Published by China Electric Power Technology Holdings Limited (CEPT), July 2009




























Published by China Electric Power Technology Holdings Limited (CEPT), July 2009




























Published by
Abstract – Harmonic currents generated by non-linear loads can cause problems in the power systems and particularly the distribution transformers as they are vulnerable to overheating and premature failure. Normally designers recommend an oversized transformer to protect transformer from overheating. K-factor transformers are specifically designed to accommodate harmonic currents. K-transformers are preferred because they have additional thermal capacity of known limits, design features that minimize harmonic current losses, and neutral and terminal connections sized at 200% of normal. K-factor transformers allow operation up to nameplate capacity without derating.
Index Terms – Additional thermal capacity, Derating, Distribution transformers, Harmonic currents, K- Factor, Nameplate capacity, Neutral and Terminal connections, Non-linear loads, Overheating.
Today’s modem offices and plants are dominated by nonlinear loads, desktop computers, solid state ballasts, PID lighting, programmable controllers, and variable speed drives to name a few. Due to these electronic loads, significant harmonic loads have been added to the building’s distribution systems. The result is premature failure of the transformer due to overheating. Till recent times, the only solution to this problem was to derate the transformer. This solution is no longer acceptable.
The effect of nonlinear loads on the electrical power systems has become matter of concern since past few years. Nonlinear loads draw currents which are not sinusoidal. They include equipment’s such as solid state motor drives, arc furnaces, battery chargers, UPS systems, and the increasing electronic power supplies. The increased use of these nonlinear loads is the cause of concern as larger percentage of power systems tend to become nonlinear. The nonlinear loads were thought to be matter of concern for industrial power systems where large static power converters were being used. But now larger application of electronics to practically every electrical load, nonlinear loads are present in commercial and even residential power system. Nonlinear loads produce harmonic currents which flow from the load towards the power source following the path of least impedances. Harmonic currents are the currents which have frequencies that are whole number multiples of fundamental frequency. The harmonic currents superimposed on the fundamental currents result in the non-sinusoidal waveform associated with the nonlinear loads. Fig.1 show the voltages and current waveforms for nonlinear loads. It can be seen that voltage waveform is sinusoidal but current waveform is not.

Harmonic currents adversely affect every component of the power system. These currents create additional dielectric, thermally, and/or mechanical stresses. Harmonic currents flowing through the power system impedances result in harmonic voltage drops which are observed as harmonic voltage distortion. The voltage distortions could become very severe when the power systems inductive and capacitive impedances become equal, a condition of parallel resonance. This condition could appear at one of the nonlinear load’s significant harmonic current frequencies (typically the 5th, 7th, 11th or 13th harmonic). Harmonic currents can cause losses in normal power components even when resonance conditions do not prevail. Due to skin and proximity effects, wiring experience additional heating. If normal wiring sizing methods are employed, then the derating for wiring for harmonics is minimal and can be ignored.
Harmonic currents cause additional heating in the form of additional winding eddy current losses in transformers. ANSI / IEEE C 57.110 provides methods to derate a transformer for any given load profile. This standard considers the winding eddy current losses to be proportional to the harmonic number required. This relationship has been found to be accurate for lower power frequency harmonics, but result in an overestimation of losses for higher harmonics (generally greater than 11th). A typical derating curve is shown in fig.2. Transformers directly supplying single phase power supplies may require derating of 30% to 40% to avoid overheating. ‘Underwriters Laboratories’ (UL) recognize the potential safety hazards associated with nonlinear loads and developed a rating system to indicate the capability of transformer to handle harmonic loads. The ratings are described in UL-I56I and are known as K-Factors. K-Factors are a weighing of the harmonic load currents according to their effects on transformer heating, as derived from ANSI / IEEE C57.110. A K Factor of 1.0 indicates a linear load (no harmonics). The higher the K-Factor, the greater the effect of harmonic heating [1].
K – Factor = Σ(Ih)2 h2 (1)
Where Ih is the load current at the harmonic h, expressed in a per-unit basis such that the total RMS current equals one ampere, i.e.
Σ(Ih)2 = 1.0 (2)
The problem associated with calculating K- Factor is selecting the range of harmonic frequencies that should be included. Some use up to 15th harmonic, others up to 25th harmonic, and still others include up to 50th harmonic. For the same load, each of these calculations can yield significantly different K-Factors, because even very small current levels associated with higher harmonics, when multiplied by the harmonic number squared, can yield significantly to the K-Factor. Based on the underlying assumptions of C57.II0, it seems reasonable to limit the K-Factor calculation to harmonic currents less than 25th harmonic. Sample calculations are given in Table No.1. In establishing standard transformer K-Factor rating; UL chose ratings of 1, 4, 9, 13, 20, 30, 40 and 50. From a practical viewpoint individual loads with K-Factors greater than 20 are infrequent. At best office areas with some nonlinear loads and large computer rooms normally have observed K-Factors of 4 to 9. Areas with high concentrations of single phase computers and terminals have observed K- Factors of 13 to 17. When multiple nonlinear loads are powered from the same source, lower harmonic current levels may be expected due to phase shifts and cancellations. In one study of commercial buildings, single phase loads with current distortion of 104%, THD (Total Harmonic Distortion) resulted in only a 7% THD at the service entrance, when added with other loads in the building. Additional studies of typical loads are beginning to provide information which could aid in the development of additional rules of thumb to use when direct load measurements are not available. K – Factor transformers are designed to be operated fully loaded with any harmonic load having K-Factor equal to or less than its K-rating. For example, a K-13 transformer can be fully loaded with any harmonic load having a K-Factor up to K-13. If the load has a K-Factor greater than 13, then the transformer cannot be safely operated at full load and would require derating.

K-Factor transformers have additional thermal capacity to tolerate the heating effects of the harmonic currents. A well designed K-Transformer will also minimize the winding eddy current losses through the use of parallel conductors and other winding techniques. The K factor indicates the multiples of the 60 Hz winding eddy current losses that the transformer can safely dissipate. Transformer load losses consist of winding I2R losses plus stray losses. Using UL best methods, stray losses are assumed to be primarily winding eddy current losses for transformers 300 KVA and smaller.
For example, a transformer having winding I2R losses of2000 watts and 60 Hz stray losses of 1000 watts would, with a K-20 rating, is required to dissipate the 2000 watts of I2R losses plus 20 times the 60 Hz stray losses of 1000 watts for a total load loss of 4000 watts without exceeding the maximum winding temperature rise. The result is a larger, more expensive transformer.
For K-Factor transformers, UL also requires that the neutral terminal and connections to be sized to accommodate twice the rated phase conductor size (double the minimum neutral capacity) of standard transformers.
There are several areas where designs are changed to accommodate the effects of harmonics.
Standard transformers, i.e. transformers not marked with a K-Factor rating, may have some tolerance to nonlinear loading, but their capability is unknown to the user and is not certified by a third party such as UL. Currently marking transformer with a K-Factor rating is not required by UL. Due to conservative design application, some unmarked transformer may therefore have enough extra thermal capacity to tolerate additional harmonic load heating. This is particularly true for 80° C or 115°C rise transformers built with 220°C insulation material which can safely withstand a 150°C winding temperature rise.
Additional over current protection should be considered for all transformers supplying nonlinear loads. The National Electric Code allows primary-only over current protection at 125°C of the transformer’s primary full load amperes. With three-phase transformers, the triplen harmonics are cancelled in the delta winding and do not appear in the input current. The output currents and transformer loading greater than is apparent from the input current. Therefore a transformer can be overloaded without the primary over-current protection ever tripping. Adding secondary over-current protection helps, but it still does not protect the transformer from the heating effects of harmonic currents. The use of supplemental protection in the form of winding temperature sensors can be used to provide alarm and/or system shutdown in the event of overload, excessive harmonic current, high ambient temperature, or inadequate cooling.

