Effect of Harmonics on Power Transformers: A Practical Demonstration and Analysis

Published by Munther Naif Thiab1, nmunther2@gmail.com, Kaleid waleed abid2, kaleidwaleedabid@gmail.com, Muhideen Abbas Hasan3, muhyabass@gmail.com,
1, College of Engineering, University of Anbar, Iraq.
2, Renewable Energy Research Center / University of Anbar. Iraq.
3, Al-Dour Technical Institute, Northern Technical University, Iraq.


Abstract: Voltage and current harmonics arise in the presence of nonlinear loads in the major supply. Moreover, the presence of harmonics is associated with several problems such as cables overheating, induction motor vibration and overheating, as well as augmented losses in the transformers. This study analyzes the particular effects of harmonics on a 1-KVA transformer. The harmonics signal was generated on the transformer by using a frequency oscillator, while the total harmonic distortion, crest factor, and K-factor were investigated using a power analyzer (Fluke-435). The results are analyzed and compared for different orders of harmonics. The results are analyzed and compared for different orders of harmonics, especially with regard to the total harmonic distortion (THD) and k-factor, present standards like IEEE 519 provide a technique to limit the ability of an existing power transformer matter to non-linear load flows based on conservative assumptions.

Keywords: Harmonics, k-factor; Power analyzer (Fluke-435); Total harmonics distortion; non-linear an unbalanced load.

1. Introduction

Over the years, harmonic current and voltage distortions have been studied and mitigated by power system engineers [1, 2]. Given the increasing number of devices that contribute to the generation of harmonics such as diodes, power transistors, and rectifiers, we conjecture that power electronic loads will be vital components of power at all stages. This is due to their influence on controllability and effectiveness of power loads, which is evident from the observable increase in the level of harmonics and power network distortions [3].

Transformers are regarded as critical components in power systems. In single-phase transformers, the measurement of the iron and copper losses is significant, specifically for transformers that feed nonlinear loads. Power losses due to increased harmonic distortions and abnormal increases in the transformer temperature can be attributed to core stray magnetic losses, losses in the windings, and eddy currents. Thus, harmonics can have a detrimental effect on the power factor of capacitors when fitted and hence, resonance must be avoided in the supply inductance. Moreover, in the presence of harmonics, there is an approximate increase in the eddy current with the square of the current and as such, eddy current presents the most concern among the sources of current losses in transformers. This necessitates the determination of the harmonic spectrum of load currents prior to the estimation of excess losses [2, 4].

In the power systems, the use of nonlinear loads can often lead to reduction in the service life of a transformer because of the possible influence of increased heat losses. Therefore, certain conditions ought to be met before analyzing the performance of a transformer, such as a knowledge of the load mix, the total harmonic distortion (THD), and the details of the content of the load current harmonics. Two factors that contribute to the additional heating observed in a transformer, these are the design principles of the transformer and the load current harmonics [2].

The conversion of a 3-phase supply into 1 or 2 single-phase supplies is usually done using special transformers such as Scott and Le-Blanc transformers or V–V transformers. These are the transformers commonly used in electric locomotive traction systems. Previous studies have investigated the annulment of harmonics in such transformers. In [5, 6], researchers showed that when 2 harmonic-generating loads are connected to single-phase transformers on each side, the generated harmonics by the loads tend to annul each other at the transformers’ primary sides. The study further opined that the degree of annulment is determined by the type of transformer and the order of the harmonic[7].

In [8], researchers reduced harmonics in series-connected converters by introducing an averaging inductor in a series-connected converter to simplify the process of pulse multiplication. The novelty of this method was realized in a 3-thyristor switching circuit scheme that can support the operation of a 12-pulse double bridge at 36 pulses. Simulation studies validated the theoretical work, with the exception of a few modifications that are required to apply the proposed method for higher pulse operation.

As regards transient and harmonic analysis in electrical networks, companion harmonic circuit models (CHCMs), which deploy an exact periodic steady state initialization method, have been proposed [9]. The suggested CHCMs are based on the application of the trapezoidal integration principle to the differential equations of electric elements in the presence of dynamic harmonics. The CHCM technique was applied in a simple network with transformer saturation-generated harmonics. The CHCMs offered a direct way of estimating the harmonics’ steady state and transient response in an electrical system.

In this work, we study the effect of harmonics on a 1-KVA transformer to investigate the relationship between the order of the harmonics and the effect on the operating efficiency of the transformer.

2. Forms of Harmonics

The effect of harmonics is usually manifested in the form of irregular current or voltage (current harmonics) or voltage (voltage harmonics) waveforms. Bridge rectifier circuits usually produce current harmonics which it affects the electrical equipment that supplies harmonic current to either the conductors or the transformers. Third order harmonics have received significant research attention, which have led to the development of electrical systems that feed single phase loads which allow the neutral conductor to draw excessive current[13]. On the other hand, components of electrical devices are vulnerable to voltage harmonics that arise when current harmonics succeed in creating sags in the voltage supply. When current is drawn by a device, a voltage drop is generated that is required for the current to flow. An example of such phenomenon is the dip in voltage observed when switching-on a table saw or a hair dryer, which is manifested by the sudden dimming of lightbulbs [14]. The magnitude of the sag is influenced by multiple factors including the impedance of the transformer and the diameter of the wire. It is widely accepted that voltage harmonics are caused by current harmonics; however, the intensity of voltage harmonics depends on the ‘stiffness of the systems’ impedance during electrical distribution’. The relationship between current distortion and voltage distortion can be elucidated through the example of the common light bulb. The current THD of the low-cost light bulb may be about 75%, which implies that harmonic current accounts for 75% of the total current drawn by the bulb. The effect of light bulbs on other home devices is low because it creates a relatively small sag in the voltage supply to the house despite the fact that the current drawn by it comprises 75% harmonics. This effect can be better observed using a voltage analyzer, where the THD voltage is observed to be below 1% [15].

Figure 1 illustrates the effect of harmonics on the shape of the waveform. The upper row (left and right) shows the fundamental frequency, which comprises two circle waves ( 4πf0 ). The third subplot in this figure (left side of second row) represents the second harmonics (2f0), while the right side represents the third harmonics (3f0). The effect of these harmonics on the main waveform is shown in the last subplots (subplot 5 and 6). From these subplots, it can be seen that the third harmonics has a relatively larger effect on the shape of the signal waveform. Thus, third harmonics contributes more significantly to the fluctuation than second harmonics. Figure (2) illustrates the effect of fourth and fifth harmonics on the waveform. It can be observed that the odd harmonics still have a greater effect on the complex waveform shape. Therefore, odd harmonics (5, 7, 9, etc.) have a more pronounced effect on the shape of the waveform than even harmonics (2, 4, 6, etc.).

Figure 1. Effects of second and third harmonic on the waveform
Figure 2. Effects of fourth and fifth harmonic on the waveform
3. Harmonics reduction

In general, the effect of harmonics can be mitigated by selecting equipment with low THD currents, thereby reducing the effective THD voltage. However, in the case that the use of equipment with low THD current is prohibitive, alternative options exists such as the addition of line chokes or isolation transformers to reduce the harmonic currents. Moreover, current distortions, which have a pronounced effect on the voltage waveform, can be reduced by using a tuned capacitor. In addition, the system load distribution can be redesigned such that the total system impedance is reduced [15, 16]. Several solutions have been proposed for reducing the effects of harmonics, and are as follows

1) Reduction of current harmonics
• Through the addition of line chokes to the harmonics producing equipment.
• Through the addition of an isolation transformer to the harmonics producing equipment.
• Through the use of a 12- pulse or 18-pulse rectifying circuit instead of 6-pulse rectifying circuit.

2) Reduction of voltage harmonics
• Through the addition of a tuned capacitor bank to the source of current harmonics.
• Through optimization of transformer size and impedance.

3) Through the use of cost-effective and energy-efficient phase-shifting transformers, which are highly reliable passive devices that can control harmonics regardless of the load level served

Effect of harmonics on transformer losses In general, transformers are designed to have minimum losses in both sinusoidal currents and rated voltage. However, in recent years, the load current is no longer sinusoidal because of the increase in the number of nonlinear loads. Thus, the presence of the nonsinusoidal currents leads to in extra losses and increase in transformer temperature [7]. There are several ways of estimating harmonic load content, such as the use of the crest-factor, percent of THD, and the K-Factor, which can be used to determine the extra heat generated by nonsinusoidal loads. The crest factor(CF) expresses the ratio of the waveform peak value to the true RMS value [6, 8], and is represented as follows.

.

where Imax = peak value of the current waveform;
Irms = true value of the current RMS.
Percentage THD expresses the ratio the root-mean-square (RMS) of harmonic currents to the corresponding RMS value of the fundamental frequency [10-12].

.

The last relation in equations (2,3,4,5) are for the determination of the extra harmonic currents and voltages to the total RMS values.

The K-factor, which is defined as the sum of squares of the harmonic current per unit multiplied by the square of the harmonic value, is also a widely used method.

.

Here, Ih(pu) indicates the harmonic current per unit based on the magnitude of the fundamental current, and h represents the harmonic number [11,17].

The Non-linear loads which source harmonics are DC-AC inverters, magnetic devices, and rotating machines. Many motors that are used in industrial applications are composed of magnetic materials and are controlled by a changing flux and magnetic field. This increasing a back electromotive force (EMF) and conventional contributes to a form of THD known as voltage distortion (THDv) The inclusive load loss be able to be scheduled as [11, 18].

.

Where, REC-R is the equivalent resistance corresponding to the eddy-current loss, RDC is Winding DC resistance, PDC is the winding eddy-current loss, and fh is The Individual harmonic.

Small DC modules (up to the peak (rms) of the transformer excitation current at rated voltage (Vrms) are predictable to have no outcome on the load carrying capability of a transformer specified by this optional practice. Higher DC components may unfavorably affect transformer proficiency and should be avoided [19]-[20]. In observation, it is significant to use the existent harmonic current values sooner than for calculated values theoretically [20].

5. EXPERIMENTAL SETUP

In this section, we present the results of a practical experiment conducted in this study to determine THD of a 1-KVA single-phase transformer. The experiment was performed using the devices listed in Table 1. The detailed used in the experiment are shown in Figure 3. A variable frequency supplier (N700E) was used for generating the 3rd, 5th, and 7th harmonic frequency on the transformer, while 600-W variable resistors were used for controlling the supplied voltage at different frequencies on the transformer.

Table 1. Components used in the experiment

.
Figure 3. Components for the practical circuit

5.1 Discussion and Results

This section discusses the effects of harmonics on the 1-KVA single phase transformer. Figure (4) gives the harmonics effects in table forms. The upper figures represent the harmonics in Ampere, Volt, and Watt from left to right, respectively. In the first table, THDf = 266 and 157.9 for line (L1) and neutral (N), respectively; however, this value reduces as the harmonics increases to 250 Hz and 350 Hz, as shown in Figures 5 and 6. The corresponding values of THDf (250 Hz) = 202.6, and THDf (350 Hz) = 195.5. The values of THDf also decreased for neutral lines in the same tables, i.e., THDf = 157.9 at 150 Hz, THDf = 117.7 at 250 Hz, and THDf = 116.2 at 350 Hz. The other values in the tables represent the values of odd harmonics from H3 to H15. The values of harmonic percentages, expressed in Volts and Watt, are also shown in the same figures. The subplots in the bottom right of Figure. illustrate the harmonic effects as a function of Volts/Amps/Hertz. The harmonic percentage decreases as the applied frequency increases, as shown in Figures 4, 5, and 6). From the same subplots, the crest factor was constant at 1.4 because of the use of variable resistors for controlling the applied currents and voltages on the transformer; this implies that currents Imax and Irms were constant in equation (1). The subplots at the bottom-center of figures represent the main signal of 230 V (source voltage) in addition to the applied harmonics voltage of 23 V in the neutral line. From this figure, it is clear that the fluctuation in the shape of the signal is due to the effect of the applied harmonic signal on the transformer.

The other subplots (bottom-center) in the same figures represent the effect of harmonics on the signal shape (5th and 7th harmonics). Finally, the last subplots (bottom-left) represent the harmonic effects on the current waveform. In these subplots, the fluctuation was observed to be for the 3rd harmonics than the other values at 5th and 7th harmonics. This observation can be as expected because the amplitude of harmonics decreases as the order increases.

Figure 4. Harmonic Effects at 150 Hz
Figure 5. Harmonic Effects at 250 Hz
Figure 6. Harmonic Effects at 350 Hz

5.2 Effects of harmonics at different frequencies and K-Factor

THD and K-factor can also be determined using the power quality analyzer (Fluke-435B). Figures 7, 8 and 9 show the amplitude of harmonics in the neutral line for the given current waveform. From the first two figures, THD and K-factor decreased as the frequency of the simulated harmonics increased. In Figure 9, THD decreased from 110.2% to 79.5%, while K-factor decreased from 42.2 to 18.2. In Figure 8, THD increases as a function of the corresponding value because the reading was taken in a high harmonics environment in the lab during the testing time, which was in addition to the already injected harmonics using the variable frequency supplier (N700E). From Figure 7, it is evident that the amplitude of harmonics decreases as the frequency on the x-axis increases. An amplitude of harmonics above 30% implies that the order of harmonics is less than 13, while a THD amplitude of less than 20% implies that the order of the harmonics is more than 17.

Figures 10, 11, and 12 illustrate the harmonic effects in neutral line for voltage waveform. From these figures, it is evident that THD and K-factor decrease as the frequency increases from 150 Hz to 350 Hz. Moreover, we can see that the maximum amplitude of harmonics lies at the odd integer of the fundamental frequency. Percentage THD in Figure 10 has an amplitude above 20% when the order of harmonics is below 31. Note that the values of harmonics are very high in Figure 10 for line voltage.

Figures 13, 14, and 15 show THD values for the voltage waveform in the neutral line. THD decreased from 40.9% at 150 Hz to 35.3% at 250 Hz, and subsequently reduced to 31.2% at 350Hz.

Figure 7. Harmonics amplitude at 150 Hz in the neutral line (NL) for current waveform (CV)
Figure 8. Harmonics amplitude at 250 Hz in the NL for CV
Figure 9. Harmonics amplitude at 350 Hz in the NL for CV
Figure 10. Harmonics amplitude at 150 Hz in the Line harmonics (LH) for CV
Figure 11. Harmonics amplitude at 250 Hz in the LH for CV
Figure 12. Harmonics amplitude at 350 Hz in the LH for CV
Figure 13. Harmonics amplitude at 150 Hz in the Neutral Line harmonics (NLH), volt
Figure 14. Harmonics amplitude at 250 Hz in the NLH, volt
Figure 15. Harmonics amplitude at 350 Hz in the NLH, volt
6. Conclusions

The distortions produced in current and voltage waveforms due to nonlinear loads can often lead to several issues in an electrical distribution system. In this study, the harmonic signals at the 3rd, 5th, and 7th order were simulated using a variable frequency supplier (N700E) by injecting the harmonics frequency on the load in a 1-KVA transformer. The results showed that the harmonics had pronounced effects on the current and voltage waveforms. Moreover, the maximum harmonics percentage occurred at the 3rd order and decreased at higher orders. The results also showed that the crest factor and K-factor decreased as the harmonics order increased.

*Corresponding Author: Munther Naif Thiab, Email id : nmunther2@gmail.com Article History: Received: Aug 15, 2018, Revised: Sep 10, 2018, Accepted: Oct 04, 2018

References

[1] A. Cataliotti et al., “Metrological performances of voltage and current instrument transformers in harmonics measurements,” in 2018 IEEE International Instrumentation and Measurement Technology Conference (I2MTC), 2018: IEEE.
[2] D. Ismail, H. Syafruddin, A. Rosnazri, M. Z. Samila, and A. H. Haziah, “The effects of harmonic components on transformer losses of sinusoidal source supplying non-linear loads,” American Journal of Applied Sciences, vol. 3, no. 12, pp. 2131-2133, 2006.
[3] S. PURUSHOTHAMAN ” ,DESIGN AND ANALYSIS OF ELIMINATION OF HARMONICS USING WIND ENERGY CONVERSION SYSTEMS,” Journal of Theoretical & Applied Information Technology, vol. 61, no. 3, 2014.
[4] S. Saodah, “Investigation of Transformer Losses and Temperature Rise,” Electrotehnica, Electronica, Automatica, vol. 66, no. 2, pp. 37-44, 2018.
[5] R. M. Patil, M. Nagaraj, and P. Venkataramu, “Harmonic Elimination System (HES) using a novel type of Pulse Width Modulation (PWM) scheme in Matlab-Simulink environment,” in Signal Processing, Communication, Power and Embedded System (SCOPES), 2016 International Conference on, 2016, pp. 40-47: IEEE.
[6] H. E. Mazin and W. Xu, “Harmonic cancellation characteristics of specially connected transformers,” Electric Power Systems Research, vol. 79 ,no. 12, pp. 1689-1697, 2009.
[7] L. UMASANKAR and N. KALAIARASI, “IDENTIFICATION OF INRUSH CURRENT AND INTERNAL FAULT CURRENTS IN A TRANSFORMER USING SELF ORGANIZING MAPS,” Journal of Theoretical & Applied Information Technology, vol. 58, no. 2, 2013.
[8] K. Xu, K. Meah, and A. S. Ula, “A novel method for reducing harmonics in series-connected rectifiers,” Electric Power Systems Research, vol. 78, no. 7, pp. 1256-1264, 2008.
[9] H. García, M. Madrigal, and J. Rico, “The use of companion harmonic circuit models for transient analysis and periodic steady state initialization in electrical networks with nonlinearities,” Electric Power Systems Research, vol. 93, pp. 46-53, 2012.
[10] S. Sadati, A. Tahani, B. Darvishi, and M. Dargahi, “Comparison of distribution transformer losses and capacity under linear and harmonic loads,” in Power and Energy Conference, 2008. PECon 2008. IEEE 2nd International, 2008, pp. 1265-1269: IEEE.
[11] N. Kotaiah and K. C. Sekhar, “INTEGRATION OF DISTRIBUTED GENERATION TO UPQC WITH UNIT VECTOR THEORY,” Journal of Theoretical & Applied Information Technology, vol. 95, no. 3, 2017.
[12] Alfredo Basulto Espinosa, “ESTIMATION OF SUBSTATION TRANSFORMER LOSSES UNDER NON-LINEAR AN UNBALANCED LOAD CURRENT,” CONGRESO ALTAE Conference. 2017.
[13] Thinh Dao, Bao Toan Phung, ” Effects of voltage harmonic on losses and temperature rise in distribution transformers,” IET Generation, Transmission & Distribution Journal,2017.
[14] Julio G. Mayordomo , Luis F. Beites, Ángel Carbonero, Xavier Yang, ,and Wilsun Xu,” An Analytical Procedure for Calculating Harmonics of Three-Phase Uncontrolled Rectifiers Under Nonideal Conditions,” IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 30, NO. 1, FEBRUARY 2015.
[15] J. Zheng, “Transformer ac winding resistance and derating when supplying harmonic-rich current,” Michigan Technological University, 2000.
[16] R.A. Barr, V.J. Gosbell,”Power system harmonic voltage limits for the future,” International Conference on Harmonics and Quality of Power (ICHQP),2014.
[17] Mahrous A. Taher, Salah Kamel, and Ziad M. Ali,” K-Factor and Transformer Losses Calculations under Harmonics,” Eighteenth International Middle East Power Systems Conference (MEPCON), 2016.
[18] H. García, M. Madrigal, J.J. Rico, ” The use of companionharmonic circuit models for transient analysis and periodicsteady state initialization in electrical networks withnonlinearities”, Electric Power Systems Research, volume 93, 46–53,2012.
[19] Task Force on Harmonics Modeling and Simulation, “Modeling devices with nonlinear voltage-current characteristics for harmonic studies”, IEEE Transactions on Power Delivery, Vol. 19, pp. 1802-1811, 2004.
[20] Dr. Abla GADO, Eng. Hassan ABO GAD, Eng. Salah RADWAN, “EFFECT OF TYPES OF LOADS IN RATING OF TRANSFORMERS SUPPLYING HARMONIC-RICH LOADS”, 21st International Conference on Electricity Distribution Frankfurt,2011.


