Reactors in a Power System

Published by Alex Roderick, EE Power – Technical Articles Reactors in a Power System, May 03, 2021.


This article highlights two common types of reactors which are the dry-type and the oil-immersed.

In an AC circuit, reactance is the opposition to current flow. A reactor, also known as a line reactor, is a coil wired in series between two points in a power system to minimize inrush current, voltage notching effects, and voltage spikes. Reactors may be tapped so that the voltage across them can be changed to compensate for a change in the load that the motor is starting. Reactors are rated by the ohms of impedance that they provide at a given frequency and current. Reactors may also be rated by the I2R loss across the device at a certain frequency at a rated current.

Two common types of reactors are the dry-type and the oil-immersed. The dry-type is open and relies on the air to circulate and dissipate the heat. Dry-type reactors are common in low-voltage applications.

Oil-immersed reactors are common in high-voltage applications. Oil-immersed reactors are placed in tanks and require a magnetic shield to prevent eddy currents from circulating in the tank. The shield is made from laminated steel sheets like the transformer core and motor stators.

Reactors may be used as line  or load reactors (see Figure 1). Line reactors are used when low line impedance allows high inrush current, when power factor correction capacitors are used, or when a motor drive causes notching. Load reactors are installed at the output of a motor drive. Load reactors help eliminate voltage spikes or reflected wave noise by slowing down the rate of change in the drive output voltage. However, load reactors have a tendency to overheat due to the harmonic content of the output waveform from the motor drive. The reactor must be designed to reduce the harmonic distortion.

Figure 1. Reactors are used as line or load reactors. Image courtesy of Transcoil
Inrush Current

Many electrical devices draw high currents at startup or have very low impedance to the flow of current. For example, electric motors typically draw many times their full-load current during startup. This inrush current can cause voltage sags that trip out other equipment. Many full-voltage motor starters use reactors to increase the impedance and limit the inrush current. Large capacitor banks used to correct for low power factor have very low impedance when the capacitor bank is first switched ON, and the capacitors begin charging. Low impedance means that the flow of current is very high. A reactor can be added in series to increase the reactance. The increased reactance increases the impedance and reduces the inrush current (see Figure 2).

Figure 2. Line reactors are used to reduce inrush current. Image courtesy of Schneider Electric
Reduced Notching

To reduce notching, the source of the notching needs to be isolated or buffered from other equipment that uses the same power distribution system. Creating a voltage divider is a relatively simple way to minimize notching. See Figure 3. When impedance in the form of a reactor is added in series with an SCR controller, the notch voltage is distributed across the new impedance and the impedance already existing in the feeder lines. The added impedance reduces the notch depth and widens the notch width. Experience has shown that the reactor should have about 3% impedance to reduce the notch depth by about 50%. This is enough to eliminate the extra zero crossovers that cause problems. Higher impedance may cause problems with sensitive equipment because the wider notch may be seen as a loss of voltage. Lower impedance may not reduce the notch depth enough to eliminate the problems.

Figure 3. A reactor can be added in series with an SCR power source to reduce notching.
Note

Transients on a line can cause electronic equipment to generate errors. Digital electronic circuits operate on low-level digital signals that can be corrupted by a false signal induced by the transient voltage.

Saturable-Core Reactors

When an iron core is saturated, substantially all the magnetic domains are aligned with the applied magnetic field. Further increases in the applied magnetic field do not result in increases in magnetic flux. Therefore, there is no increase in the voltage induced in opposition to the change in current. In other words, an inductor loses its ability to oppose changes in current when its core becomes saturated.

A saturable-core reactor is an inductor whose inductance is regulated by a magnetic field produced by a second winding wound around the same iron core as the primary winding. The “power” winding of a saturable-core reactor is the winding carrying the AC load current. The “control” winding of a saturable-core reactor is the winding carrying the DC control current. The control winding is carrying DC strong enough to create a magnetic field that saturates the core.

An increase in DC through the control winding produces an increased magnetic flux in the reactor core. An increase in the magnetic flux moves the reactor core closer to saturation and decreases the inductance of the power winding. A decrease in inductance in the power winding increases the current delivered to the load through the power winding. Therefore, a saturable-core reactor can be used as an amplifier where a relatively small DC through a control winding can control a relatively large AC through the power winding.

In actual practice, a saturable-core reactor consists of two pairs of windings (see Figure 4). The small dots near the saturable-core reactor coils indicate polarity. The power windings are in phase with each other, and the control windings are out of phase with each other. This allows the saturable-core reactor to saturate the core equally in both positive and negative alternations of the AC cycle.

Figure 4. Saturable-core reactors can use a small direct current as a way to control a large alternating current in a power circuit.

Saturable-core reactors were very popular in the plating industry before the advent of DC drives to control the current in the plating solution. In the case of a plater, the part being plated is the load. If no DC is flowing in the control coil, then the IR drop will be controlled by the amount of current in the reactor. With DC current in the control coil, the DC flux will flow in the core and limit the amount of AC flux in the core. Lower AC flux means less reactance and less impedance to the circuit current. Large amounts of AC current can be controlled by a small amount of DC current. This control is very linear and very reliable. Saturable-core reactors have fallen out of use in this type of application because the cost to build a reactor is much higher than building a DC drive.

Note

Saturable-core reactor power supplies used at high power levels are extremely reliable devices because there are no moving parts.

Chokes

A choke, also known as a line choke, is a reactor that is used to limit current to AC or DC drives in the event of short circuits inside the drive. When large short-circuit currents are drawn from the source, the choke starts to build a counter-voltage, and the voltage available to the drive is reduced. The reduced voltage causes the instantaneous electronic trip (IET) circuit to trip the drive off-line to avoid damage. Chokes have large conductors with fewer turns and offer low impedance to the line into the drive.

A common-mode choke is a reactor that reduces common-mode noise current produced by rapid motor drive or device switching (see Figure 5). Load current flows through one winding of the common-mode choke to the load and then flows through the other winding away from the load. This results in two opposite magnetomotive forces that cancel and result in zero inductance. With a common-mode noise, the currents flowing through the two windings of the common-mode choke are in the same direction. Hence, in-phase flux created in each of the windings will add together rather than being canceled as in the case of a differential noise component. This will result in a magnetomotive force that opposes the flow of the common-mode noise. 

These common-mode components will flow to the ground as shown in Figure 5. The net result is that a common-mode choke allows the load current to flow almost unimpeded while blocking the flow of common-mode noise current.

Figure 5. Common-mode chokes are used to reduce the severity of drive-induced common-mode noise. Image Courtesy of Power Systems Design

Common-mode chokes are often used to reduce drive-induced common-mode noise. A common-mode choke provides high inductance to oppose common-mode noise currents generated during drive switching. The magnitude and rise time of the noise current are reduced to the point where they are below the noise threshold of affected equipment.

Resonance

Capacitor banks are often used to correct low-power-factor situations. In systems with large amounts of capacitance used to correct power factor, high-voltage distortion can cause resonance at system harmonic frequencies. This results in series-or parallel-resonant currents, which can be very damaging to the electrical system. 

Figure 6. A reactor in series with a variable-speed motor drive shifts the resonance frequency away from any harmonics on the line.

Adding a reactor to the incoming power line to the motor drives is a common technique for minimizing the impact of motor drives on other loads in the electrical system (see Figure 6). The added reactance ahead of a motor drive alters the resonance frequency and decreases the amount of distortion in the motor drive’s input current.


Author: Alex earned a master’s degree in electrical engineering with major emphasis in Power Systems from California State University, Sacramento, USA, with distinction. He is a seasoned Power Systems expert specializing in system protection, wide-area monitoring, and system stability. Currently, he is working as a Senior Electrical Engineer at a leading power transmission company.


Source URL: https://eepower.com/technical-articles/reactors-in-power-system/

Types of Surge Arresters

Published by Lorenzo Mari, EE Power – Technical Articles: Types of Surge Arresters, December 18, 2020.


Learn about the most common types of surge arresters used to protect against transient overvoltages and lightning strikes.

Surge arresters introduce shunting resistance to the ground when a surge appears, absorbing energy from the surge without the voltage becoming excessive. They then extinguish the power follow current after dissipating the surge. The most common arrester types in power systems are silicon carbide (SiC) and zinc oxide (ZnO). This article describes these arrester types in more detail.

Characteristics of Different Surge Arrester Types

The first surge arresters provided lightning protection utilizing an air gap connected between the line and the ground. Their main drawback was the requirement of a series linear resistance and a fuse to break the power follow current. Additionally, when the gap sparks over, it creates a fault in the circuit – and an unpleasant outage when cleared by a circuit breaker.

A device able to limit the voltage without producing a power outage is more appealing.

After several generations of surge arresters, the introduction of valve-type silicon-carbide arresters in 1954 was a significant technological advance. The valve element (or valve block) consisted of a non-linear resistor – commonly silicon carbide (SiC) – whose value decreases abruptly as the voltage rises. The name valve block comes from the valving action to the flow of the current.

Silicon carbide arresters allowed for a reduction to the basic lightning impulse insulation level (BIL) of substation equipment, high fault current withstand, and smaller size, with significant economic savings.

Introduced around 1976, modern metal-oxide arresters – typically zinc oxide (ZnO) – do not need gaps and exhibit better handling characteristics for switching surges, reduced current under steady-state conditions, and reduced lead lengths.

Although silicon carbide arresters provided good service for many years, the better performance and improved power system availability make metal-oxide devices a better choice.

There are arresters with different voltage and power levels to best suit the protected equipment’s needs.

Silicon Carbide (SiC) Valve-Type Surge Arresters

SiC valve-type surge arresters employ a non-linear valve element (resistor) made of silicon carbide and inorganic binders. Silicon carbide is a compound of silicon and carbon.

Some arrester applications require that the valve element have a low resistance value during steady-state conditions to deal with particular surge and power system characteristics, creating excessive power losses. Valve-type surge arresters have spark gaps in series with the valve elements to manage this difficulty.

Series spark gaps keep the valve element isolated under steady-state conditions, in order to reduce losses, and they introduce the valve element when a surge emerges from the gap’s sparkover. There is no leakage current flow between the line and earth, allowing the valve design to deal with its voltage-limiting role and energy dissipation capacity only under surge conditions.

The total voltage across the arrester is the gaps’ sparkover level plus the voltage across the valve element. The lower the total voltage, the better the protection level.

SiC arresters also contain current limiting gaps to limit the system follow current. These gaps reduce the energy absorbed during operation, allowing for fewer valve elements, shorter arrester length, and reduced voltage levels. The arrester gaps exhibit drawbacks, like producing transients during the sparkover to engage the valve elements.

Another crucial matter is the arc-quenching ability of the arrester. Arrester design provides creative ways for quenching the arcs created in the gaps, protecting the valve element against the continuous flow of current – the follow current – after the surge is rerouted and steady-state conditions resume.

Figure 1 shows a volt-ampere characteristic for a gapped silicon-carbide arrester.

Figure 1. V-I characteristic of a gapped silicon-carbide surge arrester. Image courtesy of Industrial-electronics.

Figure 2 shows a diagram of a typical 6kV silicon-carbide surge arrester with its components: main gap units, magnetic coil, valve elements, bypass gap, and shunting resistors.

Figure 2. Schematic diagram of a gapped silicon-carbide surge arrester. Image courtesy of General Electric.

The pre-ionizing tips help to initiate the gap’s breakdown when an overvoltage develops. The bypass gap short-circuits the magnetic coil during the surge current transit, placing the surge voltage across the valve element, which presents low resistance at high voltage, and the surge current goes to the ground. The magnetic coil helps to quench the arcs into the main gaps after the surge current passes. The shunting resistors regulate the power frequency voltage across the main gap elements.

Figure 3 shows silicon carbide surge arresters for various voltages.

Figure 3. Silicon-carbide surge arresters. Image courtesy of General Electric.
Metal-Oxide Surge Arresters (MOSA)

A metal-oxide surge arrester contains non-linear metal–oxide resistive disc elements with excellent thermal energy withstand capabilities. Each disc includes powdered zinc oxide material mixed with other metal oxides. This type of surge arrester works like a high-speed electronic switch – opened at steady-state voltages and closed at overvoltages. 

Zinc oxide surge arresters are highly non-linear – their non-linear characteristic is much more pronounced than that of silicon carbide – and have low losses under steady-state conditions.

There are three types of metal-oxide arresters:

• Gapless
• Series-gapped
• Shunt-gapped

As with silicon-carbide surge arresters, the first metal-oxide arresters had a gap in series with non-linear resistors. At that time, the resistors’ thermal duty was relatively small and they could not withstand the thermal energy of the leakage current under steady-state conditions, requiring the gap. Gapless arresters appeared around 1980, and their resistors tolerate the constant small leakage current. 

Zinc oxide arresters are easy to manufacture, have low cost, and absorb or dissipate large amounts of energy. Nowadays, most arresters employed in new systems or revamps are gapless zinc oxide devices.

Figure 4 shows a gapless zinc oxide surge arrester’s cutaway, containing a single column of ZnO blocks.

Figure 4. Parts of a porcelain-housed gapless zinc-oxide surge arrester. Image courtesy of ABB.
1Porcelain insulator6Sealing cover
2Venting duct7Sealing ring
3Spring8Indication plates
4Desiccant bag9ZnO-blocks
5Copper sheet10Flange cover
.

Figure 5 shows a high voltage zinc oxide surge arrester for areas with very high lightning intensity. Note the external grading rings that long arresters regularly require to maintain constant voltage stress along their length.

Figure 5. Zinc-oxide surge arrester. Image courtesy of ABB. 
Surge Arrester Classification and Application

Based on voltage rating, protective characteristics, and durability in pressure-relief or fault-withstand characteristics, the classification of surge arresters used in power systems is as follows:

• Station arresters: Provide the best protective levels – lower discharge voltages, higher energy absorption, and more significant pressure relief. Typical applications are large substations and sites with strong surges.

• Intermediate arresters: Have inferior protective characteristics and energy discharge capability. Typical applications are small substations, underground cable protection, and dry-type transformers.

