problems. In option 2, a 2nd harmonic filter was included on Section 1 and a 3rd harmonic filter on Section 3 to provide some reduction of these non-characteristic harmonics at the 500kV PCC.
Option 4 consists of a third order filter tuned near the third harmonic to provide damping at the lower order components. Tuned branches are included at the 5th, 7th, and 11th (actually 10.5) to control the characteristic harmonics of the dc furnaces operating in the independent 6-pulse control mode. The filter on Section 3 is the same as option 3. While this configuration has excellent characteristics, the additional cost may not be warranted.
The first two options were reviewed at a meeting with the customer and it was decided to focus on Options 3 and 4. These are illustrated in Figure 6 and Figure 7, respectively. Option 3 is the simplest of the configurations evaluated and is the configuration recommended for the facility.
Figure 6 – Filter Option 3, Sections 1, 2 and 3.
Figure 7 – Filter Option 4, Sections 1 and 2 Only (section 3 is the same as option 3).
Frequency Response Characteristics
The frequency response is illustrated as a measure of the current amplification that can be expected as a function frequency. Figure 8 shows the current amplification as a function of frequency for both filter designs being considered. The frequency response at Section 1 and Section 2 are the same so only Section 1 is provided. Both filter options use the same design for Section 3 so only one frequency response curve is included for Section 3.
Figure 8 – Current Amplification vs. Frequency at 34.5kV buses
Comparing the response for options 3 and 4 shows that the additional branches and damping in option 4 provide significant reduction of the current magnification between the third and fourth harmonics. However, the performance actually at the third and fourth harmonics is very similar (actually better at the fourth harmonic for option 3). The interharmonics between the third and the fourth are much lower than the maximum values most of the time and the maximum magnification is less than 10 for the proposed design. The damping provided by the recommended design (option 3) is sufficient to prevent problems at the interharmonic frequencies.
Expected Harmonic Levels
Expected voltage and current harmonic distortion levels are evaluated for both filter options 3 and 4. Typical maximum levels are calculated using the worst case spectrums with the following harmonics included: 5, 7, 11, 13, 17, 19, 23, and 25. Short time maximums are calculated using all of the harmonic components. These levels should occur for only a very small percentage of the time since the non-characteristic harmonics are all considered at their worst case values simultaneously.
34.5kV Voltage Distortion Levels
Voltage distortion levels at the 500kV level resulting from the steel plant operation will be extremely low due to the low impedance of the 500kV system. It is more important to consider voltage distortion levels at the 34.5kV sections, where they can affect all of the steel plant loads. Table 4 gives the expected voltage distortion levels at the individual sections. The typical maximum values are well within the IEEE Std. 519 guidelines and the short time values should not cause any problems.
Table 4 – Expected Voltage Distortion levels at 34.5kV Sections
Section
34.5kV Bus VTHD
Option 3
Option 4
1,2
Typical Maximum
3.5%
3.4%
1,2
Short Time
5.6%
6.5%
3
1.9%
1.9%
Harmonic Current Levels at the PCC
The harmonic current levels are evaluated at the 500kV PCC. These are based on the combination of harmonic currents from all three 34.5kV sections. The expected harmonic current levels are compared with the limits outlined in IEEE Std. 519. For the characteristic harmonics (5, 7, 11, 13, etc.), the actual limits are used. For non-characteristic harmonics, 150% of the limits are used for comparison because IEEE Std. 519 allows the specified levels to be exceeded by this amount for up to one hour per day.
The following table shows a compares the expected harmonic current levels at the PCC with the IEEE Std. 519 limits for both filter options 3 and 4. Note that all harmonic currents are expressed in percent of a calculated demand current (first row of the table). This estimated demand current includes the effect of the filter-provided reactive compensation.
Note that even the 150% limits at the second, third, and fourth harmonics could be exceeded (depending on the filter option). However, the furnace harmonic characteristics provided for these components are considered to be conservative and the summation effects assumed for these non-characteristic harmonics should be very rare (furnaces on sections 1 and 2 both generating high non-characteristic harmonics at the same instant). It is expected that the actual maximum harmonic current levels at these harmonic orders will be well within the 150% limits.
The following table shows a comparison of expected harmonic currents at the 500kV PCC with IEEE Std. 519 limits (harmonic levels expressed in % of average maximum demand current, including the effect of reactive power compensation).
Table comparison of expected harmonic currents at the 500kV PCC with IEEE Std. 519 limits
EMTP Simulated Harmonic Injection at 500kV PCC Bus
EMTP simulations are used to verify the results of the harmonic investigation. The simulation presented here is for a two-stage filter configuration similar to Option 3. With these filters connected, the current injected into the 500kV PCC bus is shown in Figure 9. The THD of this current is about 1.4%.
Figure 9 – Frequency Spectrum of the 500kV Supply Current with Filter Option #3
SUMMARY
Flicker
Simulations show that with the normal supply, without reactive power compensation, the maximum instantaneous flicker level at the 500kV bus is around 0.4% when two dc arc furnaces are in operation. The maximum instantaneous flicker is the maximum percentage value of the fluctuation voltage on the system line-to-ground peak voltage base, within a sampling time window of 2 seconds. In other words, this 0.4% means that all frequency components of the voltage flicker are smaller than 0.4% of system nominal peak voltage. Usually, this level of flicker does not cause problems. The flicker at the steel plant 34.5kV furnace supply buses is about 4%. However, only the furnace loads are connected on these buses and these loads can withstand relatively high voltage fluctuations. Based on these results, an SVC is not required to control flicker levels. Strong source conditions will result in even lower flicker levels.
Under weak source conditions and both furnaces operating simultaneously, the maximum instantaneous flicker level reached 0.6% at the 500kV PCC bus and reached 5% at the 34.5kV furnace supply buses inside the steel plant. The simulation shows that the frequency spectra of the instantaneous flicker range from 0.5 to 30 Hz, with a great concentration within the 2 to 10 Hz range. This level of flicker, especially with these frequency components in the most sensitive range, has the potential to cause problems. If the steel manufacturer plans to operate both furnaces simultaneously with this weak source condition, installation of an SVC is recommended.
If a 95 MVAr SVC (95 MVAr tuned filter bank + 100 MVAr TCR) is installed on each 34.5kV furnace supply bus in the steel mill, with the same weak source supply, the maximum instantaneous voltage levels at the 500kV PCC bus and at the 34.5kV buses can be reduced to 0.3% and 1.5% respectively.
Reactive Power Compensation and Harmonic Filtering
The reactive power compensation is sized with consideration of a required +0.95 to -0.95 average displacement power factor within a 30-consecutive minutes metering period. The total capacitive compensation needed at each 34.5kV furnace supply bus is determined based on the steel furnace melting cycle MW load profile. The rolling mill 34.5kV bus reactive power compensation requirement is estimated based on load conditions provided by the steel manufacturer and the rolling schedules supplied by Siemens. It is estimated that approximately 65 MVAr of compensation is needed at each 34.5kV furnace supply bus and 38 MVAr is needed on the rolling mill bus. The reactive compensation requirements are used as the starting point for sizing harmonic filters. It is assumed that the filters will be installed without an SVC.
A number of different filtering options were evaluated. The filter performance evaluation and energy duty requirements for damping resistors were mainly based on the supplied ac ladle furnace, dc arc furnace and rolling mill harmonic generation characteristics. A two-stage filter combining a 3rd order filter with non-power frequency damping resistor and a tuned 2nd order filter is the recommended configuration.