Article in Journal of Advanced Research in Dynamical and Control Systems · October 2018. Source URL: https://www.researchgate.net/publication/330811342_Effect_of_Harmonics_on_Power_Transformers_A_practical_demonstration_and_analysis

Selected Aspects of Photovoltaic Power Station Operation in the Power System

Published by Andrzej LANGE1, Marian PASKO2
University of Warmia and Mazury, Department of Electrical and Power Engineering, Electronics and Automation (1), Silesian University of Technology, Institute of Electrical Engineering and Computer Science (2)


Abstract. This paper presents the results of a five-year study of a 1 MW photovoltaic power station in the Warmia and Mazury Province. The research involved measurements of active energy, currents, voltages, active, reactive and apparent power and higher harmonics of currents and voltages. The operation of this plant was analysed in terms of electricity produced and active power generated to the power grid in individual years, months and days. The analysis concerning the impact of the plant on the power grid in terms of the quality of electricity supplied included the results of three-day measurements of not only active, reactive and apparent power, but also of higher harmonics of currents generated to power grids on the low-voltage side, the results of which were recorded every second.

Streszczenie. W artykule przedstawiono wyniki pięcioletnich badań elektrowni fotowoltaicznej o mocy 1 MW z województwa warmińskomazurskiego. W czasie badań zmierzono energię czynną, prądy, napięcia, moce czynne, bierne i pozorne oraz wyższe harmoniczne prądów I napięć. Dokonano analizy pracy tej elektrowni pod względem produkowanej energii elektrycznej oraz mocy czynnej generowanej do sieci elektroenergetycznej w poszczególnych latach, miesiącach i dniach. Do analizy oddziaływania elektrowni na sieć elektroenergetyczną pod względem jakości dostarczanej energii elektrycznej przedstawiono wyniki trzydniowych pomiarów nie tylko mocy czynnej, biernej i pozornej, ale również wyższych harmonicznych prądów generowanych do sieci elektroenergetycznych po stronie niskiego napięcia, których wyniki rejestrowane były co 1 sekundę. (Wybrane aspekty pracy elektrowni fotowoltaicznej w systemie elektroenergetycznym).

Keywords: electrical power quality, higher harmonics of voltages and currents, active and reactive power, photovoltaic power plant.
Słowa kluczowe: parametry jakości energii elektrycznej, wyższe harmoniczne napięć i prądów, moc czynna i bierna, elektrownia fotowoltaiczna

Introduction

Depleting conventional energy resources such as hard coal, lignite, oil, natural gas and radioactive elements, as well as the effects of pollutions emitted from these sources, force mankind to use renewable sources of electricity. Renewable energy sources include: hydropower, solar power [1], wind power, geothermal energy, sea currents, tidal and wave energy, biofuel, biomass, biogas and ocean thermal energy. The recent Act on Renewable Energy Sources [2] has stopped the construction of new wind and water power plants. Consequently, the production from photovoltaic (PV) panels has remained for electricity generation using renewable energy sources [3, 4]. Power stations based on photovoltaic panels do not provide a fixed and rigid source of electricity, since the value of energy generated depends on solar radiation, which in our climatic conditions is not constant and is subject to dynamic changes [5, 6].

Characteristics of a photovoltaic power station

To describe the effect of the photovoltaic power station on the quality of electricity and its effectiveness, a 1 MW power station located in the Warmia and Mazury Province was selected. The power station is connected to the MV power grid by a 3×XRUHAKXS 120/50 mm2 cable line. The power station area featured a MV/LV container station with a SN = 1000 kVA transformer and MV and LV switchboards. 2×YAKY 3×240+120 mm2 cables from the LV switchboard connect six AC switchboards to which 46 three-phase SYMO 20.0-3-M inverters with rated power PN = 20 kW are connected. The inverter data are presented in Table 1. Each of the 43 inverters was connected to 88 monocrystalline photovoltaic panels, PN = 250 W, the parameters of which are presented in Table 2. Three inverters were connected to 72 monocrystalline photovoltaic panels. Panels were installed at the 30° angle. The total number of panels was 4000 and the total power installed in PV panels was 1000 kW. The rated power of a PV panel is specified in Standard Test Conditions (STC) i.e. at the sunlight intensity of 1000 W/m2 , 1.5 G AM spectrum and cell temperature of 25°C. Connecting 88 PV panels to the 20 kW inverter results in 22 kW in the PV panels, therefore each inverter is overloaded by 10%. The total power of the installed inverters is 920 kW.

Table 1. Basic data of a SYMO 20.0-3-M inverter

.

Table 2. Basic data of a SFE.MF-6-250 PV panel

.
Measurement results

The measurements were performed from the moment the power station was commissioned in May 2015 to the end of 2019. The analysis included measurement results for currents, voltages, electricity, active, reactive and apparent power, and higher harmonics of currents and voltages on the MV and LV sides of the transformer.

As results from the PV panel data, the power of the panel and its voltage increases along with a decrease in temperature (Fig. 1 and Fig. 2). This is of crucial importance on colder days of the power plant operations, when sunlight intensity is lower. At that time, the higher power of the panel resulting from lower temperature partially compensates for the lower intensity of solar radiation. However, the current generated by the PV panel decreases with a decrease in temperature (Fig. 3). The value of radiation intensity has a significant effect on the value of the current generated by a PV panel (Fig. 4). The lower the radiation intensity, the lower the current generated by the photovoltaic panel. The same applies to the power generated by the panel (Fig. 5). This is of crucial importance for determining the rated power of the power station. The Energy Law Act [7], the Act on Renewable Energy Sources [2, 8] and the Construction Law Act [9] do not explicitly define the rated power of a photovoltaic power station. Those legal acts include a reference to “installed power of electrical plant of a renewable energy source” – a photovoltaic cell using solar radiation energy. Therefore, it should be presumed that the legislator had in mind the rated power of PV panels. It has not been precisely described which parameters are used to determine this power. When applying for a building permit and related agreements and decisions (e.g. Environmental Decision, Zoning Conditions, sale of electricity from renewable energy sources at the auction of the Energy Regulatory Office –URE), the authorities (e.g. the Energy Regulatory Office) literally define the rated power of a photovoltaic power station as the sum of the power of PV panels specified in the manufacturer’s documentation. They do not go into details concerning the specificity of the panel operation. They treat this source of energy just like other sources, e.g. synchronous generators in conventional power stations, wind farms or hydroelectric power stations. Also, grid connection conditions are issued based on the same data, although the active power supplied to the power grid is not only determined by photovoltaic panels but also by the power of the inverters. If we connect 2 MW in PV panels to inverters of the total power 1 MW, the maximum power supplied to the grid will still be 1 MW. Based on the issued administrative decisions, the investor applies for the grid connection conditions. At this moment, it is the value provided in previous decisions that are submitted in the application. In order to avoid a costly and time-consuming environmental impact assessment required under the Acts [10, 11] and the Regulation [12], photovoltaic power stations up to 1 MW are designed and constructed.

Fig.1. The value of active power generated by a SFE.MF-6-250 PV panel as a function of PV cell temperature
Fig.2. RMS rated voltage UMPP at the Maximum Power Point (MPP) and RMS open circuit voltage UOC of a PV panel as a function of PV cell temperature
Fig.3. RMS rated current IMPP at the Maximum Power Point (MPP) and RMS short circuit current UOC of a SFE.MF-6-250 PV panel as a function of PV cell temperature
Fig.4. RMS current of a PV panel as a function of a SFE.MF-6-250 PV cell voltage for various irradiance levels
Fig.5. Sample diagrams of changes in power values of a PV panel as a function of voltage for different irradiance levels.

As results from the measurements performed (Fig. 6), the power station did not reach the rated value of active power either of the installed PV panels or the installed inverters in any of the months. According to legal regulations described above, the rated power of the power station is 1 MW. However, within five years of its operation, it never reached this value. In some hours, it reached the value of 900 kW, and its maximum value was 910 kW. With the connection power and the installed power of 1 MW in the power system, it lost about 100 kW, i.e. 10% of the connection power. Given the poorly developed MW power grid outside cities where these plants are being built (due to, e.g. lower land purchase costs) and the resulting shortage of network transmission capacity, each additional kilowatt of available power should be reasonably managed. Therefore, the regulations ought to be changed or made more accurate so as there are no “idle” generation capacities in the system. Figure 6 also shows high dependency of the active power generated to the grid on the season. This relationship is even more clearly demonstrated in the diagram of the average value (median) of active energy generated during one day by a photovoltaic power station (Fig. 7). In months with poorer insolation, the average value of energy provided in one day can be several times lower than in summer months. The highest value is achieved in May, when the sun shines at a large angle and a day is long, and the average air temperature is lower than in summer months such as: June, July or August. On the other hand, August has more sunny days on average than July and lower air temperatures. Figure 8 presents the values of energy generated by the PV power station in individual months of the year.

Fig.6. The value of maximum active power (15 min. interval) generated by the PV power station in individual months of the year (five-year maximum values)
Fig.7. The value of average, median, maximum and minimum active energy generated in one day by the PV power station in individual months of the year (five-year values)
Fig.8. The value of active energy generated by the PV power station in individual months

The value of energy generated in winter months, i.e. November, December, January and February, does not exceed 20% of the value of energy generated in summer months. The power station was commissioned on 21 May 2015, therefore the value of energy generated in this month was much lower than in other years. Most energy generated by the power station falls for the months of April, May, June, July, August and September. Figure 9 presents the variations of the active power values generated during the entire day by the PV power plant on selected sunny days and in individual months. Three winter months (November, December and January) clearly stand out here. In these months, active power generated to the grid is significantly lower than in other months. Even in February, March or October, on a sunny day, power generated to the power grid is only slightly lower than in May or June. At the peak of generated power, differences do not exceed 20%. The peak of the power station operation on sunny days reaching above 700 kW in summer months is recorded for maximum up to five hours a day. As results from the analysis conducted, since the time of its construction, the power station operated above 700 kW for 727 hours, i.e. 30 days out of 1686 days, which accounts for 1.80% of the entire period. In order to reduce the grid connection power, electricity storage in the form of batteries should be used to store energy in the generation peaks and to release it in the peaks of power system requirements or in hours when the electricity is most expensive. The power of such a battery would amount to about 740 kWh and the inverter power – about 200 kW. At that time, 300 kW of available connection power would be obtained, i.e. about 1/3 of the present value. Table 3 presents the values of energy generated by the power station in individual years. On average, the power station produced about 880 MWh yearly (taking into account its commissioning on 21 May 2015).

Table 3. Energy generated by the PV power station in individual years

.
Fig.9. Variations of active power generated on one entire day by the PV power station on selected sunny days in individual months (the coolest and the sunniest days in the five-year period, in which the highest active energy was obtained)

In order to investigate more precisely the effect of the PV power station on the power grid, electricity quality parameters were measured in the power station on the low voltage side, using the power quality analyser HIOKI 3196 at a 1 s interval. As results from voltage measurements on the LV side (Fig. 10), voltage increases during the day when inverters operate. Active power generated to the grid measured on the LV side (Fig. 11) is characterized by identical variability as the power measured at the MV side (Fig. 9). The negative sign of active power on the LV side (Fig. 11) results from the fact that the measurement was carried out in the same way as for the electricity receiver. As follows from the measurement of reactive power of the fundamental harmonic (Fig. 12) at the time when the panels do not operate (at night) inverters receive capacitive reactive power, and when the PV panels operate, they receive inductive reactive power and capacitive reactive power [14, 15, 16, 17, 18]. This is also confirmed by the measurement of the power factor (Fig. 13). The capacitive reactive power load of the fundamental harmonic during the time when the panels do not operate may be caused by the power consumption by cables supplying the inverters and the capacitive character of the PN semiconductor connectors in the photovoltaic panel.

Fig.10. Variations of RMS voltage on the LV side of the PV power station
Fig.11. Variations of active power generated within three days by the PV power station
Fig.12. Variations of reactive power value of the fundamental harmonic generated within three days by the PV power station
Fig.13. Variations of the power factor of the load drawn for three days by the PV power station

The measurement of higher harmonics of currents (relative values related to the first harmonic) generated by the power plant on the LV side shows that during the operation of PV panels (Fig. 14 and Fig. 15), the content of individual harmonics does not exceed 1%. The situation changes with lower values of currents generated to the grid (Fig. 16) and when the PV panels do not operate, i.e. at night. However, the values of individual harmonics in the load current (Fig. 17) do not exceed 40 A when inverters are in operation, and 1 A when inverters do not operate. During the start-up of the inverters, individual harmonics reach the values up to 100%, THDI (Fig. 18) even to 500%, and TiHDI to 100% (Fig. 19). At night, the values of some harmonics exceed 10%. This situation is caused by a very low value of the active component of current and its significant deformation. Inverters have a negative effect on voltage deformation in the low voltage grid to which they are connected (Fig. 20 and Fig. 21). The values of individual harmonics in the supply voltage do not exceed the permissible values specified in the standard [13] and the total content of higher harmonics in the supply voltage (Fig. 20).

Fig.14. Variations of higher harmonics of currents generated by the PV power station on the LV side
Fig.15. Variations of higher harmonics of currents generated by the PV power station during the start-up on the LV side
Fig.16. Variations of the RMS current on the LV side of the PV power station
Fig.17. Variations of higher harmonics of currents generated by the PV power station on the LV side
Fig.18. Variations of the content of higher harmonics of THDI currents generated by the PV power station on the LV side
Fig.19. Variations of the content of higher harmonics of TiHDI currents generated by the PV power station on the LV side
Fig.20. Variations of higher harmonics of voltages on the LV side
Fig.21. Variations of the content of higher harmonics of voltages on the LV side
Remarks and conclusions

The measurements conducted and the analysis of results lead to the following conclusions:

– The photovoltaic power station is characterized by a very high dependence of the active power supplied to the power grid on the season. In November, December, January and February, the power station supplies to the grid only 20% of the energy supplied in summer months (Fig. 7).

– At the latitude of 53° 46′, the photovoltaic power station never reached its rated power (Fig. 6). On some days and hours (12-13), the power plant reached 90% of its rated power, i.e. the power of the PV panels installed.

– The 1 MW power station at our latitude generates about 880 MWh of electricity during a year (Table 3).

– A significant amount of energy generated during the year by the PV power plant originates from the months from April to September (Fig. 7 and Fig. 8),

– The power station draws a very low reactive power of the fundamental harmonic, amounting to 2% of the apparent power (Fig. 12).

– At the time when panels do not generate power, reactive capacitive power is drawn from the grid, and when PV panels operate, reactive inductive and capacitive power of the fundamental harmonic is drawn from the grid. The power ratio changes at that time very dynamically (Fig. 13).

– The power plant generates low values of higher harmonics during operation (Fig. 14, Fig. 15, Fig. 17, Fig. 18 and Fig. 19), not exceeding 40 A (1%) for individual harmonics. However, during the start-up of the power station, when the operating current (Fig. 16) is low, the power station generates to the grid very high values reaching up to 100% for individual harmonics of currents, and the total harmonic distortion in the load current is even up to 500%. At night, inverters collect (generate) to the grid capacitive current of the content of higher harmonics reaching up to 15%.

– Inverters have a very negative effect on the low voltage power supply network (Fig. 20) distorting the network voltage from about 1% (when they do not operate) to about (2-3)% on average during the inverter operation, and in the peaks, the content of higher harmonics reaches even (6- 8)%. A distorsion of THDI current consumed by a photovoltaic power station at the start of inverters or at night (when inverters do not work) (Fig. 17 and 18) is manifested by an increase in the content of higher harmonics of THDU supply voltage (Fig. 21 and 22). “Spikes” in currents (Fig. 17) caused by an increase in the higher harmonics value of currents appear, at the same time, in the form of “spikes” (value increase) in higher harmonics of voltages (Fig. 20) and in THDU (Fig. 21).

