MG Set Provides Voltage Sag Support Voltage Sag Ride-Through

Published by Electrotek Concepts, Inc., PQSoft Case Study: MG Set Provides Voltage Sag Support Voltage Sag Ride-Through, Document ID: PQS0412, Date: December 31, 2004.


Abstract: Today’s high-tech computer and multi-media equipment require “clean” electric power protected against normal split-second voltage variations. A technology that has recently received much attention for providing this ride-through is the written-pole motor-generator set.

The written-pole motor generator, also known as the Roesel Motor Generator (RMG®) is a continuous-duty device, which provides essential electrical loads with a continuous source of clean, regulated, and isolated 60-cycle power. When a loss or variation of input utility power occurs, the Roesel Motor-Generator is designed to supply constant frequency 60 cycle power within a specified voltage range for a minimum of 15 seconds with full rated load on the unit. At reduced loads it will supply power for up to 45 seconds.

INTRODUCTION

For many years it has been the goal of utilities to supply their customers with the “best” power possible. The utility involved in this case study has implemented many research and development projects over the years to achieve this goal. These projects are used as demonstration projects that evaluate new technologies and their feasibility in solving power related issues for utility customers.

This case study describes one demonstration project that the utility implemented in an effort to supply two customers with uninterruptible power. Two sites were selected based on their sensitivity to voltage variations. One site is located in downtown Manhattan, New York and the other site is located in Westchester County, New York.

Site Selection

Manhattan Location

Customers served from the underground network in Manhattan will rarely if ever see a service interruption. The building selected for the project is one of the few buildings in the world to offer satellite accessibility, single- and multi-mode fiber optics, high-speed category 5 copper wire, and video conferencing facilities. Due to the critical nature of the tenant’s operations within this building, power quality is an important concern. A five-transformer 125/216-volt spot network supplies the building’s electrical service.

Westchester Location

A second location was selected to take part in the demonstration project. This location serves as a headquarters building for a large corporation with critical computer loads. The building’s electrical service is supplied via an automatic loop scheme on the 13.4 kV distribution feeder. The feeder supplies a pad-mounted transformer whose secondary voltage is 277/480 volts. Due to system operating procedures, this location experienced interruptions on occasion.

Building managers at both locations wanted to ensure that the customers in their facilities would never experience any interruptions. Con Edison engineers performed a study to determine the best approach to supplying uninterruptible power to this customer. This paper presents the approach used and the findings of the study performed by Con Edison.

Site Characterization

As part of the research project, the utility installed monitoring equipment to characterize the power quality at the Manhattan and Westchester locations. The monitors were configured to capture events ranging from normal capacitor switching transients to more severe long duration voltage variations and in the rare case, interruptions. The event type of most concern for this project was voltage variations and therefore, will be the only event type discussed.

After approximately three years of monitoring at both locations, the utility was able to accurately characterize the voltage variations that occurred at both facilities. Information on the magnitude and duration of voltage variations was summarized for each monitoring location.

Manhattan Location

Figure 1 illustrates the monthly sag rate that can be expected for the network involved in the project. No interruptions were recorded on the network during the monitoring period. As seen in Figure 1, 50% of the events have a sag depth of less than 25% of nominal. The monitoring instruments were configured to record voltage variations outside the limits of 90% to 110% of nominal.

Figure 1 – Sag and interruption rate and duration histogram for measurements taken on the input of the RMG at the Manhattan facility.

Another concern is the duration of the event. Figure 1 also illustrates the sag and interruption rate duration histogram for the Manhattan facility. The duration of approximately 98% of the events was less than 20 cycles (333 mS) with the majority of the events lasting between 6 and 20 cycles as illustrated in Figure 1.

Westchester Location

Figure 2 illustrates the sag and interruption rate for the input to the RMG on the radial distribution feeder. Notice that the interruption rate has increased from zero for an underground network to approximately 1 per 30 days for the radial feeder. A majority of these interruptions are of the momentary type, and are due to recloser operations on the supply feeder.

Figure 2 – Sag and interruption rate and duration histogram for measurements taken on the input to the RMG fed from a radial feeder at the Westchester facility.

Figure 2 illustrates the duration of the same measured. A majority of the events measured on the input to the RMG were between 1 and 2 seconds. Approximately 95% of the events were less than 2 seconds in duration.

Both locations proved to be acceptable for the installation and demonstration of the written-pole RMG technology. The written-pole RMG is capable of providing ride-through for up to 15 seconds at full load. As can be seen from the data, the majority of voltage sags and momentary interruptions are less than 100 cycles (1.6667 seconds) in duration.

Using the measurement information, the utility determined that both customers could benefit from the installation of the RMGs. Given the fact the RMGs could supply 15 seconds of ride-through for a complete loss of power and that 98% of the events experienced by the customers lasted less than 15 seconds, the RMG would be a good choice for voltage sag and interruption protection.

Ride-Through Performance

After the installation of the RMGs, Con Edison continued to monitor at both locations. This data would be used to verify that the RMGs operated as expected during voltage sag and interruptions.

Manhattan Location

On January 28, 1997, the network feeding the Manhattan location experienced a voltage sag where the voltage dropped 52% below the nominal 125 volts rms for 11 cycles (0.183 seconds) to 48.4%. Under normal conditions this event was severe enough to cause unprotected office and computer equipment to drop off-line, causing loss of data. Figure 3 illustrates the input and output voltages of the RMG during the voltage sag.

Figure 3 – Input and output voltage of the RMG serving the Manhattan facility during a voltage on January 28, 1997.

As seen from the measurements, the RMG provided 100% voltage ride-through for the connected load during the utility event.

Westchester Location

On October 31, 1996, the feeder that serves the Westchester facility experienced an interruption. The event lasted for approximately 1.2 seconds and the voltage on the input of the RMG went to zero (as expected with an interruption). Figure 4 illustrates the input and output voltages of the RMG during the interruption

Figure 4 – Input and output voltage of the RMG serving the Westchester facility during an interruption on October 31, 1996.

As seen from the measurements, the RMG provided 100% voltage ride-through for the connected load during the utility event.

SUMMARY

Power quality can be improved by using RMGs at customer locations. Due to the design of the utility’s system, a large percentage of power quality events experienced by customers are less than 100 cycles in duration. Since the written pole motor generator system is designed to provide 15 seconds of energy storage under full load conditions, it is an appropriate technology to evaluate for use by customers within the utility’s service territory. For sustained interruptions, the written-pole RMGs can be integrated with a backup emergency generator to provide a seamless transfer to the protected load.

The demonstration project has shown that critical customer loads may be successfully protected by the written-pole RMGs from misoperation due to these power quality events. The project has also identified several areas of concern, including voltage oscillations, which will be investigated as the project continues forward.

Installation and ongoing evaluation at the two sites has also allowed for documentation of critical issues to be considered during system specification, installation, startup and operation. These will be documented in an application guideline, which will be completed as part of this project.

REFERENCES

  1. Sinicola, Frank, “To Attract High-Tech Tenants, Give Them High-Quality Power”, Electrical World, October 1996.
  2. Braz, Aubrey, Peter Hofmann, Ralph Mauro, Christopher J. Melhorn, “An Evaluation of Energy Storage Techniques for Improving Ride-Through Capability for Sensitive Customers on Underground Networks”, PQA 95 Conference, New York, New York, May 8 – 11, 1995.
  3. Melhorn, Christopher J., Peter Hofmann, Aubrey Braz, Marek Samotyj, “Characterization of Power Quality Problems Associated with Large Commercial Customers Served from Large Underground Distribution Network Systems”, 1994 IEEE IAS Industrial and Commercial Power Systems Conference Record, Irvine, California, May 1994.
  4. M. F. McGranaghan, D. R. Mueller, M.J. Samotyj “Voltage Sags in Industrial Systems”, IEEE Transactions on Industry Applications, Vol. 29, No. 2 March/April 1993.
  5. Larry E. Conrad, Chairman, “Proposed Chapter 9 for Providing Voltage Sags (Dips) in Revision to IEEE Std. 493, the Gold Book”, PSI Energy, Plainfield ID, 1993.
  6. ANSI/IEEE Standard 446-1987, IEEE Recommended Practice for Emergency and Standby Power Systems for Industrial and Commercial Applications, Institute of Electrical and Electronics Engineers, 1987.
  7. “To attract high-tech tenants, give them high-quality power”, Electrical World, October 1996.

GLOSSARY AND ACRONYMS
MG Set: Motor-Generator Set

Improving Equipment Ride Through Voltage Sag Evaluation

Published by Electrotek Concepts, Inc., PQSoft Case Study: Improving Equipment Ride Through Voltage Sag Evaluation, Document ID: PQS0405, Date: June 30, 2004.


Abstract: Voltage variations, such as voltage sags and momentary interruptions are two of the most important power quality concerns for customers. Customers understand that interruptions cannot be completely prevented on the power system. However, they are less tolerant when their equipment mis-operates due to momentary disturbances which can be much more frequent than complete outages. Voltage variations and interruptions are inevitable on the power system. The most important of these variations occur during fault conditions on the power system.

This case presents the results of measurements and analysis of the impact of voltage sags on a process controller.

PROBLEM STATEMENT

A semiconductor manufacturer was experiencing problems with large motors tripping off-line during voltage sag conditions. If enough motors trip off-line, the entire manufacturing process can be disrupted resulting in significant lost revenue.

PLANT VOLTAGE DURING FAULT

The voltage sags were being caused by faults on the utility’s distribution system. These faults were caused by tree limbs, squirrels, accidents, etc. These faults caused a short circuit at the fault location and resulted in depressed voltages during the fault and until protective devices operated to clear the fault.

A BMI 8010 power quality disturbance analyzer was placed at the plant service entrance to record the power quality. Figure 1 is an example of a voltage sag measured at the plant that resulted in dropout of the motors.

Figure 1 – Plant Voltage during Fault
EVALUATING EQUIPMENT SENSITIVITY

A process controller was thought to be causing the motors to trip off-line. A voltage sag simulator was used to test the ride through capability of the temperature controller for voltage sags from 0.5-1000 cycles in duration. The controller was found to very sensitive to voltage sags, tripping at approximately 80% of nominal voltage regardless of duration (Figure 2). The controller was found to be more sensitive than the CBEMA (Computer and Business Equipment Manufacturers Association) curve for sags up to approximately 40 cycles in duration.

Figure 2 – Process Controller Ride-Through Capability
DETERMINING A SOLUTION

A ferroresonant or constant voltage transformer (CVT) was obtained to determine if it could improve the ride through capability of the temperature controller. CVTs work similar to a transformer being excited high on its saturation curve, so that the output voltage is not significantly affected by input voltage variations. CVTs are especially attractive for loads with relatively low power requirements and are constant. The process controller, now powered through a 120 VA CVT, was tested again. Voltage sags up to 1000 cycles in duration and down to 30% of nominal voltage did not affect the controller (Figure 3).

Figure 3 – Improved Ride-Through with CVT

To obtain ride through down to about 50% of nominal voltage, the CVT must be oversized, to approximately twice the size of the protected load. The output voltage of a CVT collapses to zero during a complete outage.