REFERENCES
IEEE Std. 519-1992, “IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems.”
RELATED STANDARDS IEEE Std. 519, “IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems.”
GLOSSARY AND ACRONYMS EMTP: Electromagnetic Transient Program PCC: Point of Common Coupling SVC: Static-Var Compensator TACS: Transient Analysis of Control Systems TCR: Thyristor Controlled Rectifier THD: Total Harmonic Distortion Voltage Flicker: Observable changes in light as a result of voltage fluctuations
Published by CEA Technologies Inc. (CEATI), POWER QUALITY Energy Efficiency Reference Guide, Chapter 5 – Where to Go For Help.
Web Resources
IEEE Standards Information
Home of the IEEE standards; in particular 446; 519; 1100 (“The Emerald Book”, considered the key IEEE reference on power quality); 1159; 1250 and 1346.
Copper.org
A site by the Copper Development Organization responsible for promoting the use of copper; check out the reference primer on power quality.
Power Standards Laboratory
A web site from principal, Alex McEachern, about voltage sags.
Underwriters Laboratories, Inc.
A good power quality reference is UL Standard 1449, second edition that describes performance specifications for surge protection devices.
Power Quality Guidelines for Energy Efficient Device Application
This guidebook has three primary objectives:
To improve guidelines for minimizing any undesirable power quality impacts of energy saving technologies;
To provide an understanding of the energy savings potential of power quality related technologies; and,
To provide guidelines for evaluating “black box” technologies.
Semiconductor Equipment Materials International
SEMI F47, Specification for Semiconductor Processing Equipment Voltage Sag Immunity, is available from SEMI.
International SEMATECH Technology Transfers
This web site is by Sematech, a consortium of semiconductor manufacturers and tool manufacturers. It contains the report, “Guide for the Design of Semiconductor Equipment to Meet Voltage Sag Immunity Standards.”
IEC Standards Information
Information about types of disturbance, emission and immunity, etc., as well as the different IEC Standards can be found at: http://www.iec.ch/zone/emc/whatis.htm
CAN/CSA-C61000-2-2-04 Electromagnetic Compatibility (EMC) – Part 2-2:Environment Compatibility Levels for Low Frequency Conducted Disturbances and Signaling in Public Low-Voltage Power Supply Systems.”
CAN/CSA-CEI/IEC 61000-2-8-04 Electromagnetic Compatibility (EMC) – Part 2-8: Environment Voltage Dips and Short Interruptions on Public Electric Power Supply Systems with Statistical Measurement Results.
CAN/CSA-C61000-3-3-06 Electromagnetic Compatibility (EMC) – Part 3-3: Limits Limitation of Voltage Changes, Voltage Fluctuations and Flicker in Public Low-Voltage Supply Systems, for Equipment with Rated Current <= 16 A per Phase and Not Subject to Conditional Connection.
CAN/CSA C61000-3-6-04 Electromagnetic Compatibility (EMC) – Part 3: Limits Section 6: Assessment of Emission Limits for Distorting Loads in MV and HV Power Systems – Basic EMC Publication.
CAN/CSA-C61000-3-7-04 Electromagnetic Compatibility (EMC) – Part 3: Limits Section 7: Assessment of Emission Limits for Fluctuating Loads in MV and HV Power Systems – Basic EMC Publication.
CAN/CSA-CEI/IEC 61000-4-11-05 Electromagnetic Compatibility (EMC) – Part 4-11: Testing and Measurement Techniques – Voltage Dips, Short Interruptions and Voltage Variations Immunity Tests.
CAN/CSA-CEI/IEC 61000-4-34-06 Electromagnetic Compatibility (EMC) – Part 4-34: Testing and Measurement Techniques – Voltage Dips, Short Interruptions and Voltage Variations Immunity Tests for Equipment with Input Current More Th an 16 A per Phase.
CAN/CSA-C61000-3-11-06 Electromagnetic Compatibility (EMC) – Part 3-11:Limits Limitation of Voltage Changes, Voltage Fluctuations and Flicker in Public Low-Voltage Supply Systems – Equipment with Rated Current <= 75 A and Subject to Conditional Connection.
CEATI Reference Documents
• T984700 5103 Canadian Power Quality Survey 2000
• T034700 5120 Review of Flicker Measurement of the CEA DPQ Survey 2000
• T014700 5113 Sag, Swell and Short Interruption Evaluation from the Canada PQ Survey 2000
• T044700 5123 Power Quality Impact Assessment of Distributed Wind Generation
• T044700 5126 Customer Power Factor Correction Capacitor Application Guide
• T014700 5110 An Automated Method for Assessment of Harmonics From Non-Linear Loads and Distributed Generators
• T004700 5108 Techniques to Assess Harmonic Distortions for Systems with Distributed Harmonic Sources
• T984700 5102 The Impact of the Electromagnetic Compatibility (EMC) Concept of Power Quality in The North American Electricity Industry
• T024700 5115 Solutions to PQ Disturbance Problems of Sensitive Equipment
• T024700 5114 Establishing Power Quality Guidelines
Published by Electrotek Concepts, Inc., PQSoft Case Study: Electric Arc Furnace Modeling for Voltage Flicker Evaluation, Document ID: PQS0313, Date: April 16, 2003.
Abstract: A steel manufacturer is planning to add a second arc furnace to their existing facility. Concerns are raised as to whether the additional furnace will cause levels of voltage flicker that might possibly affect neighboring loads. A complete time-domain model of the existing and proposed arc furnace along with a flicker meter are developed in EMTP and the results gathered are used to evaluate system changes that will be needed prior to installation of the second furnace.
INTRODUCTION
Background
A steel manufacturer has a steel making facility supplied from a 230kV switchyard. This facility currently operates a single arc furnace and a rolling mill. The steel manufacturer plans to start up a second furnace and the utility has agreed to make a number of system changes to improve the supply to the facility. The changes will be made at the 230kV switchyard that supplies the plant.
These changes are needed to meet the 230kV circuit breaker rating limitations and to improve system performance.
The steel manufacturer is fed from the 230kV switchyard through a 2.5 mile 230kV transmission line. Currently, there is one 57 MW ac furnace in operation at the steel mill. However, plans are to start the second 57 MW furnace in the near future. Flicker measurements were performed previously with the stronger system and one furnace in operation. RMS flicker levels were in the range 0.2-0.3%. With both furnaces operating and the reduced short circuit capacity, there is a significant concern that flicker levels could be objectionable for other customers supplied from this part of the transmission system. The study is designed to evaluate expected flicker levels with the planned system configuration and the possibility of both furnaces operating simultaneously.
Approach
Evaluation of arc furnace flicker requires an accurate representation for the arc furnace loads. The major difficulty in the furnace modeling is to accurately characterize the electric arc. Even in the same stage of a melting cycle, the arcing voltage and the equivalent arc resistance may change significantly, ranging from a momentary open circuit status to a momentary short circuit status. This arcing variation depends closely on the materials to be melted and is highly random in nature. It has been found that this arcing change does not obey any uniform distribution.
In this case study, arc furnace loads are represented using Transient Analysis of Control Systems (TACS) modeling capability of the Electromagnetic Transients Program (EMTP). A variable arc length is characterized using the band limited white noise method. Consequently, the equivalent arc resistance varies continuously as a random function of time. With the incorporated electrode lifting and lowering controls, an average arc voltage and the furnace heating power are controlled by a preset furnace operation voltage.