Triplen harmonic currents are phase currents which flow from each of the phases into the fourth wire neutral and have frequencies in integer multiples of three times the 60 Hz base frequency (180 Hz, 360 Hz, 540 Hz etc.). At each of these third multiple triplen frequencies, these triplen phase currents are in phase with each other and when flowing in the neutral as zero sequence currents are equal to three times their RMS phase values. The development of triplen harmonic current is shown in fig.3.
In a 3 phase, 4 wire system, single phase line to neutral currents flow in each phase conductor and return in common neutral. Since the three 60 Hz currents are separated by 120°, when balanced they cancel each other. The measured resultant current is equal to zero.
Theory also states that for even harmonics, starting with the second order, when balanced, the even harmonic will cancel in the common neutral. Other odd harmonics add in the common neutral, but their magnitude is considerably less than triplens. The RMS value of the total current is the square root of the RMS value of the individual currents squared.
ITotal = √ I260Hz + I2180Hz + I2300Hz + I2420Hz + … (3),
Where I = RMS value of current.
At any given instant, the 60 Hz currents on the three phase legs have a vector resultant of zero and cancel in the neutral. But, the third (and other odd triplen harmonics) on the phase legs are in phase and become additive in the neutral.
A. A transformer intended for use with loads drawing non-sinusoidal currents shall be marked “Suitable for non-sinusoidal current load with K-Factor not to exceed x. (x= 4, 9, 13, 20, 30, 40 or 50).”
B. Formulas to determine eddy losses and total losses where the transformer load losses (PLL) are to be determined as follows:
PLL = PDC(1 + K(PEC)) (4)
Where, PDC = Total I2R losses
K = the K-Factor rating at the transformer (4, 9, 13, 20, 30, 40 or 50).
PEC = assumed eddy current losses calculated as follows:
For Transformers rated 300 KVA or less, and for transformers Rated 300 KVA and above, in which;
PAC = Impedance loss
C= 0.7 for transformers having a turn ratio greater than 4:1 and having one or more winding with a current rating greater than 1000 amperes., or C= 0.6 for all other transformers.
PDC-I = the I2R losses for the inner winding.
The impedance losses and the I2R losses shall be determined in accordance with the test code for Dry Type Distribution and Power Transformers, ANSI/IEEE C57.12.91-1979. [4]
As stated in ANSI/IEEE C57.1 10-1986, harmonic load currents may be accompanied by DC components in the load current which are frequently caused by the loss of a diode in a rectifier circuit. A DC component of load current will increase the transformer core loss slightly, and may increase the magnetizing current and audible sound level. [3].

Relatively small DC components (up to the RMS magnitude of the transformer excitation current at rated voltage) are expected to have no significant effects on the load carrying of the transformer excitation current at rated voltage) are expected to have no significant effect on the load carrying capability of a transformer determined by this recommended practice. Higher DC load components may adversely affect transformer capability and must be corrected by the user.
Harmonic currents flowing through transformer leakage Impedance and through system impedance may also produce some small harmonic distortion in the voltage waveform at the transformer terminals. Such voltage harmonics may cause extra harmonic losses in the transformer core. However, operating experience has indicated that core temperature rise usually will not be the limiting parameter for determination of safe magnitudes of non-sinusoidal load currents.
The Noise Isolation Transformer suppresses common mode noise by introducing a ground shield between its primary and secondary windings. The ground shield provides a low impedance path to ground by capacitive coupling which prevents unwanted high frequency signals contained in the source voltage from reaching the transformer secondary.
The grounded shield between primary and secondary windings is called an electrostatic shield. This shield does not perform any function with regard to harmonic current or voltage distortion wave forms. However this shield is extremely valuable in protecting sensitive equipment’s from common mode electrical noise and transients generated on the line side of the transformer. The shielded and unshielded transformers are shown in fig, 4.
The ratio of common mode noise attenuation (CMA) on the input to that of the output of the transformer is expressed in decibels as shown in equation shown here below:
CMA = 20 log10 [Vin/Vout] dB (5)
Table No.1.Calculations for a typical nonlinear load

Table No.2. K- Factors for various types of Loads
| Load | K- Factor | ILK |
|---|---|---|
| Incandescent Lighting | K-1 | 0.00 |
| Electric Resistance Heating | K-1 | 0.00 |
| Motors (without solid state drives) | K-1 | 0.00 |
| Control Transformers | K-1 | 0.00 |
| Motor-Generators | K-1 | 0.00 |
| Distribution Transformers | K-1 | 0.00 |
| Electric Discharge Lighting | K-4 | 25.82 |
| UPS | K-4 | 25.82 |
| Welders | K-4 | 25.82 |
| Induction Heating Equipment | K-4 | 25.82 |
| PLCs and solid state controls | K-4 | 25.82 |
| Telecommunication Equipment (e.g. PBX) | K-13 | 57.74 |
| UPS without input filtering | K-13 | 57.74 |
| Multiwire receptable circuits in general care areas of health care facilities | K-13 | 57.74 |
| Main frame computer loads | K-20 | 80.94 |
| Solid State Motor Drives | K-20 | 80.94 |
| Multiwire receptable circuits in Industrial, Medical and Educational Laboratories | K-30 | 123.54 |
| Small Main Frames (Mini and Micro) | K-30 | 123.54 |
| Other loads identified as producing very high amounts of harmonics | K-40 | 208.17 |
Table No.3. Index of K-rating
| K- Factor | K-1 | K-4 | K-9 | K-13 | K-20 | K-30 | K-40 |
| ILK | 0.0 | 25.82 | 44.72 | 57.74 | 80.94 | 123.54 | 208.17 |
An isolation transformer with an electrostatic shield can have a ratio of input noise voltage (VIN) to output noise voltage (VOUT) within the range of 10:1 to 1000:1 or even higher. The calculations for K-Factor loads can be carried out with the help of information available in the Table No.2 and 3.
Transformers carries some disadvantage as under:
1.First is the issue of managing the derating when the transformer nameplate indicates greater capacity. Initially, the transformer may be operated at reduced loading. But in the future, the loading may be increased without considering the intended derating.
2.If smaller overcurrent protection is used intentionally to limit the overloading, nuisance tripping may occur due to the transformer inrush current. Larger overcurrent protection may be required for the oversized (derated) standard transformer resulting in larger conductor requirements with the associated higher feeder costs.
3.The transformers designed specifically for nonlinear loads minimize losses due to harmonic currents. They operate with the nonlinear loads more efficiently and generate less heat that need to be dissipated.
Once the harmonic current of the total load is known, and a K-Factor is specified (K4, K13 etc.), the appropriate type K-Factor transformer can be fully loaded up to 100% or nameplate KVA. All other optional feature that the industry is accustomed to can be specified.
1) Harmonic loads do cause premature failure when standard transformers are used.
2) Average reading RMS meters do not measure harmonic currents. True reading RMS meters should be used.
3) Insist on a K-Factor transformer that has been 3rd party tested. Accept no verbal claims. The proof must be on the label.
Because transformers are the power system components most affected by nonlinear loads, they are the first to receive a harmonic rating system. K-Factor ratings are based on heating effects of harmonics and are not necessarily applicable to other power system components. If harmonic rating systems for other components are needed, they will have to be developed by other methods, e.g., THD, crest factor, or some new and component-specific weighing of harmonic currents.
What is the likelihood that additional rating systems will actually be developed? That’s hard to predict. The best solution to the problem caused by harmonic currents would be preventive, i.e. the use of components does not generate harmonics. Impending standards such as IEC 555 and IEEE 519 encourage the development of such devices.
Indeed, low harmonic current power supplies and electronic ballasts are already available. As such new designs are implemented, they should gradually displace existing electronic loads (and their greater harmonics), serving to reduce the prevalence of harmonic currents over the long term.
Short term, however, projection show harmonic levels in power systems increasing as more electronic loads are added. Whether this will provide sufficient impetus for new rating system for other power system components is problematical. One thing is sure, though, until the day that harmonic currents actually diminish, K-Factor Transformers will play an important role in coping with the problems harmonics create.
References
[I] The Institute of Electrical & Electronic Engineers, “Recommended Practice for establishing Transformer capabilities when supplying Non-sinusoidal Load Currents”, ANSIIIEEE C57.110-1986, New York, 1986.
[2] Gruzs, T.M. “A survey of Neutral Currents in Three phase Computer Power Systems”, IEEE Transactions on Industry Application, Vo1.26,No.4, July/August 1990.
[3] IEEE P-l100 Working Group. Recommended Practice for Powering and Grounding Sensitive Electronic Equipments. Draft 1992.
[4] Underwriters Laboratory. Proposed Requirements and Proposed Effective Dates for the First Edition of the Standard for Dry Type General Purpose and Power Transformers, UL 156. Santa Clara CA, 1991.
[5] Computer Business Equipment Association (CBEMA). Three Phase Power Source Overloading Caused by Small Computers and Electronic Office Equipment. ESC-3 Information Letter, 1987.
[6] McGranaghan et al. “Analysis of Harmonic Distortion Levels in Commercial Buildings.” PQA 91,Paris, France, October 1991.
[7] ANSI/IEEE Standard 519-1981. IEEE Guide to Harmonic Control and Reactive Compensation of Static Power Converters.
[8] McPartland Brian J.: “Use K-Factor Transformers? Definitely! But Which K-Factor?” EDI, June 1991, Vo.2 No.6.
Published by Carelabs (Carelabz), Website: carelabz.com