• Distribution arresters: Provide the lowest protective levels and energy discharge capability. They are used in medium voltage networks.

Insulation Coordination

The system and equipment insulation’s voltage withstand ability depends on the surge’s rise time. In this instance, insulation capability is a function of time.

A surge arrester’s protective characteristics are also a function of time; hence, the need for coordinating the insulation and arrester volt-time characteristics to get adequate protection – the insulation coordination procedure.

Insulation coordination compares the system or equipment insulation’s impulse withstand ability with the voltage across the arrester for the selected discharge current, in accordance with the preferred protection level. The choice of insulation levels and coordination practices affects costs considerably. A drop of one level in BIL can reduce major electrical equipment costs by thousands of dollars.

As an example, Figure 6 shows the entire V-I withstand curve for an oil-filled power transformer and the protective characteristics of a surge arrester – front-of-wave sparkover and discharge voltage.

Figure 6. Oil-filled transformer insulation withstand and arrester protective characteristics. Image courtesy of Cooper.

The arrester’s sparkover crest voltage should be below the transformer’s chopped wave withstand. It is safer to compare the arrester’s sparkover with the transformer’s front-of-wave test when the latter is available.

Another comparison is the arrester’s discharge voltage and the 1.2/50 µs impulse sparkover with the transformer’s full-wave test (BIL).

A Review of Surge Arrester Types and Characteristics

The first surge protective devices were the rod gaps. Rod gaps are cheap but have several disadvantages: they may not protect for fast fronts, produce steep surges during sparkover, and generate a fault on every operation – they do not reseal.

Silicon-carbide valve-type surge arresters employ a silicon carbide non-linear valve element and series spark gaps. The spark gaps keep the valve element isolated under steady-state conditions – reducing losses – and activates it when a surge emerges, but they create transients during the sparkover.

Zinc-oxide arresters were introduced around 1976. Zinc oxide is a substitute for silicon carbide. ZnO arresters have a more pronounced non-linear characteristic than SiC and can be used without series gaps due to their small current at nominal voltage. Yet, they are extremely effective at limiting surge voltages.

Most arresters employed today in new systems or revamps are gapless zinc-oxide devices.

There are three classes of power system surge arresters: station-, intermediate-, and distribution-class. Station arresters provide the best protective levels but are more expensive.

Insulation coordination is essential. This coordination compares the system or equipment insulation’s impulse withstand ability with the voltage across the arrester while surge current is being discharged.


Author: Lorenzo Mari holds a Master of Science degree in Electric Power Engineering from Rensselaer Polytechnic Institute (RPI). He has been a university professor since 1982, teaching topics as electric circuit analysis, electric machinery, power system analysis, and power system grounding. As such, he has written many articles to be used by students as learning tools. He also created five courses to be taught to electrical engineers in career development programs, i.e., Electrical Installations in Hazardous Locations, National Electrical Code, Electric Machinery, Power and Electronic Grounding Systems and Electric Power Substations Design. As a professional engineer, Mari has written dozens of technical specifications and other documents regarding electrical equipment and installations for major oil, gas and petrochemical capital projects. He has been EPCC Project Manager for some large oil, gas & petrochemical capital projects where he wrote many managerial documents commonly used in this kind of works.


Source URL: https://eepower.com/technical-articles/types-of-surge-arresters/

Substation Protection Against Transient Overvoltages and Lightning Strikes

Published by Lorenzo Mari, EE Power – Technical Articles: Substation Protection Against Transient Overvoltages and Lightning Strikes, December 11, 2020.


Learn how surge arresters protect power substations against lightning and switching overvoltages.

Transient overvoltages are typical of power systems. The sources of overvoltages are direct or nearby lightning strikes, switching operations, electromagnetic pulses, and electrostatic discharges. The classical device to protect equipment in substations against the effects of transient overvoltages is the surge arrester.

The most frequent transient overvoltage in substations comes from switching operations, and the most fearful is lightning, which introduces large disturbances.

Lightning-Caused Transient Overvoltages

Lightning is a prime source of transient overvoltages. In a substation shielded from direct strikes and with relatively low ground resistance, the most likely source of lightning surges is traveling waves entering through the overhead lines.

When lightning strikes an overhead line, it initiates a traveling wave. The traveling wave’s current value depends on the magnitude of the lightning surge, the line surge impedance, and the tower footing resistance. With phase conductors adequately shielded from direct strikes, the leading cause of the traveling waves is insulator flashover; in such cases, the overvoltage magnitude is the insulator flashover value.

Lightning is random, and there is always a possibility that a lightning strike, bypassing the substation’s shield, hits the protected circuits in or close to the substation.

The standard device to protect equipment in substations against overvoltages is the surge arrester. When connected from each phase conductor to the ground, the surge arrester transfers the high surge currents safely to the ground, protecting the system and equipment – such as transformers, circuit breakers, and bushings – insulating against the consequences of overvoltages.

Some Useful Terms

There are many terms in the analysis of power system electrical transients.  A few useful terms to be aware of are:

• Power-frequency: 60 Hz or 50 Hz, depending on the country’s standard.
• Flashover: a disruptive discharge around or over an insulator’s surface. Not to be confused with sparkover, which is a surge arrester term.
• Sparkover: a disruptive discharge between the surge arrester’s electrodes. This term does not apply to gapless metal-oxide arresters.
• Power-frequency withstand voltage: the highest rms applied voltage at which an arrester will not flashover.
• Impulse withstand voltage: the highest crest value of the surge voltage at which an arrester will not flashover.
• Power follow current: power-frequency current through an arrester, during and after the passage of surge current. This term does not apply to metal-oxide arresters.
• Arrester voltage rating: maximum power-frequency rms line-to-ground voltage to which an arrester may be exposed, even under transient conditions.
• Arrester discharge voltage: the voltage across the arrester while carrying surge current.
• Arrester discharge current: The current flowing through an arrester, resulting from a striking surge.
• Power-frequency sparkover: the minimum power-frequency rms voltage that will initiate sparkover between the line and ground terminals. This term does not apply to gapless metal-oxide arresters.
• Front-of-wave sparkover: the voltage on the front of an impulse wave, rising at a preset constant rate, at which the arrester sparks over.
• 1.2/50 µs impulse sparkover: the highest impulse voltage that an arrester will allow without sparkover. This term does not apply to gapless metal-oxide arresters.
• Maximum continuous operating voltage (MCOV): the maximum rms power frequency voltage that may be applied continuously between the arrester’s terminals. This term only applies to metal-oxide arresters.

Dielectric Tests

Anomalous voltage stresses cause early insulation failure. Insulation withstand refers to the voltage tolerated by equipment insulation without failure.

Knowing the withstand capability and endurance qualities of the insulation system is vital. Insulation-type designations, as well as high-potential and surge-voltage tests, classify the insulation’s properties and state the withstand capabilities.

Overvoltage tests certify the ability of the equipment insulation to outlive various stress levels after manufacturing completion. The most common tests are:

• Basic Lightning Impulse Insulation Level (BIL)
• Chopped Wave Withstand (CWW)
• Basic Switching Impulse Level (BSL)
• Front-of-wave-test

Let’s explore each of these tests a bit more.

Basic Lightning Impulse Insulation Level (BIL)

The BIL is the full-wave test. The standard impulse is a 1.2/50 µs (T1/T2 µs) waveshape, with a crest specified in kilovolts. This means that the voltage pulse increases from zero to crest value in 1.2 µs and declines to ½ crest value in 50 µs. The rise time and duration of this waveshape replicate a lightning surge.

The oscillogram of actual voltage may be challenging to interpret, particularly at the beginning of the waveshape. In this case, the BIL test finds a virtual time zero by locating points on the wave’s front where the voltage is 30% and 90% of the crest value and draws a straight line through these points. The virtual time zero is the intersection of this line with the time axis.

Figure 1 shows the standard 1.2/50 µs open-circuit voltage waveshape.

Figure 1. Standard 1.2/50 µs open-circuit voltage waveshape.

T1 is the time from the virtual zero to a point determined by the straight line’s intersection with a horizontal line at crest voltage value. T2 is the time from the virtual zero to half the crest value on the wave tail.

Therefore, T1 = 1.2 µs is the duration of the wavefront, and T2 = 50 µs is the time from the virtual zero to ½ crest value.

Another way to compute the time to crest is 1.67 times the actual time between 30% and 90% of the crest value. The crest values are classified into discrete values. A given rated voltage may have more than one BIL level.

The lightning strike’s currents also vary over a broad span. The industry standard impulse current is an 8/20 µs (T1/T2 µs) waveshape, as shown in Figure 2.

Figure 2. Standard 8/20 µs impulse current waveshape.

Another way to compute the time to crest is 1.25 times the actual time between 10% and 90% of the crest value.

Chopped Wave Withstand (CWW)

The waveshape for this test is the same used to determine the BIL, but it collapses at a time t – specified in the standard – after the wave’s crest by sparkover of an external rod gap shunting the tested equipment. The crest voltage is from 110% to 115% of BIL (Figure 3).

Figure 3. Sparkover on the tail.
Basic Switching Impulse Level (BSL) 

The BSL test of equipment is similar to the BIL but focuses on switching impulse rather than lightning. The wave shape depends on the tested equipment.

Front-of-wave Test

This test is similar to the chopped-wave test, but the voltage is cut off by a rod gap on the rising front of the wave at a time t rather than shortly after the wave’s crest. The gap limits the voltage to a preset value (Figure 4).

Figure 4. Front-of-wave sparkover.

The previous description involves general principles of dielectric testing. Standards for individual types of equipment detail the precise tests and methods to apply to the apparatus concerned.

Operation Principle of Surge Arresters

Insulation costs are very high, so insulating the system and equipment to resist any voltage that would ever appear is not economically viable. It is also impractical to insulate for steady-state voltage and accept all outages originating from surges. It is reasonable to look for a balance between the costs of insulation and protective devices.

Surge arresters are vital to protect the substations against lightning and switching surges. Their surge protective capability determines the power system insulation levels.

The duty of a surge arrester is to avoid exceeding the system and equipment withstand capabilities. Then, whenever a surge tries to exceed the insulation capacity, the arrester will keep the voltage in the acceptable range, protecting expensive electrical devices. 

Surge arresters are generally connected in parallel with the protected equipment and are subjected to the system voltage under normal operating conditions. Under steady-state voltage, their impedance is very high. However, it decreases abruptly at higher voltages when a steep wavefront surge comes into the system. The surge arrester diverts the wave’s portion above the arrester breakdown to the ground, away from the downstream protected equipment, as shown in Figure 5.

Figure 5. Operation principle of the surge arrester.

For the surge suppressor to adequately protect the equipment, the voltage that the suppressor sees before and after the surge’s arrival must not overshoot the voltage that the equipment can carry. 

In addition to the arrester’s capability to keep the voltage within an acceptable level, a vital factor to consider is its capacity to store or dissipate energy. The diverted current through the arrester and the voltage across it make the device absorb a quantity of energy that depends on the surge’s magnitude and duration. The arrester must store or dissipate this energy without any damage.

Under steady-state conditions, its resistance should be high enough to consume little current and dissipate minimal power.

To summarize, a surge arrester should:

• Display a high resistance under steady-state conditions, consuming a small leakage current – if any – and withstand the thermal stress it produces.
• Protect against an overvoltage, discharging the surge current immediately and limiting the voltage within a specified upper value – the arrester discharge voltage.
• Withstand the thermal energy generated by the surge current through the arrester elements – the arrester discharge current.
• Restore the steady-state conditions immediately after the surge voltage and current disappear, and interrupt the follow current.
• Possess switching surge discharging capability within specified levels.
• Be capable of discharging transmission lines

Separation Distance in a Surge Arrester

The surge arrester should be as close as possible to the equipment it protects because whatever it lets through before it operates will reflect with the same polarity– the equipment’s surge impedance is usually much greater than the line’s surge impedance (Figure 6).

If there is a large separation between the equipment and the surge arrester, the terminal voltage can reach a high value before being reduced by a reflection from the arrester.

Figure 6. Surge arrester separated from a transformer. Image courtesy of McGraw-Edison Company.

Keeping the surge arrester’s leads short reduces their inductance. We must avoid a situation in which the action of a surge arrester is nearly blocked or drastically delayed by the lead’s inductance.

A Review of Substation Protection Against Transient Overvoltages

A surge is a temporary steep rise of voltage in a power system, usually due to lightning or internal causes – mainly switching maneuvers. The energy contained in a surge may cause the failure of insulation in electrical systems and equipment unless they are correctly protected.

Surge arresters protect power substations by limiting lightning and switching overvoltages to a specified protection level below the insulation withstand voltage. 

Surge arresters have non-linear voltage and current characteristics, allowing them to start conduction at a specified voltage level, hold the voltage for the overvoltage duration, and stop conduction when the voltage returns to steady-state conditions. The arresters absorb or dissipate the overvoltage energy, as well.

The dielectric tests verify the ability of the system and equipment insulation to withstand various forms of surges. 

In the next article, we dive deeper into the features and characteristics of different surge suppressors by exploring their materials, topographies, and applications.


Author: Lorenzo Mari holds a Master of Science degree in Electric Power Engineering from Rensselaer Polytechnic Institute (RPI). He has been a university professor since 1982, teaching topics as electric circuit analysis, electric machinery, power system analysis, and power system grounding. As such, he has written many articles to be used by students as learning tools. He also created five courses to be taught to electrical engineers in career development programs, i.e., Electrical Installations in Hazardous Locations, National Electrical Code, Electric Machinery, Power and Electronic Grounding Systems and Electric Power Substations Design. As a professional engineer, Mari has written dozens of technical specifications and other documents regarding electrical equipment and installations for major oil, gas and petrochemical capital projects. He has been EPCC Project Manager for some large oil, gas & petrochemical capital projects where he wrote many managerial documents commonly used in this kind of works.