Electrotek used different bandpass filters and random signal magnitude functions to characterize ac arcing resistance. A trial and error method was used to determine properties of the bandpass filters and magnitude functions for the arc characterization. In this study, the flicker is evaluated against different conditions (system supply strength), with either a single furnace operation or two furnace operation.
In order to perform a sensitivity analysis, an EMTP TACS flicker meter module was developed. This EMTP TACS flicker meter module reads a simulated voltage waveform at a specified system location during each time step of the simulation, performs the flicker calculation, and outputs instantaneous voltage flicker (DV(t)/|V|) as a part of simulation results.
Simplified Flicker Evaluation Procedures
Empirical results from other arc furnace installations can be used as an initial check of possible flicker concerns at the steel manufacturing facility. gives curves developed from a number of different arc furnace measurements around the world. The curves show where flicker is likely to be a problem in terms of the short circuit capacity at the point of common coupling. The curves are only applicable for single furnace operation. However, an equivalent flicker level for multiple furnaces can be estimated using the following relationship:
Pst is the short term flicker severity output from a flickermeter according to the IEC standards. For two furnaces of the same size, the flicker level with both furnaces operating should be about 26% greater than the flicker level for one furnace.
Figure 1 – Empirical Curves Illustrating Short Circuit Capacity and Flicker
Applying the curves of Figure 1 to the steel manufacturing configuration, we can estimate that a single furnace operation (approx. 80 MVA) will become objectionable at a short circuit capacity of about 14000 MVA and may be noticeable with a short circuit capacity as high as 25000 MVA. Previous measurements and actual experience at a short circuit level of 21576 MVA have shown no problem.
With two furnaces (equivalent size of 80×1.4=112 MVA), objectionable flicker can be expected for a short circuit capacity of about 16000 MVA (extrapolation). The expected short circuit capacities at the 230kV switchyard after system modifications will be somewhat less than this value, indicating potential problems.
EMTP MODEL DESCRIPTION
Steel Manufacturer Power Supply System
The steel manufacturer is supplied by the utility system from a 230kV switchyard through a 2.5 mile 230 kV transmission line. The steel mill loads consist mainly of two 57 MW ac arc furnaces and the rolling mill. The power circuit of the steel mill is schematically shown in the oneline diagram given in Figure 2.
Figure 2 – Steel Manufacturer Power Supply System Oneline
Two 60 MVA, 230/34.5kV, Delta-Wye, power transformers are used to supply the melt shop that includes two 57 MW ac arc furnaces. Each of these furnaces has its own 60 MVA, 33kV/728-240V, delta-Wye step-down transformer and a 34.5kV, 25 MVAr harmonic filter. The filter is tuned at 171 Hz. The melt shop auxiliary and rolling mill is supplied separately by two 20 MVA, 230/34.5kV transformers with the same winding connections. The major loads of these transformers are SCR-based dc drives supplied at either 500V or 600V. For simplification, these drives are grouped according to their supply voltages and are equivalently represented in the EMTP model by one 6 MW and one 9 MW drive as shown below. The drives are assumed to be operated at 30 degree firing angle. The 4 MVAr and 11 MVAr power factor correction/ harmonic filter units are connected at 34.5kV buses as shown.
EMTP Component Models
Important components of the system model are described in this section. This section focuses on the models for the arc furnaces and the controls, as well as the metering for flicker.
AC Arc Furnace Model For an ac arc, three variation rules were applied.
The first cause of variations is associated with the 120 Hz current zero crossings. For a constant arc length, the arc voltage Varc(t) changes with the magnitude of the instantaneous current, Iarc(t). For a positive half cycle of the arc current, the arc voltage can be expressed by:
where
Varco – a constant, unit length arc voltage threshold when iarc(t) increase C – a constant, in unit of Watts, C=Cp when di/dt >0 and C=Cn when di/dt <0 D – a constant, in unit of Amp, D=Dp when di/dt >0 and D=Dn when di/dt<0
The voltage shape for the negative half cycle is symmetrical to the positive half cycle with respect to the origin. This is a deterministic rule mainly responsible for characteristic harmonic distortion.
The second rule affecting the furnace arc is electrode lifting and lowering control. It is also referred to as electrode voltage regulation. The principle of ac voltage regulation is shown in Figure 3.
Figure 3 – DC Arc Voltage Control
With a constant voltage across a unit length of arc, a desired total arc voltage is adjusted by changing the length of the arc. An appropriate operation voltage is obtained by lifting or lowering the movable positive electrode with respect to the fixed negative electrode. As a result, the distance between the tips of the electrodes changes, resulting in a different range of arcing voltage variation. At different melting stages, the furnace heating power is adjusted by changing the arc voltage. With constant supply system impedance, this voltage change results in arc current change and arc power change. A long arc operation tends to give a high operation power factor. A short arc operation results in a low power factor.
The third rule applied is a random time variation of the arc length. For any given ac furnace arc voltage setting and distance between the tips of the electrodes, the actual arc length changes randomly with time. The factors which directly affect this random change include the physical distance between the tip of the electrode and the materials to be melted, characteristics of the materials, status of melting, and many others related to furnace design and operation conditions. As a result, the magnitude of these random changes can be dramatic; ranging from a bolted short circuit to an open circuit.
Based on the results of many studies over several decades, it is now commonly believed that the variations of an electrical arc do not obey any standard distribution rule. Namely, the arc length changes in a completely random fashion. To properly represent such a random arc change, in this study, a band-limited white noise method is used. The principle of this method is shown in Figure 4.
Figure 4 – TACS Representation of Random Variation of Arc Length
The procedure to model the random variation portion of the arc length consists of four steps:
Generate a random number between 0 and 1 at each simulation time step
Set up an appropriate sampling scheme so that the time step effects on the generated random signal are removed
Process the sampled random signal through a bandpass filter so that only signals within a considered frequency range are able to pass to the next processing stage. A typical range of frequencies characteristic of the arc variations is 4 Hz to 14 Hz.
Apply proper scaling and weighting functions which characterize the different disturbance magnitude at different melting stages. In this stage, a preset dc arc voltage is used as an input to the weighting function.
The effective arc length obtained through this procedure can be expressed by
L=Lo*(1-ΔL)
where Lo is the desired arc length calculated by the electrode regulation control logic for a given dc voltage setting value.
With all the above factors considered, the arc voltage can be structured as Va=kVao(Ia)
where Vao is the arc voltage corresponding to the reference length, Lo. Coefficient k is the ratio of the threshold arc voltage corresponding to a length L, Vat(L), to that relevant to the reference length, Vat(Lo).
Since the relationship between threshold voltage and arc length can be expressed as Vat=A+B*L
then, k is given by k=Vat(L)/Vat(Lo)=(A+BL)/(A+BLo)
where L is the arc length in cm, A is a constant taking into account the sum of anode and cathode voltage drops (40 volts), and B represents the voltage drop per unit arc length (10 volts/cm).
With the random nature included, k is k(t) = (A+BL(t))/(A+BLo(t)) = 1-Br(t)Lo(t)/(A+B*Lo(t))
where r(t) is a random number generated at time=t with magnitude ranging from 0 to 1 These furnace characteristics are implemented in EMTP TACS.
Power Meter Module
The power meter module is developed to read out active power, reactive power, apparent power, along with displacement and true power factor directly at a desired monitoring location of the simulated system. The metering module is for a 60 Hz system. Single phase circuit quantities are calculated first. Three phase quantities are obtained by taking an average of the three phases.