The disturbance analyzer was used to determine the performance characteristics of the CVT. Figure 4 shows a voltage sag recorded at the CVT input. No disturbance was triggered on the CVT output. Figure 5 shows the corresponding 24-hour strip chart for the CVT input and CVT output. The input strip chart clearly shows the voltage sag, while the output was very clean.

Figure 4 – Measured Voltage Sag at Input of CVT
Figure 5 – CVT Input and Output Strip Charts

Note: The dashed line in Figure 4 indicates the trigger point of the event and does not correspond to the dashed line in Figure 5. The event illustrated in Figure 4 can be seen just to the left of the dashed line in Figure 5.

Summary

Voltage variations, such as voltage sags and momentary interruptions are two of the most important power quality concerns for customers. Customers generally understand that interruptions cannot be completely prevented on the power system. However, they are less tolerant when their equipment mis-operates due to momentary disturbances that can be much more frequent than complete outages. These conditions are characterized by short duration changes in the rms voltage magnitude supplied to the customer. The impact to the customer depends on the voltage magnitude during the disturbance, the duration of the disturbance, and the sensitivity of the customer equipment.

Voltage variations and interruptions are inevitable on the power system. The most important of these variations occur during fault conditions on the power system. Since it is impossible to completely eliminate the occurrence of faults, there will always be voltage variations to contend with. Power quality complaints occur either when the customer has equipment that is very sensitive to these voltage sags and is critical to the overall process or when the frequency of occurrence of the interruptions or sags is interpreted as being unacceptable.

REFERENCES

M. McGranaghan, D. Mueller and M. Samotyj, “Voltage Sags in Industrial Systems,” IEEE Transactions on Industry Applications, Vol. 29, No. 2, March/April 1993.

J. Lamoree, J.C. Smith, P. Vinett, T. Duffy, M. Klein, “The Impact of Voltage Sags on Industrial Plant Loads,” First International Conference on Power Quality, PQA’91, Paris, France.

G. Beam, E.G Dolack, C. J. Melhorn, V. Misiewicz, M. Samotyj, “Power Quality Case Studies, Voltage Sags: The Impact on the Utility and Industrial Customers,” Third International Conference on Power Quality, PQA ’93, San Diego, CA, Nov 1993.


RELATED STANDARDS
IEEE Standard 1159

GLOSSARY AND ACRONYMS
CVT: Constant Voltage Transformer
CBEMA: Computer and Business Equipment Manufacturers Association

General Reference – Modeling for Voltage Variation Analysis

Published by Electrotek Concepts, Inc., PQSoft Case Study: General Reference – Modeling for Voltage Variation Analysis, Document ID: PQS0307, Date: February 4, 2003.


Abstract: Voltage variations, such as voltage sags and momentary interruptions are two of the most important power quality concerns for customers. Voltage variations and interruptions are inevitable on the power system. The most important of these variations occur during fault conditions on the power system. Since it is impossible to completely eliminate the occurrence of faults, there will always by voltage variations to contend with.

The document provides an overview of system modeling for voltage variation studies.

INTRODUCTION

Voltage variations, such as voltage sags and momentary interruptions are two of the most important power quality concerns for customers. Customers understand that interruptions cannot be completely prevented on the power system. However, they are less tolerant when their equipment misoperates due to momentary disturbances that can be much more frequent than complete outages. These conditions are characterized by short duration changes in the rms voltage magnitude supplied to the customer. The impact to the customer depends on the voltage magnitude during the disturbance, the duration of the disturbance, and the sensitivity of the customer equipment.

Voltage variations and interruptions are inevitable on the power system. The most important of these variations occur during fault conditions on the power system. Since it is impossible to completely eliminate the occurrence of faults, there will always by voltage variations to contend with. This chapter describes some of the concerns associated with short duration voltage sags and interruptions. Voltage swells can also be associated with fault conditions but these short duration overvoltages are usually not severe and problems are uncommon.

Power quality complaints occur either when the customer has equipment that is very sensitive to these voltage sags and is critical to the overall process or when the frequency of occurrence of the interruptions or sags is interpreted as being unacceptable.
On the utility system, protective systems are designed to limit damage caused by unusual events like faults or lightning strikes, and to localize the impact of such events to the smallest number of customers. This is accomplished with overcurrent protection devices, such as reclosers, sectionalizers, and fuses.

MODELING FOR VOLTAGE VARIATION ANALYSIS

Analysis Methods

Load Flow Programs – Load flow is the terminology used to describe the analysis of the flow of power from one or more sources to loads consuming energy. When the system is radial, power flows directly to the load. However, most systems today are more complex and contain a network of parallel and series paths over which power can flow.

Computer programs used to solve load flows are divided into two types – static and dynamic (real time). Most load flow studies for system analysis are based on static network conditions. Real time load flows are primarily used for optimization of generation, VAr control, dispatch, losses, and tie line control.

A load flow solution gives the power flow in all branches for a given set of operating conditions. It represents a steady state in which the influential parameters are in balance and a solution has been found. A load flow study is a collection of such solutions made when certain equipment parameters are set at different values.

A variety of system conditions can be evaluated, including contingency conditions, such as the loss of a transmission line, generator, transformer, or load. This type of analysis will often identify conditions that may cause equipment problems. In addition, analysis of this type is very useful for determining the optimum size and location of transmission and distribution capacitor banks. Digital computer programs are used extensively in load flow studies due to the complexity of the calculations involved.

Typical load flow program input and output data is provided in the following example.

Typical load flow program input and output data

Short Circuit Programs – A power system short circuit analysis can be performed to determine any of the following:

  • Calculation of system fault current duties (first cycle ratings, withstand ratings)
  • Selection and setting of protective devices
  • Evaluation of current flows for various system faults
  • Determination of bus voltages for various system faults

In general, short circuit programs use symmetrical component analysis techniques, thereby allowing the investigation of unsymmetrical faults and mutual coupling. Digital computer programs using symmetrical components are especially useful for simulating large complex networked systems.

Typical short circuit program input and output data is provided in the following example.

Typical short circuit program input and output data_1
Typical short circuit program input and output data_2

Study Procedure

The following is a suggested procedure for using a short circuit simulation program to perform fault studies:

  • Identify Study Objectives. The objectives will dictate the modeling requirements and the variables to be investigated.
  • Develop System Model. The extent of the system model depends on the objectives of the study. Very often, however, utilities maintain short circuit data files for the entire system.
  • Draw Connection Diagram and Label Buses. The bus labels will be used in the data file for identification.
  • Calculate Impedance of Component Models. Impedance for power system elements are determined and converted to a common base (i.e. % @ 100 MVA).
  • Run Solution Cases. The type of fault to be investigated must be determined before completing this step. Often, three-phase and single-line-to-ground faults are selected for protective relay settings. However, it may be desirable to simulate a fault involving unbalanced conditions.
  • Estimate Expected Results. This can be done from previous studies, from the literature, or from hand calculations. It is important to know what to expect from the simulation so that major problems can be identified quickly.
  • Sensitivity Analysis for Important Variables. Important variables from the simulation should be evaluated to determine their impact on results. These could include source strength, transformer size, line length, operating conditions, etc.
  • Solution Evaluation. Possible solutions include utility and customer options (power conditioning), as well as manufacturing design enhancements. Simulations and economic considerations are evaluated on a case-by-case basis to determine the option solution.

Computer Solution and Component Models

Variations in the fundamental frequency voltage can be evaluated with conventional analysis tools. Power flow programs provide system voltages as a function of load levels on the system. Fault programs (short circuit analysis) can calculate system voltage profiles during fault conditions for analysis of voltage sag concerns.

Analysis of large networks, such as those found in utility transmission and distribution systems, requires the use of computers and specialized programs. Hand calculations are suitable for estimating the characteristics of very simple circuits, but accurate calculation of voltage, power flows, or short-circuit currents throughout a utility system would be impractical without the use of a simulation program. Unlike power system transient analysis (using a program like the EMTP), options for fundamental frequency simulations are abundant. Many vendors provide short circuit and load flow programs and a number of utilities have even written their own simulation tools. In addition, due to the large number of system configurations and study types possible, no standards exist for specific models for all circumstances. One factor that may need to be addressed during a voltage variation study is model reduction (system simplification). All power system models will include some level of system reduction, such as equivalent impedance for a neighboring utility, however, no specific rules exist for an optimum method. Several factors that affect system reduction include:

  • model development and simulation time (not a significant factor)
  • limitations of the simulation program (i.e. number of busses)
  • problem definition
  • accuracy of system equivalents (it is the user’s responsibility to verify the model after each reduction)

Program documentation should be utilized for guidance on component modeling and simulation rules.

Voltage Sag Evaluations

The most general approach to voltage sag analysis (illustrated in Figure 1) would characterize the system voltage sag performance by analyzing the fault performance on both the transmission system and the distribution system. Computer calculations, using a short circuit analysis program, can be used to determine voltages around the system for any fault location. These calculations can be used to define an “area of vulnerability” for a particular customer. The likelihood of a fault can then be calculated from past fault records of the area, or from the fault performance of similar locations. Voltage sags and momentary interruptions are often the most costly power quality variations affecting industrial and commercial customers. Faults over a wide area of the power system can affect the operation of a facility that has sensitive equipment. Faults can occur on the transmission system or on the distribution system. For most facilities, both cases need to be evaluated to estimate the overall performance expected. For facilities that are supplied directly from the transmission level, only transmission faults usually need to be considered.

Figure 1 – Voltage Sag Evaluation Procedure

REFERENCES

Electrical Distribution-System Protection, Third Edition, Cooper Power Systems, Pittsburgh, PA, 1990.

The Impact of Voltage Sags on Industrial Plant Loads, J. Lamoree, J.C. Smith, P. Vinett, T Duffy, and M. Klein, Proceedings of the First International Conference on Power Quality (PQA ’91), Paris, France, October, 1991.

Voltage Sag Analysis – Case Studies, J. Lamoree, D. Mueller, P. Vinett, and W. Jones, Proceedings of 1993 IEEE I&CPS Conference, St. Petersburg, Florida.

Industrial and Commercial Power System Analysis – Brown Book, IEEE Standard 399-1990.


GLOSSARY AND ACRONYMS
ASD: Adjustable-Speed Drive
CT: Current Transformer
EMTP: Electromagnetic Transients Program
HVAC: High-Voltage Air Conditioning
MOV: Metal Oxide Varistor
PF: Power Factor
PWM: Pulse Width Modulation
TVSS: Transient Voltage Surge Suppressors

Analysis of Power Quality Factors: A Case Study of Windhoek, Namibia

Published by Aldrin Mubiana, Michael Mutingi, Member, IAENG, Gideon Gope, Charles Mbohwa.

Conference: Proceedings of the World Congress on Engineering and Computer Science 2016 Vol II WCECS 2016, October 19-21, 2016, San Francisco, USA.