Source URL: https://eepower.com/technical-articles/substation-protection-against-transient-overvoltages-and-lightning-strikes/

Faults and Defects in Power Transformers – A Case Study

Published by Cacilda de Jesus Ribeiro1; André Pereira Marques2,3; Cláudio Henrique Bezerra Azevedo2; Denise Cascão PoliSouza1; Bernardo Pinheiro Alvarenga1; Reinaldo Gonçalves Nogueira1

1School of Electrical and Computer Engineering, Federal University of Goiás, Goiânia, GO, Brazil,
2CELG Distribuição, Goiânia, GO, Brazil,
3Federal Institute of Education, Science and Technology of Goiás, Goiânia, GO, Brazil


Abstract – Power transformers play a fundamental role in electrical power systems, in addition to representing significant investments involved in the implementation of these systems. To reduce the costs associated with a transformer’s life cycle and to guarantee its reliability and durability, it is essential to monitor its operating conditions, its insulation system, and the working conditions of its accessories and other components. Therefore, the aim of this work is to study the faults and defects that occurred in 34.5 kV, 69 kV, 138 kV, and 230 kV oil-immersed power transformers of the electrical system and the insulation system of CELG, a major electric energy concessionaire in the state of Goiás, Brazil. The results of this study, i.e., the efficacy of the predictive technique for maintenance over the last 28 years (from 1979 to 2007), the characterization of faults and defects during this period, and the presentation of proposals for improvements in the predictive technique, aimed at reducing the number of stoppages in the electric power supply system, are expected to contribute to the body of knowledge in this field.

I. INTRODUCTION

A power transformer is one of the most important and costly devices in electrical systems. Its importance is attributed directly to the continuity of power supply, since its loss through failure or defect means a supply stoppage. This is a large piece of equipment whose substitution is expensive and involves a lengthy process.

Research for new technologies and new predictive maintenance techniques has greatly contributed to reduce supply stoppages, thereby ensuring improved reliability of energy supply. Several studies highlight the importance of optimizing maintenance processes and diagnoses of substation equipment such as transformers [1].

In this context, the purpose of this research was to study faults and defects that occurred in 34.5 kV, 69 kV, 138 kV and 230 kV power transformers immersed in mineral oil for a period of 28 years at the electric power concessionaire CELG, which supplies over two million consumers distributed in 237 municipalities with a population of approximately four million in the state of Goiás, Brazil.

A defect is considered an anomaly in a device that can cause it to operate irregularly and/or below its nominal capacity. If not corrected in time, this defect can evolve, leading to failure of the equipment and its removal from service [2].

A fault is an anomaly in a piece of equipment that inevitably causes stoppage of its operation, forcing its removal from service [2].

As it is used here, the term “stoppage” indicates that the service of a piece of equipment was interrupted, i.e., it was removed from operation due to a defect or fault. The word “transformers” also refers to autotransformers.

II. POWER TRANSFORMERS

The present work was developed based on:

• the identification of the main parts of power transformers, which were analyzed and divided into blocks of components, as shown in Fig. 1; and

• The characterization and analysis of faults and defects detected in these devices, resulting from stoppages and/or interventions which they underwent.

Fig.1. Subdivision of a power transformer into blocks
III. STOPPAGES IN THE ELECTRIC POWER SYSTEM DUE TO TRANSFORMER DEFECTS AND FAULTS

A. Number of Stoppages of the Devices

In this study, 549 service stoppages were recorded from December 1979 to May 2007, involving 255 three-phase transformers or three-phase transformer banks, and several of these devices showed more than one stoppage.

Table I summarizes the number of devices, with their respective ranges of nominal output power and by nominal voltage.

Table I
Number of Devices by Range of Nominal Three-Phase Output Power and by Nominal Voltage

.

Of the transformer service stoppages in the period considered in this work, a certain number were due to faults and other defects, as indicated in Table II, reaching a total of 549 stoppages in this period of 28 years.

Table II
Number of Transformer Stoppages

.

It should be noted that this study took into account the devices that were removed definitively from operation as well as those that were purchased over the 28-year period of this study. It is estimated that 10% of the devices under study are part of the total number of transformers that belong to the system’s technical reserve over these years.

B. Number of Transformer Stoppages versus Damaged Components

Fig. 2 shows the percentage of transformer stoppages versus damaged components in the period of 1979 to 2007, without considering stoppages caused by the protection system and by human error. In this study, it was found that the components most affected were windings (34%), bushings (14%), onload tap changers, OLTC, (10%), and de-energized tap changers, DTC (10%). The item “unidentified component” (11%) refers to components which lack reliable records for several reasons.

The insulation system of the transformers in question is composed of mineral oil and solid insulation (cellulose, varnish or polyester), although most of it consists of oil-paper. It was found that the stoppages due solely to problems in the insulation oil accounted for only 4% of the number of stoppages during the 28 years analyzed here. The degradation of a transformer’s insulation system is usually the main parameter that causes electrical faults in these devices.

Fig.2. Number of transformer stoppages versus components

The aging of oil-paper insulation in a transformer depends on aging of both the paper and the oil. The assessment of the remaining life of a transformer is the desired result of diagnostic procedures. A popular belief is that the life of the insulation paper determines the transformer’s service life [3]. Thus, when factors of transformer insulation degradation such as water, oxygen, the products of decomposition in the oil and temperature are monitored and controlled continuously, there is decrease in the degradation of the insulation system, which means less risk of electrical faults [4]. CELG carries out systematic physicochemical testing and analyses of dissolved gases to control and monitor the insulating oil of its transformers, which is the reason for the low percentage of problems involving insulating oil in its devices (4%).

C. Transformer Failure Rates Over Time

As stated above, service stoppages can be caused by both defects and faults. The difference between them is that interventions to correct equipment defects can be programmed, unlike faults, which are generally emergencies in the electrical sector. It is therefore essential to know the individual transformer failure rates.

Fig. 3 shows the transformer failure rates in the CELG system per year and class of voltage, without considering the failures resulting from the protection system and from human error. In view of these results, and as can be seen in Figure 3, although failure rates of up to 9% were recorded (1992, 138 kV), the overall rates for the entire 28-year period are quite acceptable. These rates are listed in Table 3, and were calculated using (1).

.

where:
Tf : failure rate in the period under consideration [%]
Nf : number of failures in the period under consideration
Ne,i : number of devices existing in each year i considered
t : number of years of the period considered

Fig.3. Transformer failure rates over time

Analyzed quantitatively, the slightly higher rates of the 138 kV and 230 kV transformers are justified by the smaller number of devices of these classes of voltage.

Table III lists the failure rates of 34.5 kV, 69 kV, 138 kV and 230 kV transformers that occurred in the period under study, without considering the reserve equipment (estimated at 10% of the total number of power transformers).

Table III
Transformer Failure Rates for the Period of 1979 to 2007

.

As can be seen, the transformers failure rates of CELG’s system are relatively low, which is explained by the use of predictive techniques at this concessionaire. The company’s maintenance engineering sector, which strives to ensure a continuous supply of electric power by reducing the failure rate, has sought new predictive techniques, with emphasis on the detection of partial discharges in transformers by the acoustic method.

IV. PREDICTIVE TECHNIQUES

The well-known dissolved gas analysis (DGA) technique in insulating oil is sensitive to some types of incipient faults (defects). To quantify the efficiency of this technique in detecting such defects in CELG’s equipment, a comparison was made of the total number of transformer stoppages that could have been detected by the DGA predictive technique and the stoppages effectively detected by this technique. This comparison revealed that the technique provided an efficiency of approximately 75%. However, sampling of transformer oil for DGA testing is done periodically, according to the chromatography software program CELG uses and to the specificity of each device. Thus, between one sampling and the next, the device may undergo impacts from atmospheric discharges, external short circuits, and adverse operating conditions, which may trigger or accelerate incipient faults and cause the device to fail before the next sampling, masking the efficiency of the chromatography system. It is therefore understood that the efficiency of the DGA technique, per se, is higher than 75%. In addition to DGA, another predictive technique that could be used to increase the monitoring efficiency of the state of transformer insulation is the detection of partial discharges (PDs). The DGA method has only low sensitivity for detecting partial discharges [5]. This may sometimes lead to inaccuracy in analytical methods, which may lead to errors by the person analyzing test results. Furthermore, the DGA technique does not allow for the identification of the site of an incipient fault, making it difficult to locate it, especially if its intensity is low. Particularly interesting is the use of a noninvasive method such as the acoustic PD detection method, which allows for monitoring of the evolution of PDs even while the device is in operation.

Throughout its operation, a power transformer has to withstand numerous stresses that generally result in the degradation of the oil-paper insulation system by decomposition of the paper and/or oxidation of the oil.

Degradation reduces the quality of this insulation. Partial discharges can lead to winding breakdowns, and may cause accelerated aging. PDs must be inferred in order to build an early warning system. In this context, PDs serve as an important measuring parameter for on-line monitoring [6].

To illustrate the above, the photograph in Fig. 4 depicts the failure of a 20 MVA power transformer with a nominal voltage of 69 kV/34.5 kV, showing damage sustained by a large extent of the winding.

Fig.4. Damaged winding

Systematic equipment monitoring by the DGA technique showed a slight increase in gases, however without providing a warning about the need to remove this device from service, ultimately leading to its damage by short-circuiting between the spirals.

As can be seen in Fig. 5, the short circuit caused dislocation of the winding due to an electrodynamic overload.

Fig.5. Dislocated winding

This fault could have been avoided by PD detection, preventing the defect from developing into a short circuit between spirals and, hence, failure of equipment. This indicates the need for integrating predictive maintenance techniques in order to improve diagnostic quality and ascertain the state of transformer insulation systems.

This paper therefore presents a proposal for improving predictive techniques through the implementation of a set of techniques, highlighting the combination of DGA with the detection of partial discharges by the acoustic emission method [7], which allows PD activity to be pinpointed in the equipment without requiring its shutdown.

V. CONCLUSIONS

Although the failures rates and the number of stoppages that occurred during the period under study were relatively low, it is important to implement other predictive techniques that are sensitive to incipient faults in power transformers – especially in terms of problems involving windings, bushings and tap changers, which, taken together, account for 68% of the events in components of these devices – in order to further improve the performance quality indicators reported here. Among these techniques, this paper highlights the measurement of partial discharges by the acoustic emission method, which could be allied to the DGA method, a technique well-known in the energy sector, thereby increasing the maintenance efficiency and quality of electric power supply.

ACKNOWLEDGMENTS

This work was carried out in collaboration with the Maintenance Engineering Division of CELG Distribuição, CELG D, and the Federal University of Goiás School of Electrical and Computer Engineering (EEEC/UFG) through a partnership in an R&D Project – ANEEL.

REFERENCES

[1] M. WANG; A.J. VANDERMAR; K.D. SRIVASTAVA, “Review of Condition Assessment of Power Transformers in Service”, Proceedings of 2002 IEEE Electrical Insulation Magazine, Canada, November/December, v.18, n.6, pp.12-25, 2002.
[2] J. LAPWORTH, “Transformers reliability surveys”, Journal Electra, Cigré, n.227, August, pp.10-14, 2006.
[3] I. Höhlein and A. J. Kachler, “Aging of cellulose at transformer service temperatures. Part 2. Influence of moisture and temperature on degree of polymerization and formation of furanic compounds in free-breathing systems”, IEEE Electrical Insulation Magazine, vol.21, Sept.-Oct., pp. 20-24, 2005
[4] A.P. MARQUES, “Eficiência energética e vida útil de transformadores de distribuição imersos em óleo mineral isolante” (Energy efficiency and service life of distribution transformers immersed in insulating mineral oil), Master’s Dissertation – School of Electrical and Computer Engineering, Federal University of Goiás, Goiânia, 2004.
[5] Associação Brasileira de Normas Técnicas (Brazilian Technical Standards Association), Técnicas de ensaios elétricos de alta tensão – medição de descargas parciais, NBR-6940 (High-voltage electrical testing techniques – measurement of partial discharges, NBR-6940), Brazil, 1981.
[6] C. Yonghong; et al., “Study of On-line Monitoring Method of Partial Discharge for Power Transformers Based on RFCT and Microstrip Antenna”, Proceedings of the 2005 Electrical Insulation Conference, Indianapolis, USA, October, pp.103-107, 2005.
[7] Institute of Electrical and Electronic Engineers – IEEE Std., COLE, P.T., “Location of Partial Discharges and Diagnostics of Power Transformers using Acoustic Methods”, Proceedings of 1997 IEEE Diagnostic Methods for Power Transformers Conference”, London, 1997.


Source URL: https://studylib.net/doc/18633368/faults-and-defects-in-power-transformers-%E2%80%93-a-case-study

Electrical Grounding and Bonding per NEC

Published by Joe Doughney and Lilly Vang, Consulting-Specifying Engineer, Electrical Articles: Electrical grounding and bonding per NEC, December 9, 2020.


Understanding correct grounding and bonding design and construction is crucial for proper electrical system operation and personnel safety

Learning Objectives

• Learn the proper electrical grounding terminologies.
• Understand National Electrical Code grounding and bonding requirements for solidly grounded alternating current low-voltage systems (below 1,000 volts).
•Prevent common grounding and bonding design and construction errors.


Electrical grounding and bonding is one of the many misunderstood topics of discussion in the design and construction industry. There are two main reasons for understanding grounding and applying the correct design for grounding and bonding: safety and correct operation of sensitive electronic equipment.

NFPA 70: National Electrical Code Article 250 covers the minimum requirements for grounding and bonding and, although the NEC lists requirements to abide by, it should not be taken as a design manual. Some terms and requirements discussed may be true for the European standards, however, the intent of this article is to clarify grounding and bonding design seen in the United States.

Grounding and bonding requirements

Article 250 is a complex portion of the NEC and covers many different types of systems: grounded systems (less than 50 volts, 50 to 1,000 volts and greater than 1,000 volts), ungrounded systems, systems greater than 1,000 volts, impedance grounded neutral systems, direct current systems, separately derived systems and grounding of instrument and meters/relays. The intent of this article is to discuss the requirements of solidly grounded, alternating current electrical systems less than 1,000 volts.