Flicker Meter Module
A voltage flicker calculation module was developed for this study using EMTP TACS capabilities. The method used to separate voltage flicker from its 60 Hz carrier voltage is outlined in Section 6 of the CEA research Report: “Contract NO 042 T 178, Analysis of Flicker from Arc Furnaces.” This reported study was completed in 1983 by Ontario Hydro. In this report, instantaneous voltage flicker is obtained through a signal processing procedure of four steps:
Voltage signal full-wave rectification
120 Hz notch filter
30 Hz low-pass filter
DC voltage buckoff
In the module developed for this study, a minor modification on this procedure was made. As a result, the actual signal processing is illustrated in Figure 5.
Figure 5 – Flowchart for Instantaneous Voltage Flicker Calculation
FLICKER ANALYSIS
Summary of System Conditions Studied
Simulations were performed for a variety of different system conditions and furnace operating conditions. The objective is to evaluate the range of flicker variations that are likely and the sensitivity of these variations to the possible system configurations and the arc furnace operation.
There were three different power supply alternatives simulated. The various system conditions in combination with the possible arc furnace operating conditions resulted in twelve cases for the study (3 system options times two source strengths defining the range for each option times two different furnace operating conditions).
Summary of Expected Flicker Levels
Summaries of the cases are provided in Table 1 and Table 2. These tables include the maximum magnitudes of the instantaneous flicker, using the ΔV/V (peak) and rms flicker calculation methods. Previous measurements at the steel manufacturing facility (without the new line) showed un-weighted rms flicker levels in the range 0.25-0.30 %. The results in Table 2 show good agreement with these measurement results. The simulations include a 2-second window with arc variations designed to represent the worst part of the melt cycle. Therefore, the cases with two arc furnaces operating simultaneously are actually simulating two furnaces operating in the initial melt period when the arc is the most unstable.
The percentage values given in the summary tables for the ΔV/V values are in percent of the peak line-to-ground voltage. That is, they represent the maximum deviation in the fluctuation divided by the nominal peak line-to-ground voltage. The unweighted rms values are based on a 30 Hz reference frequency and are rms values expressed in percent of the nominal rms line-to-ground voltage. The rms calculation is based on a sliding window with a period equal to about 33 msec over the two seconds of the voltage fluctuation waveform. The maximum rms value over this time period is presented in the tables.
Table 1 – Summary of Flicker Simulation Results at the 230kV Customer Bus
Table 2 – Summary of Flicker Simulation Results at the 230kV Utility Switchyard
With primary components in the range 1-10 Hz, a flicker level less than 0.5% is generally considered to be acceptable. The results at the 230kV switchyard indicate that flicker levels are acceptable for one furnace operation almost all the way down to the worst case short circuit level simulated. The flicker levels are higher at the steel manufacturer’s 230kV bus but there are no other customers supplied from this point at the present time.
For two-furnace operation, the worst case rms flicker levels are acceptable as long as the short circuit level at the 230kV switchyard is about 16000 MVA. Lower short circuit capacities at the 230kV switchyard could result in objectionable flicker levels for worst case furnace operating conditions (two furnaces in the initial bore down period of the melt).
The increase in flicker levels due to the second furnace ranged from 50-70%. This is somewhat higher than the 40% often quoted but this is probably due to the conservative nature of these cases where worst case conditions are simulated for both furnaces at the same time. This comparison is based on the ratio of maximum values for the 2-second period. A comparison of the average values over the same period will give less conservative results.
Typical Waveforms of Interest
This section provides example waveforms of Case 1F3 illustrating the simulations and the results.
A few observations are worth noting from these waveforms.
The instantaneous and rms flicker plots show significant variations. The maximum value can be significantly higher than a value averaged over a 1 or 2 second period. The maximum flicker values have been used for evaluation in this study. This should be considered a conservative approach.
The frequency spectrum of the flicker is concentrated in the range 1-12 Hz but it is difficult to pick out a dominant frequency. This means that the simplified calculation approaches for sine waves and square waves cannot be applied at all for these waveforms. The concentration below 12 Hz is typical of arc furnace variations without a static var system. These variations are in the range that has the most potential to cause complaints.
The frequency spectrum of the flicker shifts somewhat with two furnaces operating. In this case, the dominant components are in the range 8-12 Hz, rather than the 1-5 Hz range for one furnace. However, this is still in the range that can cause problems.
Figure 6 – Arc Voltage Waveform
Figure 7 – Current Waveform at Steel Manufacturer 230kV Supply
Figure 8 – Steel Manufacturer Active and Reactive Power in MW and MVAr
Figure 9 – Steel Manufacturer 230kV Voltage Fluctuation (Magnified)
Figure 10 – Steel Manufacturer 230kV Instantaneous Voltage Flicker ΔV/|V| [in 1000 times Percentage Value]
Figure 11 – Frequency Spectrum of Steel Manufacturer 230kV Instantaneous Voltage Flicker
Figure 12 – Steel Manufacturer 230kV RMS Flicker
SUMMARY
An EMTP-based arc furnace model was developed for evaluation of flicker concerns associated with supplying a steel manufacturer as they go to two furnace operation and as system changes are implemented that will affect the short circuit capacity at the 230kV substation supplying the plant. The model includes a dynamic arc representation which is designed to be characteristic of the most dynamic stages of the arc furnace melting cycle (worst flicker conditions). The flicker calculations with this model were found to have excellent agreement with previous flicker measurements with one furnace operating and a short circuit capacity of 21576 MVA at the substation. Flicker simulations were then performed to evaluate a variety of different possible system strengths with both one and two furnace operation.
The primary flicker measure used for this study is the unweighted rms value of the fluctuation envelope, expressed as a percentage of the rms line-to-ground voltage magnitude. It is desirable to keep this unweighted rms flicker level below 0.5% based on the fact that arc furnace fluctuations are usually in the most sensitive region defined on the flicker curve.
Figure 13 – Flicker Sensitivity Curve
(shows supply voltage variations, ΔV, in percent and the rate of their occurrence).
The Figure 14 shows the variations of the unweighted rms flicker with the short circuit capacity at the utility substation for both one and two furnace operation. Flicker should not be a problem at the substation for one furnace operation all the way down to the minimum short circuit capacity possible (10196 MVA). However, with two furnaces operating simultaneously in the most dynamic portion of the melt cycle, flicker levels can be expected to increase substantially. It should be noted that these should be considered worst case flicker levels, such as the level that will not be exceeded more than 0.1% of the time.
Figure 14 – Expected Flicker at 230kV Substation
Another important result of the simulations is the frequency spectrum of the flicker. With only one furnace operating, the frequency components of the flicker are spread over the range 1-12 Hz with some concentration in the range below 5 Hz. This agrees quite well with the previous measurement results where all the dominant components were below 5 Hz. This frequency spectrum becomes more concentrated in the range 8-12 Hz with two furnace operation. The higher frequency components with two furnace operation may provide some benefit because the weighting associated with the perception of flicker results in slightly higher allowable levels above 10 Hz (see flicker sensitivity curve above).
Accounting for the higher frequency components in the flicker with two furnaces operating, unweighted rms flicker levels up to about 0.7% should not cause complaints. With these criteria, flicker complaints should not be expected with two furnace operation unless the short circuit capacity is less than about 13000 MVA.
Based on these observations, it is suggested that the two furnace operation be permitted and monitoring be performed to evaluate actual flicker levels over time. These flicker levels can be correlated with any customer complaints in the area. If any problems are encountered, two possible approaches can be adopted to resolve the problem:
A static var system can be installed. Two different static var systems could be installed on the two furnace buses or the buses could be tied together and a single SVC installation designed. The single SVC installation would be much more economical. The size required is estimated to be about 85 MVAr.