LITERATURE

[1] Jastrzębska G.: Ogniwa słoneczne. Budowa, technologia i zastosowanie [Solar cells. Construction, technology and application], Wydawnictwa Komunikacji i Łączności, Warszawa, 2014
[2] The Act amending the Renewable Energy Sources Act and Some Other Acts of 7 June 2018, Dz.U. 2018 item 1276
[3] Sztymelski K.: Analiza uzysków rzeczywistej instalacji PV typu on-grid o mocy 2 kWp. Porównanie z symulacjami [An analysis of yields of a real 2 kWp PV on-grid plant. Comparison to simulations], XLI SPETO 2018 Conference, 91-92
[4] Piotrowski P.: Analysis of variable selection in the task of forecasting ultra-short-term production of electricity in solar systems, Electrotechnical Review. R. 90, No. 4 2014, 5-9
[5] Mazur. D., Żabiński T.: Prognozowanie wytwarzania energii z odnawialnych źródeł energii [Forecasting energy production from renewable energy sources], XLII SPETO 2019 Conference, 69-70
[6] Dobrzycki A, Ambrozik P.: Analiza wpływu elektrowni fotowoltaicznej na sieć elektroenergetyczną [An analysis of the effect of the photovoltaic power station on the power grid], Poznań University of Technology Academic Journal, No. 89, 2017, 321-333
[7] The Energy Law Act of 10 April 1997. Dz. U. 1997 No. 54 item 348 as amended
[8] The Renewable Energy Sources Act of 20 February 2015. Dz. U. 2015 item 478 as amended
[9] The Construction Law Act of 7 July 1994. Dz. U. 2019 item 1186
[10] The Environmental Protection Law Act of 27 April 2001. Dz. U. 2001 No. 62 item 627
[11] The Act on Providing Information about the Environment and its Protection, Public Participation in the Environmental Protection and on Environmental Impact Assessment of 3 October 2008. Dz. U. 2008 No. 199 item 1227
[12] The Regulation of the Council of Ministers of 10 September 2019 on projects which may significantly affect the environment. Dz. U. 2019 item 1839
[13] PN-EN 50160: 1998. Supply Voltage Parameters of Public Distribution Grids
[14] Goergens P., Potratz F., Godde M., Schnettler A.: Determination of the Potencjal to Provide Reactive Power from Distribution Grids to the Transmission Grid Using Optimal Power Flow. IEEE 50th International Universities Power Engineering Conference (UPEC), 1-4 Sept. 2015, 1-6
[15] Turitsyn K., Sulc P., Backhaus S., Chertkov M.: Options for Control of Reactive Power by Distributed Photovoltaic Generators. Proc. IEEE, Vol. 9, No. 6, Jun. 2011, 1063-1073
[16] Kundu S., Backhaus S., Hiskens I.: Distributed Control of Reactive Power from Photovoltaics Inverters. IEEE International Symposium on Circuits and Systems (ISCAS2013), 2013, 149-252
[17] Maknouninejad A., Kutkut N., Batarseh I.: Analysis and Control of PV Inverters Operating in VAR Mode at Night. IEEE Conference ISGT, 2011, 1-5
[18] Sarkar M., Meegahapola L., Datta M.: Reactive Power Management in Renewable Rich Power Grids: A Review of Grid-Codes, Renwable Generators, Support Devices, Control Strategies and Optimization Algorithms. IEEE Access, Vol.6, 2018, 41458-41489


Authors: dr inż. Andrzej Lange, University of Warmia and Mazury, Department of Electrotechnology, Power Industry, Electronic and Automation, ul. Oczapowskiego 11, 10-736 Olsztyn, e-mail: andrzej.lange@uwm.edu.pl
prof. dr hab. inż. Marian Pasko, Silesian University of Technology, Institute of Electrotechnology and Computer Science, ul. Akademicka 10, 44-100 Gliwice, e-mail: marian.pasko@polsl.pl;


Source & Publisher Item Identifier: PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 96 NR 5/2020. doi:10.15199/48.2020.05.05

Substation Shielding Methods for Lightning Strikes

Published by Lorenzo Mari, EE Power – Technical Articles: Substation Shielding Methods for Lightning Strikes, December 04, 2020.


This article explains different substation shielding techniques used to reduce the chance of and damage from direct lightning strikes.

Direct lightning strikes to transmission lines or substations may damage the electrical equipment and threaten any nearby personnel. 

This article focuses on the current lightning interception methods that engineers use to protect substation equipment and people from lightning flashes. Note that this article specifically looks at protection from direct strikes.

Substation Characteristics

Substations typically consist of: 

• Incoming and outgoing overhead lines
• Buses
• Circuit breakers
• Switches
• Transformers (power, current, and potential)
• Auxiliary equipment (such as carrier-current capacitors)
• Buildings

Steel structures support the line terminations, buses, and switches. The steel structures, circuit breakers, and power transformers lay on concrete foundations buried below grade.

Such substations should be protected from direct lightning strikes and from traveling waves arriving through the overhead lines. The purpose of grounding for lightning protection is to provide a secure and certain path for conducting lightning surges to Earth, protecting people and facilities.

Lightning Interception Methods

The main methods to protect substations from direct lightning strikes are:

• Protective angle and protective zone
• Electro-geometrical
• Rolling sphere
• Mesh

Let’s look at each of these methods in detail.

The Protective Angle and Protective Zone Method

Employed for shielding power lines and substations for many years, the protective angle and protective zone method gives reasonable protection. Until recently, it was the method recommended by lightning protection standards. 

The method consists of shielding by overhead ground wires, masts, or rods (Franklin’s rods). The ground wires run over the substation so that all equipment lies in the protected zone. The ground wire’s protective angle is between a vertical line through the ground wire and a diagonal line connecting the ground wire and the object to protect, as shown in Figure 1.

Figure 1. Ground wire’s protective angle α.

The ground wire’s protective zone is the volume between the base plane cbc and the diagonal planes ac, extending from the ground wire to the object’s plane. Figure 2 shows a cross-section of this volume.

Figure 2. Cross-section of the ground wire’s protective zone.

From Figure 2, the protective ratio is k=ky/y and the protective angle is α = tanˉ¹k.

Likewise, Figure 3 shows a cross-section of the protective zone for a mast or rod of height = y. In this case, we say that there is a protective cone around the mast or rod. As before, the protective ratio is k=ky/y and the protective angle is α = tanˉ¹k.

Figure 3. Cross-section of a mast or rod protective cone.

Over the years, many researchers have worked to determine the best figures for the protective ratio and the protective angle. Table 1 shows typical values still employed.

Table 1. Typical Value Employed for Protective Ratio and Angle

.

The designers allow a reduction of the angle as the protective device – ground wire, mast, or rod – height increases because those angles may be inadequate for tall structures.

The size, shape, and quantity of objects to protect establish the total number of grounding wires, masts, or rods to install. Protective devices should be sufficient to cover the entire substation, including the apparatus outside and on the main structure’s top. The overlapping of the protective zones decreases the likelihood of direct impacts (Figure 4).

Figure 4. Overhead ground wires protect the substation.

The grounded steel structure is enough to shield the buses and apparatus below it when there are no objects to protect above the substation’s top.

In small substations, masts or rods erected at the corners or columns shield the buses and apparatus falling within their protective cones (Figure 5). Another arrangement employs self-sustaining masts inside and next to the substation.

Figure 5. Vertical masts protect the substation.

The ground wires, masts, and rods must be connected to the substation’s grounding electrode and the overhead lines’ counterpoise system if any.

The ground wires of the incoming and outgoing overhead lines should terminate at the top of the substation’s steel structure — this might require steel columns extending above the main structure. For unshielded lines, the recommendation is running a ground wire for a distance of at least 1 km to reduce the magnitude of the lightning surges entering through the lines.

The Electro-Geometrical Method (EGM)

In the early 1970s, the electro-geometrical method was used to shield power lines from lightning. Later on (around 1976), its use was broadened to include substations.

The striking distance is a crucial concept for understanding the electro-geometrical method.

According to the stepping mechanism’s prestrike theory, before the stepped leader reaches the ground, a discharge similar to the leader rises from the ground to meet it. After the stepped leader establishes a ground connection, a power return strike moves up the ionized channel prepared by the leader.

The EGM theory states that when the stepped leader reaches a critical distance from a grounded structure where the average potential gradient in the gap between the leader tip and the grounded structure is equal to the streamer’s potential gradient, the gap breaks down, attracting the lightning flash to the grounded structure. This critical distance is the striking distance.

In the case of taller structures, the striking distance is the interval from the leader tip to the structure when a streamer is initiating on it.

The first element on a grounded structure within striking distance will be the point of the strike of the lightning flash. The striking distance depends on the return strike peak current; the higher the strike’s current, the greater the striking distance and vice versa.

An important concept is that the shielding system design assumes a strike current of magnitude I1. The resultant shielding might not protect the objects for strike currents I2 < I1 with a shorter striking distance, but will likely guard the items for strike currents I3 > I1 with a more considerable striking distance.

The substation’s shielding intercepts strikes of magnitude I1 or higher. Then, the substation insulation must withstand the resulting voltages, without flashover, when strikes with currents less than I1 in magnitude penetrate the shielding. Setting the design strike current by considering what the system insulation can withstand ensures that the substation will be protected when impacted by strikes with the lower current.

Not all the strikes with peak currents less than I1 will defy the shielding and strike the structures. Depending on the location of the stepped leaders, the shielding will capture some of these strikes.

The Rolling Sphere Method

The rolling sphere method is a derivative of the electro-geometrical method. It uses a fictitious sphere of radius S to locate the lightning protection devices on structures. The term rolling sphere derives from Ralph H. Lee’s studies in the USA (1977) for shielding buildings and industrial plants.

The method starting point is the existence of a spherical volume with a radius equal to the striking distance, positioned around the stepped leader’s tip. The stepped leader will attach to the first point of a grounded structure entering this volume.

The sphere should touch only the protection system elements when it is rolled around the protected structure. Where the sphere touches the equipment or buildings in the substation, lightning strikes are a hazard. In the space between the sphere and ground, lightning is improbable.

Figure 6 shows a tall structure and a rolling sphere of radius S. All points touched by the sphere are unprotected, which shows us that the roof and sections of the walls require shielding.

Figure 6. Sphere rolling over a tall structure.

Figure 7 shows the same sphere with a lower structure. Here, only the roof requires shielding.

Figure 7. Sphere rolling over a low structure.

In a substation, the sphere rolls up and over ground wires, masts, rods, fences, and any grounded metallic object to be protected (Figure 8).

Figure 8. Principle of the rolling sphere method with multiple shielding electrodes. Image from IEEE Std 998.

Figure 9 shows a sphere of arbitrary radius rotating over equipment and a mast in a substation section. Notice the unprotected portions of equipment inside the sphere.

Figure 9. Sphere rolling over equipment and a mast in a substation uncovers unprotected spots. Image based on Verdolin Solutions.

If we recall that the sphere radius – the striking distance – depends on the projected return strike peak current, and that there is less protection for lower currents, the shielding of structures sensitive to lightning strikes should use small currents and small sphere radius as design criteria.

The rolling sphere method allows us to determine the protective cone and the equivalent protective angle of a mast or rod. Figure 10 shows the protective cone (the shaded region wraps around the device) and the equivalent protective angle for two vertical masts using a sphere with a  20m radius. Note that the protective cone and angle figures depend on the device’s height for a constant sphere radius.

Figure 10. Protective cones and angles resulting from the rolling sphere method. (a) Low mast (b) tall mast.

The rolling sphere method applies equally to flat surfaces, sharp points, edges, and corners. This condition is the method’s drawback because field observations on buildings show that most strikes finish on sharp points or projecting corners. Research indicates that the connection of lightning strikes to the structures depends on the prospective return strike peak current and the structure’s geometry. This limitation in the method may cause errors under some circumstances.

The Mesh Method

The only way to make a structure lightning-proof is by enclosing it in grounded metal (Faraday cage), but this solution is not practical. The mesh method consists of enclosing the structure within a conducting mesh, attaining a practical Faraday cage. This method is useful for shielding a substation’s buildings, like the control room.

The method locates a mesh of wires on the top or at a certain distance from the building’s roof and provides down conductors for connection to the grounding electrodes. The cell size and the separation between down conductors depend on the protection level required. Most lightning currents go through the wires and grounding electrodes close to the impact point.

Figure 11. Wire mesh on the top of a building. Image based on Aplicaciones Tecnológicas.

The rolling sphere method confirms the cell dimensions for different levels of protection. Figure 12 shows that, according to the rolling sphere method, lightning can strike the building with the mesh resting directly on the roof. Thus, it is better to allow some clearance between the mesh and the building top.

Figure 12. Raising the wire mesh increases the building’s protection.
A Review of Substation Shielding

The protection of a substation against direct lightning strikes consists of providing secure conducting paths to carry the lightning currents to the ground without damaging equipment and jeopardizing personnel.

The oldest and most straightforward method is the protective angle and protective zone. It uses the protective angle for the location of grounding wires, masts, and rods. The angle α describes an inclined line that limits the protective zone. The structures located within the protective zone are significantly safe from lightning strikes.

In the case of a ground wire, the protective angle results in inclined plane surfaces below which all objects have protection against the lightning strikes. For masts or rods, the protective angle generates a conical surface protecting items below it.

The protection may not be complete if the equipment is beyond the device’s protective zone. Some of the strikes may hit the equipment or people rather than the protective device in such cases.

The protective angle and protective zone concept is rather old-fashioned, and methods have evolved to make protection more accurate. One of these methods is the rolling sphere.

In this method, a sphere is rolled over the protecting structure, and the areas which the sphere cannot touch are within the protective zone. The radius of the sphere depends on the striking distance. The striking distance is the length over which the lightning strike’s final breakdown to ground or a grounded object occurs. Higher levels of protection are achieved when the design of the protection system is based on a sphere of reduced radius.

Currently, the rolling sphere method is widely accepted.

A horizontal conductor network is often used as a protective system on structures with a flat roof, as a means of achieving an effect similar to that of a Faraday cage. This technique is the mesh method. The mesh method places the conductors on the building’s roof and connects them to the ground through down conductors that offer a short conducting path to the earth. The mesh provides multiple ways for the lightning current to flow to the ground.


Author: Lorenzo Mari holds a Master of Science degree in Electric Power Engineering from Rensselaer Polytechnic Institute (RPI). He has been a university professor since 1982, teaching topics as electric circuit analysis, electric machinery, power system analysis, and power system grounding. As such, he has written many articles to be used by students as learning tools. He also created five courses to be taught to electrical engineers in career development programs, i.e., Electrical Installations in Hazardous Locations, National Electrical Code, Electric Machinery, Power and Electronic Grounding Systems and Electric Power Substations Design. As a professional engineer, Mari has written dozens of technical specifications and other documents regarding electrical equipment and installations for major oil, gas and petrochemical capital projects. He has been EPCC Project Manager for some large oil, gas & petrochemical capital projects where he wrote many managerial documents commonly used in this kind of works.


Source URL: https://eepower.com/technical-articles/substation-shielding-methods-for-lightning-strikes-part-3-of-4/

Mitigating Harmonics in Power Systems

Published by Simon Mugo, EE Power – Technical Articles: Mitigating Harmonics in Power Systems, May 04, 2023.


This article will guide engineers in understanding harmonics, causes, types, equations, and sequences and mitigate harmonics effects.

Harmonics are fundamental frequency multiples that have existed since the beginning of the 20th Century when engineers and scientists discovered discontinuous loads, which came as a result of the vacuum tube invention. 

In the beginning, harmonics effects were negligible, and most engineers ignored them. As technology grew and with the invention of sophisticated electronics like electronic lighting, uninterruptible power supplies, programmable logic controllers, and variable frequency drives, harmonics injected power quality challenges. The effects of harmonics on the quality of signals produced by this equipment triggered changes in designs, filtering processes, and installation procedures. 

Despite engineering changes and general awareness, harmonics still need to improve. This article will empower you with key knowledge to mitigate harmonics.

Defining Harmonics

In an electrical power system, harmonics can be defined as the multiple of the current or voltage at the fundamental voltage frequency. Anytime you observe a waveform, and it deviates from the expected sinewave shape, it contains harmonics.

Causes of Harmonics

Linear or nonlinear AC signals are categorized according to how the systems draw power from the supply source. Harmonics are caused by the nonlinear systems which draw currents in short, abrupt pulses. The drawn pulses disrupt the waveforms of the current by causing distortion. The distortion generates harmonics which lead to power problems, affecting the load and the distribution system. Examples of nonlinear load systems include electronic devices like TVs.

Fundamental Electrical Harmonics

This is where power originates from the generator. Its frequency is referred to as fundamental frequency or first harmonic frequency. Its value is either 50 Hz or 60 Hz, depending on your country’s choice. All electrical and electronic systems are made to work well under this frequency.

Figure 1. Fundamental harmonics waveforms. Image used courtesy of Simon Mugo
Harmonics Orders and Complex Waveforms
Second-order Harmonics

Second-order harmonics are waveforms with frequencies at 100 Hz – that is, 50 Hz multiplied by two. This is an indication that the second harmonics have a frequency twice the fundamental frequency. Below are the waveforms for the second harmonics.

Figure 2. Second-order harmonics waveform demonstration. Image used courtesy of Simon Mugo

From the waveform graph above, when the fundamental harmonics get to zero, it gets to its high value, and so on. This is the reason the second harmonic initiates the reverse direction, implying the negative sequence current flows in the given electrical circuit. The negative sequence current affects the induction motor, where it opposes the rotating magnetic field. The result of the opposition is that the motor produces lower mechanical torque than expected. This type of harmonic is also known as the negative sequence.

Third-order Harmonics

This has a frequency triple that of the fundamental harmonic. The frequency is 150 Hz. This is a very dangerous type of harmonic. Below is its waveform.

Figure 3. Third-order harmonics waveform. Image used courtesy of Simon Mugo

From the graph, both third and fundamental harmonics currents reach zero at the same time. They both get high at the same value, but the points are opposite each other. This action makes the harmonics create a zero-sequence current, leading to an increase in the power system’s neutral voltages. Increasing the neutral voltage causes the relay to operate a circuit breaker. This effect is caused by the third harmonic current. The third harmonic is also known as triplens.

Fourth-order Harmonics

This has a frequency of 200 Hz, which is four times the fundamental frequency. Below is the figure of the waveforms.