Equipment applied to electric power systems to detect abnormal and intolerable conditions and to initiate appropriate corrective actions. These devices include lightning arresters, surge protectors, fuses, and relays with associated circuit breakers, reclosers, and so forth.
From time to time, disturbances in the normal operation of a power system occur. These may be caused by natural phenomena, such as lightning, wind, or snow; by falling objects such as trees; by animal contacts or chewing; by accidental means traceable to reckless drivers, inadvertent acts by plant maintenance personnel, or other acts of humans; or by conditions produced in the system itself, such as switching surges, load swings, or equipment failures. Protective devices must therefore be installed on power systems to ensure continuity of electrical service, to limit injury to people, and to limit damage to equipment when problem situations develop. Protective devices are applied commensurately with the degree of protection desired or felt necessary for the particular system.
Protection systems play a key role for the safe and reliable operation of today’s electricity power systems. Properly working protection devices help to maintain the safety of the system and to safeguard assets from damage. In order to ensure reliable operation, protective relays as well as recloser controls must be tested throughout their life-cycle, from their initial development through production and commissioning to periodical maintenance during operation. Our test equipment is ideal for each of these life-cycle phases and for any environment. As a reliable long-term partner, we offer state-of-the-art testing solutions which are continuously being developed and maintained to help you to keep pace with the increasingly complex requirements of your systems.
Lightning protection is a means to protect equipment, facilities and people from the effects of nearby or direct lightning events. Whereas, surge protection provides protection to equipment from the effects of more distant lightning events or power system anomalies. Five basic procedures are employed to test protection devices.
Clamping Voltage Tests
When a transient occurs, the SPD resistance changes from a very high stand-by value to a very low conduction value. The transient is absorbed and clamped at a defined level, protecting sensitive electronic circuits and diverting the transient energy to ground. A normalised current impulse of 8/20us is defined in the standards IEC 61643-1 and IEC61180-1.
Surge Withstand Tests
Surge withstand tests are intended to assess the maximum peak current carrying capability of varistors. The surge withstand capability is approximately proportional to the varistor disk size (diameter). Energy levels are much higher than for the clamping voltage tests with impulse levels in the tens of kilo amps range.
Energy Absorption Tests
High energy surges are usually generated by inductive discharges of motors and transformers. Energy absorption in an SPD is the integral current flow through and the voltage across an SPD. Surge currents of relatively long duration are required for testing maximum energy absorption capacity of an SPD. A rectangular wave of 2ms duration is sometimes used instead of the double exponential waveforms.
Combination Wave Tests
Surge events can be generated by lightning phenomena, switching transients or the activation of protection devices in the power distribution system. A surge itself is influenced by the propagation path taken so that impulses from the same event may have different forms depending upon where a measurement is taken. Combination Wave Generators (CWG) simulate a surge event in power lines close to or within building.
Duty Cycle (Flammability) Tests
A series of pulses is applied to the varistor to assess maximum rated dissipation. Exceeding the maximum rated dissipation will cause the protection device to be destroyed. A flammability risk could occur. The 8/20us current impulse is superimposed on the mains power supply
Basic devices have the ability to recognize and define fuses, protective relays, breaker trip devices, and surge suppressors and to understand their differences and uses. A common mistake for relay testers is to use spare outputs, displays, and/or LEDs for their pickup and timing tests and ignore the in-service output logic, believing that they are using the same elements in their test equations as the final logic.
Low-voltage breakers
They conduct the flow of current as long as a nominal value of current is flowing through the circuit to the load attached to it. Even at the slightest contact, current conduction occurs. But as soon as the breaker senses an excessively large amount which does not lie in its operating range (which can be checked through the ratings of the circuit breaker), the trip unit actuates the bimetallic strip and the contact breaks and immediately further flow of current is stopped. In addition to the safety operation, it also provides a kind of voltage insulation to the circuit and retains the flow after the current retains its appropriate value.
The field-testing and calibration of solid-state trip units can be performed by either primary current injection method or secondary current injection method. A coordination study is an organized effort to achieve optimum electrical distribution system protection by determining the appropriate frame sizes, ampere ratings and settings of overcurrent protective devices. When an overcurrent occurs in a properly coordinated distribution system, only the protective device nearest the fault will open. The secondary injection test is performed using a specially designed power supply unit. It should be noted that the secondary injection method only tests the solid-state trip unit logic and does not test the current sensors, wiring, or the breaker current handling components. Most solid-state trip units have terminal blocks that are equipped with test plug terminals for making the calibration test. The test set allows checking of the solid state trip unit operation without using primary current. The test set will pass enough current to check any desired calibration point. The breaker must be de-energized before checking the operation of the solid-state trip units. If the test set shows that the solid-state trip unit is not functioning properly, the trip unit should be replaced.
The primary current injection method is usually preferred because this method verifies the sensors and wiring, as well as the conduction path in the breaker. It is recommended that the primary injection test be performed simultaneously on all three phases when testing breakers with solid-state trip units. If three phase primary injection testing is not practical, then it is recommended that the sensors and wiring should be tested separately. This testing should be performed per NETA and the National Electrical Manufacturers Association (NEMA) procedures, and in accordance with manufacturer recommendations. Coordination Time-current curves are used to show the amount of time required for a circuit breaker to trip at a given overcurrent level.
Relays
A relay is an automatic device which senses an abnormal condition of electrical circuit and closes its contacts.
The first electrical test made on the relay should be a pickup test. Pickup is defined as that value of current or voltage which will just close the relay contacts from the 0.5 time-dial position. Allowing for meter differences, interpretation of readings, etc., this value should be within ±5% of previous data. Generally, one or two points on the time-current curve are sufficient for maintenance purposes. Reset the relay to the original time-dial setting and two points that could be checked and 3 and 5 times pickup. Of course, other points could be used, but the important thing is to always use the same point(s). The instantaneous unit should be checked for pickup using gradually applied current for reasons previously discussed. Wherever possible, current should be applied only to the instantaneous unit (to avoid over-heating the time unit).
There are different types of relays:
Current Relays
Relays can include phase overcurrent, current balance, negative sequence, zero sequence, thermal, and ground fault.
This is the first generation oldest relaying system and they have been in use for many years. They have earned a well-deserved reputation for accuracy, dependability, and reliability.
Contact function – Manually close (or open) contacts and observe that they perform their required function, i.e. trip, reclose, block, etc.
Pickup – Gradually apply current or voltage to see that pickup is within limits. Since preventive maintenance is the guide post, gradually applied current or voltage will yield data which can be compared with previous or future data and not be clouded by such effects as transient overreach, etc.
Dropout or reset – Reduce the current until the relay drops out or fully resets. This test will indicate excess friction. Should the relay be sluggish in resetting or fail to reset completely, then the jewel bearing and pivot should be examined. A 4X eye loupe is adequate for examining the pivot, and the jewel bearing can be examined with the aid of a needle which will reveal any cracks in the jewel. Should dirt be the problem, the jewel can be cleaned with an orange stick while the pivot can be wiped clean with a soft, lint free cloth. No lubricant should be used on either the jewel or pivot.
Test should be made to check that the overcurrent unit operates only when the directional unit contacts are closed.
Directional and Power Relays
Directional overcurrent relaying refers to relaying that can use the phase relationship of voltage and current to determine direction to a fault.
Power Directional Relays provides protection against excess power flow in a predetermined direction. And are used for anti-motoring protect on of AC generators.
The simplest pickup test for a directional unit is an in-phase test – i.e. current and voltage in phase. This test will eliminate the need for a three-phase supply, phase shifter, and phase-angle meter. However, it must be kept in mind that such a test is usually far from the angle of maximum torque (usually 60° lag for ground relays) and thus, small changes in components can yield large variations in in-phase pickup. As long as this fact is recognized and the pickup value is within limits, an angle of maximum torque check would not be necessary. Clutch pressure must always be measured in the same manner. For example, some instruction books express clutch settings in both grams and current/voltage levels. Portable pre-calibrated reactance-resistance test boxes are available for many of these tests. The use of such equipment, properly applied, will yield results which will exceed in accuracy those obtained with conventional phase-angle meters, ammeters, voltmeters, etc. In addition to the tests previously described for the overcurrent relay, the directional unit should be tested for minimum pickup, angle of maximum torque, contact gap, and clutch pressure. Further, a test should be made to check that the overcurrent unit operates only when the directional unit contacts are closed. . Either test is valid, but to have comparative data, the same method, either grams or electrical quantities should be employed each time
Voltage Relays Secondary Injection Test
Measure the relay auxiliary supply to ensure it is within the nameplate rating allowable range.
Creep or Pickup Test
Trip Time Test
Differential Relays
A test of minimum pickup should be performed. The differential characteristic (slope) should be checked and where applicable the harmonic restraint should be tested. Generally, differential relays are extremely sensitive devices and require some special consideration. For example, those relays employing ultra-sensitive polarized units as sensing devices are slightly affected by previous his-tory such as heavy internal or external fault currents. To eliminate previous history and truly perform a maintenance test, it is the usual practice to disregard the first pickup reading and use the second reading for comparison with previous and future data. By “disregard” it is not meant to imply that the initial reading be forgotten; rather it is meant that this reading not be used for comparison purpose.
Fuses
The fuse is a reliable overcurrent protective device, primarily used as a circuit protection device for over currents, overloads and short-circuits.
A time-current characteristic curve, for any specified fuse, is displayed as a continuous line representing the average melting time in seconds for a range of overcurrent conditions.
NFPA 70B recommends checking fuse continuity during scheduled maintenance, but testing to assure proper operation and protection against overcurrent conditions is not required. Fusible switches and fuse blocks require maintenance, such as tightening of connections and checking for signs of overheating as recommended per NFPA 70B.
In all cases, though, the idea is to send a small current through the fuse; if it passes through the fuse the fuse is good. If it does not the fuse is blown and needs replacement. This means that a battery is necessary to provide that small current and every fuse tester will have a battery in it. If a tester shows that a fuse is blown, the next step is to check the tester. This is accomplished by touching the test leads together or, in the case of testers without leads, to put a piece of metal (wire, coin, dinner spoon, anything metal) across the probes. If it does not indicate “good” the battery probably needs replacing.
Continuity testers will have two test leads and a small light that will light up if the leads are touched together. To test a fuse simply touch one lead to each of the electrical contacts on the fuse; if the light bulb lights up the fuse is good.
A multimeter again has two leads just like a continuity tester. However, there are many settings on a multimeter to measure amperage, voltage and resistance in several different ranges. Some multimeters are auto ranging (no need to choose a range), some are digital and some are analog meters with a needle to indicate the reading. With all multimeters the first step is to set it to measure resistance, or Ω. If different ranges are available, choose the lowest range (K means thousand on the dial, so 2K equals 2000) – usually around 200. Like a continuity tester, touch one probe to each contact on a fuse and observe the reading. A very low w reading of 1 ohm or less means the fuse is good; if it is blown the reading will be infinite, or the maximum the meter will display. An intermediate reading of several ohms probably means you aren’t making good contact; wriggle the probes on the fuse contacts or clean them and try again.
Microprocessor-Based Motor Protection Takes Protecting and Monitoring Electric Motors into the Digital Age
Before microprocessor relays, electromechanical and solid state relays were tested on an element by element basis. This was a coherent approach, allowing individual parts of the relay to be calibrated and proven. When microprocessor relays arrived, many continued this approach and tested individual elements within the relay, while others found alternative methods to test. Developing automated testing procedures for microprocessor relays can be classified into three categories:
The black box testing method, is adequate in terms of NERC compliance.
Whether functional or black box testing, the use of dynamic testing software is the logical choice to perform the testing. Dynamic tests drive relaying test sets to run in a series of defined sequences called states-such as pre-fault, fault and post-fault..
The use of element testing for microprocessor relays is likely to decline because, in part, to its noted shortcomings. The choice of functional vs. black box testing is less clear because both have their advantages and disadvantages. One thing is clear, however, regardless of the testing method employed-documentation of testing is critical, especially if the relay application is under the NERC umbrella. Tracking of testing intervals, previous test dates and last test dates are all part of the data required to be submitted during an audit. A detailed account of the testing on a subset of the full listing will often be requested. Maintaining this data by paper copy can result in much time spent tracking dates and data gathering. The larger the number of relays to track, the more daunting this task can be. Storage of all this data into a centralized database, with the ability to extract data and run audit reports, is quickly becoming a necessity to prepare for NERC audits. These reports can prevent a last minute crisis of discovering relays that were missed by tracking testing dates on a continual basis-and also provide the data needed for audit submissions. There are many different relay database programs, some home grown, others commercial. Regardless of NERC regulations, the reliance on these databases will only grow.
Circuit breakers are sometimes selected over fuses because circuit breakers can be reset where fuses have to be replaced. The most time consuming activity that results from the operation of the overcurrent protective device is typically investigating the cause of the overcurrent condition.
A known overload condition is the only situation that permits the immediate resetting or replacement of overcurrent protective devices per OSHA. If the cause for the operation of an overcurrent protective device is not known, the cause must be investigated.
Thus, having a device that can be easily reset, such as a circuit breaker, possibly into a fault condition, could be a safety hazard and a violation of OSHA regulations.
Because a fuse requires replacement by a qualified person, it is less likely to violate OSHA. Also, when an opened fuse is replaced with a new fuse in the circuit, the circuit is protected by a new factory calibrated device.
Generally, overload conditions occur on branch-circuit devices. Typically this is on lighting and appliance circuits feed from circuit breaker panel boards, where resetting of circuit breakers may be possible. Motor circuits also are subject to overload considerations.
However, typically the device that operates is the overload relay, which can be easily reset after an overload situation. The motor branch-circuit device (fuse or circuit breaker) operates, as indicated in NEC® 430.52, for protection of short-circuits and ground-fault conditions. Thus, if this device opens, it should not be reset or replaced without investigating the circuit since it most likely was a short-circuit condition.
The technical excellence and many unique features of the Protection Device Testers translate directly into benefits for the user:
Source: https://carelabz.com/what-protective-device-testing-how-done/
Published by Mirus International Inc., [2010-01-08] MIRUS-FAQ001-B2, FAQ’s Harmonic Mitigating Transformers, 31 Sun Pac Blvd., Brampton, Ontario, Canada. L6S 5P6.