The furnace operation procedures can be modified to prevent synchronizing of the melt cycles. If the two furnaces are not in the initial melt stage or are not loading scrap into the melt at the same time (this happens 2-3 times per melt cycle), there should not be any flicker problem associated with the two furnace operation. Some staggering of the melt cycles is probably beneficial from a production point of view anyway. If this approach is feasible, it would seem to be the preferred solution.
RELATED STANDARDS IEEE Std. 519, “IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems.”
GLOSSARY AND ACRONYMS EMTP: Electromagnetic Transient Program PCC: Point of Common Coupling SVC: Static-Var Compensator TACS: Transient Analysis of Control Systems TCR: Thyristor Controlled Rectifier THD: Total Harmonic Distortion Voltage Flicker: Observable changes in light as a result of voltage fluctuations
Published by CEA Technologies Inc. (CEATI), POWER QUALITY Energy Efficiency Reference Guide, Chapter 4 – Solving and Mitigating Electrical Power Problems.
4.1 Identifying the Root Cause and Assessing Symptoms
Power quality technologists employ technical instrumentation. This instrumentation can range from simple digital multi-metering through to sophisticated waveform analysis instruments. True power quality monitoring requires full-time monitoring so that steady state effects can be trended and infrequent events can be captured as they occur. A variety of electronic meters are now available for permanent monitoring that offer numerous features at moderate prices. A trained PQ specialist can also employ a portable instrument, or groups of instruments, to diagnose power quality for fixed periods of time. It should be emphasized that power quality monitoring is a highly technical and potentially dangerous skill; even many trained electricians are completely unfamiliar with the details of how power quality measurement is properly carried out.
Do not attempt to undertake a power quality measurement exercise without the help of a professional practitioner in the field.
One of the first things that should be carried out before monitoring begins is a check of the effectiveness, safety and operational characteristics of the wiring in the facility. This will ensure that problems like bad grounding, poor terminations and improperly connected loads are not masking other problems or are, in fact, not mistaken for other types of issues.
Some of the elements that might be tracked by a PQ professional are:
RMS (Root – Mean – Square) Measurements
Average Measurements
Peak Measurements
Harmonic Analysis
Power Line Event Logging
4.2 Improving Site Conditions
Consideration of disturbance sources external to the facility should only be considered after the internal electrical environment has been thoroughly checked.
4.2.1 Mitigating Effects
The key elements to mitigate power quality problems are:
Proper grounding and wiring
Effective mitigating equipment (if required)
4.2.2 Mitigating Equipment
A wide variety of products are available that can help to mitigate power line disturbances. Care should be taken to properly select effective mitigating equipment. Improper application of these products may cause new power quality problems due to unforeseen incompatibilities. Before selecting a product, the customer should have a good understanding of the cause of the problem, as well as the characteristics of the available equipment. A properly functioning system may be adversely affected by change in the electrical environment, as in a change of load in the facility. Therefore, mitigating equipment that was once effective may fail to protect sensitive equipment after such a change has occurred. When selecting equipment that has an operational heat loss, as indicated by an efficiency rating, provision should be made for adequate cooling of the equipment, especially if it is to be located in a computer room.
4.2.1.1 Dedicated Circuits
A dedicated circuit is a single circuit with one load. It is a relatively inexpensive distribution technique that can reduce load interaction. The ability of a dedicated circuit to solve power quality problems depends on its location, impedance, and other factors. To achieve the lowest possible impedance, theoretically, the load of the circuit should be as close as possible to the building service entrance. However, this could aggravate the situation if transients are a problem, since they could travel more freely through the system. For improved operation of the circuit, the neutral and the ground wires should be the same size as the current-carrying conductor.
Tips and Cautions
Dedicated circuits will solve local problems only. Properly installed dedicated circuits obviate the need for isolated grounding circuits.
4.2.1.2 Surge Protective Devices (SPDs; also known asTransient Voltage Surge Suppressors, TVSS)
SPDs are energy diverters that pass the energy contained in a transient to the ground. There are a variety of designs available including gas discharge tubes, line clamps made of semiconducting material, and hybrid designs which may contain linear inductive or capacitive components. It is important to note that transient suppressors do not provide voltage regulation or isolation.
4.2.1.3 Lightning Arresters
The lightning arrester is designed to remove large overvoltages and associated high energy levels. This is accomplished during an overvoltage by short-circuiting the line to ground in what is referred to as a crowbar effect of energy diversion. The conduction of energy to ground will cease when the current drops to zero. The response time for this technology is relatively slow. These products are used as primary arresters on main power feeders.
4.2.1.4 End-User SPDs
Faster-acting SPDs that use Metal Oxide Varistors (MOVs), or silicon avalanche diodes (SADs) can be used for lower-voltage transient attenuation. They act by clamping line voltage to a specific value and conducting any excess impulse energy to ground, regardless of frequency. The energy shunting capability of a line clamp is expressed by its joule rating, which determines the amount of energy the device can handle. It is important to realize that these units are only as good as the ground wiring that they are connected to; routing transient energy to ground may result in the mis-operation of some devices. In addition, they are quite susceptible to longer duration overvoltages, which can lead to catastrophic component failure. Silicon avalanche diodes operate on lower voltages, handle less power, but tend to act faster than MOVs, and are often used in communication systems for these reasons. Due to the clamping nature of a surge suppressor, it cannot remove voltage irregularities that occur within the sine wave envelope but do not exceed the limiting threshold.
Figure 25: Effect of Line Clamp on Transient Voltages, 120 Volt System
Figure 26: Example of Impulses Not Clamped
4.2.1.5 Power Line Filters
Filter design is a complex topic and needs to be properly addressed by a qualified power quality practitioner.
Linear Passive Filter
Design and Operation
A linear filter is composed of linear components, such as inductors and capacitors. It passes the basic power frequency (60 Hz) and attenuates other frequencies which are in the form of electrical noise and harmonics. Some filters are tuned circuits, which means they address a small range of frequencies. Examples of filters that are not tuned are the simple low pass filter, and the simple high pass filter.
Uses
Simple low pass filters attenuate high frequencies, and have the general characteristics most desired in filters for improved power quality and noise attenuation. Simple high pass filters attenuate low frequencies. Tuned shunt filters are not used for general power quality applications. Special designs are used to attenuate harmonics. A shunt connected tuned filter, which consists of an inductor, a capacitor and a resistor, is tuned to eliminate a specific harmonic order by providing a low impedance to the harmonic frequency and shunting the harmonic energy to ground. A number of these filters may be arranged in stages, with each stage selectively filtering a given harmonic frequency.
Figure 27: Examples of Untuned Filters
Examples of Harmonic Filters
Equipment which is either sensitive to electrical noise, or which creates it, is often designed with linear filters for protection of equipment. For instance, all power supplies contain electrical filters. For harmonics, multi-staged shunt filters are most effective for mitigation of lower order harmonics.
Disadvantages
Common mode noise is not necessarily eliminated by the use of linear filters.
Low pass series filters are seldom used for harmonic attenuation since they must be rated for full line current making them relatively expensive.
Shunt filters applied at individual loads can often be overloaded by harmonics produced by nearby loads or even at other customer sites.
4.2.1.6 Isolation Transformers
Design and Operation
Isolation transformers consist of two coils (primary and secondary) intentionally coupled together, on a magnetic core. They have two primary functions:
a) They provide isolation between two circuits, by converting electrical energy to magnetic energy and back to electrical energy, thus acting as a new power source. b) They provide a level of common mode shielding between two circuits.
