Published by Panida Boonyaritdachochai, Power Quality Engineer, Power Quality (Thailand) Co., Ltd.

























Published by Panida Boonyaritdachochai, Power Quality Engineer, Power Quality (Thailand) Co., Ltd.

























Published by Nat Songkram, Power Quality Section, Provincial Electricity Authority (PEA), Thailand.
























Published by Thaweesak Aranchot, Electrical Engineer, Power Quality (Thailand) Co., Ltd.
Plan
Introduction
Loads of the Building
Figure 1:
Figure 1
Figure 2:
A trend plot is showing a usage of two 36-watt fluorescent lamps in an hour.
18W x 12 – Consumed à 2.94 kWh/Day
36W x 4 – Consumed à 3.83 kWh/Day
Total = 6.77 kWh/Day


Figure 2
Figure 3:
Figure 3
Figure 4:
Figure 4
Blue area is operating area
Green area is non-operating area
Figure 5:

Figure 5
Blue area is operating area
Green area is non-operating area
A Consumption for Working Day
Load consumption of a working day in Percentage.
Average consumption is 30 kWh per day.

Figure 6:
Figure 6
Figure 7: Working day usage between middle of December to middle of January.

Figure 7 – Working day consumption
A Consumption for Non-Working day
Display a single day usage for Non- Working day (Figure 8)

Figure 8
Figure 9: Non-working day usage between December 2018 to January 2019
Figure 9
Total Consumption (Figure 10)

Figure 10
Solutions: How can we save cost of electricity?
Saving cost, we could reduce electricity of the main load for example:

We could reduce electricity of load for example, Lighting:
Published by Terry Chandler, Director of Engineer, Power Quality Inc.
Power Quality study for EV charger post
• Manufacturer of EV has experienced several internal battery charger failures in new EV’s
• 2 sites, 1 in Arizona USA, 1 in Seoul, Korea.

The plan for USA site and Korea site
• Monitor the voltage quality supplying the charger post.
• Monitor the Voltage quality and current load of the EV internal battery charger
• Record all voltage quality parameters
• Record all load factors including
• Switching
• Harmonics
• Peak currents
Charging post details
FAST CHARGING – 7.7kW of power to charge your vehicle quickly
• QUALITY – Technology that works for the life of your current plug-in vehicle and then some
• CONVENIENT – 25 feet of charging cable for installation and operation flexibility
• DURABLE – Rugged, fully sealed NEMA 4 enclosure for installation anywhere

Electrical specifications of charging post
• Service – 208V to 240V – 40A, dedicated circuit
• Charge current output power – 208V to 240V – 32A max
• Service ground monitor – Constantly checks for presence of proper safety ground
• Automatic circuit recloser after minor power faults
• Charge Circuit Interruption Device – Ground fault protection with fully automated self-test, eliminates manual user testing
Charging post normal operation
Normally, the vehicle will immediately request a charge using a special communication line in the cable. Within a few seconds the green “Charging” light on the face of the HCS will turn on and the charging cycle will begin.
After an average driving day the vehicle battery pack will require several hours to recharge completely. Charging overnight is the most convenient way to maintain healthy batteries and ensure the vehicle’s full range will be available for the next day.
The front panel on the HCS has four indicators:

Figure 1
Installation at the USA Test Setup
• Weather conditions, 105 to 120 degrees F.
• HCS Maximum Operating Temperature: -30°C to +50°C (-22°F to +122°F)
• Two cars were used for testing
• Dranetz HDPQ Explorer with 3 range Flexi CTs for recording voltage and current
• Channel A was connected to the 208V input to NCS-40 charger control panel.
• Channel C was connected to a test cable from the charger to the car.
• Installed 1 each Dranetz PowerVisa PQ monitor at Charging post B.


Dranetz HDPQ monitor connected to incoming voltage of charger post.

Connection from Charger pedestal to EV.
Tests and monitoring included
• Input and output voltage and current of NCS not attached to car.
• Input and output voltage and current of NCS when attached to car and while charging
• Input and output voltage and current when connecting and disconnecting from car.
• Input and output voltage and current when connecting a second charger to a second car.
• Several repeats of these items

Figure 2: Input and output voltage of NCS when attached to car and while charging.
Test results
Input/output with an EV car not connected.
208-volt source voltage waveform from facility source was stable and within normal tolerance of +/-5%; frequency 60.0 hertz
No current and no 208-volt output. Small square wave output for signaling to EV car
Input/output with car connected.
• Output voltage delayed until car charger signal
• Output current delayed and slowly ramps up. More details needed. But apparent “soft start”
• Amazingly fast voltage transient recorded during connection time
• Voltage dropped when charging started.
Input/output during charging switching off
•When charger shuts off, voltage transient.