Grounding and bonding practices are important and required per NEC because when done properly, it will protect personnel from electrical shock hazards and ensure electrical system operation. These practices perform the following functions:

• Keeps equipment enclosures and other normal metal parts stable and therefore, safe to touch.
• Limits unintended voltage on the electrical system imposed by lightning, line surges or unintentional contact with higher-voltage lines.
• Bonds electrical equipment together to establish a low impedance path (effective ground-fault current path) from the fault location back to supply source to facilitate the operation of overcurrent devices.
• Establishes a stable voltage to ground during operation, including short circuits.
• Keeps electromagnetic interferences from causing misoperation.
• Prevents objectionable current.

The requirements for grounding and bonding begin at the service. The NEC requires the grounded conductor(s) to be routed with the ungrounded conductors to the service entrance equipment and it shall connect to the grounded conductor(s) terminal or bus. The grounded service conductor is required to be connected to a grounding electrode conductor at each service. The main bonding jumper shall connect the grounded conductor to equipment-grounding conductors and the service entrance enclosure via the grounded conductor’s terminal or bus.

The GEC shall be used to connect the EGCs, the service equipment enclosures and where the system is grounded, the grounded service conductor to the grounding electrodes. Figure 1 details the grounding system connections.

The minimum sizes of the grounded conductor, EGC and GEC are determined based on NEC Table 250.102(C)(1), Table 250.122 and Table 250.66, respectively. The sizes for the main bonding jumpers, supply side bonding jumpers and system bonding jumpers can also be sized from Table 250.102(C)(1).

Although the grounded conductor is connected on the supply side, it shall not be connected to the EGCs or reconnected to ground on the load side of the service disconnection means except as otherwise permitted in the 2017 NEC Article 250.142(B).

Common errors

There are a few errors commonly seen in design or during construction due to a lack of understanding or misconception concerning grounding, bonding and the NEC Article 250. A few commonly seen errors are:

Error 1: Using the wrong tables for EGC, grounded conductor or GEC.

The sizing methods detailed in the NEC are the minimum requirements and it may not be adequate for the scope and size of the project. Large available short-circuit currents may require larger conductor sizes than the minimum NEC requirements.

The EGC should be sized per Table 250.122. A full-sized EGC is required to prevent overloading and possible burnout of the conductor if a ground fault occurs along one of the parallel branches. The EGC is sized in accordance with Table 250.122 based on the rating of the overcurrent protective device upstream that protects the conductors routed with the EGC.

However, the sizes for EGC in Table 250.122 does not account for voltage drop. Therefore, ungrounded conductors shall be sized while taking into account the voltage drop and per 250.122(B), the EGC shall be increased in size proportionately to the upsized ungrounded conductors. For example, given a 480-volt branch feeder circuit breaker rated 150 amperes, the EGC shall be sized 6 AWG copper or 4 AWG aluminum for a voltage drop of at most 3%.

The grounded conductor at the service should be sized in accordance with Table 250.102(C)(1), based on the size of largest ungrounded conductor or equivalent area for parallel conductors. This table can also be used to size the main bonding jumper, system bonding jumper and supply-side bonding jumper for AC systems. As stated in the notes of Table 250.102(C)(1), for ungrounded conductors larger than 1,100 kcmil copper or 1,750 kcmil aluminum, the conductor shall have an area not less than 12.5% of the area of the largest ungrounded supply conductor or equivalent area for parallel supply conductors. If the ungrounded conductors are installed in parallel in two or more sets, the grounded conductor shall also be installed in parallel.

For parallel sets, the equivalent size of the largest ungrounded supply conductor(s) shall be determined by the largest sum of the areas of the corresponding conductors of each set. For example, given that the electrical service is supplied by five sets of 500 kcmil copper conductors, the grounded conductor required in each set shall be 350 kcmil copper. The total equivalent area of the parallel supply conductors in each set is 2,500 kcmil (five times 500 kcmil given five parallel ungrounded conductors). Because the equivalent area is above 1,100 kcmil for copper, the grounded conductor(s) shall have an area not less than 12.5%. This is an area of roughly 312.5 kcmil, which according to Table 8 of Chapter 9 in the 2017 NEC, is 350 kcmil copper.

The GEC should be sized per Table 250.66. The notes at the bottom of Table 250.66 needs to be considered if there are multiple service entrance conductors or no service entrance conductors. Given the number of service entrance conductors, the size is determined either by the largest ungrounded service-entrance conductor or the equivalent area for parallel conductors. The size of the GEC is also dependent on the material of the conductor and its connection to specified electrodes in Article 250.66(A) through (C). The allowed materials are copper, aluminum, copper-clad aluminum and items allowable in Article 250.68(C).

For example, given that the electrical service is supplied by one set of 500 kcmil copper conductors, the GEC per Table 250.66 shall be 1/0 AWG copper. The location for GEC installation is at the service, at each building or structure where supplied by a feeder(s) or branch circuit(s) or at a separately derived system.

To reiterate, the GEC is the connection of the system grounded conductor or the equipment to a grounding electrode or to a point on the grounding electrode system. This leads on to error No. 2, errors in the grounding electrode system, which is commonly seen in design and construction.

Error 2: Meeting only bare minimum NEC requirements for grounding electrode system that may not satisfy project scope.

The grounding electrode system is made up of grounding electrodes that are present at each building or structure served that are bonded together. The items that qualify as a grounding electrode are detailed in Article 250.52, which includes concrete-encased electrode, ground ring encircling the building or structure, rod and pipe electrodes, plate electrodes and other listed electrodes. The NEC details the minimum requirements but not necessarily the design or construction requirement that allows for a functional system depending on the project scope.

These are the commonly seen issues in grounding electrode system that follows the NEC, but does not satisfy project scope:

  • Not installing a third grounding electrode. The NEC requires a minimum of two grounding electrodes, unless one electrode has a resistance to earth less than 25 ohms. However, commonly in construction, the ground resistance is not measured again after a supplemental grounding electrode is installed. Therefore, the ground resistance of 25 ohms is not confirmed as having been met. Per the NEC, two electrodes would meet code, but this doesn’t guarantee a low electrode-to-earth resistance. Including a grounding ring with multiple grounding electrodes is considered a best practice to ensure low resistance. Also, specifications should also require ground resistance measurements to be taken after grounding electrode system is installed to determine if additional electrodes are required.
  • Allowing 25 ohms ground resistance because it is allowed by code.
  • Installing grounding electrodes (in particular, rods) 6 feet apart because that is the minimum separation required by code.
    • Each ground rod has its own zone of influence as shown in Figure 2. The optimal spacing between rods should be twice the length of the ground rod. When the zones overlap, the net resistance of each rod increase, thus making the ground system less effective.

There are many considerations that need to be taken into account when designing and installing grounding electrode systems. These are:

  • Size of service.
  • Types of loads that will be connected.
  • Soils: the resistivity is affected by salt, moisture, temperature and depth.

While considering all of the above factors, some of the best practices seen in the industry are using ground rings around buildings, ground triangles at smaller services, exothermic welds for concealed or buried connections and ground rods and installing ground testing/inspection wells that allow easy access for ground resistance testing.

Error 3: Bonding grounded conductor (neutral) to ground bar at multiple locations.

Per Article 250.142, the neutral to ground connection is allowed on the supply side or within the enclosure of the AC service disconnecting means. This connection is also allowed at separately derived systems. If the grounded conductor is grounded again on the load side of the service, the connection between the grounded conductor and the EGC on the load side of the service places the EGC in a parallel circuit path with the grounded conductor.

Another issue that can arise out of multiple bonding locations is the risk the grounded conductor being disconnected on the line side of the service. This could cause the EGC and all conductive parts connected to it to become energized because the conductive path back to the source that would normally allow the overcurrent device to trip is not connected. In this case, the potential to ground of any exposed metal parts can be raised to line voltage, which can result in arcing and severe shock hazard.

Error 4: Grounding and bonding design for separately derived systems.

One common error in grounding and bonding design is the grounding of generators and whether a three- or four-pole automatic transfer switch is used with a four-wire power system. Grounding a separately derived system is detailed in Article 250.30. The error in grounding and bonding design for separately derived systems stems from understanding the definition of a separately derived system. As shown in Figure 3, a system is considered separately derived when the system does not have a direct electrical connection to the other supply system grounded conductor (neutral), other than through the bonding and equipment grounding conductor.

The generator also requires to be directly connected to ground when it is considered a separately derived system as shown below. If a four-pole ATS is used and the neutral is switched, the generator or secondary backup source becomes a separately derived system. It should be noted that a three-pole ATS can be used with a four-wire generator and also be considered a separately derived system if the electrical distribution system is a three-wire system. In this situation, the generator neutral would be connected to ground, but a grounded (neutral) conductor would not be brought to the ATS.

Grounding and bonding definitions

There are many requirements in NFPA 70: National Electrical Code Article 250. A common reason for confusion mainly stems from not understanding the proper definitions. Therefore, the first step to understanding Article 250 is understanding the terminology within the NEC. Below are some terms taken from the 2017 edition of NEC Article 100 and clarifications for mentioned terms.

Bonded (bonding): Connected to establish electrical continuity and conductivity. Bonding is not to be confused with grounding. Two pieces of equipment bonded together does not necessarily mean both pieces of equipment are grounded. However, it assures that the metallic parts of the bonded equipment can form an electrically conductive path for electrical continuity.

Bonding jumper, supply side: A conductor installed on the supply side of a service or within a service equipment enclosure(s) or for a separately derived system that ensures the required electrical conductivity between metal parts required to be electrically connected.

Bonding jumper, system: The connection between the grounded circuit conductor and the supply-side bonding jumper or the equipment grounding conductor or both, at a separately derived system.

Bonding conductor or jumper: A reliable conductor to ensure the required electrical conductivity between metal parts required to be electrically connected.

Bonding jumper, main: The connection between the grounded circuit conductor and the equipment grounding conductor at the service.

Effective ground-fault current path: An intentionally constructed, low-impedance electrically conductive path designed and intended to carry current under ground-fault conditions from the point of a ground fault on a wiring system to the electrical supply source and that facilitates the operation of the overcurrent protective device or ground-fault detectors. The earth is not considered as an effective ground-fault current path.

Equipment grounding conductor: The conductive path(s) that provides a ground-fault current path and connects normally noncurrent-carrying metal parts of equipment together and to the system grounded conductor or to the grounding electrode conductor or both.

Ground: The earth.

Grounded conductor: A system or circuit conductor that is intentionally grounded (I.e., neutral conductor).

Grounding electrode: A conducting object through which a direct connection to earth is established. Common grounding electrodes include rods, plates, pipes, ground rings, metal in-ground support structures and concrete-encased electrodes. All grounding electrodes at each building or structure shall be bonded together to form the grounding electrode system.

Grounding electrode conductor: A conductor used to connect the system grounded conductor or the equipment to a grounding electrode or to a point on the grounding electrode system.

Ground-fault current path: An electrically conductive path from the point of a ground fault on a wiring system through normally noncurrent-carrying conductors, equipment or the earth to the electrical supply source. Examples of ground-fault current paths are any combination of equipment grounding conductors, metallic raceways and electrical equipment.

Grounded (grounding): Connected (connecting) to ground or to a conductive body that extends the ground connection. Grounding is not to be confused with bonding. Equipment may be bonded together, but it is not considered grounded unless it is connected back to the ground.

Grounded, solidly: Connected to ground without inserting any resistor or impedance device.

Neutral conductor: The conductor connected to the neutral point of a system that is intended to carry current under normal conditions.

Neutral point: The common point on a wye-connection in a polyphase system or midpoint on a single-phase, three-wire system or midpoint of a single-phase portion of a three-phase delta system or a midpoint of a three-wire, direct-current system.

Service: The conductors and equipment for delivering electric energy from the serving utility to the wiring system of the premises served.

Service equipment: The necessary equipment, usually consisting of a circuit breaker or switch and fuses and their accessories, located near the point of entrance of supply conductors to a building or other structure or an otherwise defined area and intended to constitute the main control and means of cutoff of the supply.


Authors: Joe Doughney is an electrical engineer with CDM Smith, where he focuses on design and analysis of electrical power systems. Lilly Vang is an electrical engineer with CDM Smith. She focuses on electrical power system design and power system studies.


Source URL: https://www.csemag.com/articles/electrical-grounding-and-bonding-per-nec/

Utility Power Transmission and Distribution Systems

Published by Alex Roderick, EE Power – Technical Articles: Utility Power Transmission and Distribution Systems, October 16, 2021.


Electrical power used in residential, commercial, and industrial buildings is typically generated by a utility at a central point and transmitted and distributed to where it is required through the utility power transmission and distribution system.

A utility power transmission and distribution system controls, protects, transforms, and regulates electrical power so it can be safely delivered to the user. The utility power transmission and distribution system begins at the point of power production and normally ends at a building metered service entrance point, which is where the building distribution system begins. A utility power transmission and distribution system consists of transmission substations (step-up transformers), transmission lines, distribution substations (step-down transformers), and distribution lines (see Figure 1).

Figure 1. A utility power transmission and distribution system consists of transmission substations (step-up trans-formers), transmission lines, distribution substations (step-down transformers), and distribution lines.
Transmission Substations

A transmission substation is an outdoor facility located along with a utility system that is used to change voltage levels, provide a central place for system switching, monitoring, protection, and redistribute power. Transmission substations normally operate at high voltage (HV), 69 kV to 345 kV, and extra-high voltage (EHV), the voltage over 345 kV. Transmission substations are also used to make changes in the size and number of lines sent out from the station.

Transformers

The transformer is an electrical device that changes the voltage from one level to another by using electromagnetism. In electrical distribution systems, transformers are used to safely and efficiently increase or decrease voltage. Although a transformer can be used to increase or decrease voltage, transformers cannot be used to increase or decrease the amount of power available. Except for some minor power loss caused primarily by heat loss, the amount of power entering a transformer is the same amount of power leaving the transformer. Transformers allow utilities to distribute large amounts of power at a reasonable cost (see Figure 2). Transformers are rated in kVA, which specifies their power output capability.