Since the ability of a transformer to pass high frequency noise varies directly with capacitance, isolation transformers should be designed to minimize the coupling capacitance between primary and secondary sides, while increasing the coupling to ground. Isolation transformers have no direct current path between primary and secondary windings. This feature is not characteristic of an auto-transformer, and therefore an autotransformer cannot be used as an isolation transformer. Unshielded isolation transformers can only attenuate low frequency common mode noise. High frequency normal mode noise can be attenuated by specially designed and shielded isolation transformers, although it is not frequently required (consult with your electrical system expert).
Advantages
Isolation transformers are used to attenuate common mode noise.
They provide a new neutral to ground reference point.
They can be used to break ground loops.
Isolation transformers can reduce higher order harmonics, but will not eliminate harmonic distortion or prevent notching.
Isolation transformers may be combined with other equipment such as transient suppressors and circuit breakers to form complex circuits known as Power Distribution Units (PDUs).
Only high quality shielded isolation transformers should be used in critical applications.
Disadvantages
No voltage regulation or ride-through capabilities are available.
Poorly designed isolation transformers may produce harmonics.
The ability of an enhanced isolation transformer to attenuate normal mode noise varies, depending on the load.
4.2.1.7 Line Voltage Regulators
Design and Operation
A line voltage regulator is a device that maintains a relatively constant voltage output within a specified range, regardless of input voltage variations. Some kinds of line voltage regulators can regulate, but not “condition”, the power. They are less frequently used, and include the ferroresonant transformer, the tap switching transformer, the variable ratio transformer, the magnetically coupled voltage regulator, the induction regulator and the saturable reactor. The ferroresonant transformer and tap switcher are discussed in more detail within this section. Auto-transformers are frequently used in voltage regulation devices. If an auto-transformer is used as the variable circuit element, it develops a variable voltage which is added to the incoming AC line voltage. A sample of the input voltage is rectified, filtered and compared to a DC reference voltage. The difference is then used to off set the input voltage change. Auto-transformers are also used in Silicon Controlled Rectifier regulators. In this case, the primary voltage of the autotransformer is varied by phase control.
Uses
These products regulate voltage to protect against momentary and transient disturbances, within a certain range. Their response time is typically one cycle. Regulators are already built into some sensitive equipment. Most regulators that are built into equipment, however, are DC regulators.
Disadvantages
Voltage regulators do not have noise suppression capabilities.
Those with switching power supplies actually create noise in the input line.
4.2.1.8 Ferroresonant Transformers
In contrast to a typical isolation transformer, the ferroresonant transformer is designed to operate at saturation. The ferroresonant transformer provides the same functions as the shielded isolation transformer, but also provides instantaneous, continual voltage regulation, as well as ride-through capabilities. A ferroresonant transformer has a relatively simple design, and no moving parts; however this mitigation device was designed for older, linear electrical loads. A ferroresonant transformer is often incompatible with modern electronic loads and should be used with caution on high demand loads. Ferroresonant transformers usually have higher operating temperatures that can lead to very warm equipment enclosure temperatures. It is therefore recommended that these transformers be safely guarded from accidental contact by personnel.
4.2.1.9 Tap Switching Transformers
Design and Operation
An electronic tap switching transformer, or tap switcher, regulates output voltage by changing the ratio of primary windings to secondary windings in response to fluctuations in input voltage or load. This is accomplished with solid state switches (SCRs or TRIACS) which select the appropriate taps to compensate for the fluctuations. Voltage is regulated not continuously, but in steps. Switching occurs when line voltage passes through zero, so transients are not created.
The tap switcher can react in one or two cycles.
Either peak or RMS voltage detectors may be used.
Taps may either be on the primary or secondary side.
Uses
Where voltage fluctuation is the primary concern.
Disadvantages
Voltage output changes are not continuous. Better voltage continuity is achieved by using more taps.
If auto-transformers are used, no isolation is provided.
4.2.1.10 Power Conditioners
Devices marketed as power conditioners are often combinations of the above-mentioned mitigation devices. They often contain transient voltage surge suppression, noise filters, and isolation transformers or voltage regulators. Careful consideration of product specifications and the intended use are required in order to determine if they will be effective.
4.2.1.11 UPS Systems
“UPS” means uninterruptible power supply. A UPS system contains a component that stores energy which can be used during power interruptions. UPSs are available in a wide range, from basic battery backup to units that can supply power for days. UPS systems can be on-line or off -line (standby). Typically, the on-line systems provide greater protection and cost more. These systems may be either rotary or static. Rotary systems employ rotating machines; static systems use solid state components.
A UPS does not necessarily provide protection against high energy impulses.
A properly selected UPS system is the only product, other than a generating unit, that can protect critical loads against power interruptions exceeding 0.5 seconds and which can provide active regulated power.
Some inexpensive UPS systems with low power ratings produce a square wave output, causing some loads to malfunction. This characteristic is particularly true for standby UPS systems. The problem can be avoided by selecting a UPS system with a synthesized sine wave.
Disagreement often arises as to the preferred type of system, rotary or static. Rotary systems are often criticized for the regular maintenance they require, whereas static systems are criticized for the frequency of failed components. It should be pointed out that regular maintenance and parts replacement of rotary systems helps to prevent component failures, whereas static systems can run for a significant period of time without maintenance before failure with minimal downtime. No matter what system is selected, the user should expect that some type of maintenance or replacement will eventually be required. Multiple UPS systems can be used for redundancy in critical applications. They can be arranged in parallel, in which case they normally share loads, or in isolation, so that each UPS supplies a specific load under normal operation.
Large UPS systems (>100 kVA) typically employ inverters and wet-cell batteries, which require ventilation. Care should be taken to locate these items in protected, ventilated areas. Regardless of where the system is situated, the room should be relatively free of dust, and the temperature maintained near 25°C for optimum battery life and performance. More recently designed small UPS systems (<100 kVA) employ sealed batteries, which emit no hydrogen gas, and transistorized inverters, which are very quiet. Th e batteries are mounted in a cabinet, and the whole system can be placed in a computer room. Care should be taken to ensure that adequate battery life is available for these systems.
Battery Design and Selection
A battery is an electrochemical device that converts stored chemical energy into electrical energy.
Recharge time is typically 8-10 times the discharge time. When selecting a UPS battery, the cell size, cell life, required voltage, reliability, weight/space and manufacturer’s warranty should be considered. It is also important to note that battery discharge time as a function of load is not a linear relationship. Two basic types of batteries that are used for UPS systems are lead acid and Valve Regulated Lead Acid (VRLA). Carefully consider the minimum amount of battery time that is necessary in order to reduce capital and maintenance costs in the system.
Rotary UPS
A state-of-the-art, on-line rotary UPS is one of the most effective but more costly types of UPS systems. Although a number of designs are available, they include motor-generators with battery backups and fly-wheel systems.
4.2.1.12 Isolated Grounding Outlets
An isolated ground (IG) outlet as recognized by Electrical Codes is a receptacle, orange in colour or with an orange triangle and marked “Isolated Ground”, that is wired as an individual branch circuit outlet. This outlet has a separate green or green/yellow wire along with the normal uninsulated ground wire that runs continuously from the ground conductor terminal to the first panelboard where it is connected to the ground bus. Bonding of the conduit, boxes, etc. of the circuit is accomplished by ordinary means, i.e., conduit or a separate ground wire. The two grounds are connected only at the panelboard.