Abstract—Power quality (PQ) is concerned with control of harmonic distortions, voltage variations, voltage reductions, power interruptions and voltage surges. Enterprises devices that are sensitive to power system fluctuations, voltage surge, sag and momentary outage on the supply lasting more than a few cycles could cause several equipment malfunctions, resulting in revenue losses. Analysis of power quality is critical. This paper presents a case study Windhoek, Namibia. First, PQ occurrences are explored. A survey is presented to assess the level of consumer satisfaction with services offered. Second, some PQ mitigation and techniques are proposed to capture PQ disturbances. A comparison of results captured from January 2007 to December 2009 and in 2014 is presented. The highest number of PQ disturbances were voltage swells (6954) followed by power dips (2295). In terms of the time lost due to PQ disturbance, outage or interruptions (990420) were leading, followed by swells (1684.27) and power dips (387.75). These results indicate significant PQ disturbances.

Index Terms—Power quality, power quality disturbances, quality analysis, quality factors, Windhoek, Namibia

I. INTRODUCTION

A number of power quality (PQ) monitoring programs and surveys have been conducted across the globe [1][2]. The information collected during these surveys reflect the quality levels expected in particular power systems [3][4]. Literature indicates that power dips, swells and interruptions are the leading causes of PQ disturbances [6]. As industrial automation and control system continues to evolve, the demand for computer systems will continue to increase. Electronic devices continue to be more sensitive to power quality variations and abnormalities. As such, research into power quality and mitigation of the associated disturbances is imperative.

A. Power Quality Disturbances

PQ disturbances are classified into two categories namely as short-duration variation category and long-duration variation category [15]. Short-duration voltage variations are caused by fault conditions, switching of large loads, which require high starting currents or loose connections in a system. Short duration voltage variations can seriously affect equipment, particularly variable frequency drives, computers, programmable logic controls, and motor contactors.

Long-duration variations can either be over-voltages or under-voltages. They are usually caused by switching processes and load changes on the system.

In practice, it is crucial to set up PQ standards. The purpose of the standards is to protect utility and end user equipment from failing or mis-operating when the voltage, current, or frequency deviates from normal. Standards provide this protection by setting measurable limits as to how far the voltage, current, or frequency can deviate from normal. By setting these limits, standards help utilities and their customers gain agreement regarding acceptable levels of service. In Namibia, most of the standards were adopted from South African Standards [16], which are in line with international standards. Some of the organizations responsible for developing PQ standards include the Institute of Electrical and Electronics Engineers (IEEE), American National Standards Institute (ANSI), National Institute of Standards and Technology (NIST), and National Fire Protection Association (NFPA), and International Electro-technical Commission (IEC) [17].

Though not possible to completely eliminate all PQ disturbances, these should be kept at the reasonable levels. Some of the techniques highlighted in the literature are the use of the dynamic voltage restorer (DVR), the use of plugin hybrid electric vehicle, the use of static series compensators [20] [21] [22] [23] [24] [25]. In this respect, a myriad of PQ measurement tools have been developed, including instruments that measure and display the basic electrical parameters of voltage, current, frequency, as well as the impedance of an electrical distribution system. These instruments include ammeters, voltmeters, multi-meters, oscilloscopes, flicker meters, electrostatic voltmeters, infrared detectors, radio-frequency interference and electromagnetic interference meters, harmonic and spectrum analyzers and various types of wiring and grounding testers [26] [27[28][29].

This study aimed at analyzing power quality disturbances affecting Windhoek, Namibia.

B. Previous PQ Monitoring Programs and Survey

Throughout the world there has number of PQ monitoring programs that has been completed. Some of the PQ surveys carried out internationally are as follows: (a) EPRI DPQ(Electric Power Research Institute Distribution PQ) project: general PQ levels on MV feeders of selected utilities in USA [1], (b) NPL (National Power Laboratory) PQ study: Voltage sags, swells and transients in selected Lower Voltage systems in Canada & USA[2], (c) CEA (Canadian Electricity Association) Survey: general PQ levels at main switch boards at distribution level[33], (d) UNIPEDE survey: survey of voltage sags and interruption statistics at selected substations throughout Europe [34] and (e) Pan European PQ Survey [4]: The information collected during these surveys depicts of what is expected in electrical environment[3][4].

Standard procedures and limitations in Iran were surveyed in a distribution system. Experimental data as well as clarifying tables and graphs were presented. The results were then discussed to evaluate the strength and weaknesses of applying standard limits when real observations were to be performed. This survey is relevant to this study because it shows use of statistical tools to quantify PQ disturbances [35].

Mohamed [36] conducted a PQ survey for best power options in Malaysia. This was a questionnaire based survey with the objective of identifying best power options that can be offered to industrial customers in Malaysia.

Islam [37] described PQ audits carried out at hospitals in Western Australia and Puerto Rico. The main PQ disturbances which were observed were voltage flicker, neutral currents, and harmonic distortion. Mitigation solution were then established based on the findings. This survey is relevant to this research because within the CoW there are hospital such as Katutura, Windhoek Central, Roman Catholic etc., and these hospital operates with the equipment’s which are sensitive to PQ.

C. Current Monitoring Process in Windhoek

As the Electricity Control Board (ECB) desires to improve the quality and reliability of power, the ECB installed a PQ monitoring system, with effective PQ monitoring and reporting features [7].

TABLE I – INSTALLED PQ INSTRUMENTS

The total number of PQ monitors installed and their locations are illustrated in the Table I, covering four REDs nambely, Nored, Cenored, Erongo, and CoW

II. RESEARCH METHODOLOGY

Fig. 1 presents our research methodology. Various visits to various institutions were undertaken to establish the availability PQ data. Amongst them that were approached were NamPower, City of Windhoek (CoW) and Electricity Control Board (ECB). Interviews were conducted during visits to NamPower, CoW and ECB. Some raw data was available at ECB, however, the data required further analysis and interpretation.

Fig. 1. Research methodology

All PQ data for substations were analyzed for PQ disturbances. In line with research objectives and the available PQ data, a PQ survey was conducted. An additional month was allowed to give ample time to the respondents. PQ disturbances were classified using MS Excel. Mitigation solutions were suggested based on this analysis.

The research was aimed at investigating the experiences and opinions of end user consumers on the effects of PQ disturbances and the malfunctions. The sample comprised mining, hospital, hotel/leisure, newspaper publishing, residential building, non-residential building and others. The questionnaire was distributed to 40 industrial customers. Data was collected using the questionnaire which was distributed randomly to selected customers across the country through an online web-based system.

III. CASE STUDY BACKGROUND

The Electricity Control Board (ECB) seeks to improve the quality and reliability of supply to the state. Between 2006 and 2010, ECB outsourced the project to the Regional Electricity Distributors (REDs) and the city of Windhoek to install power quality measuring instruments in their various selected substations [7]. In May 2011, ECB delegation visited all the REDs to assess the outcome of the quality of service. The delegation established that all the REDs were on track with regards to PQ monitoring, and most had installed a PQ monitoring system, with good PQ monitoring and reporting features. With this backdrop, key research questions are:

  • What are the factors affecting PQ in Windhoek?
  • What are existing standards for PQ in Namibia?
  • What are the solution/improvements for PQ?

In this respect, the specific research objectives are as follows:

  1. Investigate the specific PQ events affecting Windhoek substations;
  2. Carry out a pilot survey on PQ in order to assess the level of consumer satisfaction with the services offered;
  3. Analyze the PQ disturbances, and their effects on the supply network;
  4. Monitor the PQ disturbances and suggest suitable monitoring instruments.

The research suggests recommendations that if implemented will go a long way in solving PQ problems.

IV. LITERATURE REVIEW

PQ is defined as a set of electrical limitations that allows equipment to function in its intended manner without substantial loss of performance or life expectancy [8]. PQ study is needed for a number of reasons, either as power suppliers or as power consumers. Some of the main reasons are not limited to: i) Municipalities’ or REDs Perspective[9], (ii) Consumer’s Perspective[10], (iii) Equipment Manufacturers’ Perspective[11], (iv) Increase in Sensitive loads[12], (v) Increase in Nonlinear loads[12], (vi) Increase in Interconnected Power System[12], (vii) Source of Supply[13], (viii) Supply Verses End Use Issues[13] and ix) Increase in Generation of Renewable Energy[14]. PQ disturbances are classified into two categories namely as short-duration variation category and Long-duration variation category [15].

V. RESULTS AND DISCUSSIONS

PQ events data from 15 CoW’s substations and ECB was analyzed. Fig. 2 shows the total number of PQ disturbances per substation. Additionally, Fig. 3 presents the seasonal PQ disturbances. It can be seen that Shilunga, Elizenheim TRF1 and Jan Brand MiniSub Avis have consistently higher disturbances than Gloudina P Station Ludwigsdorf, Shilunga Cimberbasia and Gough Ms Rocky Crest.

Fig. 2. Total number of PQ disturbances per substation
Fig. 3. Seasonal PQ disturbances

While some sites clearly exhibit their worst PQ performance during the mid-winter months (June to August), this is not consistent across all sites. Gloudina P Station Ludwigsdorf had a definite peak in PQ index in the June – August quarter. Shilunga experienced its highest PQ levels between December and February (perhaps due to airconditioning load – the load on Shilunga zone substation is predominantly commercial-retail). The exact reasons for the relatively better or worse seasonal trend are unknown; however, it will be related to loading levels during the various seasons. Further investigation into these seasonal trends is an area of further research.

A. Response Analysis

Data collection occurred from March to May 2015. Participants were contacted telephonically followed by mailing the questionnaire. Out of 40 selected participants, 11 (28%) responded, which is acceptable for this type of research [5]. Data obtained from the respondents were analyzed using the SPSS software along with MS Excel. Respondents were mainly industrial customers from the mining industry, hospital, bank, hotels, manufacturing, newspaper, residential, non-residential and others.

Fig. 4. Percentage of respondents

TABLE II – NUMBER OF RESPONDENTS PER QUESTION

Fig. 4 shows the percentage of respondents per industry. The highest response is obtained from the others (34%), which includes office building and consumers, followed by mining and manufacturing (22%) that consist of food, plastic and paper industries, residential and non-residential building (11%). There were no (0%) responses from hospitals, bank, hotels and newspaper publishing.

Table II shows the number of respondents per question, detailing the answered and the skipped questions, together with other statistics such as the median, mean, and standard deviation.

B. Comparative Results Analysis

Although a large volume of data is not available for comparison, based on available literature, there is considerable evidence to suggest that sags, swells and interruptions were leading in previous results compared to current results.

TABLE III – UNITS FOR MAGNETIC PROPERTIES

Table III summarize the lost time in seconds and their respective frequencies. Due to the instruments malfunctions on some of substations (2014), not all data for current analysis were captured. In terms of time lost due to interruptions, previous results (2007-2009) show worse outages (990420 seconds) compared to the 2014 results with lost time of 72321 seconds. In terms of frequency of interruptions, previous results showed worse interruptions as compared to the current data. Substation Goreangab Busbar 1(583 406 s) was ranked the highest in terms of the time lost due to interruption, followed by CBD 2 (95210s) and Gough Ms Rocky Crest (69653s). Exact causes of power outages is not an area of this research, however it is assumed that it might be caused by aging of electrical equipment’s, damage to electrical transmission lines or poor maintenance.

Considering frequency of disturbances, previous results were leading with swells (6954) compared to 2014 results in which swells recorded only 14. Above all, there is a common denominator that voltage dips, swells and outages existed in both periods. This literally translates that there is a need to address these disturbances.