Figure 4. Fourth harmonic waveforms. Image used courtesy of Simon Mugo

When the fundamental harmonic current gets to the highest value, the fourth harmonic does the same too. From the graph, this is true for both the negative and the positive sides. This is why such harmonics increase the current that flows in a conductor, which increases the equipment temperature. It is also known as positive harmonic.

Fifth-order Harmonics

Fifth-order harmonics have a frequency of 250 Hz and characteristics similar to third-order harmonics but with a higher operating frequency. Below are the waveforms for the harmonic.

Figure 5. Fifth-order harmonic waveforms. Image used courtesy of Simon Mugo
Waveform Analysis

From the waveforms above, it is clear that a complex waveform comprises a combination of the harmonics and fundamental waveform, each having its phase angles and pick values.

For a simple example, if we have the fundamental frequency given as E=Vmax(2πft) we can calculate the values of the harmonics as shown below.

Second Harmonics
.
Third Harmonics
.
Fourth Harmonics
.

Where 2πf=ω
This process goes on and on for higher orders of harmonics.
Therefore, the equation for the complex waveform can be deduced a

Harmonic Sequencing

Below is a summary of the harmonic sequencing, demonstrating how the frequency changes from fundamental frequency to higher orders.

Table 1. Table of Harmonic Sequence

.

Some systems use the 60 Hz fundamental frequency. The same harmonics apply under a similar calculation method.

Table 2. Harmonic Effects

.
Harmonics Summary

From the article, it is clear that:

• Harmonics is the deviation of the fundamental frequency in multiples of two or more.
• Harmonics leads to an increase in heat generated by a system, the amount of voltage currently released by an object, and it affects the torques released by motors.
• Fundamental harmonics have a frequency of 50 Hz or 60 Hz, depending on the country’s choice.
• Harmonics is defined as the multiple of the current or voltage at the fundamental frequency.
• Fundamental electrical harmonics is where power originates from the generator and its frequency. The frequency at fundamental electrical harmonics is referred to as fundamental frequency.
• Second-order harmonics have frequencies of 100 Hz – or 50 Hz, the value of fundamental frequency multiplied by two.
• Third-order frequency is triple the fundamental frequency meaning its frequency is 150 Hz.

Image used courtesy of Simon Mugo


Author: Simon Munyua Mugo is a Mechatronic Technical Tutor and Head of Research and Innovation at Mumias West Technical and Vocational College, Kenya. He has a Bachelor of Science in Mechatronic Engineering from Dedan Kimathi University of Technology, Kenya.


Source URL: https://eepower.com/technical-articles/mitigating-harmonics-in-power-systems/

Wind Plant IEEE Std. 519 Compliance Evaluation

Published by Electrotek Concepts, Inc., PQSoft Case Study: Wind Plant IEEE Std. 519 Compliance Evaluation, Document ID: PQS1201, Date: January 25, 2012.


Abstract: This case study presents the results for a wind plant substation IEEE Std. 519 harmonic measurement compliance evaluation. The wind plant substation supplied 65 wind turbine generators and the power quality monitor was connected to the 34.5 kV transformer secondary winding, which was considered the point of common coupling (PCC) for the harmonic analysis.

INTRODUCTION

A wind plant substation IEEE Std. 519 harmonic measurement compliance case study was completed for the 34.5 kV wind plant substation shown in Figure 1.

Figure 1 – Illustration of Oneline Diagram for Harmonic Measurement Data Evaluation

The wind plant substation was supplied from a 230 kV transmission line and included a 180 MVA, 230/34.5/13.8 kV step-down transformer with a number of 34.5 kV collector circuits supplying 65 2.3 MW (690 V secondary) Type 4 full conversion wind turbine generators. The monitor was connected at the 34.5 kV transformer secondary, which was considered the point of common coupling (PCC).

The twenty-four day monitoring period was from November 16, 2009 through December 13, 2009. The power quality instrument used to complete the harmonic measurements was the Dranetz Power Xplorer PX5. The instrument samples voltages and currents at 256 points-per-cycle and follows the IEC 61000- 4-7 method for characterizing harmonic measurement data. This involves analysis of continuous 200msec samples and storing aggregated 10-minute minimum, average, and maximum trend data. The measurement and statistical harmonic analysis was completed using the PQView® program.

MEASUREMENT DATA ANALYSIS

Figure 2 shows the measured total plant power production during the twenty-four day monitoring period. Statistical analysis of the 61,901 individual steady-state power measurements yielded an average value of 27.081 MW, a maximum value of 144.872 MW, and a CP95 value of 129.203 MW. CP95 refers to the cumulative probability, 95th percentile of a value.

Figure 3 shows the measured total plant rms (Phase A) current trend. The corresponding phase current histogram is shown in Figure 4. The average value was 543 A, the maximum value was 2,449 A, and the CP95 value was 2,177 A (130 MVA). The CP95 value was used for the facility load current rating in the IEEE Std. 519 harmonic analysis.

Figure 2 – Measured Total Plant Power Production
Figure 3 – Measured Total Plant RMS Current Trend
Figure 4 – Measured Total Plant RMS Current Histogram

The IEEE Std. 519 harmonic voltage distortion limits for the wind plant installation are summarized in Table 1. The harmonic measurement data is evaluated on a statistical basis where the limit must be met 95% of the time (CP95).

Table 1 – IEEE Std. 519 Voltage Limits for the Wind Plant Substation

.

Figure 5 illustrates the corresponding measured total harmonic voltage distortion (THD) trend with an overlay of the IEEE Std. 519 total distortion (VTHD) limit of 5%. The average value was 2.18%, the maximum value was 4.23%, and the CP95 value was 4.09%. The measured voltage distortion was below the IEEE Std. 519 limit of 5%.

The harmonic current limits for the wind plant installation that are summarized in Table 2 are applied to the currents measured at the point of common coupling (PCC). The short-circuit ratio is not relevant for this application because the standard stipulates that power generation equipment must meet the most stringent limits. The limits are for the worst-case normal conditions lasting longer than one hour. For shorter periods, such as during start-ups or unusual operating conditions, the limits may be exceeded by 50%.

The standard provides the current limits as a percentage of IL, the maximum load current. The measured CP95 value of the load current was 2,177 A (refer to Figure 4). Table 3 shows the resulting current in both percent and amperes. Each of the lower order harmonic currents (h<11) must be no more than 4% of the maximum load current.

Table 2 – IEEE Std. 519 Current Limits for the Wind Plant Substation

.

Table 3 – Harmonic Current Limits at the PCC

.
Figure 5 – Measured Total Harmonic Voltage Distortion Trend

Figure 6 shows the measured total demand distortion (TDD) current trend with an overlay of the IEEE Std. 519 current distortion limit of 108.9 A. The average value was 35.75 A, the maximum value was 54.55 A, and the CP95 value was 51.65 A. The measured total demand current distortion was well below the IEEE Std. 519 limit of 5% (or 109.8 A).

Figure 7 shows the measured 5th harmonic current distortion trend in amperes with an overlay of the IEEE Std. 519 current distortion limit of 87.1 A. The average value was 11.63 A, the maximum value was 28.92 A, and the CP95 value was 23.24 A. The measured 5th harmonic current distortion was below the IEEE Std. 519 limit of 4% (or 87.1 A).

Figure 8 shows the measured 7th harmonic current distortion trend in amperes with an overlay of the IEEE Std. 519 current distortion limit of 87.1 A. The average value was 30.91 A, the maximum value was 48.01 A, and the CP95 value was 43.80 A. The measured 7th harmonic current distortion was below the IEEE Std. 519 limit of 4% (or 87.1 A).

Figure 6 – Measured Total Current Demand Distortion Trend
Figure 7 – Measured 5th Harmonic Current Distortion Trend
Figure 8 – Measured 7th Harmonic Current Distortion Trend

Figure 9 shows the statistical summary of total harmonic voltage distortion (VTHD) and a number of the individual harmonics for the twenty-four day monitoring period. The analysis shows that the predominate harmonics for the measured substation bus voltages were the 5th, 7th, 11th, and 13th. The measured values were below the IEEE Std. 519 voltage distortion limits, which were 5% THD and 3% for any individual harmonic.

The statistical summary in Figure 9 corresponds to the voltage distortion measurement data previously shown in Figure 5 (voltage distortion trend). Statistical analysis of the measurement data yielded a CP05 of 0.75%, an average distortion of 2.18%, and CP95 value of 4.09%.

Figure 10 shows the corresponding statistical summary of total harmonic current distortion and a number of the individual harmonics for the twenty-four day monitoring period. The analysis shows that the predominate harmonics for the measured substation currents were the 5th, 7th, 11th, and 13th. The base current for the statistical summary was 2,177 A, which was the CP95 load current value previously used in the IEEE Std. 519 evaluation.

The statistical summary in Figure 10 corresponds to the harmonic current data previously shown in Figure 6 (current demand distortion trend). Statistical analysis yielded a CP05 value of 0.74%, an average current of 1.64%, and a CP95 value of 2.37%. Analysis of the measurement results showed that the harmonic currents did not exceed the IEEE Std. 519 TDD limits during the twenty-four day measurement period.

Figure 9 – Measured Statistical Summary of Voltage Distortion and Harmonics
Figure 10 – Measured Statistical Summary of Current Distortion and Harmonics
Figure 11 – Example of a Calculated Substation Current Waveform

Figure 12 shows the corresponding calculated voltage waveform created using the measured harmonic spectrum data. The fundamental frequency voltage was 20.395 kV, the rms voltage was 20.089 kV, and the voltage distortion was 3.33%.

Figure 12 – Example of a Calculated Substation Voltage Waveform
SUMMARY

This case study summarizes a wind plant substation IEEE Std. 519 harmonic measurement compliance analysis for a twenty-four day monitoring period. The wind plant substation supplied 65 2.3 MW wind turbine generators (149.5 MW total). The monitor was connected to the 34.5 kV transformer secondary winding, which was considered the point of common coupling (PCC) for the harmonic analysis.

The twenty-four day monitoring period was from November 16, 2009 through December 13, 2009. The power quality instrument used to complete the harmonic measurements was the Dranetz Power Xplorer PX5. The instrument samples voltages and currents at 256 points-per-cycle. The measurement and statistical harmonic analysis was completed using the PQView® program. Analysis of the measurement results showed that the harmonic voltages and currents did not exceed the respective IEEE Std. 519 limits during the twenty-four day measurement period.

Mitigation alternatives for reducing harmonic distortion levels include methods for modifying the power system to reduce or eliminate the harmonic resonances that can cause very high current or voltage distortion levels. For example, a passive shunt harmonic filter may be added to the utility or customer system to divert the troublesome harmonic currents off the system and into the filter.

In addition, the rating of power factor correction capacitor banks may be changed to shift the harmonic resonance frequency and reduce the resulting voltage distortion levels. This is often one of the least expensive options for both utilities and their customers. Voltage regulation and power factor correction considerations should be evaluated before changing capacitor bank ratings.

REFERENCES

1. IEEE Recommended Practice for Monitoring Electric Power Quality,” IEEE Std. 1159-1995, IEEE, October 1995, ISBN: 1-55937-549-3.
2. IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems, IEEE Std. 519-1992, IEEE, ISBN: 1-5593-7239-7.

A 3 kV DC Electric Traction System Modernisation for Increased Speed and Trains Power Demand – Problems of Analysis and Synthesis

Published by Adam SZELĄG, Tadeusz MACIOŁEK, Politechnika Warszawska, Instytut Maszyn Elektrycznych


Abstract. A 3 kV DC supply system, used on railways in Poland, since 1936, has power delivery capacity that allows reaching by trains a maximum speed of 250 km/h. Currently, the maximum trains service speed on Polish railway is 160 km/h, although speed record reached in 1994 was 250,1km.Therefore, it is worth modernising the system to increase power demand of trains with speeds 200-220 km/h, which will start service in year 2014. It requires application of proper methods to find compromise between the required effectiveness and the cost of the investments. The paper presents a system approach for analysis and synthesis of the 3 kV DC supply system used in a process of feasibility studies including a concept and a preliminary design.

Streszczenie. Stosowany na kolei w Polsce od 1936 r. system zasilania 3 kV DC pozwala na zasilanie pociągów osiągających maksymalne prędkości 250 km/h. Obecnie maksymalna prędkość pociągów na kolei w Polsce nie przekracza 160 km/h, aczkolwiek rekord prędkości osiągnięty w Polsce w 1994 r. wyniósł 250,1 km/h. Dlatego istotne jest, aby przeprowadzić modernizację zasilania trakcyjnego dla zapewnienia wymaganej energii dla pociągów o prędkościach 200-220 km/h, które pojawią się w 2014 r. Wymaga to zastosowania odpowiednich metod, aby uzyskać kompromis pomiędzy wymaganą efektywnością zasilania a kosztem inwestycji. W artykule przedstawione jest systemowe podejście do zagadnień analizy i syntezy stosowanych w procesie projektowania trakcyjnego układu zasilania, 3 kV DC w projektach koncepcyjnych i wstępnych dla celów studiów wykonalności (Modernizacja systemu zasilania trakcji elektrycznej 3 kV DC dla zwiększonego poboru energii pociągów o podwyższonej prędkości jazdy – zagadnienia analizy i syntezy)

Keywords: electric traction system, system analysis, modelling and simulation, power demand.
Słowa kluczowe: system trakcji elektrycznej, analiza systemowa, modelowanie i symulacja, zapotrzebowanie na energię.

1. Introduction

Last year plans of construction of the so-called Y high speed railway line with maximum speed over 300 km/h with 2×25 kV 50 Hz power supply, postponed by the Polish Government, caused that focus has been put back at the 3 kV DC traction power supply system which has been used in Poland since 1936, but its power delivery capacity has not been reached. So it is worth analysing how it is possible to maximise usage of 3 kV DC system electrical energy delivery capacity for the increasing power demand and speed of trains over 200 km/h, even up to 250 km/h as it is applied in Italy at Dirretissima railway line [2]. A system analysis makes a useful tool for preliminary study and a concept design of an electrified transport system.

List of the used symbols:

ETS – electric traction system
PSN – AC power supply network,
TPSS – traction power supply system,
ETV – electric traction vehicle,
TS – traction substation

2. Electric transport system

Elements of both the analysis and synthesis appear in the examination of issues and phenomena related to the functioning of the ETS. Therefore, methods with application of ETS subsystems models and their implementation, which allow the introduction of elements of the analysis – e.g., determination of a group of functional parameters of ETS power supply have been developed as [2, 4, 5, 6] substations load, catenary, voltage drops, efficiency, consumption and energy loss, etc. including: environmental conditions on the basis of the input parameters (characteristics) of the system. These include: distances between substations, types of rectifier units installed in the traction substations, catenary sections, the parameters of the electrical power engineering system. Other specified functional parameters are as follows: defined traffic, types of trains, locomotives, time-table with consideration of the technical limitations imposed on the ETS (technical criteria and reliability, the impact of ETS on the surrounding technical infrastructure and the environment – harmonics, voltage fluctuations, and stray currents). Dynamic model of the ETS system can be presented in the generalized manner in shape of a set of equations describing the respective subsystems [3,4,7] (Fig. 1):

.

where: i=1,..,5
and structural equations:

.

where: Xi (t) – vector of state variable of ith subsystem, Yi (t) – output vector of ith subsystem, Ui (t) – control (input) vector of ith subsystem, Zi (t) – vector of disturbances of ith subsystem, Hi – structural matrix.

Dimensions of the matrix structural equations Hi depend on the number and types of ETVs moving along the railway line, the TPPS system and number of traction substations TS as well as their scheme of supply from the power system [1,4,6].

Elements of the analysis will also appear: when evaluating the possibility of maintenance of the existing supply system in the conditions of masses and train speed growth and the introduction of new locomotives with higher power,

– when determining the degree of utilisation of the existing devices installed in the supply system (the use of installed power), the load of wires and rectifier units of traction substations, energy transmission efficiency and power quality,

– when solving problems of compatibility of subsystems (electrical engineering power supply – traction supply system – traction vehicles – control and signalling systems) and electrical devices.

Elements of synthesis involve:

– selection and configuration of DC and AC power supply system (installed power, cross sections of wires, distances, supply voltage at AC side of PSN),

– selection of locomotives proper for a category of trains (mass and speed) for a specified line, based on the requirements for the functioning of ETS (traffic forecast) with consideration of limitations arising from the need of fulfilling the technical criteria (international and national standards and regulations) as well as reduction of distortions introduced by the ETS to the surrounding environment.

Fig. 1 Functional scheme of ETS system after decomposition into subsystems and presentation of exemplary time runs

Fig. 1 Functional scheme of ETS system after decomposition into subsystems and presentation of exemplary time runs (time axis scaled in seconds) of input and output values (TT – time-table; DTT – demanded time-table, RTT – actual (resulted) time-table ,TD – transport demand, TO – transport output; Ic- ETV’s current, Up-voltage in catenary, IDC – TS’s current, UDC – voltage at TS’s busbard, PAC – power taken by TS from PSN).

Due to the fact that the issue of synthesis usually cannot be solved explicitly, some additional criteria are being introduced:

– maximising utilisation of the installed devices power,
– to provide reserve in a case of emergency,
– possibility of overcoming speed reductions by trains with occurrence of traffic disturbances,
– the system’s openness to changes in the traffic volume (the possibility of staging the development of ETS supply system with increase of energy demands from ETVs and maximising the use of existing infrastructure (optimal adaptation of ETS infrastructure for the transport forecast),
– minimisation of energy transmission losses

Combining elements of the analysis and synthesis of ETS results in a complex problem, which will deal with the selection of ETS elements and determination of their parameters (rated power, overload, sections, etc.) and their mutual dependencies (e.g. voltage at the ETV’s collector functioning as dependence between TPSS and ETV or changes of traction substation load giving an influence on PSN, similarly changes of voltage in the PSN have the impact on the operation of traction substation).This refers to the exploited (manufactured) devices as well as to defining the requirements for implementation of new measures due to the defined demand for transport (traffic forecast- traffic flow TD and the resulting demand for electrical energy EE (Fig. 1), functional requirements – quality and reliability of supply, and the interaction between different ETS’s subsystems as well as between ETS and the environment.