Figure 2. Transformers are used in electrical distribution systems to safely and efficiently increase or decrease voltage to allow utilities to distribute large amounts of power at a reasonable cost. Image Courtesy of GE

The main advantage of increasing voltage and reducing current is that power may be transmitted through small gauge conductors, which reduces the cost of power lines. For this reason, the generated voltages are stepped up to high levels for distribution across large distances and then stepped down to meet user requirements. Though both current and voltage can be stepped down or up, when it comes to transformers, the terms “step up” and “step down” always refer to voltage.

Transmission Lines

A transmission line is an aerial conductor that carries large amounts of electrical power at high voltages over long distances. To be safe, transmission lines must be positioned far enough apart. The transmission voltage level is determined by the required transmission distance as well as the amount of power carried. A larger transmission voltage is chosen when dealing with longer distances or larger transmitted power levels (see Figure 3).

Figure 3. Transmission voltage increases with distance or transmitted power

There is a wide variety of transmission line voltages, ranging from a few kilovolts to hundreds of kilovolts. Transmission-line voltage is stepped up to allow large amounts of power to be transmitted using smaller conductors. Since conductor sizes are based on the amount of current they can safely carry without overheating, low current levels can be carried over small size conductors. The amount of current changes inversely with the amount of voltage for a given power level (see Table 1).

Power, Voltage, and Current Relationship

Table1. The amount of current changes inversely with the amount of voltage for a given power level.

In addition, increasing the transmitted voltage lowers the power losses between the utility generator and the final delivery point. Doubling the transmitted voltage can reduce the power loss by up to 75%. Because transmitting power at high voltages reduces the required size and weight of the conductors, the poles and towers that support the conductors can be smaller and spaced farther apart. Therefore, greater transmitted voltages allow for smaller conductor sizes, higher power transmission, and lower construction and material costs.

Utility generators that output three-phase power have high-voltage distribution lines arranged in groups of three. In addition to the power lines, a neutral/ground conductor is also routed with the power lines. The neutral/ground conductor is routed on top of power lines and used as a grounding wire to help dissipate lightning strikes. The neutral/ground conductor is grounded at every power pole and at the transmission and distribution substations. The voltage on the power lines is stepped up and down many times before it reaches the end-user.

Distribution Substations

A distribution substation is fundamentally an outdoor facility that is located near the point of electrical service use and is used to adjust voltage levels, provide a central place for system monitoring, switching, and protection, and redistribute power. Distribution substations take high transmitted voltages and reduce the voltage for further distribution. Transmission substations operate at higher voltages, whereas distribution substations operate at lower voltages. The output voltages of distribution substations typically range from 12 kV to 13.8 kV.

Distribution substations provide a location along the distribution system near the end-user to easily test the system, adjust voltage output, add new lines, disconnect lines, and redirect power during distribution system problems such as power outages caused by lightning strikes. See Figure 5. Distribution substations take the incoming power and, after changing the voltage level, produce multiple outputs with different voltages on each line.

Figure 4. Distribution substations provide a convenient place along with the distribution system for maintenance, checks, and line adjustments. Image courtesy of OSHA
Distribution Lines

Distribution lines are used to carry electrical power from a distribution substation to the building service entrance. Distribution lines connect parts of the system together and are often run in multiple lines so that electrical power can be switched to meet changing power requirements and switched between different utilities. The term “grid” is used to describe the network of interconnected transmission and distribution lines.


Author: Alex earned a master’s degree in electrical engineering with major emphasis in Power Systems from California State University, Sacramento, USA, with distinction. He is a seasoned Power Systems expert specializing in system protection, wide-area monitoring, and system stability. Currently, he is working as a Senior Electrical Engineer at a leading power transmission company.


Source URL: https://eepower.com/technical-articles/utility-power-transmission-and-distribution-systems/

Cars with Electric Drive and External Costs of Road Transport

Published by Wojciech GIS1, Zdzisław KORDEL2, Maciej MENES1,
Motor Transport Institute (1), The University of Gdańsk (2)


Abstract. The paper describes external environmental costs of road transport. Article presents also an assessment of the so-called reduction. “Marginal costs” such as the cost of fuel emissions, noise and greenhouse gas emissions, by the introduction into service, in the real perspective of 2020, electric cars. European project eMAP is described, in which are involved the authors of this article. The project is related to the assessment of demand and supply, in perspective 2030, of electric cars: Battery Electric Vehicles (BEV), Plug-in hybrid electric vehicles (PHEV), Range extended electric vehicles (REEV) and Fuel cell hydrogen vehicles (FCHV). The analysis will be carried out for the EU countries, in particular for Finland, Germany and Poland and eastern EU countries.

Streszczenie. W artykule odniesiono się do środowiskowych kosztów zewnętrznych związanych z eksploatacją samochodów osobowych. Dokonano w tym zakresie oceny redukcji tzw. „kosztów uniknionych” tj. kosztów emisji zanieczyszczeń z paliw, hałasu I emisji gazów cieplarnianych przez wprowadzenie do eksploatacji, w realnej perspektywie 2020 roku, w kraju elektrycznych samochodów osobowych. Przedstawiono też Europejski Projekt eMAP w którego realizację zaangażowane są ze strony polskiej, autorzy niniejszego artykułu. Projekt związany jest z oceną popytu i podaży, w perspektywie 2030 roku, osobowych samochodów elektrycznych Bartery Electric Vehicles (BEV), Plug-in hybrid electric vehicles (PHEV), Range extended electric vehicles (REEV) and Fuel cell hydrogen vehicles (FCHV) w krajach UE, w tym w szczególności Finlandii, Niemczech i Polsce oraz w krajach wschodnich UE. Samochody o napędzie elektrycznym a koszty zewnętrzne transportu samochodowego.

Słowa kluczowe: samochody elektryczne, koszty eksploatacji
Keywords: electrical cars, costs of transport

Introduction

Every human activity directed at the environment, both positive and negative, brings with it the need to cover the cost of protecting it, as well as environmental losses, mainly economic ones, caused by that activity. It is, admittedly, quite idealistic statement because present economic activity and that in the future is largely contradictory with this environmental ideology. It is well known [1] that the negative impact of economic activity on the environment often eludes the market self-regulation mechanisms. Indeed, if some elements of the ecosystem, as a free good, have a market price equal zero, the use of them, either by the consumer or by the manufacturer is an uncontrollable phenomenon. Therefore, the active policy is required from each state to protect the environment.

In general it can be said that human activity causes external effects, which are apparent in cases where different entities use common resources, for which ownership has not been clearly defined. Areas that bear the effects of transport activities outside the transport market can be classified into three groups [2]:

– non-renewable resources / natural environment and non-productive human capital,
– public production and consumption,
– private production and consumption.

The man’s use of all elements of the ecosystems with the market price equal to zero, has certain negative social and economic consequences, whose end, according to marginalistic theory comes only when the marginal productivity and usability of these elements becomes negative. Polish example can be cited in which about 25% of the country territory is covered by the Natura 2000 program, which with the orthodox approach to the issue of environmental protection would mean that not a single kilometre of motorway or expressway should be built, so there will be no issue of final marginal costs.

In addition, one must admit that the costs of natural environment protection are nowadays quite fashionable issue, and its value increases at a time when the budgets of the Member States of the European Union begin to look for sources of financial incomes. This can be seen, in particular, in Polish realities, where the introduction of high fees in the e-toll system bears no reflection on the quality of a transport infrastructure. It must also be noted that the rates for the use of road infrastructure in Poland should be taking into account at the financial capabilities of the Polish road transport companies and the state financial system, and should not be related to the rates in other EU Member States, especially those from the Euro zone.

One of the most important human economic activity adversely affecting the environment is transport, widely described in the White Papers of the European Union.

External costs of the road transport

In the expert literature produces various definitions of external costs. One must admit that some of them are very general and the others contain an attempt to formulate some concrete facts, which are to be the determinant of these external costs. It can also be said that the concept of external costs is very general and relates more to the philosophy of economic functioning of modern economic market than to a specific market.

Now, taking into account the company, one can say that acting in a particular economic environment, both closer and further, its financial situation is mainly due to the impact of external costs such as: fuel, tires, tolls and insurance, as well as large investments appearing in the development of energy industry. These instruments have a major impact on the cost of the company, and will also influence the financial possibilities of introducing electric vehicles.

Use of the term – “external costs of transport” can be, according to the authors, used only in the consideration of environmental issues at the macroeconomic level. These considerations, in the consequence, will be reflected in the costs of the enterprises because only they are capable of generating these costs, trying to cover them with their activities by one hundred percent. It seems, therefore, that in talking about the external costs in transport one should, taking into account the basic economic unit, which the enterprise is, distinguish two categories of costs:

– external costs resulting from the principles and rules of operation of businesses on the market,
– environmental protection costs associated with the operation of transport.

This division seems to be logical from the point of view of economic calculation in the enterprise. The functioning of enterprises is based on the influence of the external instruments and these are, as mentioned earlier, dependent on the impact of the closer or further surroundings. It’s obvious. Less obvious becomes the impact of environmental protection costs on the level of costs in the company because this level is often dependent on the general mood of environmental protection activists in Europe.

Ecological intention to reduce greenhouse gas emissions in the European Union may be a good one, but insoluble in the short term. It should also be taken into account that not only road transport is the emitter of carbon dioxide, but also all the economic sectors and supply chains that use electricity from coal. It is easy to say that, to a large extent, I do not produce, electricity from coal and I just only import it. It is after all a kind of hypocrisy that has taken root in the European Commission. This raises the question, if one needs to reduce carbon emissions, who should bear the costs if it, the state or the enterprises? Of course, if these costs will be covered by the state, it will still have to pass these costs on the electricity users, because the state is an abstract being with the real budget. So if it is to be the companies, in what amount, and depending on what the indicators? It should be recalled that the Polish road transport companies already pay an environmental levy, whose rates are annually determined by the Marshal Offices. This problem will be completely resolved in the future when humanity will produce electricity from sources not emitting carbon dioxide.

A.Tylutki and J.Wronka [4] state that the external costs of transport are the costs connected with negative for the environment and human life consequences of the activities of transport: air, water and soil pollution, noise emissions, traffic accidents, ground reclaiming and road congestion. While D.M. Newberry classified external traffic effects as [5]:

– costs associated with traffic congestion,
– costs associated with the deterioration of the technical condition of roads,
– costs associated with environmental pollution,
– the external effects of accidents.

These external effects are particularly evident in urban areas, because of their network of road infrastructure are the most intensively used, and spatial density is the highest [6].

In general, one can say that the external transport costs are the costs that are and will be covered by the general public and businesses today and in the future. It is possible to single out here, first of all, the costs associated with the impact of transport, such as: air, soil, water pollution, noise, climate changes, accidents, reclaim of land, landscape degradation and the time lost in traffic jams / congestion /. These costs can generally be called the social costs of transport. These should also include all the expenses to be incurred on a modern energy infrastructure that allows the future use of electric cars.

External costs of transport can not be precisely calculated, and their levels can be the result of a consensus between businesses and economic policy of the state. It was only in 2011, that the research subject of the European Commission under the name COFRET (Carbon Footprint of Freight Transport) began, which is to show the impact of carbon dioxide emissions on the costs of supply chain and thus the companies [7]. The fact is that the transport does not pay the full social costs, including the environmental ones, which may lead to disturbances of the competition on the transport market. It should be noted though, that this is not the fault of transport. Well, at the moment when you the state became a participant in the market / excluding demand, supply and price / it takes on the responsibility for the effective functioning of the socio-economic market. This means that pushing environmental protection policy it must be responsible for the level of environmental costs in the situation when it shifts them entirely onto the companies. It can be assumed that as a result of distorted price mechanism, the absence of the full environmental protection costs / the transport does not fully bears these costs, but one has to take into account the fact that other sectors of the economy should be involved in covering these costs, if only the chemical one/.

External environmental costs of road transport

The air pollution is today one of the very serious environmental problems. Needless to say, that the emission of these pollutants adversely affects the quality and length of human life, disturbs the balance of ecosystems and causes also irreversible socio-economic consequences for the future of humanity. It is worth to mention here a worldwide debate on the issue of climate change in the Earth where it is assumed that, so-called, greenhouse effect of the climate change, is caused by carbon dioxide [8]. It is assumed that the main culprit of this emission – 25% is transport, out of which from 80 to 90% of the road transport. The EU policy on reducing exhausts emissions assumes that by the 2030, member states are expected to reduce carbon dioxide emissions by 20%, and by the 2050 – by (80 – 95)% [9].

In Poland, the biggest environmental problems creates the large scale of road transport activities. In the period 2000 – 2008 there was an increase of emissions from the road transport sector, classified as greenhouse gases, i.e. carbon dioxide, by 37.7%, methane by 23.1% and nitrous oxide emissions by 38.3% [10, 11].

In Poland, for example, the cost of the negative impact of transport on the environment represent approximately 28 – 29% of the external costs of transport, including [10, 11]:

– costs of air pollution, about 11%,
– costs of climate change, around 5%,
– costs of noise, about 11%,
– other environmental costs, about 1 – 2%.

The remaining 71% of the external costs of transport are the effects of human and material transport accidents [10], [11]. In total, it is estimated that the external transport costs are now equivalent to 6% of GDP and are not included in the accounting [10, 11].

It is estimated that the individual domestic motorism will have the largest share in the passenger transport, increasing demand in 2020 by 26 – 35% compared to 2009 and by 36 – 54% in 2030 [10, 11].

The European Commission’s vision of an integrated strategy of the European transport sector development until 2050, assumes a reduction, by at least 60% till the 2050 of the greenhouse gases emissions from the transport sector compared to 1990 level, through a transition to alternative and “green” propulsion technologies in vehicles and the creation of a Single (Uniform) European Transport Area. By 2030 the greenhouse gas emissions are to be reduced in this sector by about 20% compared with the level in 2008 [10, 11, 12].

The direction is and, as it can be assumed, will be the electrification of vehicles. It is expected that the share of electric vehicles equipped with rechargeable batteries in the new cars market, sales will increase from 1 – 2% in 2020 to 11 – 30% in 2030. For the hybrid vehicles with plug in charging, the share is expected to be about 2% in 2020 and 5 – 20% by the 2030 [10, 11]. According to the European Commission’s strategy, by the 2030 there will be eliminated 50% of vehicles from the public transport with conventional internal combustion engines, and by 2050 they will not be present in European cities [10, 11]. In Poland, the above course of action in terms of electrification of vehicles, also seems to be inevitable.