VI. CONCLUSIONS

From this study, a number of lessons and recommendations were derived, including the following:

  • There is need for further studies on the impact of PQ in terms of engineering, economy and environmental impacts. In Namibia, PQ data is a scarce.
  • There is need for comprehensive standards on PQ, especially as the nation enters deregulation market.
  • Since compact fluorescent lamps are nonlinear loads which inject harmonics in an electrical system, causing network voltage distortions, further research is necessary.
  • There is a need to quantify the cost incurred as a result of PQ disturbances.
  • Electricity providers must provide detailed information about their PQ compliance to customers.
  • The scope of continuous PQ monitoring programs should be extended to regional electricity distributors.

ACKNOWLEDGMENT

The authors would like to than the NamPower, Windhoek, Namibia, for their assistance in providing relevant information.

REFERENCES

[1] Sabin, D.D., Grebe, T.E., and Sundaram, A., “RMS Voltage variation statistical analysis for a survey of distribution system power quality performance,” IEEE PES Winter Meeting, 1999.
[2] Dorr, D.S., Point of utilization power quality study results, 1995.
[3] Gosbell, V.J., Integral Energy Power Quality Centre – Newsletter No.5. University of Wollongong, 2001.
[4] Targosz, R. and Manson, J., “Pan European LPQI Power Quality Survey”, Vienna, Italy, 2007.
[5] G. Van Dessel, “How to estimate your population and survey sample size”, 2013.
[6] A. Mohamed, H.Shareef, M.A. Hannan, A. Ayob, R. A. Begum, and M. F. Faisal, ‘Power Quality Survey for Premium Power Options in Malaysia’, 2012.
[7] Electricity Control Board, Electricity Control Board Annual Report. 2011.
[8] Parimal S. Patel, “Improved control method of UPQC for unbalanced and non-linear load conditions,” India, 2015.
[9] Sakthivel K. N., Das S. K., and Kini K. R., “Importance of quality AC power distribution and understanding of EMC standards IEC 61000-3-2, IEC 61000-3-3 and IEC 61000-3-11,” vol. 8th International Conference on Electromagnetic Interference and Compatibility (INCEMIC 2003), 423-30. 2003a.
[10] Brauner G. and Hennerbichler C., “Voltage dips and sensitivity of consumers in low voltage networks, Part 1: Contributions, CIRED” IEEE International Conference and Exhibition on Electricity Distribution, vol. 5 No. 482, 2001.
[11] Romano C. and Perli G., “Technological evolution of MV equipment technological evolution”, 18th International Conference and Exhibition on Electricity Distribution (CIRED 2005). 2005.
[12] S. Jain, S. S.Thakur, and.S. P. Phulambrikar, “Improve Power Quality And Reduce The Harmonics Distortion Of Sensitive Load,” 2012.
[13] Energy @ Work for the CEA and Technologies Inc., Power Quality-Energy Efficiency Reference Guide.
[14] E. Vilchez and J. Stenzel, “Impact of Renewable Energy Generation Technologies on the Power Quality of the Electrical Power Systems,” 22nd International Conference and Exhibition on Electricity Distribution (CIRED 2013), 10-13 June 2013, pp. 1-4
[15] Nor Asrina Binti Ramlee, Detection of Voltage Disturbances in Power Quality Using Wavelet Transforms. Universiti Tun Hussein Onn Malaysia, 2012.
[16] Electricity Control Board, Quality of Supply and Service Standards. 2004.
[17] J. Arrillaga, N.R Watson, and S. Chen, Power Systems Quality Assessment. John Wiley & Sons, 2000.
[18] ECB Namibia: seeking independent power producers, 2004.
[19] D. Francis and T. Thomas, “Mitigation of voltage sag and swell using dynamic voltage restorer,” IEEE International conference, Kottayam, 2014.
[20] D. Rajasekaran, S. Sekhar Dash, and P. Vignesh, “Mitigation of voltage sags and voltage swells by Dynamic voltage restorer,” IET International conference, Bangalore, 2011.
[21] A. Ashourpouri, M. Dargahi, and S. Nabavi Niaki, “Residential voltage dip and swell mitigation using Plug-in Hybrid Electric Vehicle in smartgrid,” IEEE power engineering conference, Hobart, 2013.
[22] M. Eskander and S. Amer, “Mitigation of voltage dips and swells in grid-connected wind energy conversion systems,” IEEE conference, Fukuoka, 2009.
[23] H. Awad and F. Blaabjerg, “Mitigation of voltage swells by static series compensator,” IEEE 35th annual conference on Power Electronics Specialists Conference, Vol.5, 2004, pp. 3505 – 3511.
[24] A. Pathan, S. Vanamane, and R. Chile, “Different control techniques of Dynamic Voltage Restorer for power quality problems,” IEEE International conference, Hougly, 2014.
[25] V. Jayalakshmi and N. Gunasekar, “Implementation of discrete PWM control scheme on Dynamic Voltage Restorer for the mitigation of voltage sag /swell” IEEE International conference, Nagarcoil, 2013.
[26] Paun M. Power Quality Monitoring. Task Force Power Quality Monitoring Kevin Niall (IE) Chair: A EURELECTRIC comments paper, 2009.
[27] Z. Kokolanski, M. Srbinovska, A. Simevski, C. Gavrovski, and D. Dimcev, “Power Quality Monitoring and Power Measurements by Using Virtual Instrumentation,” vol. ELECTRONICS, VOL. 13, NO. 1. 2009.
[28] Bilik P. “Internet-Ready Power Network Analyzer for Power Quality Measurements and Monitoring,” 2012.
[29] D. Divan, W. Brumsickle, and J. Eto, “A New Approach to Power Quality and Electricity Reliability Monitoring – Case Study Illustrations of the Capabilities of The I-GridTM System”, April. 2003.
[30] Key, T., “Diagnosing power quality – related computer problems,” IEEE Transactions on Industry Applications, Vol. 15, No.4 vols. 1979.
[31] G.T. Heydt, G.G Karady, B. Cummings, and J. Tang, “Improved application of power acceptability curves and their application to certain three-phase loads,” Journal of Electrical Machines and Power Systems, Vol. 27. 1999.
[32] M.A.S, Jamali S, and N. Ghaffarzadeh, Detection and classification of power quality disturbances using discrete wavelet transform and wavelet networks. 2010.
[33] D.O. Koval, and Leonard, J.J., Rural power profiles. 1994.
[34] Electromagnetic compatibility – Part 2.8: Environment– Voltage dips and short interruptions on public electric supply systems with statistical measurement Results, IEC Draft Technical Report – Edition 1.0, IEC 61000-2-8:2004, vols. 2002.
[35] H. Mokhtari, S. Hasani, and M. Masoudi, “Power Quality Survey in a Distribution System, Standard Procedures and Limitations,” 2007.


Manuscript received July 16, 2016, revised August 01, 2016.
A. Mubiana was enrolled as a student in MEng Industrial Engineering at the Namibia University of Science and Technology, P Bag 13388, Windhoek, Namibia.

M. Mutingi is a Senior Lecturer at the Namibia University of Science Technology, P Bag 13388, Windhoek, Namibia. He is also a Visiting Senior Research Associate at the Faculty of Engineering and the Built Environment, Johannesburg, South Africa(email: mmutingi@nust.na).
G. Gope is a Lecturer at the Namibia University of Science Technology, P Bag 13388, Windhoek, Namibia (ggope@nust.na).

C. Mbohwa is a Professor with the Faculty of Engineering and the Built Environment, Johannesburg, South Africa (cmbohwa@uj.ac.za)


ISBN: 978-988-14048-2-4
ISSN: 2078-0958 (Print); ISSN: 2078-0966 (Online)

Source URL: https://www.researchgate.net/publication/332320019_Analysis_of_Power_Quality_Factors-A_Case_Study_of_Windhoek-Namibia

Distribution Substation Voltage Variation Measurement Data Evaluation

Published by Electrotek Concepts, Inc., PQSoft Case Study: Distribution Substation Voltage Variation Measurement Data Evaluation, Document ID: PQS1007, Date: October 15, 2009.


Abstract: This case study presents a voltage variation data analysis for a 12.47 kV substation monitoring location for a three-month period. The analysis included trends of the rms voltage and unbalance and statistical analysis of the rms variation events. The results of the analysis showed that most of the events were short duration voltage sags. Constant voltage transformers, coil-lock devices, magnetic synthesizers, and a number of power-electronic based power conditioners may be used for protection against voltage sag events.

INTRODUCTION

A voltage variation measurement analysis case study was completed for the 12.47 kV utility system shown in Figure 1. The utility substation included a 20 MVA, 161 kV/12.47 kV step-down transformer and a number of distribution feeders that supplied a mix of residential, commercial, and light industrial customers. In addition, one of the feeders had a switched 600 kVAr power factor correction capacitor bank.

MEASUREMENT RESULTS

The three-month monitoring period was from January 1, 2009 thru March 31, 2009. The power quality instrument used for the voltage variation measurements was the Dranetz-BMI Encore Series™. The instrument samples voltage at 256 points-per-cycle, current at 128 point-per-cycle, and follows the IEC 61000-4-3 method for characterizing measurement data. The measurement and statistical analysis was completed using the PQView® program.

Figure 1 – Illustration of Oneline Diagram for Measurement Data Evaluation

Figure 2 shows the measured rms voltage regulation trend on the 12.47 kV substation bus during the three-month monitoring period. One pole-mounted 600 kVAr distribution feeder capacitor bank was switched on-and-off each day using time clock controls in an attempt to maintain a relatively constant voltage profile. Statistical analysis of the 25,520 individual steady-state measurements yielded a minimum rms voltage of 12.427 kV, an average voltage of 13.022 kV, and a maximum voltage of 13.499 kV. In addition, the CP95 value was 13.277 kV (106.5% of nominal). CP95 refers to the cumulative probability, 95th percentile of a value.

Figure 2 – Measured Substation Bus Voltage Trend

Figure 3 shows the measured negative sequence voltage unbalance trend on the 12.47 kV substation bus during the three-month monitoring period. Statistical analysis of the 25,520 individual steady-state measurements yielded a minimum value of 0.244%, an average value of 0.492%, a maximum value of 0.894%, and a CP95 value of 0.629%.

Voltage unbalance is a steady-state quantity defined as the maximum deviation from the average of the three phase voltages or currents, divided by the average of the three phase voltages or currents, expressed in percent. Voltage unbalance can also be quantified using symmetrical components. The ratio of the negative sequence (or zero sequence) component to the positive sequence component is used to specify the percent unbalance. The negative sequence (or zero sequence) voltages in a power system generally result from unbalanced loads causing negative sequence (or zero sequence) currents to flow.

The primary source of voltage unbalance less than two percent is unbalanced single-phase loads on a three-phase circuit. Voltage unbalance can also be the result of capacitor bank anomalies, such as a blown fuse on one phase of a three-phase bank. Severe voltage unbalance (greater than 5%) can result from single-phasing conditions. Voltage unbalance is most important for three phase motor loads. ANSI Std. C84.1 recommends that the maximum voltage unbalance measured at the service entrance under no load conditions should be 3%. Voltage unbalance greater than this value can cause significant motor heating and subsequent failures. Unbalance detection circuits may be used to protect induction motors from this condition.