In developing new methods for analysis and system design with respect to exploited lines as well as newly constructed, it must be assumed that in principle one is dealing with a complex problem, which combines elements of both synthesis and analysis. All the assumptions made at the stage of analysis of functioning conditions of the existing ETS as well as design of new lines or improvement actions e.g.:

-aiming at: – rationalisation of energy consumption or effective energy consumption (improvement of its usage),
-introduction of a new stock or changes in traffic,
-introduction of new control systems

must take into account existing state of ETS, its parameters and functional requirements. Therefore, all the actions (as forecasts) oriented towards improvements (as increasing efficiency) should result from the analysis of the existing state and then on the basis of results of such an analysis, by application of assumed technical criteria (e.g. rationalising the energy consumption, maintaining the distortion level at permissible limits) lead to changes (choice of modernisation option-elements of synthesis), which will improve or even enable the operation of a system.

Fig. 2a,b Graphs showing exemplary changes of energy delivery capacity of ETS

Fig. 2a,b Graphs showing exemplary changes of energy delivery capacity of ETS (obtained by modernisation stages M1 and M2 of the existing TPSS of the ETS’s) versus time due to increase of demand for energy (blue broken lines) by transport means. Please observe reduction of the energy delivery capacity (RE1<E1, RE2<E2) of TPS during the modernisation processes, which will force reduction of traffic (RE1<D1 during M1; RE2<D2 during M2).b.) modernisation undertaken early enough with lower reduction of capacity (t1 in Fig.2b < t1 in Fig. 2a and RE1 in Fig 2a < RE1 in Fig. 2b) to get the required energy delivery capacity E1 to E3 high enough above the energy demand D1 before its increase to D2 due to traffic increase.

3. Application of a system analysis in the ETS.

The analysis of the ETS system as a research method is used when the situation occurs, in which the state of the system is currently or will in future be unsatisfactory, and it can be anticipated that the actions (modernisation) may improve the situation significantly (Fig. 2). After the analysis we obtain the system description of the situation, as well as courses of action, which will produce positive effects.

The results of such an analysis may be used by policy ma-kers to choose the most advantageous solution due to the certain criteria. In addition, a system analysis allows for the justification of purpose of the selected variant against pressures from the side of interest groups and against the wrong interpretation of the phenomena. It is a crucial factor because the results may have significant influence on the range and cost of the infrastructure modernisation.

The results obtained from the analysis of the system also allow reference to the unexpected events or disturbances in the functioning of the system.

In Fig 2a there is shown time-varying demand for energy used by moving ETVs and effectiveness (energy delivery capacity) of TPSS. Application of a system analysis to ETS allows assessing effectiveness of ETS when increase of demand for energy due to changes in traffic is expected (from D1 to D2). When the effectiveness E1 (energy delivery capacity of the ETS) is becoming close to the energy demand (time point t1) implementation of improvement processes – modernisation is to be started – point A (period of modernisation M1 between t1 and t2 – points A-B, period t4–t5, M2-points C-D). Effectiveness of ETS during modernisations M1 and M2 energy delivery capacity is reduced (for modernisation period M1 – effectiveness RE1 between points B-C and RE2 during M2 – between points C-D) as well as change of demanded energy delivery due to change of traffic (increase from D1 to D2).

As example we could assume the existing two-track ETS with 3 kV DC supply and a bilateral supply scheme with traction cabin TC in the mid-points between neighbouring traction substations TS – fig.3a. As a measure to enhance the energy delivery capacity of ETS, after application of the system analysis, the improvement of ETS to by process of modernisation M1 is undertaken. It may be, for instance, construction of new traction substations in positions of traction cabins (Fig. 3b). This will enhance the effectiveness of the ETS above the increasing demand D (period t2-t4). And again, when as a result of the system analysis it was predicted, that additional modernisation M2 of the ETS is required; a construction of traction cabins TC between traction substations may be done (Fig. 3c). It could slightly improve the effectiveness of the 3 kV DC ETS above the energy demand level (Fig. 2a).

In order to maintain the energy capacity proper for energy delivery even during the modernisation process it is required to start it before the demand will be increased and assure that during the process of the modernisation power capacity will be high enough (Fig. 2b).

System analysis of the assumptions is not conducted for a particular decision maker, but in most cases, the decision maker orders such an analysis so to obtain as much information for undertaking a decision as it is possible. The result should include all the possible consequences of any line of conduct. The analyst should clearly establish the expectations of the decision maker, outline possible alternatives, consider consequences of each option, and then arrange them accordingly to selected criteria. In practice, decisions are not always proceed with accordance to such a scheme, but if it deviates from such a scheme, it occurs only to a minor extent. System analysis related to ETS should also be based on this scheme. To achieve the objectives (such as reduction of electricity consumption by railway vehicles, an increase in average driving speed, reduction of the amount of emergency on the railways, etc.) set by the decision maker, one creates different types of solution variants (e.g. reconstruction of the supplying substation, changes in the profile line, change of traffic, etc.).

To explore the various options, models that can be used to assess the effects of the variant or the cost of its implementation are created. Specifically the cost, effectiveness and feasibility of the option are the important factors [8,9,10].

For different variants may emerge the need to use different models. The use of different models may be necessary to prioritise the options for different purposes. The analysis should end with a rearrangement of variants and be presented to the decision maker together with the effects of each variant. In the majority of issues related to ETS, factors affecting the results are considerable and their mutual relations rather complex. Such a situation causes that intuitive approach will often lead to erroneous and costly solutions. Application of coupled models, in mathematical terms, is necessary for the appropriate formulation of description of ETS functioning and analysis of its operation in different variants of solutions.

4. Procedure for an ETS system analysis

Finding the solution for the improvement of the existing state or choosing the best target variant requires knowledge and clarification, as careful as possible, the aims of decision maker. On such account, one should determine options to achieve these objectives. A further step is to rank the possible options. Implementation of such a procedure will generate further questions. In order to determine the possible variants to achieve, it is not sufficient to be aware of goals, but also to know the area in which the decision maker has the freedom of action. For the ranking or comparison of variants, one may need to anticipate the consequences that will result from implementation of each variant (also those that do not link directly to the realisation of goals). Determination of the consequences of each option requires the use of an appropriate cause-effect model, which will allow the decision maker to indicate the consequences of the choice of a particular variant. Such a model should also take into account the uncertainty of future conditions, such as changes of external conditions other than those assumed in the analysis.

In extreme cases, the variants may differ considerably among themselves, because in principle the implementation of a goal is possible through different ways of proceeding. In such situation it may be necessary to apply various models for different groups of variants. It can be also justified to use models of different degree of specificity depending on the analysis of a state. Main steps of system analysis include:

Main steps of system analysis include:

a) formulation of a problem taking into account assumed goals,
b.) defining and working out the variants,
c.) selection of variants on the basis of constraints,
d.) development of forecasted situations ,
e.) construction of models,
f.) application of models for foreseeing effects,
g.) comparison and ranking of the obtained variants.

Analysis of the results or a preliminary version of final results may lead to a modification of the previous assumptions.

Typical interactive loops that occur are following:

a) improvement options loops, in which occur a modification of parameters in various options for attainment options preferably pursuing the goals; in some cases this process can be implemented by means of optimisation procedures;

b) problem formulation loops, in which on the basis of the results of an analysis the modification of goals is performed;

c) analysis of restrictions loops, in which it is, evaluated how, changes of restrictions influence the degree of goal accomplishment;

d) loops of tuning (adjusting) models, in which particular elements of models or complete models are either simplified, for the purpose of attaining less specific but more certain decisions, or detailed so as to emphasis the more important characteristics of variants.

Furthermore, if one considers that the process of implementation of the selected option may be too long, it must be accounted that the actual conditions, in which the variant is carried out, may differ from those assumed at the stage of analysis. In such case, refinement of options for changeable conditions – during the process of implementtation and if it is possible – correction of a project, can be applied. At each stage of the system analysis contacts of an analyst with a decision maker (or contracting the project) are of high importance. The original formulation of the problem is never exhaustive and does not include the whole spectrum of situations. The results of the analysis have an impact only on the initial view regarding the solutions. Both the goals and the restrictions can be modified during the process of analysis, and the considered time horizons may be a subject to changes.

5. Formulation the problem

Formulation of the problem includes:

-identification of the tasks to be solved,
-determination of the scope of the solutions for these tasks,
-clarification of the objectives,
-determination of what devices and to what extent may the proposed solutions affect,
-initial proposal for the approach to the analysis

Stage of formulation of the problem should give an initial indication of the purpose and if possible, identify the objectives in a quantitative manner, identify preliminary alternatives for analysis, lead to the definition of restrictions and a determination of the expected effects. Formulation of the problem is therefore a very important step, because its correct implementation allows the determination of whether the problem is artificial or trivial, and also provides a framework in which one can move through the later stages of analysis. Difficulties encountered during the formulation of the problem:

a) the interrelations of the subsystems – changes in one subsystem affect other subsystems and assessment of impacts of the performed actions in interrelated objectives, constraints and consequences for the individual subsystems is difficult to conduct;

b) the difficulty of determining the goals, without the approximate values of the effects, which will result from the introduction of options, it is difficult to define precisely the objectives;

c.) lack of clear criteria for selection, the decision maker preferences may be difficult to define, and they may change within time.

Therefore, this step should be the object of application of a system analysis.

The goal, which designates the decision maker (e.g. ETS operator) to be achieved, can be declared in a more or less detailed manner (“energy efficiency”), and can also be defined in quantitative terms (e.g. “to reduce traction energy consumption by 10%”, “to reduce transmission losses on the DC network by 20%“,” to reduce demanded peak power by 5%”, etc.).

The decision maker may seek to achieve different objectives. Sometimes the decision maker gives only the most important goals while an analyst (project contractor) must be aware of the possibility of unspecified purposes or purposes given in the form of restrictions. Usually, while solving issues the decision maker determines several goals, among which there are competing goals, that is, that the improvement in one of these objectives leads to deterioration in other aspects (e.g. efforts to reduce losses increase requirements for installed power, which in turn increases the idle losses of transformers). In this case, one should use the following approach:

a) determine the sequence of objectives;
b) identify the most important goal;
c) all the objectives should be transformed into restrictions and one should seek solutions possible to be implemented,
d) establish evaluative system by ranking goals.

With the overall goal of rationalization of energy consumption on the railways, the decision maker may also have other objectives: to increase the average speed of selected categories of trains, improve comfort, increase safety on the railway lines, improve punctuality, and reduce failure rates. Some of these goals are competitive, while other can be achieved in the same ways of implementation (e.g., by reducing gradient of track energy consumption for traction purposes is reduced and also the ride comfort is increased).

To evaluate the analysed options one should have a measure value of the effects, which are brought by each of variant. Some of the results are easy to estimate numerically, while other – the more abstract – are not. The efficiency of the power system, the maximum power demand or the global energy consumption on the railway line can be written in the form of numbers, and parameters such as: ride comfort requires preparation of tools to describe this rather abstract and ambiguous concept (e.g., through the application of special tariffs for journeys with a high standard of the offered transport service).To compare the options it is not enough to describe the quantitative results obtained in each of them. One should use the criteria enabling the proper ranking of the options.

However, since there are often not universal, objective criteria for sorting options, so in each individual case, such criteria should be established, mainly on the account of the value scaled by the decision maker. Using these criteria, one can also take into consideration the opinion of external factors, which will be influenced by the effects resulting from the implementation of a given variant.

During the formulation of the problem one must also specify the area of restrictions. They may arise from the physical properties of the analysed systems (e.g. power capacity of the supply), but also from the accepted standards (e.g. level of voltage in catenary) or imposed require-mints (e.g. density of traffic or maximum power of trains). These variants, which are not prohibited by the restrictions (do not meet the criteria) are called permissible or attainable.

Some restrictions are permanent and can never be exceeded (e.g. cross-section of catenary due to applied type of support structures), some may change over time (as increase of power capacity due to investments in power supply system) and due to the change in requirements (e.g. change in assumed time-table and type of locomotives), and some are imposed by the top-down decisions. For the restrictions that could be alleviated (e.g. density of traffic), the analyst should carry out the consideration of how such alleviation would affect the achievement of the objectives (e.g. lower density of traffic may require bigger mass of trains), and what would be costs of such restrictions reduction.

In the analysis of the phenomena occurring in the ETS, the restrictions may include: technical parameters of the vehicles and the supply system, speed limits on the sections of the line, minimum voltage at the pantographs of trains. A restriction may also constitute a lack of opportunity of location traction substations at the specific point of the ETS or change in the type of catenary or lack of possibility to implement a freely shaped time-table.

6. Creation and selection of variants

Variants taken into consideration during a system analysis can vary considerably. They do not have to constitute their substitutes and do not have to assure the performance of the same functions.

The initial stage of variants’ creation should com-prise all the possible ways of proceeding, so giving at least partial chances for the accomplishment of objectives. In the set of analysed variants, usually the so called „zero” (do nothing) option is included. This variant is mainly used for comparative purposes (as a ‘reference option’).

Usually during the analysis of the selected variants occur new variants, which at the beginning have not been known to the both analyst and decision maker.

For the purpose of an exemplary task of rationalisation of energy consumption of ETS, a range of creation of diverse variants may be wide. This may include: changes in time schedule, rolling stock replacement, reconstruction of the supply system or even the reconstruction of the whole line (e.g. alleviation of the route profile). Each of the variants can to various extent influence the achievement of a goal and costs of their implementation are also diverse. For these or even other methods aiming at reduction of energy consumption on railway lines, it is possible to create a huge amount of options to be considered. Since the number of variants that have been generated at the beginning of the analysis may be large, they should undergo a pre-selection. Many variants can be rejected at the outset, because they do not comply with the restrictions. This can be observed using very simplified models, which give approximate results. In this manner, variants that are worse than others, at least in one aspect and in other aspects no better than remaining options can be eliminated.

Further stages should be conducted on detailed models with respect to quantitative parameters. The last stage of the ETS analysis should, in a possibly full and accurate manner, describe the processes occurring after the implementation of various options, so as the decision maker knows the extent to which each of they pursue goals and what are the further effects. At this stage one can enter the optimisation procedures. Multi-criteria optimising algorithm can be applied with usage of a scalarization approach and a goal function or penalty function defined for the optimisation algorithm.

Since the parameters, on which we have the influence, usually do not change continuously (e.g. it is impossible to select smoothly the cross-section of catenary, power supply and transformers parameters, numbers and parameters of rectifier units) the number of possible variants is significantly narrowed and the search for global analytical solution is not justified. In that case it is possible to use any of the random algorithms.

To anticipate the effects of the implementation of different options it is necessary to use system models. It is most preferable when models are formalized and written in a mathematical form. On the basis of such models one can develop the computer implementation of models in order to conduct the simulation tests.

Analysed variants may differ among sets of data assumed. Set of data regarding the state of environment can be taken as constant (when these parameters are strictly defined) or variable (when there is uncertainty about these parameters). In the latter case, it is recommended to conduct a sensitivity analysis of the effects of variants on the changes of the environment state so as to assess the uncertainty of achieving the objectives for each of the variants.

An exemplary division of the electrified railway line parameters at the design stage of this line can be a division into: independent (top-down set)-the size of transport and into dependent (those we have an influence on) -technical parameters of a supply system (to meet the technical criteria for the implementation of the given traffic flow) or organisation of train schedules at a given transport demand.

Obviously, for the proper construction of models it is not enough to know the general form of mathematical equations describing the analysed system as they should be verified and tuned to the actual conditions.

7. Range of applications of modelling and simulation techniques in the ETS

The range of applications of computerised techniques to area of ETS may be enlisted to one of the following groups, due to:

a.) CAD (computer-aided design) during planning stage of the ETS, its subsystems and components,

b.) analysis strategy of operation of the ETS – design of timetables, traffic control, centralised and decentralised control and management of the ETS,

c.)for design of operational service and control system, operational, control, surveillance and decision supporting systems-e.g. methods of optimisation of ETVs motion and operation of TPSS with regard to energy consumption,

d.) the use of specialised software for ETS simulations during steady and dynamic states – for the analyses of supply system loads, main circuits of electric traction vehicles, control and signalisation systems, mutual interactions between subsystems (ETVs-TPSS; high power circuits-track circuits, etc.) and electromagnetic fields- in the range of distorting inference of the ETS and its influence on the surrounding environment and technical infrastructure.

Due to the complexity and multi-aspect nature of phenomena as well as available technical devices, methods of the analysis and design are oriented at considering certain types of problems as:

a.) energy problems (delivered power, energy consumption, energy losses etc.), regarding the phenomena occurring at electrical steady states in AC and DC circuits; for the analysis of such problems it is sufficient to use static models considering the average and equivalent values, such as peak, average and equivalent power and currents of load or stray currents flow ,

b.) electromechanical aspects – concerning both motion and power collection by the ETVs as well as resultant TPSS load, which is associated with energy problems. The mutual interaction of TPSS and ETVs should be taken into account, due to the influence of voltage in a catenary on motiontraction parameters of the ETVs (dependence of voltage in catenary on the ETV’s traction characteristics). The derived models should incorporate dynamics of load changes of TPSS and ETVs motion. Therefore, they have nature of dynamic models (with regard to phenomena of ETVs electromechanical constants values in range of tens of seconds), in which during the analysis of state of the ETS system at the given time step, the ETS state at the previous step is taken into account.

c.) electromagnetic problems and transient states– occurring in much shorter time than the phenomena of electromechanical type (b), which requires the development of models for analysis of the fast-changing phenomena (such as short circuit, overvoltage, transients) and analysis time runs for the content of the component variables (including harmonics) and the resulting ability to assess interferences introduced by ETS to the surrounding technical infrastructure.

d.) problems with traffic and transport management (for set volume of transport, traffic structure, types, masses, train speed). For each group of problems a)-d.) equations take a specific form, thus in the following project, emphasis was put on the proper selection of models for the problem under consideration.

Proper functioning of the ETS is conditioned by, apart from fulfilment of functional requirements (realisation of transport tasks), an attempt to redeem technical requirements and constraints regarding e.g. capacity of energy transmission by TPSS to ETV (groups a. and b.), but also the proper cooperation with both surrounding technical infrastructure and environment.