To estimate the external environmental costs of road transport (passenger cars only) in Poland, by the 2020 it was assumed that in the absence of active government policy in relation to the road transport sector, in 2020 there will be, in operation, approximately 25,000 electric cars. This will be only 0.12% of the total number of passenger cars, forecast at 20.9 million [13]. The expected increase in the activity of government policy resulting from the provisions of the “EU White Paper” of 2011 [12], on the impact of the road transport sector on the environment, may contribute to an increase in the number of electric cars in the country, to about 100,000 in 2020.

The impending time to introduce stricter pollution charges for polluting the environment in 2020 may result in a sharp increase in the interest, as part of the transport policy, in the change of passenger cars fleet structure, particularly in terms of increasing the share of vehicles powered by alternative fuels, which would increase the number of electric vehicles to around 300,000.

It can be assumed that during the analysed period there will be drastically tightened rules on the technical condition of passenger cars in operation, which in turn will shorten the life time limit for the operating cars to, e.g. about 10 years old, and the eliminated cars, with environment-friendly government policy, can be replaced by electric cars.

With a projected increase of the national fleet of electric cars to 300,000, it justifies a claim that the benefits, known as “avoidable costs” will be reached, that would have occurred in the operation of passenger cars powered by internal combustion engines.

To perform a economic simulation accounting of the amount of “avoidable costs”, the category of external costs not occurring in the case of electric passenger cars, was included, namely [14-17]:

– unit cost per of air pollution (PM (PM10 and PM2.5) NOx, NMVOC, SO2, i.e. 0.0256 PLN / paskm,
– unit cost of noise, i.e. 0.0235 PLN / paskm,
– unit cost of climate change (cost of greenhouse gases emission, such as CO2, CH4 and N2O) i.e. 0,0370 PLN/pas-km, which together makes up the environmental external costs in 2012.

It was assumed that in Polish realities of 2020 the electric passenger cars will replace mainly carriage conducted by passenger cars with combustion engines in urban and suburban traffic in the proportion of 50% -50% for every mentioned traffic area. The authors are of the opinion that in 2020 electric passenger cars will not be used in the significant numbers.

In order to calculate abovementioned unit costs for 2012 the output cost data was used, from the available literature, and first of all, [14-17], taking into account both the relationship of GDP for the EU-27 countries and Poland, as well as the annual inflation rates. It was assumed that:

– average annual passenger car mileage – 15 thousand km,
– average number of people travelling in a passenger car – 1.5.

With the above assumptions, the “avoidable costs” for 300,000 electric cars will reach in 2020 (adjusted for inflation) about 844 million PLN, it would be about 2% of the cost of air pollution, noise, climate change, caused by the passenger cars fleet in 2020. These are tangible sums for the national economy.

It should be born in mind that equally important, in the introduction of electric cars to be used, are intangible benefits associated with improving the health of urban residents, where the concentrations of both pollutants and noise intensity is relatively high. It can be estimated that the spending on health care related to a group of “civilisation” diseases, (air passages, allergies, etc.) would be reduced by about 20%.

Technical progress forces a change in thinking and actions of those responsible for the policy in relation to the entire national economy, including the road transport sector, which will cause the increase in the number of electric cars. It is obvious that now this figure, for 2020, may be determined only by the estimates.

It should also be borne in mind that technological progress will create gradual decrease in the purchase prices of electric cars, which will cause the increase in the number of their potential buyers.

The European eMAP project as a support in the evaluation of external environmental costs of the road transport

The advantage of the electric drive is a zero carbon dioxide emission from the vehicle itself. A very important problem are the limitations in the energy storage by batteries [11]. Important are also determinants of the implementation of an integrated system e- mobility, both in the European Union, as well as in Poland.

Studies on the possibilities of implementing electric vehicles appear in a number of international projects and programs, for example, [18-23]. One such European project currently implemented in the framework of the ERA – NET Plus Electromobility + is a European eMAP project (Electromobility – scenario based Market potential Assessment and Policy options) carried out with the participation of the Motor Transport Institute and the authors of this article.

The main objective of the eMAP European Project (2012-2015; total budget: app. 1.24 mio. Euro) is to analyse feasible deployment paths of electric vehicles for the time horizon until 2025-2030. This will be done using a scenario based market model which specifies consumer demand and market supply of electromobility [24].

Socio-economic impacts of deployment of electromobility on greenhouse gas emissions, local emissions, transport costs, energy supply safety and technological change in industry and economy will be evaluated under various scenarios. Political supporting actions and strategies of electric vehicles will be identified and their impacts on the deployment paths analyzed and evaluated. In the end, recommendations for optimized political strategies will be derived [24].

The regional scope of the project focuses on Europe, most importantly the three partner countries Finland, Germany, and Poland. These vehicle markets will be analyzed in detail with regard to demand structure and supply of electric vehicles and necessary infrastructures for example in mega cities (Berlin), major cities (Cologne, Helsinki) and dense populated areas (Rhein/Ruhr, Warsaw) [24].

The main objectives of the eMAP project are [24]:

– to identify the main characteristics of drivers and pinpoint impediments on side of the customers and the suppliers of electromobility,
– to quantify the demand for electric vehicles given different scenarios,
– to quantify supply of electric vehicles in different market segments,
– to make a forecast of development paths of electromobility based on scenarios,
– to make a thorough socio-economic evaluation of the deployment path of electric vehicles given the different scenario outcomes,
– to determine and evaluate measures and strategies to increase speed of the adaption of electric vehicles,
– to provide policy options and recommendations for optimized deployment programs.

Partners of eMAP are: Federal Highway Research Institute (BAST), Institute for Transport Economics/University of Cologne (UOC), Institute of applied social sciences (INFAS), German Aerospace Centre (DLR), Institute of Vehicle Concepts, Technical Research Centre of Finland (VTT) and Motor Transport Institute (ITS).

In the focus of the project are vehicle concepts which use only electrical energy or use electrical energy in addition to petroleum fuel or gas. The considered power train concepts include Battery electric vehicles (BEV), Fuel cell hydrogen vehicles (FCHV), Plug-in hybrid electric vehicles (PHEV) and Range extended electric vehicles (REEV)) are included which can be driven with electricity alone [25].

In general, electric vehicle demand decisions of customers will depend on the relative attractiveness of electric vehicles compared to vehicle types with conventional power train concepts (Fig.1). Differences in comfort and flexibility of usage of EV will play an important role in this respect. Also the higher upfront costs, but lower running costs of EV mainly caused by relatively low electricity costs and relatively high efficiency of batteries and motors are feeding into the decision making process of customers [25].

Beside comfort, upfront and running costs, attractiveness of electromobility for consumers depends for Plug-in vehicles on availability of charging and service stations. Therefore, also the availability of infrastructure for electromobility for loading and service, including the integration of electric vehicle storage capacity into the electricity grid has to be integrated in the demand analysis [25].

Market supply and the market introduction of further variants and models of EV will depend on technological developments, economies of scale, learning curve effects etc. The structure and volume of market supply of EV will be addressed by trend analysis of observable vehicle market trends in Finland, Germany, and Poland. In addition, expert interviews of the automotive stakeholders will be used to forecast technological development of components, and time, volume, and type of market introduction of EV [25].

Fig.1. Influence of various factors on the choice of the electric car

For the German passenger car market several forecasting studies based on scenarios were done. For example : AT Kearny, Bain & Company, McKinsey, Boston Consulting Group, Roland Berger. The Fraunhofer study provides a scenario model based on comprehensive desktop analysis of vehicle usage patterns which is then used to derive demand potential of electric vehicles in Germany [26]. The following two models are also based on comprehensive analysis of consumer and vehicle data to derive demand potential and vehicle cost development [25]:

– The Institute of vehicle concepts (DLR) has developed a computer based scenario model (VECTOR21 (Fig.2)) to predict market shares of new power train concepts (HEV, BEV FCV etc.) for Germany between 2010 and 2030,

– With focus on battery electric vehicles (BEV) (16 kW, 24kW) the Institute for Transport Economics (UOC model), which will support the work of the project coordinator BAST as a subcontractor, has done a market forecast for the time horizon 2015 – 2020 for Germany.

Fig. 2. An example of VECTOR21 model – run result for the new vehicle fleet in Germany

Abbreviations: CNG (Compressed Natural Gas) – car running on Compressed Natural Gas, DHyb (Diesel hybrid) – hybrid car with a self ignition engine, CNGHyb (Compressed Natural Gas, hybrid) – hybrid car with an engine running on Compressed Natural Gas, G (gasoline) – car running on petrol, GHyb (Gasoline hybrid) – hybrid car with a spark ignition engine, D (diesel) – car running on diesel oil, BEV (Battery Electric Vehicle), EREV (Extended Range Electric Vehicle)

The eMAP project will use especially the VECTOR21 model, but will also follow the UOC-model and the Fraunhofer study as a starting point for a scenario model on deployment of electromobility. The eMAP project will make progress in the following directions [25]:

– The conclusions of the VECTOR21 model are restricted to the German passenger car market. On a contrary, in the eMAP project a transnational approach is used. Scenario based forecasts will be done for three national markets: Finland, Germany, and Poland, but also for the remaining part of EU-27,

– In the VECTOR21 model and also in the UOC-model the customer purchase decision is modelled with focus on the vehicle market. However, a more comprehensive approach for consumer decision making will be provided in eMAP. Because electromobility opens new possibilities for modal split, especially in urban travelling, the decision making process has to be broadened. Therefore, the stepwise process of consumer decision making already shown in the VECTOR21 model will be further enlarged by an additional step of modelling mobility decisions about travelling modes,

– The scope of the supporting political actions considered in the framework conditions will be broadened. In the studies analyses about financial incentives dominate. However, beside financial support, also different research funding schemes, infrastructure investments, special e.g. priority rules for EV, and information and awareness campaigns for electromobility have to be included.

The Institute for Transport Economics (UOC) has done a socio-economic assessment of electromobility. The assessment is based on the forecast of market volume of BEV (24 kW) and City-BEV (16 kW) for Germany for the time horizon 2015 – 2020. The assessment comprises impacts of electromobility on local (noise, PM, NOx) and global emissions (CO2) which are transferred to monetary benefits by using environmental damage cost-unit rates [25].

The eMAP project with regard to socio-economic impact evaluation will be based on the UOC-model, but enlarges the assessment further in the following directions [25]:

– A socio-assessment is done for Finland, Germany, Poland, and also for the remaining part of EU-27,

– The shift to electromobility has strong effects for fuel based tax income, and thus on the public budgets. Therefore based on the scenario results of fleet penetration of EV a financial analysis will be done. A financial analysis covers monetary transfer payments and tax revenues which are not considered in the cost benefit analysis,

– A usual cost-benefit assessment is restricted to an assessment of impacts which can be expressed in monetary values like transport costs changes and environmental benefits. Therefore, structural effects of the deployment of electromobility for employment, less dependency from crude oil, competitiveness of automotive industry etc. are not part of the cost-benefit assessment. To make a thorough assessment of the impacts the shift to electromobility will have on society a broader approach is used integrating monetary, quantitative and qualitative effects in the assessment. This is done by a multi-criteria analysis.

Fig.3. Share of public and private promotion measures in strategy for promotion of EV
Conclusion

The European Union is conducting research studies to identify opportunities for tackling the problem of carbon dioxide emissions from cars in favour of gradual entry into service of electric cars. This is a very complex problem due to the issues such as.:

– production capacity of the energy industry,
– technical infrastructure for charging batteries,
– technical capabilities to produce a new generation of batteries,
– servicing electric cars,
– level of costs of operating electric cars.

It should be stressed that solving these problems will be associated with a significant financial expenditures, which will fall to the external costs of transport, and their levels will be one of the decisive application factors for the modern electric vehicles. On the other hand “avoided costs” incurred by the replacement of conventional vehicles powered by internal combustion engines with these vehicles will not be meaningless.