Many years ago, this arrangement was implemented to reduce common-mode noise problems. Common-mode noise is better attenuated at each device in the system and is in fact effectively filtered at the input of modern electronic devices.
The IEEE Emerald Book states that:
“This type of equipment grounding configuration is only intended to be used for reducing common-mode electrical noise on the electronic load equipment circuit as described in the NEC. It has no other purpose and its effects are variable and controversial.”
Isolated grounding receptacles are no longer recommended for installation in any situation. The effects they are supposed to solve can be more easily and cheaply mitigated with robust electrical system design.
4.2.3 Preventative Measures
4.2.3.1 Distribution System Considerations for Sensitive Loads
The quality of the power supplying sensitive loads is very heavily influenced by other loads within a customer’s facility. If there are “heavy” loads such as motors or heating, ventilating and air conditioning systems being supplied, voltage drops and electrical noise can be generated causing power quality problems for sensitive loads such as computer loads. As an illustration, consider the following distribution system supplying both motor loads and sensitive electronic loads. In this case the sensitive loads are fed from phase to neutral, and motors are fed phase to phase.
Figure 28: Motor and Sensitive Loads Supplied from the Same Feeder
If the feeder has a resistance of 0.075 ohms, during a motor start the voltage drop along the feeder is:
V = IR= 160A x 0.075 Ω = 12V
Voltage at the sensitive loads is 120 -12 =108V Voltage at the motors is 208 – (√ 3 x 12) =187V
If the motor is a 10 HP motor, it will draw an inrush current in the order of 160 A for a short period of time when starting.
The impedance of the feeders to the distribution panel supplying the motor and sensitive loads will cause a voltage drop of 12 volts or more while the motor is starting. Because of this voltage drop the sensitive loads will be supplied with only 108 volts for a short period of time. Unless the sensitive loads have an adequate amount of stored energy to ride through the voltage sag, they may malfunction. In addition, the current drawn for the first one or two cycles of the motor start, while the stator is magnetizing, is 2 to 3 times higher than the normal starting current. This will lead to only 84 V feeding the sensitive loads during this time.
If the motor load and the sensitive loads are supplied from separate feeders then the voltage drop does not occur in the feeder supplying the sensitive loads.
Figure 29: Motor and Computer Loads Supplied from Separate Feeder
An even better approach is to effectively create a new supply system for the sensitive loads by using a transformer in addition to a separate feeder.
Figure 30: Isolation Transformer Added to Computer Feeder Supply
A transformer establishes a separately derived power source. The transformer can be of the step-down type to reduce the supply voltage to the utilization voltage of the equipment or an isolation transformer if the supply voltage is already at the appropriate voltage.
Typical voltages for computer equipment are 120 volts single phase and 120/208 volts three-phase wye. If the sensitive loads are susceptible to some form of RFI (radio frequency interference), the transformer may utilize a shield that isolates electrical and magnetic noise coupling from the primary to the secondary of the transformer. This shield is connected to ground. The neutral on the secondary of the transformer must be connected to ground per the applicable Code in your jurisdiction.
4.2.4 High Frequency Grounding Considerations
Equipment grounding and the grounding of the electrical distribution system provide a low impedance path to ground for low frequencies (mainly 60 Hz and up to the 11th harmonic). Computers and microprocessor controlled equipment operate at high frequencies (in the 100s of MHz for control devices and well into the GHz region for IT and communications equipment).
IT equipment transfers data between various pieces of equipment at very high frequencies utilizing low signal levels. In the past, where these signal levels were referenced to the local ground system, they were susceptible to electrical noise and interference. Examples of the types of interfaces that suffered from noise coupling problems were the RS-232 interface and the Centronics printer interface. Grounded interconnection standards like these have been largely superceded by isolated and higher speed connections like Ethernet, fibre optics and USB. Where older analog communications systems and digital interface standards are still used, these types of equipment need an effective means of grounding for both low and high frequencies. A more effective approach is to eliminate all ground-referenced communication interfaces in a facility with newer, higher speed and noise immune interfaces.
Effects of Frequency on Conductors
Wiring systems used within a building generally have low impedance at low frequency, but as the frequency increases the impedance increases. “Real” wiring can be modeled by a wire with resistance and inductance and stray capacitance to ground distributed along its length.
For a grounding conductor to be effective at high frequencies it must be short to minimize the effects of stray capacitance and distributed inductance along its length. A rule of thumb is that the conductor should be shorter than 1/20th of the wavelength at that frequency. This means a length shorter than 1.4 m at 10 MHz. The single point, parallel path ground, which makes for a good equipment ground, is a less reliable high frequency signal ground.
In order to satisfy both equipment grounding and signal grounding requirements, a hybrid system should be employed. This system is a combination of the parallel path ground combined with a multipoint ground for good high frequency performance.
One such method, described in IEEE 1100-1999, The Emerald Book, is a signal reference structure.
Figure 31: Equivalent Circuit of a Wire
Signal Reference Structure
A ground plane is a conducting surface that has low impedance over a range of frequencies. The ideal situation would be to have all communications equipment located on a ground plane so that short connections could be made from the equipment to the plane.
While it is usually not practical to have a true ground plane, an effective alternative is a grid of conductors spaced on regular intervals, bonded at their intersections on the subfloor of a room’s raised floor, where it exists. This is called a Signal Reference Grid (SRG). In the absence of a raised floor, the bonded interconnection of equipment racks and trays at regular intervals also creates a SRG effect.
Figure 32: Signal Reference Structure or Grid
The grid is grounded to the electrical system ground at the point where the supply enters the room. All powered equipment is also grounded at this point making the equipment grounding a single point system.
Equipment is bonded to the reference grid via short conductors creating a low impedance path to ground for high frequencies. This hybrid system satisfies both equipment and high frequency grounding requirements and complies with the Electrical Safety Code. It creates a more stable and robust environment for all equipment connected to it in the event of a voltage transient or system fault impacting the electrical system.
4.3 Troubleshooting and Predictive Tips
4.3.1 Tips
Distribution Wiring and Grounding
Check that the electrical contractor is reputable, and practices proper grounding and wiring techniques. The electrical installation should be tested with instruments to determine compliance to Codes and equipment requirements. Have all wiring inspected.
Electrically separate highly sensitive loads from other loads. This may involve using separate buses, or separate distribution transformers. Th e Code generally does not allow separate AC services to be used in a facility.
Ensure that all equipment is CSA certified for safety reasons. Before purchasing mitigating equipment, ensure that all distribution and grounding problems have been identified and corrected. Then identify any problems that require mitigating equipment.
Ensure that all components of interconnected IT equipment are bonded to the same grounding system.
For the purposes of signal grounding, never assume that two physically separated points of a ground system will be at the same potential. Use isolation techniques or current transmitters for physically separated equipment.
If significant changes have been made in an electrical system, and a low voltage condition exists, notify the utility.
Mitigating Equipment
Ensure that overvoltage protection exists at the powerline entrance to the building and at other susceptible points
When purchasing electrical products, ensure that they will effectively perform the functions that are required, and cause minimal degradation of the power system. It is a good idea to request a demonstration of the equipment within the plant, when possible, especially for mitigating equipment.
Following installation of mitigating equipment, verify that the problem is solved.
Always identify any equipment sensitivity requirements, such as sensitivity to voltage fluctuations, in specifications.