In case of negative assessment in the analysis with application of models from group c), ETS given variant, even if it turns out to be optimal because of other criteria (e.g. energy consumption) should be rejected as not meeting the basic technical conditions. Solving the subproblems of the system operation may be impaired due to the interferences Z (Fig.1.) occurring in any subsystem (as disruption of traffic organisation, power supply system breakdown, short circuit in the catenary, damage to rolling stock, unplanned slowdown etc.). Therefore, the main task is to maintain the proper functioning of the system even under conditions of interference and the possibility of transition to a state of normal operation (e.g. traffic congestion release, catch up the delay) at the lowest cost (power consumption).

Fig. 3 Stages of modernisation the existing of the ETS (a.), after M1 modernisation (b.) and after next one M2 (c.)

To ensure the functioning of the system in conditions of distortions it is necessary to introduce certain breakdown restrictions in the description of a system operation. These restrictions will depend on the type of corrective actions (improvements) to be taken in case of failure. This approach sometimes requires an algorithm with conditional instructions, the automatic decision-making methodology performed by the simulation program (elements of artificial intelligence) or by the operator from the outside (stop of the program and the need to take a decision on the selection of an algorithm of further simulation or changes in assumptions).

In situation when in the program there are various algorithms of proceeding and choice of solutions, which support the work of operator, in case of a need for intervention, one can speak about elements of an expert system (decision-making support). Such a comprehensive approach to problem analysis and design ETS – selection of technical solutions required to deliver the overarching goal: supply of adequate quantities of electricity of a certain quality parameters to ETV, performing the set transport constitutes a fundamental assumption with respect to the formulation and the required structure of the ETS model system and its subsystems.

Fig. 4 Results of simulations of movement of a 426 t train set with influence of voltage on a rated power Pn availability (50%; 75%; 100%). (Pn=5,5 MW).
Conclusions

The necessity of development and modification of classical methods, established long time ago and used in the analysis and design of ETS ensures from the fact that there was, especially in the country, synthesis approach to issues that takes into account not only the complexity of electrical and mechanical phenomena occurring in the STE but also specificity resulting from local conditions in Poland (such as significantly lower than in other countries which use the 3kV DC power supply options for the ETV because of the large voltage drop in the supply system) and the interaction between the subsystems. An important feature is a combination of a simulation package with blocks of postprocessors analysis, which allows the support of system functioning evaluation (the comparison of set up and executed timetables, meeting the technical criteria, efficiency, energy consumption per unit, introduced distortions, etc). Due to the significance of such issues as compatibility of electrical subsystems and environmental impact as well as energy-electromechanical orientation of developed simulation software, results obtained with the help of programs for ETV’s motion simulation can be supplemented with the use of simulations developed in the course of these project models of ETS subsystems. They are designed for analysis of issues as: interference from higher harmonics, voltage fluctuations or transients in power supply or disturbance emission. This allows for conduction of detailed simulation studies on selected, identified as critical elements for the functioning of ETS conditions of cooperation of selected subsystems in transient states (short-circuit, overvoltages in TPSS and the possible to occur interferences between subsystems TPSSETV and impacts on traffic control circuits. Voltage at the pantograph of the locomotive influences the power developed by the traction drive according to its traction characteristic. It is defined by EN 50-338 standard. In order to put into service with maximum speed above 200 km/h on CMK railway line train sets with nominal power up and above to 6 MW it is required to enhance its traction power supply system. During the performed studies [7] a set of analyses has been performed for different time-tables and variants of operation of the power supply system. The main aim was to find the effective solution to modernise the power supply system to the stage allowing obtaining the required speed with utilisation of the installed on board of vehicles power.

In Fig. 4 there are presented results of simulation of a 426 t train-set with maximum speed of 220 km/h – a theoretical run on a section of track with speed restrictions. – speed “v” versus position of the train. It may be observed influence of the available power (100%, 75% and 50% of nominal power Pn = 5,5 MW) on traction parameters of the train – specifically opportunity of acceleration (as route sections 10000 to 30000 or 165000 m) in a region of higher speeds (above 180 km/h) or maintaining maximum speed, when gradient is increasing (as sections 65000 to 75000 or 195000 to 205000 m). A system analysis with application of the described in the paper method has been worked-out in order to receive the effective power supply system for a defined traffic forecast. It appeared, as a result of the analysis, that it is required to construct additional traction substations TS in locations of traction cabins TC (migration from a scheme 3 a. to 3 b.) in areas, where the power capacity of the supply 3 kV DC system and trains power demand by trains were not balanced with high enough level of voltage in catenary

REFERENCES

[1] Arrillaga J., Smith B. – AC-DC Power System Analysis. IEE London, 1998
[2] Capasso A., Buffarini G.G., Morelli V., Lamedica R. – Supply system characteristics and harmonic penetration studies of the new high speed FS railway line Milan-Rome-Naples. IEE Int. Conference on Main Line Railway Electrification, York (UK), 1989
[3.] Kaczorek T. Teoria wielowymiarowych układów dynamicznych liniowych. WNT, W-wa, 1983.
[4.] Lewandowski M. -A Analiza zjawisk elektromechanicznych w szynowym pojeździe trakcyjnym z uwzględnieniem zmian współczynnika przyczepności kół napędowych Zeszyt “Elektryka” nr 139, OWPW, 2009
[5]. Mincardi R., Savio S., Sciutto G. – Models and tools for simulation and analysis of metrorail transit systems. COMPRAIL’94- Computers in Railways – Fourth Int. Conference on Computer Aided Design, Manufacture and Operation in the Railway and Other Mass Transit Systems, Rome, 7-9 September, 1994
[6] Szeląg A., Mierzejewski L. – Ground transportation systems. (in: The Encyclopedia of Electrical and Electronic Engineering. Volume: Suplement I, John Wiley &Sons, Inc., NY, USA ,2000)
[7] Szeląg A.- Zagadnienia analizy i projektowania systemu trakcji elektrycznej prądu stałego z zastosowaniem technik modelowania i symulacji. Prace Naukowe PW, Seria ELEKTRYKA, s. 178, z. 123, 2002
[7] Szeląg A., Maciołek T., Drążek Z., Patoka M., Urban A., Załuska Z. at all– Ekspertyza dotycząca układu zasilania sieci trakcyjnej linii CMK, praca na zlecenie PKP Energetyka S.A., 2012 (not published)
[8]. PHARE Project no PL 9309/0203 „Power Supply Study for E-20 Railway Line Kunowice-Warsaw section” (ITALFERR, Włochy, Politechnika Warszawska) (not published)
[9] EC Project UserGroup and InfoBank to support rail interoperability. GMA2-2000 32015 Projekt Badawczy V-tego Ramowego Programu Unii Europejskiej. 2002-2003
[10] Projekt EUROPEAID/112846/D/SV/SI, Pomoc Techni-czna we wdrożeniu systemu GSM-R,ERTMS/ETCS i zdalnego sterowania urządzeniami stałymi systemu trakcji elektrycznej sieci kolejowej Kolei Słoweńskich. (Kolprojekt, Holland Railconsult, Austrokonsult, Omegaconsult), 2003 (not published)


dr hab. inż. Adam Szeląg, doc. dr inż. Tadeusz Maciołek Politechnika Warszawska, Instytut Maszyn Elektrycznych, Plac Politechniki 1, 00-661 Warszawa, E-mail Adam.Szelag@ee.pw.edu.pl; Tadeusz.Maciolek@ee.pw.edu.pl


Source & Publisher Item Identifier: PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 89 NR 3a/2013

Seasonality Effect on Working and Prediction of the Production of Electricity in Onshore Wind Farm

Published by Mateusz DUTKA1, Bogusław ŚWIĄTEK1, AGH University of Science and Technology, Department of Power Electronics and Energy Control Systems (1)


Abstract. This paper describes relevant issues of the energy prediction from onshore wind farms. The use of a neural network to forecast wind power production and its resistance to changing seasons is examined. Different structures of neural networks are presented with a comparison of their forecasts accuracy.

Streszczenie. Artykuł opisuje możliwości prognozowania produkcji energii w śródlądowych farmach wiatrowych. Analizie poddano możliwość predykcji z wykorzystaniem sztucznych sieci neuronowych uwzględniających wpływ sezonowości. W artykule zaproponowano różne struktury sieci neuronowych oraz porównano ich skuteczność.(Wpływ sezonowości na pracę i prognozowanie produkcji energii elektrycznej śródlądowej farmy wiatrowej).

Keywords: wind power forecasting, impact of seasonality, BP-neural network, efficiency, energy balancing
Słowa kluczowe: prognozy farmy wiatrowe, wpływ sezonowości, sieci neuronowe, efektywność, stabilizacja systemu energetycznego

Introduction

In many areas of central Europe, in particular in Poland, a rapid development of renewable energy is more than visible. The growing significance of renewable sources entails the necessity of combining customers into groups within a region or a commune and the use of appropriate energy storage [1]. The electricity balance could be managed on the commodity exchange. In this case, the creeping trend model can be useful [2]. The model allows forecasting prices in a 24-hour horizon. The proper preparation of data for further analysis is associated with their normalization [3]. Among all renewables, the wind and the solar energy have been the fastest growing ones. Although in Poland, the construction of the first offshore wind farm is still being discussed, there is a tendency in the construction of inland farms with a growing number of turbines and their total installed capacity. The increasing number of wind farms located in Poland forces investors to locate farms in areas characterized by more difficult weather conditions. Farms are built on smaller areas or near existing farms which introduces interaction between turbines. In particular, when it comes to seasonal variability of wind and its turbulence. In order to increase the accuracy of prediction of wind speed [4], energy production [5] [6] in wind farms, various types of statistical and physical models have been successfully developed [7] [8].

This paper examines three neural network models for energy production forecasts from onshore wind farms, based on the use of artificial neural networks. The main advantage of this method is a relatively short time needed to obtain a good accuracy forecast [3]. The method uses models which were built on the basis of data from the farm and takes into account the impact of seasonality.

Analyzed farm are consists of 15 wind turbines manufactured by Enercon GmbH type E 70 – E4 with rated power 2 MW. The average annual energy production is over 50 000 MWh. The wind park with a total installed capacity 30 MW is located on a hill with the area of 270 ha. The relative height of the plateau is about 150–170 m (350 – 470 m m.a.s.l.). The wind turbines are located approximately 450 m away from one another. Installation height of a generator hub is 85 m, rotor diameter is 71 m, swept area: 3959 m2 . This study uses data from years 2012-2014 (full three years) consisting more than 150,000 vectors (10-minute intervals) registered form the SCADA. The study was performed with the use of following parameters: wind speed, wind direction and the power generated by each of the turbines and the total power generated by the wind farm.

The seasonality impact on work wind farm

The power generated by wind turbines depends significantly on wind speed, but also on the density of air. During the year, weather conditions change periodically. Slight changes in wind speed, temperature, pressure and humidity can evoke a significant change in power generated by the wind turbine. The impact of seasons on wind speed and direction and the volume of production was analyzed.

The following Fig.1-4 show the number of wind speed sets with a resolution of 1 m/s recorded by the turbine. Figures summarize operating conditions of a wind farm as the number of registered occurrences of wind speed in the whole analyzed seasons.

Fig.1. Percentage of the number of occurrences depending on wind speed – spring
Fig.2. Percentage of the number of occurrences depending on wind speed – summer
Fig.3. Percentage of the number of occurrences depending on wind speed – autumn
Fig.4. Percentage of the number of occurrences depending on wind speed – winter

Analyzing the Figures 1-4 differences in wind strength between seasons are noticeable. During the spring and summer wind mostly blows at a speed of 5-6 m/s, during the autumn it increases to 6-7 m/s, while in the winter it reaches even 7-8 m/s. The biggest differences are visible between summer and winter. Although the speed changes to a small extent, it has a significant impact on the quantity of produced energy. Figures 5-6 summarize the frequency and volume of energy depending on the wind direction changing in increments of 15 degrees for two of the most different seasons (summer and winter) when the highest and lowest power outputs are recorded. The distribution of wind directions for both seasons is similar, most of the time the wind blows from the south and south-west.

Fig.5. The frequency and the amount of power of a wind farm depending on wind direction – summer
Fig.6. The frequency and the amount of power of a wind farm depending on wind direction – winter

Fig. 5 and Fig. 6 show two of the most different seasons of the year in which the highest and lowest power outputs are recorded. The distribution of wind directions for both seasons is similar, most of the time the wind was blowing from the south and south-west.

The amount of energy production is strongly dependent on the variable wind speed. Figure Fig. 7 and Fig. 8 below are showing the dependence of power on wind speed for summer and winter.

Fig.7. Power variation depending on wind speed – summer
Fig.8. Power variation depending on wind speed – winter
Fig.9. Difference in power variation depending on wind speed for summer and winter

Fig.7 and Fig.8 shows that different average production volumes for the same wind speeds are visible.

As can be seen in Fig. 9 in winter production is on average even higher by 8% for the same wind speed ranges compared to the summer period for wind speeds of 12-15 m/s,. For a smaller wind speed 3-12 m/s the opposite situation is visible.

Wind power can be described by dependence:

.

where: Pt – turbine power [W], cp – efficiency, D – diameter of the rotor, ρ – air density.

The wet air density can be expressed by the formula:

.

where: ρ – density of air [kg/m3], P – pressure [Pa], T – temperature [K], φ – relative humidity [%], φ=e/E2·100 [%], e – current vapor pressure [Pa], e = E2·φ/100, E1 – maximum vapor pressure [kg/m3], Rps – individual dry gas constant air [J/kg·K], RH2O – individual fixed gas steam [J/kg·K]

As can be seen from the formulas (1) and (2), besides the wind speed there are also other factors that determine the volume of energy production including temperature, humidity or pressure. The table 1 provides additional information about changes to this parameter depending on the season.

Table 1. Summary of characteristic parameters of wind power generation in a seasonal view

.

The average wind speed varies slightly depending on the season, the difference is only 1.8 m/s. Bigger differences are observed for parameters like average, minimum and maximum temperature. An undesirable situation is lowering the temperature below 0°C, which may cause icing of windmill blades. This phenomenon changes the aerodynamics of the blades of windmills and it can result in a significant reduction in the generated electric energy, and in extreme cases, it might cause a damage to the fan. Below zero temperatures were registered in autumn and winter. During this period, a strong increase in the average 15-minute power of a wind farm was observed. An increase of 3.6 MW (autumn) and 4.9 MW (winter) compared to the summer, which is over 52% and 70% of the power-to-average power farm for this season.

Unwanted operating states of wind farm

Over the years 2012-2014 the speed of the wind has varied widely. In order to ensure the safety and maximize the efficiency of wind, farm turbines are subject to restrictions due to the speed of the wind. For the considered wind turbines three ranges of wind speed are defined: Cut-in Wind Speed (0-3 m/s), Rated Wind Speed (3-28 m/s) and Cut-out Wind Speed (more than 28 m/s). An analysis of the frequency of farms in these speed ranges for the data from the years 2012-2014 showed no incidents causing an emergency shutdown of the turbine due to too strong wind (Cut-out Wind Speed more than 28 m/s). During vast majority of 15-minute measurements (over 80% of all measurements), wind speed was in the range of normal operation of the wind farm. The differences in the size of the datasets, depending on season, were in the range of ±6,1%.

Fig.10. Percentage of the number of occurrences for operating mode – four seasons

Because of the climatic conditions in Central Europe, temperatures falling below 0 Celsius degrees, it is necessary to take into account the additional phenomenon of ice on the blades of a windmill. This phenomenon changes the aerodynamics of the blades of windmills and it can result in a significant reduction in the generated electric energy, and in extreme cases, it might cause a damage to the fan.

Building neural models when considering the seasonality

A. Selecting the forecasting models

This chapter presents the results of prediction of the power output of an onshore wind farm operating with 15 turbines for three different forecasting models. The learning process of the neural network was performed using back propagation (BP-neural network) and the Levenberg Marquard algorithm. The verification of the models was performed using the real weather data. The training sets were selected in such a way to get two full years, including all four seasons.

The verifying data sets contains measurements from one full year. Various types and structures of artificial neural networks dedicated to the prediction of the energy in wind farms have been proposed in [4]. ANN have an opportunity to expand, because they can work independently or together with another wind power forecasting method. They both are forms of hybrid structures [5]. Model I is a reference point built on the full annual figures. Model II contains four submodels dedicated to each season independently. Model III takes into account seasonal phenomenon in the form of information about the month for which the forecast was made.

Model I – Pout = f (Vavg)

The first and the simplest model forecasts produced power depending on the average wind speed for the entire wind farm. The operating rules of the neural network Model I are shown in Fig. 11.

Fig.11. Single BP-neural network on the input average wind speed

Model II – Pout (seasons) = f (Vavg)

The second model was constructed in a similar way to the first, except that the preparation of four models of learned neural networks using selected data sets for different seasons. As a result, four neural networks for each season separately.

The operating rules of Model 2 are shown in Fig. 12.

Fig.12. Four neural network for each season independently

Model III – Pout = f (Vavg ,month )

Model III is similar to the model I and, with the difference that the impact of seasonality as an additional input neural network was taken into account as an additional input for neural network. At the input of the neural network the average wind speed for the entire farm and the number of the month for which projections were made introduced.

The operating rules of Model III are presented in Fig. 13.

Fig.13. – Single BP-neural network, the input average wind speed and the date (month)

where: Pout – output power of the wind park MW, Date (month) – number of the month for which the forecast was made (ranging from 1-12),

.

Table 2. Summary of differences between the analyzed models

.

B. Indicators models

The evaluation of the effectiveness of the models was carried out for a period of one year, by comparing:

• revaluation, underestimation and absolute forecast error

.

• mean absolute forecast error MAE,

.

• mean absolute percentage error MAPE

.

Frequency of obtaining the forecast with the accuracy of 0.75 MW and 1.5 MW, which corresponds to ± 2.5% and ± 5% of the installed capacity of wind

Verification and comparison of models

This chapter presents the results of estimation of electricity production for three proposed models. The prediction was made for an onshore wind farm.