Figure 3 – Measured Substation Bus Negative Sequence Unbalance Trend

Solutions to voltage unbalance include balancing single-phase loads (both utility and customer) on three-phase circuits, minimizing system impedance differences (e.g., transmission line transposing), and utilizing power electronic-based power conditioning devices, such as static VAr compensators and power line conditioners.

This case summarizes an investigation of rms voltage variations. Voltage variations, such as voltage sags and momentary interruptions, are often the most important power quality concern for customers. These conditions are characterized by short duration changes in the rms voltage magnitude supplied to the customer. The impact on the customer depends on the voltage magnitude during the disturbance, the duration of the disturbance, and the sensitivity of the customer’s equipment. Although utilities continuously strive to provide reliable power to their customers, a number of normal operating conditions may cause voltage variation events.

Voltage sags and momentary interruptions are inevitable on the electric power system. Many of these variations occur during faults on the power system, and since it is impossible to eliminate the occurrence of faults, there will always be voltage variations on customer systems. Other sources of voltage variations include unbalance, induction motor starting, and voltage flicker. Table 1 shows the rms variation event summary listing for the three-month monitoring period. The table shows the date-and-time for each event, as well as the phase-to-neutral voltage magnitude in both volts (kV) and per-unit and the event duration in both seconds and cycles.

Figure 4 shows the corresponding waveform and rms characteristic for the worst-case voltage sag event measured during the monitoring period (Event #9). The magnitude of the voltage sag was 44.3% and the duration was 5 cycles. The voltage sag occurred during a thunderstorm. It was caused by a short-duration fault and subsequent fuse clearing on one of the distribution feeder branch circuits.

Table 1 – Event Listing for Measured RMS Variations

Event NumberEvent TimeMagnitude (kVφN)Magnitude (per-unit)Duration (sec)Duration (cycles)
11/8/2009 11:47:27.33005.5870.7760.0583.5
21/22/2009 06:25:56.42005.8630.8140.0583.5
31/27/2009 10:02:34.21405.9430.8250.0754.5
41/27/2009 11:23:22.89306.1360.8520.0674.0
51/28/2009 11:12:27.89205.6310.7820.0925.5
62/1/2009 07:55:20.59006.4010.8890.17510.5
72/11/2009 15:27:45.33406.1460.8540.1589.5
83/13/2009 12:50:27.65605.1320.7130.0754.5
93/14/2009 09:39:49.06703.1890.4430.0835.0
103/14/2009 10:59:51.24003.7080.5150.1177.0
113/24/2009 15:22:58.98106.4360.8940.1086.5
Figure 4 – Measured Substation Bus Voltage Sag Event

When there are a significant number of events, it is generally not desirable to show the results for each individual measurement. One method for summarizing rms variation event data is to graph the magnitude and duration data on one single scatter plot. This method may also include an equipment tolerance (e.g., CBEMA) overlay. Figure 5 shows a summary of the events listed in Table 1 along with a CBEMA overlay. The graph also shows the number of events that are outside the equipment sensitivity characteristic.

Figure 5 – Measured Bus Voltage RMS Variation Magnitude Duration Characteristic

Voltage variation indices may be used to assess the service quality for a particular customer or utility system. One commonly used benchmarking value is known as SARFI, which stands for System Average RMS Variation Frequency Index. SARFI represents the average number of specified rms variation measurements that occurred over the assessed period. For example, SARFI70 is a measure of the number of voltage sags that can be expected with a minimum voltage below 70%. Another popular use of SARFI is to define the threshold as a curve. For example, SARFICMEBA would represent the number of rms variation events outside the commonly used CBEMA voltage tolerance envelope. The CBEMA curve was originally developed by the Computer Business Equipment Manufacturers Association. The curve was first published in IEEE Std. 446-1995.

The calculated SARFI values for the three-month monitoring period are summarized in Table 2. The SARFI90 value of eleven can be determined by counting the number of events in Table 2 with a voltage magnitude below 90%. In addition, the SARFICMEBA value of four that is shown in the table corresponds to the data previously shown in Figure 5.

Table 2 – Summary of RMS Voltage Variation SARFI Values

SARFI-CBEMASARFI-ITICSARFI-SEMISARFI-90SARFI-70SARFI-50SARFI-10
42111210

Voltage sags are momentary undervoltage conditions. They are characterized by a decrease in the rms voltage (between 0.1 and 0.9 per-unit) at the power frequency for a duration of 0.5 cycles to 1 minute. They are typically caused by a fault somewhere on the power system. The voltage sag may occur over a significant area while the fault is actually on the system. As soon as a fault is cleared by a protective device (e.g., fuse), voltage generally returns to normal on most parts of the system, except the specific line or section that was actually faulted. The voltage magnitude during the fault is influenced by system characteristics, system protection practices, fault location and type, and system grounding.

Figure 6 shows the rms variation magnitude histogram for the three-month monitoring period. The cumulative frequency characteristic shows that a majority of the events had voltage magnitudes greater than 70%. Figure 7 shows a three-dimensional cross tabulation view of the rms variation measurements captured during the monitoring period and summarized in Table 1. The figure illustrates that a vast majority of the events had voltage magnitudes between 70-90% and durations that were less than five cycles.

The measurement results and customer equipment sensitivity were used to determine the appropriate mitigation alternatives. Equipment sensitivity is the primary factor that determines if a voltage variation event will disrupt a customer load or process. Some loads may be sensitive to just the magnitude of a voltage variation event, while other loads may be sensitive to both the magnitude and duration of the event.

Figure 6 – Measured Bus Voltage RMS Variation Magnitude Histogram
Figure 7 – Measured Bus Voltage RMS Variation Magnitude-Duration Summary

Power conditioning alternatives for voltage sags and momentary interruptions include a number of alternatives for utilities, customers, and equipment manufacturers. Determining which devices of an electrical load or process are sensitive to voltage variations will allow the selection of the appropriate type and rating for the power conditioner(s).

Modifications to the design of sensitive customer equipment may be the least expensive option, however, it is not always practical to implement. Modifying the utility system may also not be practical and may be, indeed, quite expensive. Power conditioning equipment, applied between the utility system and sensitive customer equipment, may be the most cost effective solution for voltage variation problems.

It is possible to make the equipment being used in customer facilities less sensitive to voltage sags and momentary interruptions. Clocks and controls with low power requirements can be protected with a small battery or large capacitor to provide greater ride-through capability. Motor control relays and contactors can be selected with less sensitive voltage sag thresholds. Controls can be set less sensitive to voltage sags unless the actual process requires an extremely tight voltage tolerance. This solution requires coordination with equipment manufacturers but the trend seems to be in the direction of increased ride-through capability. For instance, most programmable logic controllers use switched-mode power supplies that have a ride-through capability of about four cycles. Therefore, it should not be necessary to trip these controllers under short voltage sag conditions.

Since a vast majority of the measured rms variations events were short-duration voltage sags, the residential and commercial customers can use uninterruptible power supplies for their power conditioning solution. An uninterruptible power supply (UPS) is a power-electronic based device that provides a continuous voltage to a load by supplying power from a separate source when utility power is lost. A UPS is often used to protect computers, telecommunication equipment, or other critical electrical equipment where an unexpected power disruption could cause severe business disruption or data loss. A standby UPS (a.k.a., off-line UPS) with a ride-through range of 5 to 20 minutes will protect the sensitive equipment from most of the voltage sag events. This type of device is the most common configuration for commodity UPS units available at retail stores for the protection of small computer and entertainment system loads.

Industrial customer mitigation options include constant voltage transformers (CVTs), coil-lock devices, uninterruptible power supplies, magnetic synthesizers, dynamic sag correctors (DySC), dynamic voltage restorers (DVR), and motor-generator sets. Customers have the option to protect their equipment from voltage variation phenomena at a number of locations, including the point-of-entry and point-of-use. Generally, a combination of point-of-entry and point-of-use devices will provide the greatest level of protection.

Many voltage sag conditions for the industrial customers can be addressed by using constant voltage transformers. CVTs are especially attractive for constant, low power loads. Variable loads, especially with high inrush currents, present more of a problem for CVTs because of the tuned circuit on the output. A typical CVT circuit is shown in Figure 7. CVTs are an attractive option because they are relatively maintenance free, with no batteries to replace or moving parts to maintain. They are particularly applicable for industrial process control devices such as programmable logic controllers, motor starter coils, and the electronic control circuits of adjustable-speed drives. The negative aspects of CVT applications are efficiency (heat), size, weight, and availability in limited rating ranges. In addition CVTs have difficulty with dynamic and harmonic rich loads often requiring significant over rating. Over rating provides better performance and sag correction, but with a penalty of less efficiency, size, weight, and cost.

Figure 8 – Schematic for a Constant Voltage Transformer
SUMMARY

This case study presents a voltage variation data analysis for a 12.47 kV substation monitoring location for a three-month period. The analysis included trends of the rms voltage and unbalance and statistical analysis of the rms variation events. The results of the analysis showed that most of the events were short duration voltage sags. Constant voltage transformers, coil-lock devices, magnetic synthesizers, and a number of power-electronic based power conditioners may be used for protection against voltage sag events.

Voltage sag protection may be implemented on a single coil or piece of equipment. Correction may also be chosen for large portions of a facility or even for the entire facility. The selection of voltage sag mitigation will consist of engineering aspects as well as a cost versus benefit evaluation. The most cost-effective customer power conditioning solutions for this case were uninterruptible power supplies and constant voltage transformers.

The case showed that power quality monitoring can be used to characterize voltage variations at various locations on utility and customer power systems. The length of the monitoring period is dependent on the nature of the power quality problem. For example, voltage flicker trends may be collected over several days or weeks, while voltage sag and momentary interruption levels may need to be monitored for months, or even years to show the influence of seasonal variations. The monitoring period for this study was three months. Additionally, the objectives of a monitoring program determine the choice of measurement equipment, method of collecting data, disturbance thresholds, data analysis requirements, and the overall effort required.

REFERENCES

  1. IEEE Recommended Practice for Monitoring Electric Power Quality,” IEEE Std. 1159-1995, IEEE, October 1995, ISBN: 1-55937-549-3.
  2. IEEE Recommended Practice for Emergency & Standby Power Systems for Industrial & Commercial Applications (IEEE Orange Book, Std. 446-1995), IEEE, ISBN: 1559375981.
  3. American National Standard for Electric Power Systems and Equipment – Voltage Ratings (60Hz), ANSI Std. C84.1-2006, National Electrical Manufacturers Association, December 2006.