Consider the interaction between mitigating equipment and the load. For instance, if the mitigating equipment has a high impedance, and the load has high inrush current (due, perhaps, to the starting of large motors), a voltage sag could result
The noise suppression capabilities of some products may be specified in terms of peak attenuation, which may not be appropriate for some applications. In addition, it is important to know the conditions under which the attenuation was measured.
Proper installation of electrical equipment is very important and yet often overlooked. For example, many ferroresonant transformers and power conditioners are improperly installed due to incorrectly sized primary conductors or breakers.
Equipment Ratings
The purchaser should check if quoted equipment capabilities apply to units operating at no load, partial load or full load.
All electrical equipment should be properly sized. Products may be sized by power, in volt amps (VA), or by maximum current rating in amps. To determine proper sizing, the following steps should be taken:
Determine the load operating voltage, current, and/or VA from the nameplate rating.
Sum all individual VA ratings of the loads. To obtain an estimate of the power consumed by the load, which is the real power in watts, calculate: Real Power = VA x Power Factor.
Many nameplate ratings assume a power factor of unity. If this is not a good assumption, factor this in. Some units are rated in Primary Power ratings. If this is the case then the sum of all secondary loads will have to be divided by the efficiency of the unit in order to obtain the Primary Power rating. It is especially important to obtain the power requirements for sensitive loads from the manufacturer.
Best Practices
Reduce the number of disturbance sources.
Maintain a malfunction log.
Customers should be aware of the level of harmonics they are producing. If a customer is exceeding the acceptable limits of the distribution system, they may be required to shut down their facility.
To minimize problems related to voltage sags use reduced voltage starters on motors
If installing an isolation transformer, ensure that the ground on the secondary side is properly connected.
Above all, know and understand the technology of mitigating equipment before applying it.
4.3.2 Troubleshooting
If an electrical end-user suspects that a power quality problem exists in his facility, there are a number of steps that may be taken to troubleshoot the problem. The key is a process of elimination. Reputable consultants may be contacted by the customer to assist the process:
Define the type of disturbance, frequency of occurrence and magnitude of the problem.
Determine which power conductors — hot, neutral or ground — have problems; this is critical, since some mitigation techniques only address problems with a specific conductor. For grounding problems, the source of the problem must be fixed; no mitigating equipment will provide a solution.
Check wiring for loose connections.
Check that proposed solutions actually work and follow-up.
Published by Electrotek Concepts, Inc., PQSoft Case Study: Wind Plant Voltage Flicker Data Analysis, Document ID: PQS1202, Date: January 26, 2012.
Abstract: This case study presents the results for a wind plant voltage flicker data analysis. The characteristics of voltage flicker are mainly determined by load characteristics and the short-circuit capacity. The wind plant substation supplied 65 wind turbine generators and the power quality monitor was connected to the 34.5 kV transformer secondary winding, which was considered the point of common coupling (PCC) for the voltage flicker harmonic analysis.
INTRODUCTION
A wind plant voltage flicker data analysis case study was completed for the 34.5 kV wind plant substation shown in Figure 1.
Figure 1 – Illustration of Oneline Diagram for Voltage Flicker Data Analysis
The wind plant substation was supplied from a 230 kV transmission line and included a 180 MVA, 230/34.5/13.8 kV step-down transformer with a number of 34.5 kV collector circuits supplying 65 2.3 MW (690 V secondary) wind turbine generators. The monitor was connected at the 34.5 kV transformer secondary, which was considered the point of common coupling (PCC) for the analysis.
The twenty-four day monitoring period was from November 16, 2009 through December 13, 2009. The power quality instrument used to complete the voltage flicker measurements was a Dranetz Power Xplorer PX5. The instrument samples voltage and current at 256 points-per-cycle, and follows the IEC 61000-4-15 method for characterizing voltage flicker data. The sampling rate also allows characterization of low to medium frequency oscillatory transients and harmonics through the 63rd harmonic. The voltage flicker measurement and statistical analysis was completed using the PQView® program.
MEASUREMENT DATA ANALYSIS
Error! Reference source not found. shows the measured 34.5 kV substation bus voltage during the twenty-four day monitoring period. Statistical analysis of the 61,901 individual steady-state voltage measurements yielded an average value of 20.141 kV, a maximum value of 20.502 kV, a CP95 value of 20.399 kV, and a CP99 value of 20.445 kV (1.03 per-unit).
Figure 2 – Measured Substation vs. Voltage Trend
IEEE Std. 1453 and IEC 61000-2-2 include specifications for measurement of voltage flicker and recommended compatibility levels. The standards recommend a compatibility level of Pst= 1.0 for power systems met by 99% of the measured values (CP99) with a minimum assessment period of one week. Table 1 shows the voltage flicker compatibility levels for Pst and Plt for low voltage and medium voltage systems.
Table 1 – Flicker Compatibility Levels for Medium Voltage Systems
Flicker Quantity
Compatibility Levels (CP99)
Pst
1.0
Plt
0.8
The envelope of the 60 Hz variations is defined as the flicker signal, Vf, and its rms magnitude is expressed as a percent of the fundamental. Voltage flicker appears as a modulation of the fundamental frequency (similar to amplitude modulation of an am radio signal). Therefore, it is easiest to define a magnitude for voltage flicker as the rms magnitude of the modulation signal. This can be obtained by demodulating the waveform to remove the fundamental frequency and then measuring the magnitude of the modulation components. A magnitude that is as low as 0.5% can sometimes result in perceptible light flicker if the frequencies are in the range of 1-5 Hz.
The voltage flicker severity is dependent on factors such as the turbine/transformer ratings, distances from substations, and the power system source strength. Flicker mitigation alternatives include increasing the source strength and power electronic-based mitigation equipment, such as static var compensators.
Figure 3 shows the measured short-term voltage flicker Pst trend at the 34.5 kV substation bus during the twenty-four day monitoring period. Figure 4 shows the corresponding voltage flicker histogram. Statistical analysis of the 8,880 individual flicker measurements yielded a CP50 value of 0.08, a CP95 value of 0.15, and a CP99 value of 0.19. The results show that the CP99 compatibility limit of 1.0 is not exceeded.
Figure 5 shows the measured long-term voltage flicker Plt trend at the 34.5 kV substation bus during the twenty-four day monitoring period. Figure 6 shows the corresponding voltage flicker histogram. Statistical analysis of the 417 individual flicker measurements yielded a CP50 value of 0.09, a CP95 value of 0.15, and a CP99 value of 0.19. The results show that the CP99 compatibility limit of 0.8 is not exceeded.
This case study summarizes a wind plant voltage flicker data analysis. The characteristics of voltage flicker are mainly determined by load characteristics and the short-circuit capacity. The measurement results showed that both the short-term (Pst) and long-term (Plt) voltage flicker measured at the 34.5 kV wind plant substation bus did not exceed the respective CP99 compatibility limits.
REFERENCES
IEEE Recommended Practice for Measurement and Limits of Voltage Fluctuations and Associated Light Flicker on AC Power Systems, IEEE Std. 1453-2004, IEEE, 2005, ISBN: 0- 7381-4482-7.
IEEE Recommended Practice for Monitoring Electric Power Quality, IEEE Std. 1159-1995, IEEE, October 1995, ISBN: 1-55937-549-3.
IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems, IEEE Std. 519-1992, IEEE, ISBN: 1-5593-7239-7.
RELATED STANDARDS IEEE Std. 1453
GLOSSARY AND ACRONYMS DFT: Discreet Fourier Transform PCC: Point of Common Coupling TDD: Total Demand Distortion THD: Total Harmonic Distortion