As voltage becomes more and more distorted, it will begin to have a negative effect on the connected equipment. A flat-topped voltage waveform can affect a switch-mode power supply (SMPS) in at least 2 major ways:

When an SMPS is supplied by a voltage waveform with a flattened peak (red trace in Figure 9.1) rather than a nearly pure sinusoidal voltage (blue trace), the DC bus voltage is reduced proportionately (red trace). With a lower DC bus voltage, the SMPS will need to draw more current in order to deliver the same amount of power required by the load (I = P/V). This increase in current will result in increased component heating from higher I2R losses and a reduced life expectancy of the components due to their higher operating temperature. For example, a 10% decrease in peak voltage (from 169V to 153V) will increase the SMPS line current by about 11% which will in turn increase the I2R portion of the SMPS losses by about 23%. The correlation of SMPS failures with increased voltage distortion is usually subtle because equipment aging takes time to accumulate.
The first purpose of the large filter capacitor on the DC bus of an SMPS is to reduce the voltage ripple. The second purpose is to support its electronic load during a power disturbance that produces a momentary power interruption or major power dip. Since a typical SMPS is capable of operating for short periods at voltage levels as low as 70%, we can calculate the reduction in ride-through time if the initial voltage stored in the capacitor is below its rated peak voltage. For instance, if the peak voltage supplied to the SMPS is flat-topped by 30%, the ride-through capability is essentially zero and the I2R losses are twice those present at rated peak voltage.

With the correct initial peak voltage, the stored energy in the capacitor will often provide several cycles of ride-through capability before its voltage is reduced to 70% of nominal. This is dramatically reduced however, when the SMPS supply voltage is flat-topped because the energy stored in the capacitor is proportional to the square of the voltage. Figure 9-2 shows how a 10% reduction in the peak voltage supplied to computer equipment will reduce the power dip ride-through time by about 37%. Without the correct peak voltage, the smoothing capacitor in the SMPS will not be fully charged. Initially lower stored energy means that the capacitor will support the load for a much shorter period during a power interruption. When voltage flat-topping becomes severe enough, brief power interruptions such as those characterized by the lights flickering, will begin to affect equipment that would otherwise be unaffected.
In order to ensure reliable operation of power electronic equipment as well as other equipment on the power system, it is important to simultaneously maintain the correct level of both RMS voltage and peak voltage. This can best be achieved by using harmonic mitigation equipment that minimizes voltage distortion throughout the system by removing the harmonic currents from interacting with the upstream supply and distribution equipment.
Harmonics and Harmonic Mitigating Transformers (HMT’s) Questions and Answers
This document has been written to provide answers to the more frequently asked questions we have received regarding harmonics and the Harmonic Mitigating Transformer technology used to address them. This information will be of interest to both those experienced in harmonic mitigation techniques and those new to the problem of harmonics. For additional information visit our Website at www.mirusinternational.com.
Published by Xitron Technologies, Manufacturers of Engineering and Production Test Equipment, An ISO 9001:2000 registered company, AN102 Application Note.