RELATED STANDARDS
IEEE Std. 1159, ANSI Std. C84.1, IEEE Std. 446

GLOSSARY AND ACRONYMS
ASD: Adjustable-Speed Drive
CF: Crest Factor
DPF: Displacement Power Factor
PF: Power Factor
PWM: Pulse Width Modulation
THD: Total Harmonic Distortion
TPF: True Power Factor

Electric Power Quality and Ship’s Safety

Published by J. Mindykowski2, E. Szmit1, T. Tarasiuk2
1 Polish Register of Shipping, Electrical and Automation Department
2 Department of Marine Electrical Power Engineering of Gdynia Maritime University


1.Introduction

The issue of electric power quality onboard ships has seemed of utmost importance, in particular nowadays when a great progress in implementation of electric drives for ship’s thrusters, propellers and other smaller drives is evident. Ship’s electric power systems are isolated power systems. Similar systems are installed on aircraft, oil platforms and small islands, in industrial plants with seasonal character of operation and also as emergency electric supply systems in banks, hospitals, hotels, large supermarkets and skyscrapers [1], [2]. Characteristics of those systems are: scarce in other cases proportion of single consumer power to electric source power (some consumer powers are often comparable to generator power supplying them) [3] and relatively high short-circuit impedance of generators installed in the systems under consideration [1]. Finally, electromagnetic disturbances observed in isolated power systems are more serious than those observed in large connected systems in their normal operation. What is unique in ships power systems ? Answer is simple. System is installed on mobile object – the ship – and simultaneously is deciding for its operational control. Effects of incorrect system operation can be very serious and consequences of ship’s casualties are known very well from the news. Indeed, question of the electromagnetic disturbances determining electric energy quality in ship’s power systems has not only technical aspect and / or vessel operational safety. Paltry quality of electrical energy on ships has also its economic dimension. In spite of relatively not big power (normally no more than few MVA) of a single electric plant, large number of ships (30 395 of 1000 gt and above as of 1.01.2003 [4]) shows the measure of presented problem excellently.

2.Electromagnetic disturbances in ship’s power networks

Wide spectrum of electromagnetic disturbances, radiated and conducted, is present in the ship’s electric networks causing disorder in their element operation. Typical conducted, and particularly prolonged disturbances, as:

  • voltage and frequency variations;
  • voltage asymmetry;
  • distortions caused by harmonics, inter-harmonics, transient pulse disturbances;
  • improper distribution of active and reactive power between generating sets working in parallel.

The disturbances introduce many difficulties into operation of the ship’s crew and owner’s technical service, independently on basic value – the ship’s safety. Electric and electronic devices, the power network elements are the “causes” of disturbances and at the same time the “victims” of the waveform distortions. Ragged design and carrying out of installation give rise to the EMC disturbances, often causing the asymmetry and voltage level changes. Switching process in distribution switchgears and electrical consumers and also overvoltage during fuse blow out were traditionally causes of signal distortion in power network. Presently distortions are caused by still more popular power electronic converting systems used in machinery auxiliary drives, but not only. Drives consisting of power converters are applied to thrusters, big technological consumers and main propellers of the vessels. Marine generating sets are “weak” power sources (with 15-20 % impedance) compared to “stiff” sources (4-6 % impedance) more common in land industrial applications.

Converters of electrical power in co-operation with so weak power sources generate harmonic and inter-harmonic distortions causing inadmissible disturbances in power system. Distortions 15% and even 20% and above were observed onboard ships many times [5], [6], [7].

The examples of all above mentioned disturbances, i.e. voltage and frequency deviations, voltage asymmetry and distortions of voltage waveform are shown in Fig 1 to 5. Presented examples are the original results of some tests which were carried out on ships by personnel of Marine Electrical Power Engineering Department of Gdynia Maritime University. The test purpose was to settle the real voltage parameters (in fact its quality), supplying Main Distribution Boards of examined ships.

Fig. 1 represents variations of voltage rms value during the start-up and running of the thruster driven by 1,3 MW electric motor, when two generators with power 1,75 MVA each operated parallel. In that case overload of ship’s electric power plant had caused automatic switching off a less important services and next switching on the third generator with the same power, for parallel operation. Fig. 2 shows frequency variations for that case accordingly.

Fig. 1 Voltage variations during starting and running of the thruster [3]
Fig. 2. Frequency variations during starting and running of the thruster [3]

Voltage asymmetry in the system with nominal parameters Un=440 V and fn=60 Hz is shown in Fig. 3. Presented voltage asymmetry is so interesting because one can see harmonic distortion and pulse interference, too. Phenomena observed in that example were caused by shaft generator with power converter working on ship’s network with simultaneous failure of harmonic filter (3-phase LC passive filter).

Rys. 3 Voltage asymmetry (3,7%) [8]

Next two presented samples are also from the ship equipped with shaft generator working in network through power converter. However in that case all system components were operating correctly. Fig. 4 shows voltage inter-harmonic and harmonic distortion, e.g. interharmonic quantity is ca. 0,4% at frequency ca. 150 Hz when total harmonic distortion THD amounts 4,4% on Main Distribution Board 220 V bus-bars. It means that between power converter and the connection point of measuring apparatus, transformer attenuating commutation over-voltage was present. Fig. 5 shows the same measurement however measuring instrument was connected directly to 440 V bus-bars. In that case one can see the notching caused by commutation over-voltage in power converter. The THD coefficient amounts 13,5% for that case.

Fig. 4. Un=220V voltage inter-harmonic and harmonic distortion [9]
Fig. 5. Un=440V voltage pulse interference [9]

Finally, it is worth to present an example of distribution of active power between generating sets working in parallel. Such an example registered during ship manoeuvring has been shown in Fig. 6. There have been two generating sets working in parallel during analysed phenomenon. The active power load of generating set no 2 (PG2) has been depicted by bold line.

Fig. 6. Exemplary changes of active power load of respective generating sets working in parallel during ship manoeuvring.

It should be stressed that improper distribution of the active (as well as reactive) load can be hazardous. It may cause artificial overload and real collapse of whole supply system (switching operating generators off). The possible risk, especially during manoeuvring, can be hardly overstated.

The last of presented examples (Fig. 6) results from joint research of Marine Electrical Power Engineering Department of Gdynia Maritime University and Electrical and Automation Department of Polish Register of Shipping.

3. Harmonic distortions cause a lot of damages in electrical power system

Harmonic distortions can cause following typical damages to and malfunction of most elements and units of ship’s power network [10]:

Electric power sources:

  • Overheating and, in result, damage to bearings, winding and sheets packages of generators, because of a premature thermal ageing of insulation.

Electrical power consumers:

  • Overheating of the stator and rotor of fixed speed electric motors, risk of bearing damage because of the motor high temperature, additional rises of insulation temperature and its premature thermal ageing. A special hazard is present in the case of explosion proof motors operating in explosion hazardous areas. Unintentional tripping of circuit-breaker protections, interference with all control, electrical and electronic systems including radio- navigation and communication equipment, lighting, etc.

Electrical energy networks:

  • Overheating of cables as result of decreased ability to carry rated current because of reduction of effective cable cross section area by so called skin effect, also risk of cable damage due to resonance.
  • Overheating and premature thermal ageing of transformer sheets packages and winding insulation.
    It is important that harmonic distortion are present together with voltage and frequency variation and also voltage asymmetry, most frequent. Fig. 3 shows it. Negative synergy effect of above mentioned phenomena can be expected for many power consumers. That kind of interference synergy was discovered in tests of temperature rises in induction motor windings at different supply conditions [11].
4. Harmonic distortion – the past and the present time

Ian C Evans, author of “Harmonic Mitigation for AC Thruster & Small Propulsion Drives”, advises that one of the classification societies have noted 24% voltage distortion (UTHD) in an offshore installation tested. He also says that voltage distortion of 12 – 19 % is relatively common, albeit not continuous in these installations, where up to 85% of the electrical load consists of electric drives [6, 7]. Distortion level measured on ships’ bus-bars by Department of Marine Electrical Power Engineering of Gdynia Maritime University are described in [3, 9, 11] and confirm international observations. However, the classification societies determined harmonic distortion limit on 5-10% level recognising possibility of serious faults of the electric network and, in result, general safety of the ship [14, 15].

Table 1. Results of voltage distortions measured in different vessels [5], [6], [7], [9]


It shows, a gap is between ships practice and classification societies attitude. Problem is that, classification societies determining harmonic level limits did not assign the method of their testing onboard. However, the limits of electric power disturbances were stated when the risk caused by power-electronic elements and systems was not present. DC driving systems not generating so serious interference had dominated on ships at that time

5. Harmonic mitigation – the present time and the future

Global forecasts give information about several times growth of power electronic (measured in the million USD of installed “electric” propeller value or “electric” ship’s number) [7]. It enhances the issue.

Fig. 7 Global forecast of ship’s electric drives application

Individual classification societies have to revise their rules in connection with the fast development of the AC drives introducing many of harmonic and inter-harmonic distortions. These is the opinion of classification societies, marine electricians and electrical equipment producers. Recently some modifications of industrial standards were done. Many of the IEC and IEEE standards concerning permissible levels of electrical power parameters determining its quality and measuring methods are present now [16], [17], [18]. Polish and international standard PN-IEC 60092-101 “Electrical installations in ships – Part 101: Definitions and general requirements” has also set up many limits of quality parameters of electrical power [19]. Some exemplary parameters of that standard are placed in Table 2

Table 2. Chosen quality parameters of electrical power stated by PN-IEC 60092-101 standard


However none of classification societies have implemented many of that parameters into their rules up to now. Continuous monitoring of electric power quality is not also carried out onboard, presently. Sometimes some observations, occasional measurements are being carried out but they are not adequate solution because of large variation of power quality parameters during ship’s operation. It is worth to note that some producers of power system control devices are introducing some means of power quality verification but it can not be considered as a global solution.

The expected development of electric drives for ship propulsion is the next and new challenge for marine specialists. Therefore, it is necessary to introduce special requirements for electromagnetic interference prevention (by correction of energy parameters in ship’s electrical power system) and their effects (by increasing of consumers immunity) and also to monitor power quality in ship’s networks. Possibility of current control has appeared with the development of transducer technology and advanced method of electrical signal processing and also specialised devices for real time data processing. High yet prices of suitable systems are decreasing continuously (cost of signal processor amounts from a few to a several hundred dollars) [10].

6. Conclusion

Tests, studies and analysis carried out during research onboard ships indicate necessity of complex solution of power quality problem in ships power systems, unequivocally. Specific means to prevent against electromagnetic disturbances and their effects are required. It may be done by correction of power quality in ship’s power systems and improvement of the electric consumers’ EMC immunity. On the other hand monitoring of electrical power quality is needed. Therefore problem of electrical power quality and its assessment should be one of priority in designing, construction, classification and utilisation of ship’s electric systems, now and in the future. It is evident that on the one hand the matter applies to shipyards and ship’s owners and on the other to classification societies surveying ships production and exploitation processes [20].

Suitable solution of that problem requires sufficient knowledge and experience. The preparation of appropriate staff for shipyards, owners and classification societies, as well as research of new methods and ways to limit the influence of poor power quality on the effective economically and safe operation of ships are the tasks of maritime universities.