REFERENCES

[1] Winiarski B., Polityka gospodarcza, Wydawnictwo PWN, Warszawa 2006,308
[2] Pawłowska G., Zewnętrzne koszty transportu. Wydawnictwo Uniwersytetu Gdańskiego, Gdańsk 2000, 17
[3] http://ec.europa.eu
[4] Tylutki A., Wronka J., Znaczenie kosztów zewnętrznych dla polityki transportowej, Przegląd Komunikacyjny 1995, nr.8
[5] Kowalewski M., Oszczędności kosztów zanieczyszczania środowiska w analizach kosztów i korzyści ex ante i ex post inwestycji drogowych. Transport a Unia Europejska. Zeszyty Naukowe Uniwersytetu Gdańskiego nr 33/2006,196
[6] Shefer D., Rietveld P., Congestion and safety on highways: Towards an analitycal model. Urban Studies 1997, nr 34, s.679-693, za: M.Kowalewski, oszczędności kosztów zanieczyszczenia środowiska, 198
[7] http://www.cofret-project.eu
[8] Deklaracja drugiego Szczytu Ziemi z inspiracji ONZ, Johanesburg 2002
[9] Skiner I., Van Essen H., Smokers R., Hill., EU Transport GHG: Routes to 2050. June 2010
[10] Strategia Rozwoju Transportu do 2020 roku (z perspektywą do 2030 roku). Projekt. Ministerstwo Infrastruktury, marzec 2011 roku
[11] Uwarunkowania wdrożenia zintegrowanego systemu e – mobilności w Polsce. Ministerstwo Gospodarki, czerwiec 2012 roku
[12] Biała Księga. Plan utworzenia jednolitego europejskiego obszaru transportu – dążenie do osiągnięcia konkurencyjnego i zasobooszczędnego systemu transportu. KOM(2011) 144 wersja ostateczna
[13] Waśkiewicz J., Chłopek Z., Pawlak P.: Prognozy eksperckie zmian aktywności sektora transportu drogowego. Praca ITS Nr.7200/ZBE. Instytut Transportu Samochodowego, Warszawa,12 października 2012 r.
[14] Niebieska Księga. Analiza kosztów i korzyści projektów inwestycyjnych w sektorze transportu. Publikacja wsparta ze środków pomocowych UE w ramach projektu Phare PL 2002/000 – 580.01.08
[15] Jaspers. Niebieska Księga. Nowe wydanie, grudzień 2008
[16] Maibach M., Schreyer C. Sutter D., Van Esssen H., P., Boon B., H., Smokers R., Schroten A., Doll C., Pawlowska B., Bak M.: Handbook on estimation of external costs in the transport sector. Version 1.1. Report Delft, February 2008
[17] Van Essen H., Schroten A., Otten M., Sutter D., Schreyer Ch., Zandanella R., Doll C.: External Costs of Transport in Europe. Update Study for 2008. Report Delft, November 2011
[18] ScelecTRA. Electromobility+ – Launching seminar, September 13th 2012
[19] EV-STEP. Electromobility+ – Launching seminar, September 13th 2012
[20] DEFINE. Electromobility+ – Launching seminar, September 13th 2012
[21] SELECT. Electromobility+ – Launching seminar, September 13th 2012
[22] COMPETT. Electromobility+ – Launching seminar, September 13th 2012
[23] E-FACTS. Electromobility+ – Launching seminar, September 13th 2012
[24] http://www.project-emap.eu
[25] Application Form for eMAP project
[26] Biere D., Dallinger D., Wietschel M., Ökonomische Analyse der Ernstnutzer von Elektrofahrzeugen, Zeitschrift für Energiewissenschaft, S: 173-181, 02, 2009


Authors: Professor Ph.D. Zdzisław Kordel, Uniwerytet Gdański, ul Bażyńskiego 1a 80 – 952 Gdańsk, E- mail: ZdzislawKordel@wp.pl, DEng. Wojciech Gis, Instytut Transportu Samochodowego, ul.Jagiellońska 80, 03-301 Warszawa, E-mail: wojciech.gis@its.waw.pl; MA Maciej Menes, Instytut Transportu Samochodowego, ul.Jagiellońska 80, 03-301 Warszawa, E-mail: maciej.menes@its.waw.pl


Source & Publisher Item Identifier: PRZEGLĄD ELEKTROTECHNICZNY, ISSN 0033-2097, R. 89 NR 10/2013

An Introduction to Harmonics

Published by Alex Roderick, EE Power – Technical Articles: An Introduction to Harmonics, May 06, 2021.


This article will provide a basic introduction of harmonics in power engineering.

A harmonic is a current or voltage component at a frequency that is an integer (whole number) multiple (2nd, 3rd, 4th, etc.) of the fundamental frequency. For example, when the power supply is 60 Hz AC, the first harmonic (60 Hz) is the fundamental frequency. Other multiples of the fundamental harmonic are the second harmonic (120 Hz), third harmonic (180 Hz), fourth harmonic (240 Hz), etc. When these harmonics are present in a circuit, the resulting waveform consists of the sum of the fundamental and the higher harmonics at every instant. See Figure 1. The result is a distorted waveform from the contribution of the harmonics.

Figure 1. Harmonics are multiples of the fundamental waveform. Image courtesy of SALICRU
Note:

High-frequency harmonics can shorten the operating life or cause the failure of electrical equipment.

The basic design of most electrical distribution equipment assumes that the current and voltage waveforms of the circuit will be sinusoidal. In power distribution systems, there are different types of nonlinear components that draw current disproportionately with respect to the source voltage. This causes non-sinusoidal current waveforms that contain harmonic components. For example, the equipment that draws current in pulses for only a portion of the cycle will cause harmonic components. 

Knowledge of harmonics present on a power line is important for working on any power distribution system. When evaluating power quality, the incoming power, types (linear and nonlinear) and the number of loads, and equipment used in the distribution system must all be tested. A power quality meter can be used to measure the amount of voltage and current harmonics on a line. The amount of each harmonic present on the line and related information are indicated by numeric data and the frequency spectrum on the graphic display of the power quality meter. See Figure 2.

Figure 2. A power quality meter can be used to indicate the presence and magnitude of harmonics.
Odd-and Even-Numbered Harmonics

Odd harmonics are odd multiples (3rd, 5th, 7th, etc.) of the fundamental. They add together and increase their effect. Loads that draw odd harmonics have increased resistance (I2R) losses and eddy current losses in transformers. If the harmonics are significant, a transformer must be derated to prevent overheating.

Even harmonics are even multiples (2nd, 4th, 6th, etc.) of the fundamental. Even harmonics are generally fairly small because most non-linear loads in power systems produce odd harmonics and even harmonics tend to cancel each other. If even harmonics are present, this fact may be used as a troubleshooting tool. They generally indicate that a DC current may be present in the secondary winding of the transformer. The DC offset is typically caused by half-wave rectification due to a failed rectifier.

On alternate half-cycles, a DC offset may cause a transformer to become saturated and draw exceedingly high currents, causing the primary to burn out. The transformer core can experience a strong vibration and a very loud noise as a result of these issues. Generally, a DC offset of more than 1% of the rated current can cause problems.

Triplen Harmonics

Triplen harmonics (triplens) are odd multiples of the third harmonic (3rd, 9th, 15th, etc.). Only single-phase loads generate triplen harmonics. Three-phase loads do not generate triplen harmonics. Triplen harmonics can cause problems such as overloading of neutral conductors, telephone interference, and transformer overheating. Special types of transformers are used to reduce triplen harmonics.

Single-phase electronic loads connected phase-to-neutral, such as 120V office circuits or 277V lighting circuits, generate third harmonics with decreasing amounts of the higher odd harmonics.

Three-phase electronic loads connected phase-to-phase, such as 208V power supplies or 480 V variable-speed motor drives, do not generate the triplen harmonics, but they do generate significant levels of the other higher-level harmonics. See Figure 3. 

Figure 3. Triplen harmonics are generated by circuits wired phase-to-neutral.
Third Harmonic

Single-phase electronic loads generate third harmonics in addition to smaller amounts of higher odd harmonics. Only the triplen harmonics contribute to the high neutral currents problem. The 9th, 15th, and higher triplen harmonics have a relatively lower current level and distort the neutral current just marginally. Hence, they do not have a noticeable impact on the actual rms neutral current.

Since the higher harmonics are relatively smaller, the third harmonic, as a percentage of total rms current, multiplied by three, is a fairly good estimate of the percent neutral current that results from three identical non-linear single-phase loads. Thus, the neutral current is at about 100% of the fundamental phase current when the third harmonic is at 331⁄3% of the fundamental phase current.

Harmonic Sequence

The harmonic sequence is the phasor rotation of the harmonic with respect to the fundamental (60 Hz) frequency. The order in which waveforms from each phase (A, B, and C) cross zero is referred to as phasor rotation. Phasor rotation is simplified by using lines and arrows instead of waveforms to show phase relationships. See Figure 4. The harmonic phase sequence is critical because it determines how the harmonic affects the operation of loads and components like conductors in a power distribution system.

Figure 4. Phasor rotation of Positive, Negative, and Zero Sequence Harmonics
Positive Sequence

Positive sequence harmonics (1st, 4th, 7th, etc.) have the same phase sequence as the fundamental harmonic. Positive sequence harmonics cause additional heat in transformers, conductors, circuit breakers, and panels in a power distribution system. A positive sequence harmonic rotates in the same direction as the fundamental in an induction motor.

Negative Sequence

Negative sequence harmonics (2nd, 5th, 8th, etc.) have the opposite phase sequence compared to the fundamental harmonic. Like positive sequence harmonics, negative sequence harmonics cause additional heat in power distribution system components such as transformers, conductors, circuit breakers, and panels. A negative sequence harmonic rotates in the opposite direction from the fundamental in an induction motor. The reverse rotation is not enough to cause the motor to reverse direction, but it does reduce the forward torque of the motor. The reduced torque causes a higher motor current to be drawn and results in excessive heating.

Zero Sequence

Zero sequence harmonics (3rd, 6th, 9th, etc.) do not produce a rotating field in either direction. However, zero-sequence harmonics do cause component and system heating. Zero sequence harmonics do not cancel but can add together in the neutral conductor of 3-phase, 4-wire systems. Single-phase appliances that use rectifier power supplies, including computers, fluorescent lighting with electronic ballasts, and other common electronic devices, contribute significantly to current on neutral wires.


Author: Alex earned a master’s degree in electrical engineering with major emphasis in Power Systems from California State University, Sacramento, USA, with distinction. He is a seasoned Power Systems expert specializing in system protection, wide-area monitoring, and system stability. Currently, he is working as a Senior Electrical Engineer at a leading power transmission company.


Source URL: https://eepower.com/technical-articles/an-introduction-to-harmonics/

What Are the Five Major Types of Renewable Energy?

Published by Govind Bhutada, Visual Capitalist – Energy, June 9, 2022.


Five Major Types of Renewable Energy. Image by Visual Capitalist.
The Renewable Energy Age

This was originally posted on Elements. Sign up to the free mailing list to get beautiful visualizations on natural resource megatrends in your email every week.

Awareness around climate change is shaping the future of the global economy in several ways.

Governments are planning how to reduce emissions, investors are scrutinizing companies’ environmental performance, and consumers are becoming conscious of their carbon footprints. But no matter the stakeholder, energy generation and consumption from fossil fuels is one of the biggest contributors to emissions.

Therefore, renewable energy sources have never been more top-of-mind than they are today.

The Five Types of Renewable Energy

Renewable energy technologies harness the power of the sun, wind, and heat from the Earth’s core, and then transforms it into usable forms of energy like heat, electricity, and fuel.

The above infographic uses data from Lazard, Ember, and other sources to outline everything you need to know about the five key types of renewable energy:

Energy Source% of 2021 Global Electricity GenerationAvg. levelized cost of energy per MWh
Hydro 15.3%$64
Wind 6.6%$38
Solar 3.7%$36
Biomass 2.3%$114
Geothermal <1%$75
Editor’s note: We have excluded nuclear from the mix here, because although it is often defined as a sustainable energy source, it is not technically renewable (i.e. there are finite amounts of uranium).

Though often out of the limelight, hydro is the largest renewable electricity source, followed by wind and then solar.

Together, the five main sources combined for roughly 28% of global electricity generation in 2021, with wind and solar collectively breaking the 10% share barrier for the first time.

The levelized cost of energy (LCOE) measures the lifetime costs of a new utility-scale plant divided by total electricity generation. The LCOE of solar and wind is almost one-fifth that of coal ($167/MWh), meaning that new solar and wind plants are now much cheaper to build and operate than new coal plants over a longer time horizon.

With this in mind, here’s a closer look at the five types of renewable energy and how they work.

1. Wind

Wind turbines use large rotor blades, mounted at tall heights on both land and sea, to capture the kinetic energy created by wind.

When wind flows across the blade, the air pressure on one side of the blade decreases, pulling it down with a force described as the lift. The difference in air pressure across the two sides causes the blades to rotate, spinning the rotor.

The rotor is connected to a turbine generator, which spins to convert the wind’s kinetic energy into electricity.

2. Solar (Photovoltaic)

Solar technologies capture light or electromagnetic radiation from the sun and convert it into electricity.

Photovoltaic (PV) solar cells contain a semiconductor wafer, positive on one side and negative on the other, forming an electric field. When light hits the cell, the semiconductor absorbs the sunlight and transfers the energy in the form of electrons. These electrons are captured by the electric field in the form of an electric current.

A solar system’s ability to generate electricity depends on the semiconductor material, along with environmental conditions like heat, dirt, and shade.

3. Geothermal

Geothermal energy originates straight from the Earth’s core—heat from the core boils underground reservoirs of water, known as geothermal resources.

Geothermal plants typically use wells to pump hot water from geothermal resources and convert it into steam for a turbine generator. The extracted water and steam can then be reinjected, making it a renewable energy source.

4. Hydropower

Similar to wind turbines, hydropower plants channel the kinetic energy from flowing water into electricity by using a turbine generator.

Hydro plants are typically situated near bodies of water and use diversion structures like dams to change the flow of water. Power generation depends on the volume and change in elevation or head of the flowing water.

Greater water volumes and higher heads produce more energy and electricity, and vice versa.

5. Biomass

Humans have likely used energy from biomass or bioenergy for heat ever since our ancestors learned how to build fires.

Biomass—organic material like wood, dry leaves, and agricultural waste—is typically burned but considered renewable because it can be regrown or replenished. Burning biomass in a boiler produces high-pressure steam, which rotates a turbine generator to produce electricity.

Biomass is also converted into liquid or gaseous fuels for transportation. However, emissions from biomass vary with the material combusted and are often higher than other clean sources.

When Will Renewable Energy Take Over?

Despite the recent growth of renewables, fossil fuels still dominate the global energy mix.

Most countries are in the early stages of the energy transition, and only a handful get significant portions of their electricity from clean sources. However, the ongoing decade might see even more growth than recent record-breaking years.

The IEA forecasts that, by 2026, global renewable electricity capacity is set to grow by 60% from 2020 levels to over 4,800 gigawatts—equal to the current power output of fossil fuels and nuclear combined. So, regardless of when renewables will take over, it’s clear that the global energy economy will continue changing.


Author: Govind graduated from the University of British Columbia with a Bachelor of International Economics before joining Visual Capitalist as a Writer. He is focused on trends in commodities, mining, and energy but occasionally strays into other topic areas. Govind is an avid coffee drinker and loves a flat white.


Source URL: https://www.visualcapitalist.com/what-are-the-five-major-types-of-renewable-energy/

Modeling of Overvoltages in Gas Insulated Substations

Published by Tomasz KUCZEK, Marek FLORKOWSKI, ABB Corporate Research Center in Krakow, Poland


Abstract. Gas Insulated Substations (GIS) are broadly used for transmission and distribution of electric power. Due to the interactions with a network and various environmental phenomena like lightning the GIS are subjected to the Very Fast Transients (VFT). Such VFT can be also created within GIS mainly by the disconnector operations. Paper will present an approach towards modeling of transient phenomena in GIS. The simulation of transients in exemplary high voltage power supply substation will be shown.