In today’s industrial workplace, the proliferation of solid state devices (lighting ballasts, motor drives and controls, communications equipment, and other DC-powered loads) has created a major problem for specifying engineers, contractors and building owners. The non-linear nature of their switched-mode power supplies generate harmonic currents that cause transformers and system neutrals to overheat and destroy themselves.
K-factor is a weighting of the harmonic load currents according to their effects on transformer heating, as derived from ANSI/IEEE C57.110. A K-factor of 1.0 indicates a linear load (no harmonics). The higher the K-factor, the greater the harmonic heating effects.
When a non-linear load is supplied from a transformer, it is sometimes necessary to derate the transformer capacity to avoid overheating and subsequent insulation failure.
The reason for this is that the increased eddy currents caused by the harmonics increase transformer losses and thus generate additional heat. Also, the RMS load current could be much higher than the kVA rating of the load would indicate. Hence, a transformer rated for the expected load will have insufficient capacity.
The K-Factor is used by transformer manufacturers and their customers to adjust the load rating as a function of the harmonic currents caused by the load(s).
Generally, only substation transformer manufacturers specify K-factor load de-rating for their products. So, for K-factors higher than 1, the maximum transformer load is de-rated.
Some manufacturers, who produce both transformers and products like motors or ballasts, are sensitive to measuring K-factor since they know that poor K-factors of ballasts and motors will de-rate the maximum load their transformers can carry. From the customer’s viewpoint, K-factor must be established in order to calculate the size of the transformer that is needed. In other words, if a company with many offices were to install poor quality electronic ballasts having a poor K-factor, a larger transformer would be needed than is apparent from the overall power consumption calculation.
The K-factor is a number derived from a numerical calculation based on the summation of harmonic currents generated by the non-linear load. The higher the K-factor, the more significant the harmonic current content
The algorithm used to compute K-factor is:

Details of the calculation method can be found in IEEE Standard 1100-1992.
So, the higher harmonics are heavily weighted. As an example, a current signal having a 10% 3rd, 5% 5th, and 3% 7th harmonic content, would have a K-factor of 1.18. From manufacturers specifications, one can read the load de-rating that has to be applied for this K-factor.
Underwriters laboratory (UL) recognized the potential safety hazards associated with using standard transformers with nonlinear loads and developed a rating system to indicate the capability of a transformer to handle harmonic loads. The ratings are described in UL1561 and are known as transformer K-factors.
K-factor transformers are designed to reduce the heating effects of harmonic currents created by loads like those in the table below. The K-factor rating is an index of the transformer’s ability to withstand harmonic content while operating within the temperature limits of its insulating system.
| Load | K-Factor |
|---|---|
| Electric discharge lighting | K-4 |
| UPS with optional input filtering | K-4 |
| Welders | K-4 |
| Induction heating equipment | K-4 |
| PLCs and solid state controls (other than variable speed drives) | K-4 |
| Telecommunications equipment (e.g. PBX) | K-13 |
| UPS without input filtering | K-13 |
| Multiwire receptacle circuits in general care areas of health care facilities and classrooms of schools, etc. | K-13 |
| Multiwire receptacle circuits supplying inspection or testing equipment on an assembly or production line | K-13 |
| Mainframe computer loads | K-20 |
| Solid state motor drives (variable speed drives) | K-20 |
| Multiwire receptacle circuits in critical care areas and operating/recovery rooms of hospitals | K-20 |
To help get around the problem of successfully applying derating factors to conventional transformers, the K-factor is used by transformer designers to develop transformers made especially for non-linear loads and the extra heating caused by the harmonic currents. Transformers come in basic K-factors such as 4, 9,13, 20, 30, 40, and 50.
The strategy is to calculate the K-factor for your load and then specify a transformer with a K-factor of an equal or higher value. In this way, the transformer can be sized to the load without derating. The advantage of using a K-factor transformer is that it is usually more economical than using a derated, oversized transformer.
9770-A Carroll Centre Road, San Diego, CA 92126 • Tel: (858) 530-8099 • Fax (858) 530-8077 • sales@xitrontech.com • support@xitrontech.com
Affinity Energy – Infographic: Understanding the Impacts of Power Quality.