Bibliography:
[1] De Abreu J.P., De Sa J.S., Prado C.C.: Harmonic voltage distortion in isolated electric systems. 7th International Conference “Electrical Power Quality and Utilization” Kraków, 17-19 September 2003, pp. 469-472.
[2] Dzwonkowski A.: Niezawodność zasilania wybranych obiektów przemysłowych o sezonowym charakterze pracy. Przegląd Elektrotechniczny Nr 6/2003, pp.452-456.
[3] Tarasiuk T.: Analiza metod i układów do wyznaczania wskaźników jakości energii w okrętowych systemach elektroenergetycznych. Rozprawa doktorska, Politechnika Gdańska, Gdańsk 2001.
[4] Shipping Statistics and Market Review Institute of Shipping Economics and Logistics Nr 4, April 2003
[5] Reinecke H., Schild W.: Harmonics in main electric supply systems with semiconductor rectifiers and subsequent methods of compensation. IMECE’91 China, pp. 1-10.
[6] Evans Ian C: Harmonic Mitigation for AC Thrusters & Small Propulsion Drives. The Harmonic Solutions Co. Uk.
[7] Evans Ian C: Electric Ships, The future is electric, Driving ahead – the progress of electric propulsion The Motor Ship, September 2003, pp. 28-33.
[8] Dudojć B., Mindykowski J.: Pomiary diagnostyczne filtrów harmonicznych jako instrument do poprawy jakości energii w sieciach okrętowych. Prace Naukowe Katedry Elektroenergetyki Okrętowej; Zeszyt monograficzny 1997, pp. 120-131.
[9] Mindykowski J., Szweda M., Tarasiuk T.: Measurement equipment for ships electrical power systems; Proceedings of the 20 th IEEE Instrumentation and Technology Conference, Como, Italy 2004, pp. 1367-1372.
[10] Szmit E., Mindykowski J., Tarasiuk T.: Zaburzenia elektromagnetyczne na statkach to wspólny problem armatorów, stoczni, uczelni morskich i towarzystw klasyfikacyjnych. Budownictwo Okrętowe, No 3/2004 March 2004, pp. 30-31.
[11] Gnaciński P., Mindykowski J., Tarasiuk T., Influence of electrical power quality on induction cage machine durability. 7th International Conference “Electrical Power Quality and Utilization” Kraków, 17-19 September 2003, pp. 455-462.
[12] Polski Rejestr Statków – Publication 11/P “Environmental tests of marine equipment”, Gdańsk 2002.
[13] IACS Unified Requirements – E10 “Testing procedure for electrical, control and instrumentation equipment, computers and peripherals covered by classification. IACS Blue Book
[14] Lloyds Register – Classification of Ships Rules and Regulations, Part 6 “Control, Electrical, Refrigeration and Fire”, January 1998.
[15] Germanischer Lloyd – Rules for Classification and Construction, Volume I Part 1 “Seagoing Ships” Chapter 3 “Electrical Installations”, Edition 1998
[16] PN-EN 6100-2-4 “Electromagnetic compatibility EMC) Part 2: Environment Section 4: Compatibility levels in industrial plants for low frequency conducted disturbances”.
[17] IEC 61000-4-30 “Electromagnetic Compatibility (EMC): Testing and Measurement Techniques – Power Quality Measurement Methods”.
[18] IEEE 1159:1995 IEEE “Recommended Practice on Monitoring Electric Power Quality”.
[19] PN-IEC 60092-101 “Electrical installations in ships – Part 101: Definitions and general requirements”.
[20] Szmit E., Mindykowski J., Tarasiuk T.: Jakość energii elektrycznej na statkach wspólnym problemem armatorów, stoczni, uczelni morskich i towarzystw klasyfikacyjnych. Fair of Electrical Engineering, Electrical Power Engineering and Lighting Techniques “Electric Wiring”, session “Electrical Power Quality”, Proceedings edited by Stowarzyszenie Elektryków Polskich Oddział Gdańsk, Gdańsk 2004, pp. 23-30.


ResearchGate, Article, January 2004.
Source URL: https://www.researchgate.net/publication/237640225_Electric_power_quality_and_ship’s_safety

Distribution Feeder Voltage Sag Evaluation

Published by Electrotek Concepts, Inc., PQSoft Case Study: Distribution Feeder Voltage Sag Evaluation, Document ID: PQS0905, Date: October 15, 2009.


Abstract: This case study shows the results for simulations completed to evaluate the impact of a distribution feeder fault on the operation of a customer adjustable-speed drive during the resulting voltage sag and momentary interruption. The simulations for the case were completed using the PSCAD program. A voltage swell on the feeder primary is also illustrated. The potential solution of increasing the dc link capacitance for the adjustable-speed drive was shown to be effective for the simulated conditions.

INTRODUCTION

A distribution feeder voltage sag evaluation was completed for the system shown in Figure 1. The simulations for the case study were completed using the PSCAD program. The case involved simulating a voltage swell/sag/interruption event during a fault on the 12.5kV distribution feeder and then determining the dc link voltage for a typical customer adjustable-speed drive. An example of a representative measured voltage waveform is shown in Figure 2.

The accuracy of the simulation model was verified using three-phase and single-line-to-ground fault currents and other steady-state quantities, such as feeder and customer load currents. The circuit modeled for the case involved a 5-mile, 12.5kV distribution feeder supplying a 1500 kVA customer step-down transformer (12.4kV/480V).

The waveform shown in Figure 2 illustrates a voltage swell, a voltage sag, and an interruption. A voltage swell is an increase in rms voltage magnitude above 1.1 per-unit for a duration of 0.5 cycles to 1 minute. Voltage swells are much less common than voltage sags and the magnitudes are not usually severe.

The most common cause of a voltage swell is a single-line-to-ground fault. During a single-line-to-ground fault, the voltage magnitude on the unfaulted phases can increase due to the zero sequence impedance. On an ungrounded system, the voltage on the unfaulted phases can be as high as 1.73 per-unit. On most systems, the voltage swell is less than 1.40 per-unit.

The simulated event began as a single-line-to-ground fault for 4 cycles and then evolved into a phase-to-phase fault for an additional 3 cycles. The feeder circuit breaker opened after approximately 11 cycles and reclosed after a 4-cycle delay. These switching times were selected to approximate the characteristics from the measured waveform. During the single-phase fault, a voltage swell occurs on the other two healthy phases. A voltage sag occurred during the phase-to-phase fault and a momentary interruption occurred while the circuit breaker was open.

Figure 1 – Oneline Diagram for Distribution Feeder Voltage Sag Evaluation
Figure 2 – Measured Voltage Swell and Interruption Waveform

In addition to the voltage swell and voltage sag event on the distribution feeder primary, a customer transformer was modeled so the voltage on the 480-volt bus could be determined. A typical 10 hp adjustable-speed drive was included in the simulation model to determine the potential for nuisance tripping of the drive due to an undervoltage on the drive’s dc link. The oneline for the drive model is shown in Figure 3.

Figure 3 – Customer Adjustable-Speed Drive Simulation Model

Voltage sags cause a decrease in the dc link voltage for an adjustable-speed drive. The drive will likely trip off-line if the voltage falls below the dc link trip voltage. During short duration voltage sags, it may be possible to support the dc link voltage using a larger dc link capacitor. The drive may also experience high inrush currents when the voltage is restored.

SIMULATION RESULTS

The simulated three-phase 12.5kV distribution feeder voltage is shown in Figure 4. The voltage swell, voltage sag, and momentary interruption are all contained in the one figure. The rms voltages for phases A and B are shown in Figure 5 and Figure 6, respectively. The rms voltage quantities were determined using a digital rms meter in the simulation program. The rms voltage characteristic of a voltage swell, followed by a voltage sag, followed by momentary interruption that was shown in Figure 2 is well represented with the simulation result shown in Figure 6.

Figure 4 – Illustration of Three-Phase Feeder Voltage during Fault Event
Figure 5 – Illustration of Phase A RMS Voltage during Fault Event
Figure 6 – Illustration of Phase B RMS Voltage during Fault Event

The resulting three-phase 480-volt customer secondary bus voltage is shown in Figure 7. The 12.5kV/480V step-down customer transformer is connected delta/wye-ground. For a single-phase fault on the primary of a delta/wye-ground transformer, the secondary phase-to-ground voltages would be 0.58, 1.00, and 0.58 per-unit, respectively. This is illustrated in Figure 7 during the initial portion of the event.

The resulting simulated dc link voltage for the typical 10 hp adjustable-speed drive is shown in Figure 8. The magnitude of the dc link voltage decreases during the voltage sag and momentary interruption. For this case, it was assumed that the dc bus low voltage trip voltage was 390 volts, which is 60% of the nominal 650-volt value.

Figure 7 – Illustration of Three-Phase Customer Bus Voltage during Fault Event
Figure 8 – Illustration of Drive’s dc Link Voltage during Fault Event

Figure 9 shows the simulation results for the case of increasing the dc link capacitance from 1,200μF to 5,000μF. The resulting simulated dc link voltage is slightly above the assumed undervoltage trip level so the drive does not trip for this condition.

Figure 9 – Illustration of the Effect of the dc Link Capacitance on the dc Link Voltage
SUMMARY AND CONCLUSIONS

This case study shows the results for simulations completed to evaluate the impact of a distribution feeder fault on the operation of a customer adjustable-speed drive during the resulting voltage sag and momentary interruption. A voltage swell on the feeder primary is also illustrated. The potential solution of increasing the dc link capacitance for the adjustable-speed drive was shown to be effective for the simulated conditions.

REFERENCES

  1. IEEE Std. 1159-1995, IEEE Recommended Practice on Monitoring Electrical Power Quality, ISBN 1-5593-7549-3.
  2. IEEE Std. 1159.3-2003, IEEE Recommended Practice for the Transfer of Power Quality Data, ISBN 0-7381-3578-X.
  3. TOP, The Output Processor®, Electrotek Concepts, Inc., http://www.pqsoft.com/top/

RELATED STANDARDS
IEEE Std. 1159.3, IEEE Std. 1159

GLOSSARY AND ACRONYMS
ASD: Adjustable Speed Drive
UPS: Uninterruptible Power Supply
PSCAD: Power Systems Computer Aided Design

Using Portable/Emergency Generators Safely

Published by U.S. Department of Energy (DOE), Office of Cybersecurity, Energy Security, and Emergency Response, Website: energy.gov


Image: U.S. Department of Energy (DOE), energy.gov

Power outages are common during disasters, and they can last for several days. You can reduce your losses and speed the recovery process with an emergency generator.

Portable generators made for household use can provide temporary power to a few appliances or lights. Commercial generators can help prevent service interruptions at businesses and critical infrastructure facilities, such as hospitals, water treatment facilities, telecommunications networks, and emergency response agencies. Federal, state, and local regulations may require you to obtain a permit to operate a generator. Make sure you follow these regulations when you operate and maintain your generator.

General Safety and Usage Guidelines for Backup Generators

Be sure to use your generator correctly. Using a generator incorrectly can lead to dangerous situations:

  1. Carbon monoxide poisoning from engine exhaust. Even if you can’t smell exhaust fumes, you may still have been exposed to carbon monoxide. If you start to feel sick, dizzy, or weak while using a generator, get fresh air right away. If you experience serious symptoms, get medical attention immediately. Consider installing battery-operated carbon monoxide alarms. Be sure to read the manufacturer’s instructions and take proper precautions.
  2. Electric shock or electrocution.
  3. Fire.

Use a portable generator only when necessary, and only to power essential equipment.

Position generators outdoors and well away from any structure. Running a generator inside any enclosed or partially enclosed structure can lead to dangerous and often fatal levels of carbon monoxide. Keep generators positioned outside and at least 15 feet away from open windows so exhaust does not enter your home/business or a neighboring home/business.

Keep the generator dry. Operate your generator on a dry surface under an open, canopy-like structure and make sure your hands are dry before touching the generator. Do not use the generator in rainy or wet conditions.