The forecasting method, using artificial neural networks to generate satisfactory results enables the predictions. When considering selection of a variety of structures, a strong dependence of the quality of forecasts on the selected training set was observed. Table II presents the results of forecasting accuracy for each model of forecasting for three models.

Table 3. Summary of results forecasts for the proposed models – the annual results

.

Fig. 14 and Fig. 15 show the results of forecasting accuracy for different seasons:

Fig.14. The accuracy of forecasts – the percentage of errors coming within + -2.5% of installed capacity
Fig.15. The accuracy of forecasts – the percentage of errors coming within + -5% of installed capacity
Conclusion

The long-term electrical and meteorological data from three years of wind farm operation (covering seasonality impact) were used to examine the forecast methods based on three different neural network models.

The analysis of measuring data confirmed the impact of the seasons, and thus the impact of cyclical changes on the energy production volume. The changes of wind speed and temperatures have a significant impact on the operation of the wind farm. The largest volume of energy production was recorded in autumn and winter. The smallest average energy production was registered in summer. Despite an insignificant increase in average wind speed in fall and winter, the average energy production changed noticeably, in the autumn there was an increase of 80%, and in winter, an increase of over 108% compared to summer in which production was the smallest.

Due to the seasonal changes of meteorological phenomena 3 models of neural networks optimized for the impact of seasonality on working wind farm have been proposed and compared. The third model was the best, but it need long-term data. At the of input of the model information about wind speed and the month for which the forecast energy production was carried out, has been given. Such incorporate cyclic phenomena in this case turned out to be most effective. The disadvantage is the need for a large training set to train the neural network. Such a set would allow to prepare a wide range of forecasts of energy from a wind farm. Too little data may result in not full restoration of the power curve of a wind farm. For summer and autumn a bit better was Model II prepared on selected data for individual seasons. For spring and winter the simplest Model I turned out to be slightly better than the Model II.

REFERENCES

[1] Całus D., Oźga K., Popławski T., Michalski A., Szczepański K., Możliwości i horyzonty ekoinnowacyjności – Zielona energia, Wydawnictwo Instytut Naukowo-Wydawniczy “Spatium”, Częstochowa 2018
[2] Popławski, T., Weżgowiec M., Krótkoterminowe prognozy cen na Towarowej Giełdzie Energii z wykorzystaniem modelu trendu pełzającego, Przegląd Elektrotechniczny, 91, (2015), nr 12, 267-270
[3] Ciechulski T., Osowski S., Prognozowanie zapotrzebowania mocy w KSE z horyzontem dobowym przy zastosowaniu zespołu sieci neuronowych, Przegląd Elektrotechniczny, 94, (2018), nr 9, 108-112
[4] Yuan-Kang Wu, Po-En Su, Ting-Yi Wu, Jing-Shan Hong, Yusri M. H., Probabilistic Wind-Power Forecasting Using Weather Ensemble Models, IEEE Transactions on Industry Applications, (2018), 54, 6, 5609-5620
[5] Yang M., Lin Y., Zhu S., Han X., Wang H., Multi-dimensional scenario forecast for generation of multiple wind farms, Journal of Modern Power Systems and Clean Energy, 2015, 3, 3, 361-370
[6] Ciu M., Ke D., Gan D., Sun Y., Statistical scenarios forecasting method for wind power ramp events using modified neural networks, Journal of Modern Power Systems and Clean Energy, 2015, 3, 3, 371-380
[7] Safari N., Chung C. Y., Price G. C. D., Novel Multi-Step ShortTerm Wind Power PredictionFramework Based on Chaotic Time Series Analysisand Singular Spectrum Analysis, IEEE Transactions on Power Systems, (2018), 33, 1, 590-601
[8] M. Qi, G. P. Zhang, Trend Time Series Modeling and Forecasting With Neural Networks”, IEEE Transactions on neural networks, vol. 19, no. 5, May 2008
[9] D. Wu, H. Wang, Application of BP neural network to power predioction of wind power generation unit in microgrid, Engineering Technology and Applications, London 2014.
[10] Z. Liu, W.Gao, Y.-H. Wan, E. Muljadi, “Wind Power Plant Prediction by Using Neural Network”, IEEE Energy Conversion Conference and Exposition, August 2012
[11] Wen-Yeau Chang, “Short-Term Wind Power Forecasting Using the Enhanced Particle Swarm Optimization Based Hybrid Method, Energies, (2013), 6, 4879-4896


Authors: mgr inż. Mateusz Dutka, AGH University of Science and Technology, Department of Power Electronics and Energy Control Systems, 30 Mickiewicza Ave., 30-059 Krakow, POLAND, E-mail: mdutka@agh.edu.pl; dr inż. Bogusław Świątek, AGH University of Science and Technology, Department of Power Electronics and Energy Control Systems, 30 Mickiewicza Ave., 30-059 Krakow, POLAND, E-mail: boswiate@agh.edu.pl.


Source & Publisher Item Identifier: PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 95 NR 7/2019. doi:10.15199/48.2019.07.25

Transformer Derating

Published by Electrotek Concepts, Inc., PQSoft Case Study: Transformer Derating, Document ID: PQS0324, Date: October 10, 2003.


Abstract: A principal effect of harmonic distortion is to increase losses and heating in almost every component in the electric power system. While contributing almost no useful work, harmonic components of voltage and current increase the RMS value of voltages and currents. Interaction of harmonic quantities and resistive loss mechanisms in power system components generates excess heat.

Power transformers are also affected by harmonic distortion. Distortion of transformer load current is the most significant impact, leading to higher than normal temperatures at “hot spots” within the windings.

This case presents an evaluation of transformer derating due to harmonic current.

PROBLEM STATEMENT

120 Volt, 75 kVA Transformer supplying computer workstations was running very hot at an office building. A check of the load current that the transformer was supplying showed that the amperage level was below the transformer rating. A spectrum analyzer was used to record the following waveform (Figure 1).

Figure 1 – Load Current Waveform and Spectrum
TRANSFORMER DERATING

A principal effect of harmonic distortion is to increase losses and heating in almost every component in the electric power system. While contributing almost no useful work, harmonic components of voltage and current increase the RMS value of voltages and currents. Interaction of harmonic quantities and resistive loss mechanisms in power system components generates excess heat. Some losses are actually sensitive to frequency, so that the power loss per ampere of harmonic current is actually greater than that for fundamental frequency currents.

Power transformers are also affected by harmonic distortion. Distortion of transformer load current is the most significant impact, leading to higher than normal temperatures at “hot spots” within the windings. If harmonic distortion of the load current is high, transformers must be derated to account for the increased heating effect of the distorted current. Guidelines for transformer derating are detailed in ANSI/IEEE Standard C57.110.

K-Factor Definition

K-Factor is defined in UL Standards 1561 (low voltage) and 1562 (medium voltage) as:

.

where:
h……………………………………………………………..harmonic number
Ih……………………………………………………harmonic current (amps)

Transformer Derating Using C57.110

ANSI/IEEE Standard C57.110 applies to general-purpose transformers that are subjected to a load current with a total harmonic distortion greater than 5%. The object of the standard is to determine the value of nonlinear current which results in transformer heating equal to that produced when the transformers is supplying rated linear load. Transformer derating can be determined using:

.

where:
PEC-R ……….Eddy current loss at hot spot under rated conditions

Transformer derating depends upon the per-unit rated eddy current loss factor at the hot spot (PEC-R). This factor can be determined by:

1. Obtaining the factor from the transformer designer
2. Using transformer test data and the procedure in C57.110
3. Typical values based on transformer type and size

Table 1 – Typical Values of PEC-R

Reference: “Adjustable-Speed Drive and Power Rectifier Harmonics. Their effects on Power System Components”, D.E. Rice, IEEE No. PCIC-84-52 / *Applies to any transformer with LV sheet type winding

Table 2 summarizes the calculations required to determine the transformer derating and K-Factor for the load waveform illustrated in Figure 1.

Table 2 – Transformer Derating Calculations

.

The K-Factor for the illustrated waveform is determined to be

.

and the transformer derating value is

.

Note: PEC-R assumed to be 8% for this case

Effect of PEC-R

The impact of PEC-R on transformer capability is summarized in Figure 2. As can be seen from the figure, as the eddy current loss factor increases the load current that can be supplied is reduced.

Figure 2 – Transformer Capability vs. PEC-R
SUMMARY

The K-Factor for the load current illustrated in Figure 1 was determined to be 7.56 and the transformer derating value was found to be 82% of it’s rated load current.

This means that the customer has several options when purchasing a transformer to supply this load:

− A 75kVA transformer with a K-13 rating (next standard size chosen)
− A K-1 transformers with a 91.5kVA (75/0.82) rating

REFERENCES

Reference: “Adjustable-Speed Drive and Power Rectifier Harmonics. Their effects on Power System Components”, D. E. Rice, IEEE No. PCIC-84-52.
IEEE Recommended Practice for Electric Power Distribution for Industrial Plants (IEEE Red Book, Std 141-1986), October 1986, IEEE, ISBN: 0471856878
IEEE Recommended Practice for Industrial and Commercial Power Systems Analysis (IEEE Brown Book, Std 399-1990), December 1990, IEEE, ISBN: 1559370440

Clean Power for Office Towers

Published by Raghavan Venkatesh, EE Power – Technical Articles: Clean Power for Office Towers, April 12, 2018.


This article features EPCOS AG product PQSine S series designed for 3-phase grids with or without neutral conductors and enables harmonics to be filtered.

The complex power networks of skyscrapers and other modern buildings must serve a wide range of nonlinear loads. Cutting-edge active power conditioning solutions based on the EPCOS PQSine S series of active harmonic filters help skyscrapers and large commercial buildings eliminate potential power quality issues.

The many power electronics systems in use in large commercial buildings such as skyscrapers include nonlinear loads such as variable speed drives, UPS systems, computers and servers, lighting, TV sets, and more. A major challenge facing building operators is the harmonics pollution in their power networks, leading to a marked deterioration in the quality of the supply voltage.

TDK field applications engineers are joining forces with specialized power quality distribution partners to create cutting-edge power conditioning solutions for such buildings based on the PQSine S series of active harmonic filters.

The Danger of Harmonic Pollution

The nonlinear current draw results in harmonics that cause distortion in the sinusoidal voltage, which in turn can cause interference for other loads. Harmonics are integer multiples of the basic frequency, i.e. of the line frequency of 50 Hz or 60 Hz. The harmonics have varying amplitudes and can extend into the upper kHz range. Harmonic pollution has a series of negative effects on power quality, including:

• malfunctions of other loads due to poor grid power quality;
• additional current load on the neutral conductor, as the harmonic currents of the 3rd, 9th, 15th, and 21st orders, and more. are accumulative and lead to inadmissibly high currents;
• phase asymmetry (specifically when operating single-phase switch-mode power supplies) which additionally promotes the generation of harmonics.

In addition, harmonics can severely impair the function of sensitive devices or even destroy them. IT networks with their servers and PCs are a typical example, where the malfunction of network devices can lead to corrupted data and enormous consequential damage.

Towering Power Quality Challenge

Due to the sheer size of skyscrapers and the complexity of its various electrical loads and systems, power quality, therefore, plays a central role in ensuring the lowest possible energy consumption and costs, as well as avoiding overheating, production/process downtimes, and malfunction of equipment.

The major electrical loads and their characteristics are:

Elevators

The required reactive power compensation for up to more than 100 elevators is very dynamic, and changes very fast between capacitive and inductive during operation and when they feed recuperative power back into the network. The THD-I is also very high and changes rapidly. The main contributors to THD are in the 5th, 7th, 11th, and 13th orders.

Indoor and outdoor lighting

All lights are LED and CFL (compact fluorescent lamp), which are used to save energy, generate significant harmonic distortion in the range from 150 Hz up to 2500 Hz. Large-screen LED digital billboards (with up to more than 2000m² dot-matrix lighting); the main harmonic current is of the 3rd order, but harmonic distortion is also present up to the 50th order.

Air-conditioning

The inverters employed are a source of harmonic distortion and require reactive power compensation. They produce dominant harmonics typically in the 5th, 7th, 11th, and 13th order, but also in the 17th and 19th order and above.

Fans, water pumps, cooling machines, and fire protection

The many smaller 6-pulse power converters in the system contribute current harmonics in the 5th and 7th order and above.

IT networks, UPS, security systems, and access control systems

The many SMPS in the servers, clients and other network devices generate harmonics from the 3rd to 23rd order and above. Moreover, they require a reliable and secure power supply without interruptions.

Complete Power Conditioning Solution

The extremely complex load profile of skyscrapers requires both dynamic reactive power compensation and the mitigation of harmonics over a broad frequency spectrum. An ideal solution for such large commercial towers is a complete power conditioning solution based on the PQSine S series of active harmonic filters. The first step is a detailed analysis of the building’s power network. In this case, TDK field application engineers work together with specialized power quality distribution partners. For new skyscrapers, this will take place during the building’s construction phase. Such analyses generally reveal significantly elevated THD levels and transient harmonics in all feeders of a building’s network (Figure 1).

Figure 1: Typical performance analysis of a power supply system, showing the presence of significant harmonic distortion in all harmonics, especially in the 3rd, 5th, 7th, 11th, and 13th orders.

In a typical office tower distortion is especially high in the 3rd, 5th, 7th, 11th, and 13th harmonics. Based on the analysis and the requirements for power quality, energy savings, reliability, the advanced PQSine S series of active harmonic filters and power optimizers represents an ideal solution (Figure 2). The PQSine S series extends the comprehensive portfolio of EPCOS components and systems for power quality solutions covering solutions such as active and passive harmonic filters, detuned capacitor banks, and low and me

Figure 2: EPCOS PQSine S series of active harmonic filters can be installed in-floor cabinets (left) or wall-mounted cabinets (right)
PQSine S Series for High Performance and Reliability

The PQSine S series is designed for 3-phase grids with or without neutral conductors and enables harmonics of up to the 50th order (2500Hz/3000Hz) to be detected and filtered. In addition to outstanding filtering capabilities, PQSine active harmonic filters also ensure balancing of the loads to all three phases. Moreover, neutral conductor currents are also compensated when using 4-wire devices. These features avoid line resonance and ensure high performance and reliability.

Figure 3: Functional principle of EPCOS PQSine. PQSine ensures a sinusoidal current draw. Harmonics and phase shifts are effectively reduced.

The optimized active harmonic filtering solution with PQSine has the following key features:

• Harmonic and reactive power compensation dual function. The PQSine S series of active filters effectively compensate system harmonics, while at the same time providing fast reactive power compensation for both capacitive and inductive loads, which can keep the system power factor at very nearly 1.0.

• Intelligent switching design special bus system, to ensure that any two of the three ACB cabinets (two incoming and one bus coupler) are always switched in for performance and redundancy purposes.

• Ultrafast reaction speed The PQSine S series of active filters feature a reaction time of under 50 μs and can thus respond quickly to the high and rapidly changing loads;

• Modularity and scalability In order to allow for future system expansion to meet changing power conditioning requirements, each installed PQSine cabinet has two or three empty slots.

Optimum reliability is ensured by means of a series of self-monitoring systems. The most important of these are overload protection, shutdown on overtemperature, protection against overvoltage or undervoltage and fan monitoring. The PQSine S series includes a 7-inch TFT color touch-screen for user-friendly input and reading of the data. PQSine offers a number of Modbus (RTU) and TCP/IP (Ethernet) interfaces for control, programming, and diagnostics purposes.

The PQSine S series of active harmonic filters are based on the latest state of the art in power electronics technology. They are installed in parallel to the polluting loads. The active filter analyzes the line current and its associated harmonics and generates a compensation current which neutralizes the harmonic currents and creates an almost sinusoidal waveform (Figure 3). With its fast reaction time, PQSine offers excellent performance for fast-changing loads, such as those generated by elevators. Using the data determined in real-time, PQSine feeds a compensation current into the grid, which cancels the nonlinearity of the load current.

Optimized design for demanding harmonics order to optimally compensate harmonic currents from the electrical loads in a recent installation, a total of 76 PQSine S series units were installed for the various feeders on eleven levels of the skyscraper. Figure 4 shows a typical single line diagram of an electrical distribution board.

Figure 4: Typical single line diagram of an electrical distribution board.
Reliable Harmonic Current Compensation for a Wide Range of Applications

After the installation of the complete power conditioning solution, the TDK field application engineers and their partners typically perform a comprehensive power quality analysis with a specific focus on harmonics as proof of the installation’s effectiveness. According to the power quality data gathered on-site at a recent installation, the PQSine S series limits the system THD-I to below 3 percent. The system current was about 160 ARMS during the specific measurement. Overall, the PQSine solution successfully delivered the highest level of power quality. The current phases were sinusoidal with a very low level of THD-I (Figure 5), and the power factor was nearly 1.0.

Figure 5: With the PQSine active harmonic filter and power optimizer, the current phases were sinusoidal with a very low level of THD-I and the power factor was nearly 1.0.

PQSine has proven very effective in mitigating harmonics and also providing dynamic reactive power compensation to ensure the optimal power quality for all loads and users of large commercial buildings. PQSine active harmonic filters and power optimizers are especially suitable for fast current harmonics, reactive power compensation or neutral current compensation in a wide range of power networks in

• Data centers and IT-enabled service facilities,
• Renewable energy power generation,
• Process industries,
• Sensitive manufacturing facilities, and
• Office buildings, shopping centers, hospitals.

This article originally appeared in the Bodo’s Power Systems magazine.


Author: Venkatesh Raghavan holds a Ph.D. and a Master’s Degree in High Voltage Engineering at the Indian Institute of Science and at the Anna University respectively. He also holds a Bachelor’s Degree in Electrical and Electronics Engineering. He is currently the President of EPCOS since February 2008.


Source URL: https://eepower.com/technical-articles/clean-power-for-office-towers/

PQ Investigation for SW County School District No. 1 Harmonic Considerations Associated with PC Loads

Published by Electrotek Concepts, Inc., PQSoft Case Study: PQ Investigation for SW County School District No. 1, Document ID: PQS0323, Date: October 10, 2003.