$15 billion is the annual cost of power quality issues. $130,000 are the potential costs for downtime in lost revenue for facilities. For mission critical facilities, that translates to $14,000 to $6.5 million every hour. It takes 17 hours for plants to restart after shutdown. You do the math.
Typical power quality symptoms include:
Types of power quality issues include:
The benefits of improving power quality include:
The negative effects of PQ issues include:
Ways to improve power quality include:
Source: https://affinityenergy.com/power-quality-infographic/
Published by
Abstract. Flexible AC transmission systems or FACTS are devices which allow the flexible and dynamic control of power systems. This paper is aimed toward the benefits of utilizing FACTS devices with the purpose of improving the operation of an electrical power system.
Power quality is an issue that is becoming increasingly important to electricity consumers at all levels of usage. Sensitive equipment and non-linear loads are commonplace in both the industrial and the domestic environment, because of this a hightened awareness of power quality is developing. The sources of problems that can disturb the power quality are: power electronic devices, arcing devices, load switching, large motor starting, embedded generation, sensitive equipment, storm and environment related damage, network equipment and design.
The solution to improve the energy quality (PQ-Power Quality) at the load side is of great important when the production processes get more complicated and require a bigger liability level, which includes aims like to provide energy without interruption, without harmonic distortion and with tension regulation between very narrow margins. The devices that can fulfil these requirements are the Custom Power; a concept that we could include among the FACTS, but that is different to them because of their final use. In fact the topologies that they employ are identical to the ones in the FACTS devices with little modifications and adaptations to tension levels, therefore they are most oriented to be used in distribution networks of low and medium tension, sometimes replacing the active filters.
Recent developments in electrical power systems such as deregulation, open access, and cogeneration are creating scenarios of transmission congestion and forced outages. Addition of new transmission lines is an almost impossible solution due to environmental and other considerations, and developing new approaches to Power System Operation and Control is the need of the hour for overload relief and efficient and reliable operation. Flexible AC Transmission Systems (FACTS), with the underlying concept of independent control of active and reactive power flows, offer an attractive alternative for achieving the objectives.
The use of static power converters in electricity networks has the potential of increasing the capacity of transmission of the electric lines and improving the supply quality of the electric energy. The devices used to achieve this, are the FACTS (Flexible Alternating Current Transmission Systems). The FACTS technology has a collection of controllers, that can be used individually or co-ordinated with other controls installed in the network, thus permitting to profit better of the network’s characteristics of control.
The FACTS controllers offer a great opportunity to regulate the transmission of alternating current (AC), increasing or diminishing the power flow in specific lines and responding almost instantaneously to the stability problems. The potential of this technology is based on the possibility of controlling the route of the power flow and the ability of connecting networks that are not adequately interconnected, giving the possibility of trading energy between distant agents.
Flexible Alternating Current Transmission System (FACTS) is a static equipment used for the AC transmission of electrical energy. It is meant to enhance controllability and increase power transfer capability. It is generally a power electronics based device.
FACTS is defined by the IEEE as “a power electronic based system and other static equipment that provide control of one or more AC transmission system and increase the capacity of power transfer.”
The FACTS devices can be divided in three groups, dependent on their switching technology: mechanically switched (such as phase shifting transformers), thyristor switched or fast switched, using IGBTs [4]. While some types of FACTS, such as the phase shifting transformer (PST) and the static var compensator (SVC) are already well known and used in power systems, new developments in power electronics and control have extended the application range of FACTS. Furthermore, intermittent renewable energy sources and increasing international power flows provide new applications for FACTS. The additional flexibility and controllability of FACTS allow to mitigate the problems associated with the unreliable of supply issues of renewable. SVCs and STATCOM devices are well suited to provide ancillary services (such as voltage control) to the grid and fault ride through capabilities which standard wind farms cannot provide ¡Error! No se encuentra el origen de la referencia.. Furthermore, FACTS reduce oscillations in the grid, which is especially interesting when dealing with the stochastic behavior of renewable.
In a liberalized market, the added value of FACTS, and especially power flow controlling devices, is the ability to control flow paths and therefore the ability to resolve congestions and optimally utilizing available grid infrastructure ¡Error! No se encuentra el origen de la referencia., ¡Error! No se encuentra el origen de la referencia.. Although FACTS devices are currently quite expensive, it is expected that with a growing utilization and experience, prices will drop considerably.
The benefits of utilizing FACTS devices in electrical transmission systems can be summarized as follows [1]:
In many countries, increasing the energy transfer capacity and controlling the load flow of transmission lines are of vital importance, especially in de-regulated markets, where the locations of generation and the bulk load centers can change rapidly. Frequently, adding new transmission lines to meet increasing electricity demand is limited by economical and environmental constraints. FACTS devices help to meet these requirements with the existing transmission systems.
There are different classifications for the FACTS devices:
Depending on the type of connection to the network FACTS devices can differentiate four categories
Depending on technological features, the FACTS devices can divided into two generations
These two classifications are independent, existing for example, devices of a group of the first classification that can belong to various groups of the second classification.
The main difference between first and second generation devices is the capacity to generate reactive power and to interchange active power.
The first generation FACTS devices work like passive elements using impedance or tap changer transformers controlled by thyristors. The second generation FACTS devices work like angle and module controlled voltage sources and without inertia, based in converters, employing electronic tension sources(three-phase inverters, auto-switched voltage sources, synchronous voltage sources, voltage source control) fast proportioned and controllable and static synchronous voltage and current sources.
Table 1. Two generations of the FACTS devices [2]
First Generation
| FACTS devices | Attributes of control |
|---|---|
| Static Var Compensator, SVC (TCR,TCS,TRS) | Voltage control and stability, compensation of VAR´s. muffling of oscillations |
| Thyristor Controlled Series Compensations (TCSC,TSSC) | Current control, muffling of oscillations, transitory, dynamics and of voltage stability, limitation of fault current |
| Thyristor Controlled Reactor Series (TCSR,TSSC) | Current control, muffling of oscillations, transitory, dynamics and of voltage stability, limitation of fault current |
| Thyristor Controlled Phase Shifting Transformer (TCPST,TCPR) | Control of active power, muffling of oscillations, transitory, dynamics and of voltage stability |
| Thyristor Controlled Voltage Regulator (TCVR) | Control of reactive power, voltage control, muffling of oscillations, transitory, dynamics and voltage stability |
| Thyristor Controlled Voltage Limited(TCVL) | Limits of transitory and dynamic voltage |
Second Generation
| FACTS devices | Attributes of control |
|---|---|
| Synchronous Static Compensator (STATCOM without storage) | Voltage control, compensation of VAR´s, muffling of oscillations, stability of voltage |
| Synchronous Static Compensator (STATCOM with storage) | Voltage control and stability, compensation of VAR´s, muffling of oscillations, transitory, dynamics and of tension stability |
| Static Synchronous Series Compensator (STATCOM without storage) | Current control, muffling of oscillations, transitory, dynamics and of voltage stability, limitation of fault current |
| Static Synchronous Series Compensator (STATCOM with storage) | Current control, muffling of oscillations, transitory, dynamics and of voltage stability |
| Unified Power Flow Controller (UPFC) | Control of active and reactive power, voltage control, compensation of VAR´s, muffling of oscillations, transitory, dynamics and of voltage stability, limitation of fault current |
| Interline Power | Control of reactive power, voltage |
| Flow Controller (IPFC) or Back to Back (BtB) | control, muffling of oscillations, transitory, dynamics and of voltage stability |
The concept of FACTS devices was presented in 1979, but the practical implementation and development of new analytical procedures are still in evolution. One of the objectives of the paper is to present the state-of-the-art technology and analysis of FACTS devices. Since the field demonstration of the world’s first UPFC in 1998, another FACTS controller, namely Sent Transformer (ST), has been proposed. In contrast to the UPFC, which uses a large number of solid-state switching devices, the ST uses time-tested components, such as transformer and load tap changers, but provides the same independent active and reactive power flow control as the UPFC at a much lower cost.
The FACTS devices are installed on electric power (high voltage AC) transmission lines to stabilize and regulate power flow for the dynamic control of voltage impedance and phase angle. Power lines protected by FACTS devices can support greater current because anomalies—frequency excursions, voltage drop, phase mismatch, malformed wave shape, power spikes, etc.—that would otherwise cause breakers to trip are removed or greatly reduced by FACTS conditioning.
A FACTS device can also limit the amount of current that flows on a line by effectively increasing the line’s impedance. This enables a much greater degree of flow control than provided by a switch or breaker. In particular, when current applied to a FACTS-protected line is greater than the device will allow, the power merely flows elsewhere rather than tripping a breaker, and power continues to flow on the protected line.
Essentially, lines can be run closer to their theoretical capacities when they are protected by FACTS devices. For a large line, that can mean substantial additional power. High voltage, high-power FACTS devices are building-sized and expensive, but they are lower cost and have less impact per added unit of electric power than new transmission lines. This is the essential benefit of operating standalone FACTS devices on individual lines.
FACTS devices offer an additional benefit: consider an interconnected network where two identical lines are carrying power, one at 50% of its capacity (for this example assume that capacity refers to the line’s operational limit under local conditions), the other at 99%. Assume that any additional load will be supplied equally through the two lines and that there is sufficient generating capacity to support the additional load being considered. Under these conditions additional load can be supplied only up to the limit of either line, and since one is at 99%, the system can support only about twice the remaining 1% (half of the additional power would go to each line). Additional power would cause the 99% line’s protective breakers to trip, at which point all power would attempt to pass through the remaining line, which would then also trip; the generators, being disconnected from their loads, would shut down, and the system would go dark.
However, if the line at 99% were held there by a FACTS device, any added power would go through the 50% line while power continued to flow in the 99% line at its original level. The capacity of this network considered as a whole would be increased by 25%, over and above the stabilizing and regulating benefits provided by the FACTS device. Note that this benefit cannot be recognized by analyzing just the FACTS device and its assigned branch, but only by considering the entire network. For a system that often operates in this sort of unbalanced state, FACTS devices can provide substantial additional capacity simply by forcing more of the network to carry the level of power it was designed to carry.
This idea leads to a new mode of operation: FACTS Devices can also direct power to less utilized parts of the transmission network, effectively increasing the capacity of the network, in addition to their customary standalone roles. Because optimum flow for the network as a whole cannot be achieved by considering only single branches, FACTS devices can perform this function only in cooperation with one another, so in this report such devices are referred to as Cooperating FACTS devices, or CFDs.
In practice, however, the additional communication required of CFDs opens the potential for subverting the operation of a cooperative system. This report considers both the operational and security aspects of CFDs operating in an electric power system network.
There are three factors to be considered before installing a FACTS devices:
Of these three factors, the last one is of great importance, because the desired effect and the proper features of the system depend of the location of FACTS.
Steps for the identification of FACTS Projects:
1.Serial controllers Can consist of a variable impedance as a condenser, coil, etc or a variable electronics based source at a fundamental frequency. The principle of operation of all serial controllers is to inject a serial tension to the line. A variable impedance multiplied by the current that flows through it represents the serial tension. While the tension is in quadrature with the line current the serial controller only consumes reactive power; any other phase angle represents management of active power. A typical controller is Serial Synchronous Static Compensator (SSSC).
2.Controllers in derivation. As it happens with the serial controller, the controller in derivation can consist of a variable impedance, variable source or a combination of both. The operation principle of all controllers in derivation is to inject current to the system in the point of connection. Available impedance connected to the line tension causes variable current flow, representing an injection of current to the line. While the injected current is in quadrature with the line tension, the controller in derivation only consumes reactive power; any other phase angle represents management of active power. A typical controller is Synchronous Static Compensator (STATCOM).
3.Serial-serial Controllers. This type of controllers can be a combination of coordinated serial controllers in a multiline transmission system. Or can also be an unified controller in which the serial controllers provide serial reactive compensation for each line also transferring active power between lines through the link of power. The active power transmission capacity that present a unified serial. controller or line feed power controller (also called BtB), makes possible the active and reactive power flow balance and makes the use of transmission bigger. In this case the term “unified” means that the DC terminals of the converters of all the controllers are connected to achieve a transfer of active power between each other. A typical controller is the Interline Power Flow Compensator (IPFC).
4.Serial-derivation Controllers. This device can be a combination of serial and derivations controllers separated, coordinately controlled or a unified power flow controller with serial and derivation elements. The principle of operation of the serial-derivation controllers is to inject current to the system through the component in derivation of the controller, and serial tension with the line utilizing the serial component. When the serial and derivation controllers are unified, they can have an exchange of active power between them through their link. A typical controller is Unified Power Flow Controller (UPFC), witch incorporating function of a filtering and conditioning, becomes a Universal Power Line Conditioner (UPLC).
Table 2 describe the technical benefits of the principal FACTS devices. For each problem the conventional solution (e.g. shunt reactor or shunt capacitor) also can be used. For dynamic applications of FACTS in addressing problems in transient stability, dampening, post contingency voltage control and voltage stability. FACTS devices are required when there is a need to respond to dynamic (fast-changing) network conditions. The conventional solutions are normally less expensive than FACTS devices – but limited in their dynamic behavior. It is the task of the planners to identify the most economic solution.
Table2. Technical benefits of the main FACTS devices

The UPFC may be seen to consist of two VSCs sharing a common capacitor on their DC side and a unified control system.

On Figure 1 we can see two back-to-back voltage source converters (VSCs), with one VSC connected to the AC network using a shunt transformer and the second connected to the AC network using a series transformer.
While operating both inverters as a UPFC, the exchanged power at the terminals of each inverter can be imaginary as well as real.
The mathematical UPFC model has been derived with the aim of being able to study the relations between the electrical transmission system and UPFC in steady and transient conditions.