Streszczenie. Stacje izolowane gazem SF6 (GIS) są szeroko wykorzystywane w elektroenergetycznych systemach przesyłowych i dystrybucyjnych. W wyniku zjawisk przejściowych takich jak operacje łączeniowe oraz wyładowania atmosferyczne, stacje GIS narażone są na występowanie przepięć bardzo szybko zmiennych. Artykuł przedstawi zasady modelowania zjawisk przejściowych w stacjach GIS oraz przykładową analizę przepięć generowanych poprzez operowanie odłącznikiem. (Modelowanie przepięć w stacjach elektroenergetycznych izolowanych gazem SF6)

Keywords: very fast transients overvoltages, switching, GIS substation, disconnector, EMTP/ATP modeling, simulation
Słowa kluczowe: szybkozmienne zjawiska przepięciowe, stacja izolowana gazem SF6, odłącznik, EMTP/ATP modelowanie, symulacja

Introduction

The Very Fast Transients (VFT) in power systems cover a frequency range from 100 kHz up to hundreds of MHz [1, 2]. VFT are an effect of GIS disconnector opening or closing, as well as other events such as operation of a circuit breakers or grounding switches. An electromagnetic wave is generated, which propagates along the busbars and substation apparatus. Due to the fact that in can be multiple times reflected at joints between substation equipment, its maximum overvoltage peak values can reach significant levels. Their magnitude is in the range of 1.5 to 2.0 p.u. of the line-to-neutral voltage crest, but they can also reach values as high as 2.5 p.u. to 3 p.u. in case of ultra high voltage systems. These values are generally below the Basic Insulation Level (BIL), but VFT can speed up insulations aging and degradation processes due to their frequent occurrences.

The fact of VFT occurrence in high voltage power systems forces to study them in an analytical manner. It is important to recognize its possible maximum overvoltage peak values in order to determine if those are below acceptable insulation levels.

This paper presents a state of the art modeling principles for this kind of phenomena. Also exemplary 380 kV GIS substation have been analyzed. Overvoltage waveforms during GIS disconnector closing operation have been calculated along with their maximum peak values. All simulations have been performed using ATPDraw 5.6p6 software package.

VFT phenomenon description

During the closing or opening operation of the disconnector in adjacent bay of GIS substation (Fig. 1) an electric arc occurs multiple times between the contacts. These so called re-strikes and pre-strikes are a result of the relatively slow speed of disconnector contacts moving. Sparks occurrence result in generation of overvoltage wave, which propagates along the substations. Its propagation is characterized by multiple reflections at substation equipment joints, which leads to high overvoltage peak values. It also has to be pointed out, that after the disconnector opening operation, the capacitive trapped charge voltage remains on the disconnector load side. It is being discharged very slowly through the GIS spacers and other equipment. However, during reclosing of the disconnector this voltage can have a significant influence on generated overvoltages. The typical value of trapped charge voltage can be expected in the range of 0.3 ÷ 0.6 p.u. Nonetheless, for Insulation Co-ordination studies it is always required to analyze the worst case working conditions for specific network. Thus, it should be assumed, that the trapped charge voltage is equal to -1 p.u. of nominal system voltage, whereas the cosine source side voltage is equal to +1 p.u. It also has to be assumed that the studied system is running at its highest power frequency nominal voltage. It results then in significant potential difference between contacts during the spark occurrence, which leads to generation of most severe overvoltages.

Fig.1. VFT generation principle – disconnector operating in the GIS substation: US – voltage at disconnector source side, UL – voltage at disconnector load side

The switching and lightning overvoltages are a typical concern in high voltage power systems. Switching oscillations inside the GIS substations (Very Fast Transients) are characterized by a very high rise times, which results in the fact that in studied range of frequencies surge arresters are visible mainly as a phase to ground capacitance. Their nominal voltage-current nonlinear characteristics does not have significant influence on overvoltages suppression.

It has to be also said, that necessity of VFT analysis comes out of the fact, that the ratio of nominal system voltage and Switching Impulse Withstand Level (SIWL) is significantly less for ultra high voltage system than for medium voltage systems for instance. Comparison between nominal system ratings and acceptable switching overvoltage levels have been summarized in Table 1 [3, 5].

Table 1. Comparison of ratio between highest system voltages and their maximum switching impulse acceptable levels

.

As it is clearly visible in Table 1, the ratio between peak values of acceptable switching overvoltage and highest power frequency voltage for systems at 24 kV is equal to 7.40 p.u., whereas for ultra high voltages like for 765 kV is equal to 2.48 p.u. As it was stated before, overvoltages generated during Very Fast Transients phenomenon can reach peak values as high as 2.0 ÷ 3.0 p.u. Since this is very close to the maximum acceptable levels, the analysis of VFT overvoltages, quantity and frequency is very important.

Modeling principles for VFT

Very Fast Transients are characterized by rise times in the range of 4-100 ns. Thus, it has to be modeled as an appropriate distributed and lumped elements. The travelling nature of VFT forces one to use appropriate values of surge impedances with associated wave propagation speed and element length as well as phase-to-ground capacitances [4]. Detailed description have been presented in Table 2.

Table 2. GIS substation equipment modeling data for VFT

.

Special attention was paid to the power transformer modeling. It was represented by means of inductance, resistance and capacitance of HV bushings as well as capacitance of HV side windings. Parameters are evaluated from the frequency response analysis of the transformer. Typical values and used model have been presented in Figure 2.

Fig.2. High frequency model of the HV transformer side; CD – HV side windings capacitance, CE, R1, L1 – capacitance, resistance and inductance of HV bushings

During the GIS disconnector closing operation, the voltage breakdown takes about 4 ns. The modeling of this event is made in EMTP/ATP with an exponentially decreasing resistance r from very high value to zero with a time constant equal to τ = 0.6·10-9 s, which results from disconnector capacitance and arc fixed resistance. The nonlinear arc resistance during closing event is implemented with use of MODELS language in EMTP/ATP according to formula (1):

.


where: τ – time constant.

This non-linear resistance is in series with a fixed resistance of 0.5 Ω, which represents the spark resistance after voltage breakdown.

For the worst case operating conditions, the damping of the Very Fast Transients, which occurs due to ohmic losses inside the GIS substation and mostly due to transition of the surge from inside to the outside earthing system at the bushing should not be considered.

Exemplary VFT analysis of 380 kV GIS substation

A typical 380 kV GIS substation has been considered for the VFT analysis. A single line diagram of part of the substation has been presented in Figure 3. It consists of 280 MVA power transformer that is energized through overhead transmission line interconnected to the substation with HV cable.

Fig.3. 380 kV GIS substation – overall network diagram for VFT analysis

Singular switching operation (closing) of the disconnector have been simulated in EMTP/ATP software. As it is visible in Figure 3, circuit breaker CB2 is open during entire process of disconnector closing event, whereas circuit breakers CB1 and CB3 are closed and provide current path, which have been marked with dashed line. For the worst case operating conditions it has been assumed, that system is working at maximum allowed power frequency voltage (420 kV) and at the switching time instant source side voltage is at its maximum (+1 p.u.).

Overvoltage waveforms have been obtained at following locations (according to Fig. 3):

• disconnector load side – position (1),
• disconnector source side – position (2),
• transformer HV terminals – position (3),
• GIS-cable termination – position (4).

During the calculations, maximum overvoltage peak values have been obtained and compared to the Switching Impulse Withstand Voltage (SIWL) that is equal 1050 kV for 380 kV systems [5]. The nominal voltage in per units have been calculated according to formula (2):

.

As it was discussed above, value of trapped charge voltage UTC at disconnector load side may have significant influence on generated overvoltages. Thus, two values of this voltage have been considered:

• case 1: UTC = -0.5 p.u. = -171.45 kVpeak
• case 2: UTC = -1 p.u. = -342.9 kVpeak

Simulation results

As it was described, the disconnector closing event was modeled as an exponentially decreasing resistance. For this study, this operation was issued at the time instant of t = 10 μs. The nonlinear resistance decreases from very high value to 0.5 Ω in about 4 ns (Fig 4). This behavior is independent from value of trapped charge voltage, thus it is the same for both cases with -1 p.u. and -0.5 p.u.

Fig.4. Disconnector nonlinear resistance during closing event

For each waveform, maximum overvoltage peak value have been obtained in kilovolts as well as in per units. Also percentage ∆% difference between both scenarios have been calculated, according to formula (3):

.

where: UC1, UC2 – calculated voltages at case 1 and case 2.

Summarized results for both analyzed scenarios have been presented in Table 3.

Table 3. Simulation results summary

.

As it has been presented in Table 3, the highest overvoltage peak value occurred at the operated disconnector terminals and is equal to 655 kV, which reaches level of almost 2 p.u. It can be also observed, that overvoltage magnitude decreased during propagation through the entire GIS substation. At the transformer terminals its peak value is equal to 551 kV, whereas at GIS extraction point it decreased to 464 kV. Once the overvoltage wave extracts out of the GIS, it is very quickly dumped on substation overhead connections and high voltage cables. Such behavior is visible for both analyzed cases, that is with -0.5 p.u. and -1 p.u. of trapped charge voltage at disconnector load side. However, as it have been expected, calculated maximum overvoltage peak values are significantly lower with smaller trapped charge. Calculated voltage difference is in the range of 8.0 – 12.2 % and it is an obvious reason why during the typical insulation coordination studies all of the analyzes should be performed with -1 p.u. of assumed trapped charge voltage.

All reported values are well below maximum acceptable level of 1050 kV (Switching Impulse Withstand Level). During the insulation coordination processes it is necessary, to have all overvoltages below the safety margin of 80 % of SIWL, that is below 840 kV. As it is clearly visible in Table 3, all reported values are within acceptable limits.

Calculated overvoltage waveforms at specific locations of studied GIS substation have been illustrated in figures 5 to 8 for case 1 and in figures 9 to 12 for case 2.

Fig.5. VFT overvoltage waveforms, voltage at disconnector load side, trapped charge voltage UTC = -0.5 p.u.
Fig.6. VFT overvoltage waveforms, voltage at disconnector source side, trapped charge voltage UTC = -0.5 p.u.
Fig.7. VFT overvoltage waveforms, voltage at transformer HV terminals, trapped charge voltage UTC = -0.5 p.u.
Fig.8. VFT overvoltage waveforms, voltage at GIS-cable termination, trapped charge voltage UTC = -0.5 p.u.
Fig.9. VFT overvoltage waveforms, voltage at disconnector load side, trapped charge voltage UTC = -1 p.u.
Fig.10. VFT overvoltage waveforms, voltage at disconnector source side, trapped charge voltage UTC = -1 p.u.
Fig.11. VFT overvoltage waveforms, voltage at transformer HV terminals, trapped charge voltage UTC = -1 p.u.
Fig.12. VFT overvoltage waveforms, voltage at GIS-cable termination, trapped charge voltage UTC = -1 p.u.

As it is visible in all figures representing VFT overvoltage waveforms, disconnector have been closed at time instant of t = 10 μs. All overvoltage waveforms are characterized by multiple wave reflections resulting with very high frequencies in the range of 6 MHz to 10 MHz. In figures 5 and 9 it can be observed, that the disconnector load side is preloaded with trapped charge equal to -0.5 p.u. and -1 p.u. respectively. In figures 8 and 11, where voltage waveform at transformer HV terminals have been represented, one can observe, that the overvoltage wave is delayed in time of 300 ns from the assumed disconnector closing time instant of 10 μs. This can be explained with the fact, that overvoltage wave propagates along entire GIS substation from the operated disconnector up to the transformer. Since this distance is equal to 86 m wave propagation speed can be easily calculated to 286 m/μs, which corresponds very well with assumed value of 290 m/μs. These values differ due to the presence of GIS equipment capacitances that smooth the overvoltage wave.

Conclusions

It has been presented, that with a detailed analysis and use of appropriate tools and modeling techniques, it is possible to evaluate maximum overvoltage peak values resulting from GIS disconnector closing operation. It is necessary to check if overvoltages are below maximum acceptable level of 80 % of Switching Impulse Withstand Level. It has been calculated, that maximum overvoltage peak value occurs at operated disconnector, however reported values are below the maximum acceptable levels. Based on studied cases with two different values of trapped charge it can be concluded, that during typical insulation coordination studies, for the worst case conditions it should be assumed, that trapped charge voltage at disconnector load side is equal to -1 p.u. As it has been presented, maximum overvoltage peak values can reach values up to 2.0 p.u. in this particular case. However, it has to be added, that phenomenon of Very Fast Transients propagation inside the GIS substations is very complex and complicated. Its analysis has to be performed with special attention to a specified substation layout, busbars lengths and cable or transformer connections and terminations.

REFERENCES

[1] CIGRE Working Group 33/13.09, Monograph on GIS Very Fast Transients, 1989
[2] Furgał J.: Analysis of Overvotlage Risk of the Insulation of a Transformer Protected by Use of Lightning and Surge Arresters, Wydawnictwa AGH, Kraków, 2003, ISSN 0867-6631
[3] Andrew R. Hileman: Insulation Coordination for Power Systems, CRC Press Taylor and Francis Group, New York 1999
[4] IEEE Working Group on Modeling and Analysis of System Transients Using Digital Programs: Modeling and Analysis Guidelines for Very Fast Transients, IEEE Transactions on Power Delivery, Vol. 11, No. 4, October 1996, p. 2028 – 2035
[5] IEC 60071-1:2006, Insulation co-ordination – Part 1: Definitions, principles and rules


Authors: Tomasz Kuczek, MSc. Eng., E-mail: tomasz.kuczeki@pl.abb.com, Marek Florkowski, D.Sc. Eng., E-mail: marek.florkowski@pl.abb.com, ABB Corporate Research Center, Starowiślna 13A., 31-038 Kraków, Poland


Source & Publisher Item Identifier: PRZEGLĄD ELEKTROTECHNICZNY (Electrical Review), ISSN 0033-2097, R. 88 NR 4a/2012