Abstract: The County School District has a concern for increasing computer loads at the local High School. There are approximately 300 computers currently in use at the school and plans are to increase the number of computers significantly over the next 3-4 years. The existing computer loads are on the same circuits with lighting loads, other office loads, and building HVAC loads.

Electrotek Concepts conducted a brief survey of the facility on August 8, 1995. This case study describes the findings from the site survey and outlines recommended procedures for dealing with the new computer loads.

INTRODUCTION

The County School District has a concern for increasing computer loads at the local High School. There are approximately 300 computers currently in use at the school and plans are to increase the number of computers significantly over the next 3-4 years. The existing computer loads are on the same circuits with lighting loads, other office loads, and building HVAC loads.

The personal computer loads are characterized by a current waveform that has significant harmonic components. These harmonic components are dominated by the third harmonic which appears in the zero sequence circuit (for balanced circuits), which means that the third harmonic components add in the neutral. The result can be neutral circuits which are significantly overloaded if they are not designed for this type of load. The harmonic components can also require derating of the transformers that supply the computer load.

Wiring and grounding considerations are also important with the computer loads. High neutral currents from the PC loads can also flow in the ground circuits if there are incorrect neutral-ground bonds in any sub-panels or loads. The ground currents can cause interference, improper operation of protective devices (breakers), and safety concerns.

System Configuration

The high school is supplied from a 1000 kVA transformer that steps down to 480 Volts. There are a number of transformers that then step down from 480 volts to 120/208 for the various loads in the facility. Figure 1 gives an overview of the system configuration. The 500 kVA transformer supplies most of the load in the main building. The 300 kVA transformer was added for the auditorium load.

Figure 1 – One-Line Diagram on the Main Supply to the High School

Concerns Evaluated

Important concerns evaluated in the site survey and summarized in this report include:

• Harmonic generation from nonlinear loads.
• Overloading of neutral conductors due to harmonic current levels.
• High voltage distortion on the auditorium circuits.
• Transformer derating considerations for harmonic currents
• Wiring and grounding concerns at building panels and loads.
• Requirements for main transformer rating in the future.

HARMONIC GENERATION BY NON-LINEAR LOADS

Harmonic currents result from the operation of nonlinear loads in the system. These include adjustable speed drives for fan motors and chiller compressors in HVAC systems, fluorescent lighting (with or without electronic ballasts), electronic dimmers for lighting, and electronic power supplies for computers and other electronic equipment.

These nonlinear loads look like sources of harmonic currents to the rest of the system. Voltage distortion results as the harmonic currents flow through the impedance of the conductors, transformers, and system. Longer conductor runs will result in higher voltage distortion levels due to the higher impedance of the circuit.

Measurements were performed previously at the high school to characterize some of these loads. Important results are included here for illustration purposes. These include measurements of the harmonic distortion in the stage lighting circuits which use electronic dimmers and measurements of a typical circuit that is dominated by computer loads.

Harmonics from Computer Loads

Panel PE is a typical panel that supplies computer loads at the high school. Measurements were performed for the total load at Panel PE. Figure 2 below gives an example of the waveform measured.

Figure 2 – Current Waveform for a Circuit serving Computer Load Based on Measurements at Panel PE (adjusted to an equivalent three phase load level of 10 kVA)

A summary of the three phase measurements at Panel PE are provided below in Table 1.

Table 1 – Panel PE Measurement Results

.

Note that the neutral current is higher than the phase current at this panel. The neutral current would even be higher if the three phase currents were balanced. In the balanced case for load current waveforms like the one in Figure 2, the neutral current can be as high as 173% of the rms phase current. It will be dominated by the third harmonic component since this is the component that adds in the neutral.

Harmonics in the Auditorium Dimmer Circuit

The stage lights for the auditorium in the high school use electronic dimmers which result in significant harmonic generation. The harmonic content of these load currents depends on the actual load level. When the dimmers are near full load, the percentage harmonic component is not as great but the load current magnitude is higher. At light loads, the percentage distortion is high but the load current is lower.

Measurements were performed at three different load levels to illustrate this characteristic. The results are summarized in Table 2 and example waveforms are provided in Figure 3.

Table 2 – Current and Voltage Measurements for the Stage Lighting Circuit

.
Figure 3 – Lighting Circuit Load Currents at Different Operating Levels.

Note that the highest voltage distortion levels for this circuit occur when the lighting is near 50% load. At this operating point, the actual amperes of harmonic current components are the highest. The voltage distortion is high because the circuit supplying the lighting has a high impedance due to the long 120 volt circuit supplying this load. The impedance would be much lower and the distortion would be reduced if the auditorium load was supplied with a 480 volt circuit and the step down transformer was installed closer to the auditorium.

EVALUATING NEUTRAL CONDUCTOR LOADING DUE TO HARMONICS

Single phase nonlinear loads can have significant harmonic components at triplen frequencies (3, 9, 15, etc.). When these loads are combined in a three phase circuit, the triplen harmonics show up as zero sequence components. That means they add in the neutral. If there are 10 amps of third harmonic on each phase in the three phase circuit, the neutral current will include 30 amps of third harmonic.

For this reason, neutral currents in 120/208 circuits in many commercial buildings are actually higher than the phase currents. The neutral currents are dominated by third harmonic components from single phase electronic loads, like Pcs. Figure 4below illustrates a typical case in a circuit dominated by PC loads.

Figure 4 – Phase currents and neutral current for a circuit dominated by single phase electronic loads.

The rms neutral currents in this type of circuit can be as high as 173% of the rms phase current. The actual neutral current magnitude will depend on how much of the load on the circuit has a waveform like the ones in Figure 4.

An approximate formula for calculating the neutral current magnitude as a percentage of the rms phase current is given below. The formula is based on the assumption that the circuit loading is balanced, that the nonlinear load watts are a pnl fraction of the total load, and that the load current has a third harmonic component equal to 70% of the fundamental.

.

This relationship is illustrated in graphical form in Figure 5.

Figure 5 – RMS neutral current as a function of the portion of electronic load in the circuit, pnl.

It is important to note that the neutral current problem is usually restricted to 120/208 volt circuits supplying a significant percentage of single phase electronic load. Neutral currents are very seldom a problem at service entrance locations, due to delta-wye transformers and harmonic cancellation between different types of loads.

The figure shows that the neutral current will be equal to the phase current when approximately 50% of the load on the circuit is electronic loads. For circuits with higher percentages of electronic load, the neutral current will exceed the phase currents. If these circuits are loaded based on the capacity of the phase conductors, the neutral conductor could be overloaded.

Possible solutions to the neutral conductor overloading problem include the following:

− increase the neutral conductor size or use two neutral conductors.
− use a separate neutral for each phase conductor.
− apply a third harmonic filter at individual loads.
− use an isolation transformer, zig-zag transformer, passive filter, or active filter (three phase devices) on the load side of the neutral conductor to be protected.

Implications for SW County High School

With the number of PCs planned and existing at the high school, a number of circuits will be dominated by electronic loads. There is a concern for neutral conductor loading on these circuits. Panel PE and Panel I are examples of panels that supply load that is dominated by PCs.

Most existing circuits do not seem to be loaded close to their rating. In addition, circuits examined have neutral conductors that are the same size as phase conductors (they could be undersized according to the code). As a result, neutral conductors are not being overloaded at the present time. Circuit loading should be reviewed periodically on circuits that are dominated by computer load to assure that neutral conductors are not being overloaded.

New circuits that are installed to supply future PC loads should have neutral conductors that are sized for this type of load. Neutral conductors in new circuits supplying pc loads should have a rating of about twice the phase conductor rating.

TRANSFORMER DERATING REQUIREMENTS

Transformer heating is one of the primary concerns associated with harmonic current distortion levels in a facility. ANSI/IEEE Standard C57 series states that a transformer can only be expected to carry its rated current if the current distortion is less than 5%. If the current distortion exceeds this value, then some amount of derating is required. ANSI/IEEE Standard C57.110 provides calculation procedures that can be used to evaluate the required derating as a function of the expected current harmonic spectrum and the transformer design. The primary cause of the concern is that the transformers can be overheated by distorted load currents that cause higher eddy current losses inside the transformer than were anticipated by the designer.

At the inner winding “hot-spot”, the load loss (PLL) can be considered to have two components: I2R loss and eddy current loss (PEC). The relationship is given by:

.

The I2R loss is directly proportional to the square of the rms value of the current. However, the eddy current loss is proportional to the square of the current and frequency. It is defined by:

.

where:

KEC = a design-dependent proportionality constant

With all values expressed in per unit of rated load quantities, the per-unit full load loss under harmonic current conditions is given by:

.

where:

PEC-R = eddy current loss factor under rated conditions

The required transformer derating is calculated based on the additional heating that can be expected for a specific harmonic current spectrum and the eddy current loss factor for the transformer. The derating is expressed as the per unit value of a particular distorted current that will cause the same heating as the rated sinusoidal current.

The first task is to measure, calculate, or estimate the harmonic content of the transformer load current. Then, the expected harmonic current spectrum can be used to calculate the k-factor of the load current. The k-factor of the load current can be used to purchase a transformer that is designed to handle the level of harmonic distortion specified. The k-factor is only dependent on the current waveform. There is no need to get any information about the transformer design in order to use the k-factor. K-factor is calculated using the following formula.

.

The increased transformer losses at harmonic frequencies are caused by increased eddy current losses. If the transformer has very low eddy current losses, there will not be a significant impact due to harmonic components. If the transformer has high eddy current losses, significant derating will be necessary for harmonic components. The transformer eddy current losses are characterized by the eddy current loss factor, PEC-R. This number can be from the transformer designer, from the transformer test data and the procedure in C57.110, or estimated based on typical values. A typical value for dry type transformers used to step down from 480 volts to 120/208 volts within facilities is about 8%.

The transformer derating is expressed as the per unit rms current (with distortion) that will cause the same heating as the rated sinusoidal current. It can be calculated from the following equation using the transformer eddy current loss factor and the k-factor of the load current.

.

where:

.

PEC-R = eddy current loss factor
h = harmonic number
Ih = harmonic current

Probably the worst case condition for one of the step down transformers within the facility is virtually 100% electronic load. Figure 6 illustrates the waveform and the required transformer derating for this condition. Note that the k-factor for this waveform is 7.6. A transformer with a k-factor greater than 7.6 could be loaded to its nameplate rating for this load current waveform.

Figure 6 – Required transformer derating as a function of the eddy current loss factor.

Implications for SW County High School

Both of the step-down transformers (500 kVA and 300 kVA) at the high school main switchgear could have relatively high percentages of nonlinear load. However, the nonlinear load is not approaching 100% of the load on the transformer. Also, these transformers do not appear to be operating near their rating at the present time. A conservative limit for these transformers would be 80% of their nameplate ratings. Loading on the high school step down transformers should be monitored periodically and kept below 80% of the transformer rating to prevent overheating due to harmonic components.

New circuits to supply additional PC loads can be supplied from the main 500 kVA transformer as long as the transformer loading is kept below 80% of the nameplate. If new loads will result in this limit being exceeded, additional transformer capacity should be added. A new transformer to supply electronic loads (PCs) should not be loaded above 60% of its nameplate or a transformer with a k-factor rating of 13 should be purchased.

The main supply transformer for the facility (1000 kVA) should not require any significant derating for harmonic components. The step-down transformers prevent the flow of zero sequence harmonics and there is significant cancellation of harmonics for all the loads within the facility. The main supply transformer should not require significant derating for harmonic levels.

WIRING AND GROUNDING CONSIDERATIONS

Many power quality problems that occur within end user facilities are related to wiring and grounding practices. Sometimes the solution to a power quality problem is simply to tighten a loose connection or replace a corroded conductor. Therefore, an evaluation of wiring and grounding practices is a necessary first step when evaluating power quality problems in general.

Check RMS Voltage Levels

Service entrance should be within +/- 5% of nominal volts. Utilization should be within +6, -13% of nominal volts. The long circuit runs required when the step down transformers are located at the main switchgear can result in reduced voltage magnitudes at the actual loads. Measurements at various panels in the high school show that the voltage can be as low as 110 volts. This should not result in any problems.

Check for extra neutral-ground bonds

There should be only one neutral-to-ground bond per separately derived system (at the transformer or at the main panel). This is a common problem which causes load currents to flow in the building ground system, creating the potential for serious interference problems. This can be checked by measuring the current in the green wire grounds at the service entrance or at the source of the separately derived system. These currents should be very close to zero. If any current is flowing in the ground, the source of the current should be found and corrected.

Visual inspection of a couple sub panels at the high school indicated that the neutral bus in some sub panels may be grounded. Figure 7 below illustrates the possible problem that can be caused by this extra neutral-to-ground connection – some of the neutral return current is introduced into the ground system where it can cause interference.

Figure 7 – Introduction of neutral return current into the ground system
(caused by an extra neutral-to-ground connection

Check for overloaded neutral conductors

This has already been discussed related to supplying electronic loads with high third harmonic current components. The neutral currents should be measured with a true RMS meter and checked against the ampacity of the neutral conductors.

Checking grounding electrode system

The grounding electrode system consists of all the grounded elements of the building that are bonded together to form a grounding system. This can include ground rods, metal water pipe, building steel, concrete-encased electrodes, a ground ring, etc. All of these things should be bonded together to form the best equipotential reference for equipment in the building as possible.

It is not advisable to have separate, isolated ground rods for individual equipment in the facility. If a separate ground rod is driven for equipment, it should be bonded with the overall building grounding electrode system.

Guidelines for the grounding electrode conductor are provided in Table 3.

Table 3 – Guidelines for the grounding electrode conductor size.

.

Overall circuit layout considerations

Are sensitive equipment loads on separate circuits from disturbing loads? Loads that are switched or that have power electronic components create transient disturbances which can impact the operation of some sensitive equipment. Loads like switched motors, copiers, laser printers, elevators, etc. should be on separate circuits from sensitive equipment. The separate circuits provide isolation for high frequency transients and a clean ground reference for the sensitive loads.

For new computer loads at the high school, dedicated circuits could be designed with additional neutral capacity to handle the harmonic components.

Separately derived systems

Separately derived systems permit the bonding of the ground and neutral. In circuits with significant neutral currents (e.g. single phase electronic loads), a significant neutral-to-ground voltage will build up if there is a significant length between the loads and the supplying transformer. Using an isolation transformer close to the loads minimizes the neutral-to-ground voltage and also provides isolation for transient overvoltages.

Check for ground loops

Ground loops are probably the most common cause of interference in network systems and also the most common problems with multi-port devices in general. Multi-port devices have more than one type of interface. For instance, a television has a power input and a cable input; a computer has a power input and a phone input for the modem and a network input for a LAN. All of these ports require a ground reference. This multiple ground reference scenario creates the potential for serious ground loop problems.

Ground loops problems are best avoided by making sure all equipment that is tied together through other ports (e.g. on a LAN) has the same ground reference. This means that all the equipment is part of the same separately derived system. Figure 8 illustrates this as the grounding bubble principle. If an external ground reference goes outside the bubble, there is the potential for ground loop interference.

Figure 8 – Example system illustrating the bubble principle of grounding (All equipment with other ground ports to the same power system ground reference. Figure is courtesy of Scott Peele at Carolina Power and Light.)

Implications for Sweetwater County High School

The most important wiring and grounding concern at the high school is extra neutral-to-ground connections at sub panels. Most of the circuits from the main switchgear to the sub panels use conduit grounding. The sub panels should not have the neutral bus connected to the ground bus and case in the panel. This extra connection could result in loss of overcurrent protection for these circuits and interference concerns when PCs are connected up in networks.

New circuits for computer loads should include a separate green wire safety ground conductor. This will facilitate checking for unwanted ground currents in these circuits.

New circuits for computer loads should use a step down transformer as close to the loads as possible. This will prevent excessive neutral-to-ground voltages and long lengths of circuit with high neutral currents that could cause interference.

EVALUATING THE MAIN TRANSFORMER REQUIREMENTS

The addition of new computer load could result in the need for additional transformer capacity in the main supply from the utility. This depends on the existing load levels for the 1000 kVA supply transformer.

The utility performed some measurements at the 480 volt service entrance last year but these were primarily designed to evaluate harmonic distortion levels. Measured levels were compared to the IEEE 519-1992 guidelines and harmonic current levels were not found to be a problem. Some of the plots included with the report appear to be the result of either transient inrush conditions or caused by saturation of Cts (high even harmonic current components should not exist in the steady state). These should not be representative of the normal harmonic current components. As stated in the report, normal harmonic current levels are well within guidelines and should not result in the need for derating of the main transformer.

It would be useful if additional measurements could be performed to characterize the existing transformer loading as a function of time. This would provide a benchmark for evaluation of future transformer capacity requirements.

If the supply transformer is replaced with a larger unit, it should be sized based on the expected future loading at the high school, including the ultimate level of computer penetration.

SUMMARY

General Recommendations

− Harmonic voltage distortion can be high on the auditorium lighting circuits due to the dimmer loads and the high impedance created by the overall circuit length. The voltage distortion could be reduced if the step-down transformer for these circuits was located closer to the loads. Even though the voltage distortion is high, it should not be a problem for the lighting circuits.

− If the voltage distortion on these lighting circuits needs to be reduced, the most economical solution would be a zig-zag transformer applied close to the lighting loads. This would reduce the zero sequence components and the corresponding voltage distortion. The transformer is rated in zero sequence amps. A transformer rated for approximately 250 amps would be needed based on the measurements.

− Existing computer loads are resulting in neutral current magnitudes that exceed the phase currents in some circuits. However, the circuits are not heavily loaded. These circuits should be monitored periodically to make sure that neutral conductor capacities are not exceeded.

− New computer loads can be supplied with dedicated circuits that have a neutral conductor rated for twice the current of the phase conductors.

− Loading of the facility step-down transformers should be monitored periodically. As a conservative limit, they should not be loaded above 80% of their nameplate capacity.
− A new facility step-down transformer dedicated to computer load should have a k-factor of 13 or should only be loaded up to 60% of its nameplate capacity.

− Existing sub panels should be checked for neutral-to-ground connections. The neutral bus in the sub panels should be isolated from the ground bus and the case.

REFERENCES

ANSI/IEEE Standard C57.110
IEEE 519-1992