The active power demanded by the series converter is drawn by the shunt converter from the AC network and supplied to bus m through the DC link. The output voltage of the series converter is added to the nodal voltage, at say bus k, to boost the nodal voltage at bus m. The voltage magnitude of the output voltage VcR provides voltage regulation, and the phase angle δcR determine the mode of power flow control.
In addition to providing a supporting role in the active power exchange that takes place between the series converter and the AC system, the shunt converter may also generate or absorb reactive power in order to provide independent voltage magnitude regulation at its point of connection with the AC system.
The UPFC equivalent circuit shown in Figure 3 consists of a shunt-connected voltage source, a series-connected voltage source, and an active power constraint equation, which links the two voltage sources. The two voltage sources are connected to the AC system through inductive reactances representing the VSC transformers. In a three-phase UPFC, suitable expressions for the two voltage sources and constraint equation would be:

Where ρ indicates phase quantities, a, b, and c.
Based on the equivalent circuit shown in the Figure 2, and assuming three-phase parameters, the following transfer admittance equation can be written:



Flexible Alternating-Current Transmission Systems (FACTS) is a recent technological development in electrical power systems. It builds on the great many advances achieved in high-current, high-power semiconductor device technology, digital control and signals gained with the commissioning and operation of high-voltage direct-current (HVDC) links and static VAR compensator (SVC) systems, over many decades, may have provided the driving force for searching deeper into the use of emerging power electronic equipment and techniques [5]. Due to the, every time higher requirements of the liability and quality of the electricity the implantation of devices capable of guaranteeing these requirements will keep increasing.
FACTS devices are improving the operation of an electric power system. The influences of such devices on steady state variables (voltage levels, transmission losses, and generating costs) are very remarkable. The benefit for each type of FACTS can be associated with its particularities and properties. They control the interrelated parameters that rule the operation of the transmission systems, including the serial impedance, the derivation impedance, the current, the voltage, the phase angle and the muffling of oscillations to different frequencies under the nominal frequency.
References
Published by Carelabs (Carelabz), Website: carelabz.com

Circuit Breaker Testing is utilised to test the operation of each switching systems and the programming of the entire tripping structure. Circuit Breaker Testing is essential to ensure the safe and reliable performance of this key link in the power asset chain. Circuit breakers perform three main tasks:
Performing circuit breaker testing is more challenging with comparison to other electrical components like transformer as the short circuit current is greater. In the US market and regions of frequent earthquakes, the most popular high-voltage circuit breakers are “dead tank” units, whereas in central Europe “live tank” breakers are standard. Elsewhere both circuit breaker types are obtainable.
A circuit breaker might stay idle years, but if a malfunction occurs it has to detach fault currents of huge kiloamps gradually within a few milliseconds. Major errors that happen on circuit breakers are incorrect behavior, short circuits in the coils, damage/wear to the mechanical connections or the insulation material. Therefore, circuit breakers need to be regularly and carefully tested. Circuit breakers perform a vital role in protecting expensive equipment from damage through faults i.e. connecting and disconnecting the electrical power in a reliable way; this requires proving their reliability with on field tests during installation and with regular maintenance tests during its lifetime to prevent costly failures and problems that could even compromising the safety of the substation. Testing the performance of your circuit breakers regularly is therefore an essential and cost-effective part of any maintenance strategy. Circuit breaker testing particularly concentrates on obtaining motion and time values on the units. However, our testing solutions have revolutionized circuit breaker testing. Performing the tests without use of the station battery greatly increases safety throughout the testing process.
Type Tests of circuit breaker
Type tests are organised with the aim of proving the abilities and making sure the rated characteristic of the circuit breaker are exact. Such tests are conducted in the specially built testing laboratory.
Routine tests are done as per references of standards of Indian Engineering Service and Indian Standards. These tests are performed on the manufacturers’ premises. Routine tests confirm the proper functioning of the circuit breaker. The routine tests confirm the proper functioning of the circuit breaker. Routine testing doesn’t necessarily include complex gear in order to ensure that a circuit breaker is functional. Some guidelines and recommendations for these tests include routine maintenance and verifying that that circuit breaker performance is in line with manufacture’s calibration curves. It is crucial that these tests are performed under stable conditions at suitable temperature so that there are no variations in the data. Some of the tests are listed below.
Preventative maintenance depend operating conditions for circuit breakers. Primary inspections of CB (circuit breakers) will look at particulate matter that’s contaminating the inner workings of the CB. Accumulation of particulates can generally be disposed of by flipping the lathe on the breaker “Off” and “On” switch to clear away the accumulated dust
By analysing the current consumed by the trip coil during the circuit breaker’s operation, it is possible to determine whether there are mechanical or electrical issues present. In many cases, such issues can be localised to aid in finding the root cause. Optionally, monitoring the tripping supply’s voltage during the operation can detect issues arising with tripping batteries.
For individual breaker resistance testing, load and line conductors should be preferably disconnected. If not detached the test values will also involve the characteristics of the connected circuit. Resistance testing is crucial for verifying that the insulating material which makes up the molded cases breakers are performing correctly. In order to test for insulation resistance, an instrument known as a megger is used. A megger instrument applies a known DC voltage to a given wire for a given period of time in order to test the resistance within the insulation on that particular wire or winding. It is vital that voltage is employed as the resistance checked with an ohmmeter may differ when there are no report of potential differences. It should also be noted that if you apply a voltage that is too high for that insulation to withstand, then you could potentially damage the insulation.
Connection testing is important to make sure that an appropriate electrical connection is available and to recognise traces of overheating denoted by colour difference. It is important that electrical connections are properly installed to the CB to prevent and reduce overheating.
Normal wear and tear of contacts within the CB emerges after extended usage. An easy method to identify traces of weakening within the circuit breaker is to quantify the resistance across every pole of the breaker. Indications of abnormal conditions within the CB such as erosion and contamination of contacts are evident if there are excessive millivolt drops across the breaker. The contact resistance test is important in finding out if or not a circuit breaker is still apt for functioning.
Overload tripping components of CBs can be tested by inputting 300% of the breaker rating into each pole of the circuit breaker to determine that it will open automatically. The motive of this is to make sure that the circuit breaker will operate or not. Refer to NETA standards for trip times that are acceptable for the overload tripping test. When trying to find out tripping characteristics, it is advisable to consult with manufacturer’s manuals.
In routine tests, it is relevant to find out that the magnetic feature is functional and will trip the circuit breaker instead of finding the precise value at which the instantaneous magnetic feature functions.
Different circuit breaker test equipment are used to check the operation and condition of circuit breakers on the power systems. How to test a circuit breaker involves many different test techniques and type of testers. This will define how to test a circuit breaker through different testing tools to be applied to check the equipment under a range of conditions or operation types. Discover how to test a circuit breaker with the different test sets that you can need.
To consider how to test a circuit breaker, it is required a deep knowledge of the breaker itself:
In this sense, how to test a circuit breaker becomes a trending analysis since test results are not always definitive but have meaning just when compared to previous data or results.
The timing tests of the different open and close operations of the breaker is an efficient way of how to test a circuit breaker, analyzing not only the trip times but also the essential synchronism of the poles in the different operations. This define how to test a circuit breaker through different simulations of its operation, which can be directly commanded from the circuit breaker analyzer, or initiated by an external signal, checking the opening or closing time of each pole, in single or combined operations, and checking the possible difference between poles or mismatch time which may lead to a dangerous lack of synchronism. How to test a circuit breaker with a circuit breaker analyzer depends also on the type of possible problems to be confirmed, which leads to check other features such as the possible bouncing, the proper performance of the pre-insertion resistances, the coils condition, and the mechanical analysis through contact travel speed and acceleration data with the use of the appropriate transducers.
Circuit breakers generally bear a huge value of current. Greater contact resistance cause greater losses, low current carrying capability and threatening hot spots in the breaker, so that the resistance testing with micro-ohmmeters are other way of how to test a circuit breaker for identifying and avoiding upcoming issues. How to test a circuit breaker with a micro-ohmmeter requires also reliable measurements and a wide injection range with high power that enables for longer test leads, less connections problems, and more accurate measurements.
The analysis of the tripping time characteristics of LV circuit breakers and molded-case circuit breakers is performed using high current injection, as the way to check the entire functionality. How to test a circuit breaker of this type depends on its maximum rated current, the trip protection settings and the inverse curve types which will define the overload and short-circuit trip pickup levels and time delays; all these features must be checked with the appropriate primary injection test set with the capacity to simulate the corresponding high current faults required and capture the answer of the breaker. A system which be easily upgraded in power capacity enables how to test a circuit breaker in the different possible situations and range of breakers; how to test a circuit breaker of this kind also needs a bendable design of the test set to fruitfully attain the certain large current job, and a design that create possible to position it nearer to the breaker, and so decreasing the power needed with smaller test leads; this is the case of the Raptor System, a modular and flexible primary injection system which easily and quickly adapts its power capacity to the several high currents ratings of the different circuit breakers.
Source: https://carelabz.com/what-circuit-breaker-testing-how-circuit-breaker-testing-done/
Published by Mirus International Inc., [2010-01-08] MIRUS-FAQ001-B2, FAQ’s Harmonic Mitigating Transformers, 31 Sun Pac Blvd., Brampton, Ontario, Canada. L6S 5P6.