Disconnect the power coming into your home/business. Before you operate your generator, disconnect your normal source of power. Otherwise, power from your generator could be sent back into the utility company lines, creating a hazardous situation for utility workers.

Make sure your generator is properly grounded. Grounding generators can help prevent shocks and electrocutions. Refer to OSHA guidelines for grounding requirements for portable generators. 

Plug equipment directly into the generator. Use heavy-duty, outdoor-rated extension cords that are in good working condition and have a wire gauge that can handle the electric load of any connected appliances.

DO NOT plug the generator into a wall outlet. NEVER try to power your house/business by plugging the generator into a wall outlet or the main electrical panel. Only a licensed electrician should connect a generator to a main electrical panel by installing the proper equipment according to local electrical codes. Make sure the electrician installs an approved automatic transfer switch so you can disconnect your home’s wiring from the utility system before you use the generator.

Maintain an adequate supply of fuel. Know your generator’s rate of fuel consumption at various power output levels. Carefully consider how much fuel you can safely store and for how long. Gasoline and diesel fuel stored for long periods may need added chemicals to keep them safe to use. Check with your supplier for recommendations. Store all fuels in specifically designed containers in a cool, dry, well-ventilated place, away from all potential heat sources.

Turn the generator off and let it cool before refueling. Use the type of fuel recommended in the manufacturer’s instructions.

Inspect and maintain your generator regularly. Check aboveground storage tanks, pipes, and valves regularly for cracks and leaks, and replace damaged materials immediately. Tanks may require a permit or have to meet other regulatory requirements. Purchase a maintenance contract and schedule at least one maintenance service per year, such as at the beginning of every hurricane season. Keep fresh fuel in the tank, and run the generator periodically to ensure it will be ready when you need it.

Disclaimer: Because every emergency is different and for your safety, follow the guidance from your state and local emergency management authorities and local utility companies. The information provided on the U.S. Department of Energy’s website is for general information and not an endorsement of any particular material or service. Before you engage in activities that could impact utility services, such as electricity or natural gas, contact your local utility company to ensure that your activities are done safely.

For additional resources, visit ready.gov or benefits.gov. State and local emergency management authorities and local utility companies may also provide helpful guidance.


Source URL: https://www.energy.gov/ceser/activities/energy-security/emergency-preparedness/using-portableemergency-generators-safely

Customer Induction Motor Starting Evaluation

Published by Electrotek Concepts, Inc., PQSoft Case Study: Customer Induction Motor Starting Evaluation, Document ID: PQS0904, Date: October 15, 2009.


Abstract: This case study shows the results for simulations completed to determine the severity of an undervoltage condition during starting of a customer induction motor starting. The simulations for the case were completed using the PSCAD program. The effectiveness of a primary resistor starter is also summarized.

INTRODUCTION

A customer induction motor starting evaluation was completed for the system shown in Figure 1. The simulations for the case study were completed using the PSCAD program. The case involved simulating an undervoltage condition during starting of a 500 hp motor on a 480-volt customer bus. An example of a representative measured voltage waveform is shown in Figure 2. The accuracy of the simulation model was verified using three-phase and single-line-to-ground fault currents and other steady-state quantities, such as motor full load current. The circuit modeled for the case involved a 230kV system supplying a 34.5kV distribution feeder that supplies a 1,500 kVA customer step-down transformer (34.5kV/480V).

Figure 1 – Oneline Diagram for the Induction Motor Starting Evaluation
Figure 2 – Example Motor Starting Voltage Waveform

Motor starting is one of the most common causes of voltage variations. An induction motor will draw several times its full load current during starting. This lagging current creates a voltage drop across the impedances of the system. If the started motor is large enough relative to the system short-circuit capacity, these voltage drops can produce severe voltage sags on the system. Even small and medium horsepower motors can have inrush currents that are six-to-ten times the normal steady-state current levels. Motor starting voltage sags can dim lights, cause contactors to drop out, and disrupt sensitive customer equipment. These voltage sags may also affect the motor starting itself, because severe voltage sags may prevent the motor from successfully starting. Motor starting voltage sags may persist for many seconds.

Relevant system and induction motor data for the case included:

Three-phase induction motor rating: 500 hp
Rated induction motor voltage:480 V
Motor efficiency: 92.0%
Motor full load power factor: 90.0%
Motor full load slip: 2.0%
Motor full load current:542 A
Motor three-phase rating: 450 kVA
Motor starting current (5.7 x IFL): 3089 A
Motor locked rotor kVA:2565 kVA
Short-circuit current at motor terminal:28 kA
Short-circuit kVA at motor terminal: 23280 kVA
SIMULATION RESULTS

For a full voltage start, the voltage drop in per-unit of nominal system voltage may be estimated using the following expression:

where:
V(pu) = actual system voltage (per-unit)
kVASC = system short-circuit kVA at motor (kVA)
kVALR = motor locked rotor kVA (kVA)

On a 480-volt bus, this rms phase-to-neutral voltage drop would be 249.6 volts. This full voltage starting condition was simulated in the first case. The phase A current is shown in Figure 3. The figure also includes the calculated rms current. The rms voltage and current quantities were determined using digital rms meters in the simulation program. The maximum simulated peak current for the full voltage start was 4275 A and the full load rms current was 565 A. The three-phase 480-volt bus voltage during full voltage motor starting is shown in Figure 4. The rms voltage is shown in Figure 5. The minimum rms voltage for the case was 250.3 volts, which is very close to the hand-calculated value of 249.6 volts.

Figure 3 – Illustration of the Full Voltage Start Motor Current
Figure 4 – Illustration of the Full Voltage Start Three-Phase Bus Voltage

Assuming that the maximum allowable voltage drop is 5%, the simulated 10% voltage drop for the full voltage starting case indicates that some type of mitigation is required. There are several motor starting techniques to limit the motor starting current including autotransformer starters, resistance and reactance starters, delta-wye starters, and shunt capacitor starters.

Figure 5 – Illustration of the Full Voltage Start RMS Bus Voltage

The second case investigated the effectiveness of a primary resistor motor starter to achieve the 5% voltage limitation. A primary resistor starter has one or more sets of resistors which are connected in series with the motor during starting. The resistors are typically bypassed by a contactor once the motor has reached full speed. Figure 6 shows the motor current for the case with a primary starting resistor. As can be observed from the figure, the magnitude of the starting current is lower than the full voltage case; however the motor takes somewhat longer to reach full speed.

Figure 6 – Illustration of the Primary Resistor Starter Motor Current

Figure 7 shows the simulated rms voltage for both the full voltage and primary resistor starter cases. The primary resistor starter reduces the magnitude of the voltage drop so that is very near the assumed 5% limit.

Figure 7 – Illustration of Voltage Drop for Full Voltage and Primary Resistor Starting
SUMMARY AND CONCLUSIONS

This case study shows the results for simulations completed to determine the severity of an undervoltage condition during starting of a customer induction motor starting. The effectiveness of a primary resistor starter is also summarized.

REFERENCES

  1. IEEE Std. 1159-1995, IEEE Recommended Practice on Monitoring Electrical Power Quality, ISBN 1-5593-7549-3.
  2. IEEE Std. 1159.3-2003, IEEE Recommended Practice for the Transfer of Power Quality Data, ISBN 0-7381-3578-X.
  3. TOP, The Output Processor®, Electrotek Concepts, Inc., http://www.pqsoft.com/top/

RELATED STANDARDS
IEEE Std. 1159.3, IEEE Std. 1159

GLOSSARY AND ACRONYMS
ASD: Adjustable Speed Drive
UPS: Uninterruptible Power Supply
PSCAD: Power Systems Computer Aided Design

In Case of a Power Outage

Published by Silicon Valley Power® (SVP), City of Santa Clara, California, USA.


Photo: Silicon Valley Power®

Power outages are inconvenient for everyone, and we at Silicon Valley Power (SVP) do everything we can to reliably maintain your power. When we do have an outage, SVP is dedicated to resolving the problem as quickly as possible. We take pride in being ranked among the top 10 percent of utilities in the nation for power reliability.

If the power does go out, here are a few things you can do to make sure that you, your family and those around you stay safe and sound.

Be Prepared
  • Visit the USDA food safety site or go to USDA.gov, look for “Food Safety,” print out the safety guidelines and tape them inside a food cupboard.
  • Have a cooler, and keep ice packs and/or containers of water stored in your freezer. During an outage, the ice packs can protect your food in the cooler, or they can be moved from the freezer to your refrigerator to help keep it cool.
  • Plan ahead and know where dry ice and block ice can be purchased.
  • Keep canned food on hand along with a hand-operated can opener.
  • Have flashlights and fresh batteries readily available to use during a power outage.
  • Emergency lights that turn on when the power goes off can be useful and can be found at any hardware store or online.
  • Plug electronic equipment into surge protectors to protect against a surge when power is restored.
  • Have a battery-operated radio and fresh batteries or hand-cranked radio available.
  • Find out more practical information for power outage readiness.
Keep Your Food Safe in an Emergency

If you lose your power, you’ll want to be sure that the food in your refrigerator remains safe to eat for as long as possible.

Here are some valuable Food Safety tips from the U.S. Department of Agriculture:

  • Keep an appliance thermometer in the refrigerator and one in the freezer at all times. Built-in temperature displays may not function during an outage.
  • Keep meat, poultry, fish, and eggs refrigerated at or below 40 °F.
  • Keep frozen food at or below 0 °F.
  • Keep the refrigerator and freezer doors closed as much as possible. Check thermometers only when opening doors for another reason.
  • The refrigerator should keep food safely cold for about 4 hours if it is unopened.
  • If you have frozen ice packs or containers of water, you can place them in the refrigerator to help keep the temperature cool.
  • A full freezer should hold the temperature for approximately 48 hours (24 hours if it is half full) if the door remains closed. See the Food Safety guidelines for more information.
  • Know USDA guidelines about packing frozen food closely together in the freezer if the freezer is not full.
Stay Connected During a Power Outage

It is most likely that you will lose the connection to your home Internet equipment such as a router or modem, and certainly lose external power for your electronic equipment such as computers and TVs during a power outage. In addition, you may lose connection to external wireless and cell phone services.

The Federal Emergency Management Agency has tips that can help in an emergency. Here are some ideas that may help you maintain or regain connection to Internet access and/or cell phone service, if it is available, during a power outage:

  • Most mobile devices that are powered or charged using a USB cable require a 5-volt power source, not a 110-volt household outlet.
  • Most modern laptop computers have USB ports that provide 5-volt power. You can connect using the USB power cord that you normally use to charge your phone. Keep your laptop charged, as it can be a source to recharge your cell phone during an outage.
  • Your vehicle’s lighter outlet can provide numerous recharges for your cell phone using an inexpensive USB adapter. Connect the adapter using the USB power cord that you use for your phone.
  • An extra battery pack or solar battery pack for your cell phone is wise and inexpensive.
  • Unplug unprotected electronic equipment to protect against a power surge when electricity of restored, or use a surge protector.

Last Updated: 2020-09-16


Source URL: https://www.siliconvalleypower.com/svp-and-community/outages-and-alerts/in-case-of-a-power-outage