The switch-mode power supply (SMPS), used in most digital electronic equipment, is an excellent example of a non-linear load. Because it draws current in non-sinusoidal pulses, the SMPS is a significant generator of harmonic currents. When found in high densities multiple SMPS can be a major contributor to voltage distortion. Figure 8-1 shows how the pulsed current consumed by a single-phase SMPS will produce voltage distortion in the form of flat-topping. Since current is consumed only at the peak of the voltage waveform (to charge the smoothing capacitor), voltage drop due to system impedance will also occur only at the peak of the voltage waveform. A flattened voltage peak will reduce the DC bus voltage of the SMPS, reduce its power disturbance ride-through capability, and increase both its current draw and I2R losses.

Another way to analyze the operation of the system with non-linear loads is to calculate the effect of each individual harmonic current as it flows through the various impedances of the distribution system. Fourier analysis tells us that the 2-pulse current drawn by the SMPS rectifier has a fundamental frequency component plus all of the odd harmonics (3rd, 5th, 7th, 9th, 11th, etc.) When modeling the distribution system, we can think of each SMPS as a generator of harmonic currents. Each harmonic current injected into the power system by a non-linear load will flow through the system impedance, resulting in a voltage drop at that harmonic frequency. The amount of voltage drop follows Ohm’s Law (Vh = Ih x Zh) where:
Vh = voltage at harmonic number h
Ih = amplitude of current harmonic h
Zh = impedance of the system to harmonic h.
Figure 8-2 shows the relationship between system impedance and the voltage and current distortion components at several points in a typical power system.
We can calculate the RMS value of the voltage or current distortion if we know the RMS values of all of the components. Parseval’s Theorem tells us that the RMS value of a waveform is equal to the square root of the sum of the squares of the RMS values of the fundamental component and all of the harmonic components of the waveform.

The fundamental is not a distortion component, so the RMS value of the distortion is just the square root of the sum of the squares of the harmonic components. Usually this is expressed as percentage of the value of the fundamental component and is called the Total Harmonic Distortion, or THD.
Voltage total harmonic distortion (Vthd) is calculated as:

Similarly, current total harmonic distortion is calculated as:

Voltage distortion then is a function of both the system impedance and the amount of harmonic current in the system. The higher the system impedance (ie. long cable runs, high impedance transformers, the use of diesel generators or other weak sources) the higher the voltage distortion.
In Figure 8-2, we see that voltage distortion is greatest at the loads themselves, since the harmonic currents are subjected to the full system impedance (cables, transformer and source) at that point. This is a characteristic most often misunderstood. It means that even if voltage distortion levels are low at the service entrance, they can be unacceptably high at the loads themselves. It also emphasizes the importance of keeping system impedances relatively low when servicing non-linear loads.
Voltage distortion can be minimized by removing the harmonic currents (Ih) and/or lowering the system impedance (Zh) to the harmonics.
Harmonics and Harmonic Mitigating Transformers (HMT’s) Questions and Answers
This document has been written to provide answers to the more frequently asked questions we have received regarding harmonics and the Harmonic Mitigating Transformer technology used to address them. This information will be of interest to both those experienced in harmonic mitigation techniques and those new to the problem of harmonics. For additional information visit our Website at www.mirusinternational.com.
Published by Dranetz Technologies, Inc., Application Note

IEEE Std. 519-2014, IEEE Recommended Practice and Requirements for Harmonic Control in Electric Power Systems is the most current recommended practice from the IEEE related to harmonics measurement and compliance. Although the recommended practices from the IEEE are usually only followed in North America, IEEE 519-2014 is used in Latin America, Asia, India and other parts of the world. As a result, there is a lot of interest in IEEE 519 2014 and how it is applied.
IEEE 519-2014 includes the harmonic measurement techniques of the widely used IEC 61000-4-7. IEEE 519-2014 adds two additional parameters, along with new requirements for statistics reporting for harmonic compliance. Therefore, instruments that only measure to IEC 61000-4-7 are missing required capabilities.
The Dranetz HDPQ Plus and SP are among the few instruments that fully comply with the measurement and reporting requirements of IEEE 519-2014. This application note focuses on the requirements of IEEE 519-2014 and how they apply to Dranetz instruments.
The original IEEE 519-1992 recommended practice included descriptive information about harmonics and harmonic compliance limits. However, instrument measurement methods were not defined. The result was different manufacturers used different harmonic measurement techniques that produced different and inconsistent results.
IEEE 519-2014 addresses this by referencing the harmonic measurement techniques of IEC 61000-4-7. IEC 61000-4-7, and the broader IEC 61000-4-30 power quality measurement standard are well established, and have been adopted around the world. IEEE 519- 2014 states “…any instrument used should comply with the specifications of IEC 61000-4-7 and IEC 61000-4-30.” As a global supplier of power quality monitoring products, Dranetz products have complied with both of these standards since their inception in the early 2000’s.
IEC 61000-4-7 defines a harmonic measurement window width of 200ms, which is 12 cycles at 60Hz and 10 cycles at 50Hz. Each (DFT, Discrete Fourier Transform) harmonic analysis uses this 200ms window of data for its computations and this window is the smallest resolution for harmonic measurements in the Dranetz HDPQ family. Harmonic analysis is based on the evaluation of continuous 200ms windows without gaps.

For statistical analysis, IEEE 519-2014 adds two parameters to the measurement methods of IEC 61000-4-7: Very Short Time Harmonics and Short Time Harmonics. It is important to note that these two new parameters are unique to IEEE 519-2014 and are not part of IEC 61000-4-7. This means that an instrument measuring to IEC 61000-4-7 does not necessarily comply with IEEE 519-2014.
Very short time harmonics are assessed over a 3- second interval and include 15 consecutive 200ms (12/10 cycle) windows. Without going into the specific details, harmonic components are aggregated over this interval and are then used for statistical evaluation.
Short time harmonics are assessed over a 10-minute interval and are an aggregation of 200 consecutive very short time values. Short time harmonics are aggregated over the required (10 minute) interval and then used for statistical evaluation.
IEEE 519-2014 states that very short time harmonics should be accumulated over a one day period and the 99th percentile values should be calculated for each individual harmonic to the 50th each day. Short time harmonics should be accumulated over a one week period, and the 95th and 99th percentile values should be calculated for each individual harmonic to the 50th each week.
IEEE 519-2014 also includes recommended harmonic limits measured at the PCC (Point of Common Coupling). The intent is to manage the harmonics at the interface point between utility system owners and end users, so the specified limits apply only at the PCC and not for individual loads.
For voltage harmonics, the recommended limits for individual harmonics and VTHD are specified at various bus voltages measured at the PCC. Acceptable limits are based on the bus voltage, with higher bus voltages having lower acceptable limits (they are farther away from the harmonic generating loads).
Similarly, recommended limits for individual current harmonics are specified at several different bus voltage levels at the PCC, but TDD (Total Demand Distortion) is referenced and not ITHD. This means that TDD must also be computed by the instrument which is not part of IEC 61000-4-7. Current harmonics measured at higher bus voltage levels have lower acceptable limits (they are farther away from the harmonic generating loads).
The actual compliance limits are outside of the scope of this application note, so see section 5 of IEEE 519- 2014 for more details.
Although Dranetz products have measured harmonics to IEC 61000-4-7 for many years, IEEE 519-2014 adds the two new harmonic measurement parameters and new statistical evaluation requirements. The only Dranetz portable product that can fulfill these requirements are the Dranetz HDPQ Plus & SP family.
The Dranetz HDPQ Plus & SP have built in harmonic statistics reports that include very short time and short time harmonics. The report produces pass/fail daily and weekly voltage and current harmonic compliance in full accordance with IEEE 519-2014.
To view the report, press the Harmonics Statistics Report button in the View Data page.
You will then see a list of daily and weekly harmonic statistic reports over the month 31 days, with each indicating pass or fail. There will be one very short time 99th percentile report for each day, and two short time reports for each week (one for the 99th percentile and the other for the 95th percentile).

Simply select a report in the list and press OPEN to view the details of the compliance for each harmonic to the 50th.

Dran-View 7 software also includes IEEE 519-2014 harmonic compliance reporting that uses the statistical data compiled by the HDPQ Plus & SP instruments (only).
IEEE 519-2014 is a significant update to the original version from 1992. In addition to specifying new harmonic measurement parameters and compliance limits, IEEE 519-2014 includes the harmonic measurement techniques of the globally accepted IEC 61000-4-7 harmonic standard.
The Dranetz HDPQ Plus & SP family are among the few products available that fully conform to both the measurement and compliance reporting requirements of IEEE 519-2014.
Dranetz Products: Dranetz HDPQ® Plus & SP Family
Website: Dranetz.com , Call 1-800-372-6832 (US and Canada) or +1-732-287-3680 (International)
Have a WordPress.com account? Log in now.