Harmonic voltage and current with charger on and off


Input/output during connection of second car
• Voltage dropped further when second car connected.
• No noticeable transient when second car connected.
• Harmonic voltage distortion increase…..
Change instrument setup to provide better details for inrush current.
• During connection to car and intermittent connection was observed. This may be a contributing factor. Further investigation required
Monitoring Vrms during charger testing long term graph show voltage surge during the charger connection test. No voltage sags occurred. (Figure 3)

Figure 3
Voltage rise during test not due to testing of charger post or charger (Figure 4).

Figure 4
Source voltage variations with charger off (Figure 5).

Figure 5
Source voltage transient to charger post (Figure 6).

Figure 6
RMS Voltage variations due to charger operation (Figure 7).

Figure 7
Harmonics charger on (Figure 8).

Figure 8
Harmonics charger off (Figure 9).

Figure 9
Summary
• Source voltage is fed direct to EV charger without filtering, regulation or surge protection.
• Harmonics increase when EV charger comes on is dependent on the source impedance and will vary site to site.
• The EV chargers are at risk to damage due to source voltage PQ events.
• Not all source voltage PQ issues are from the utility
• Some charger sites have transient voltage surge suppression.
• The EV charger loads will vary by EV manufacturer. Tested units showed charger current and supply voltage from the charger post are controlled by the EV charger.
PQSynergy™ is an international forum to share experiences, requirements, questions, information, customer requirements, problems and solutions in the fast growth area of quality of supply requirements of sensitive loads, energy conservation and management and power quality monitoring and solutions.
For more information, you can visit the website: www.pqsynergy.com
View and download papers:
| PQSynergy™ Papers | Publishers |
|---|---|
| A Case Study for Energy Usage Report | Thaweesak Aranchot, Electrical Engineer Power Quality (Thailand) Company., Ltd. |
| Challenge in Solar Rooftop PV | Mayura Srion, Chief of Power Quality Analysis Section, Customer Service Division PEA Udon Thani 1, Thailand |
| Challenges with integrating PV into MV grid | Thomas Pua, Senior Product Development Engineer, Power Standards Lab, USA |
| Distributed Energy Storage System (ESS) and the Grid | Kerk See Gim, Senior Manager, Power Automation, Singapore |
| Power Generation and Air Pollution | Jay Babin, Managing Director, E-Flow (Thailand) Company, Ltd. |
| Power Quality Causes and Effects with Biomass Power Plant | Danaisak Tangsakha, Chief of PQ Analysis, Customer Service Division,Engineering & Service Department, PEA Nakhon Pathom, Thailand |
| Power Quality Practitioner™ Workshops | Terence Chandler, Director of Engineering, Power Quality Inc., USA |
| PQSim200 | Robert James Stewart, Electrical Engineer, Power Quality (Thailand) Company., Ltd. |
| How can Blockchain Technology be used for Electrical Utilities in the future | Robert James Stewart, Electrical Engineer, Power Quality (Thailand) Company., Ltd. |
| Implementation of Four Lenses of Innovation | Kittipon Daychosawang, Engineer, Department of Customer Service, PEA Chiang Mai 2, Thailand |
| Intro to PQDIF and its Applications | Thomas Szollossy, Senior Technical Support Engineer, Power Quality (Thailand) Company, Ltd. |
| Introduction to IEC 61850 | James Mater, General Manager, Smart Grid, Quality Logic Inc., USA |
| Leadership is . . . Probably Not What You Think It Is | Eric Stojkovich, President, ESC Pacific Inc., USA |
| Power Quality Techniques for Crushing Plant Solutions | Suwipha Kittitanapisarn, Chief of Power Quality Analysis Section, PEA Chiang Mai, Thailand |
| PQMS at Con Edison | Terence Chandler, General Manager, Dranetz Asia, Dranetz Corporation |
PQSynergy™ is an international forum to share experiences, requirements, questions, information, customer requirements, problems and solutions in the fast growth area of quality of supply requirements of sensitive loads, energy conservation and management and power quality monitoring and solutions.
For more information, you can visit the website: www.pqsynergy.com
View and download papers:
| PQSynergy™ Papers | Publishers |
|---|---|
| 30 Years of History of PQ in Asia (And the World) | Terry Chandler, A Power Quality PractitionerTM , Director of Engineering, Power Quality Thailand LTD/Power Quality Inc. USA |
| Active Harmonic Mitigation-What the Manufacturers Don’t Tell You! | Tony Hoevenaars, PEng., MIRUS International Inc. |
| Generating Electricity Through Incineration, Opportunity or Threat for Thailand | – |
| New Issues and Opportunities for Power Quality | William (Bill) Howe, Program Manager Power Quality Research, EPRI |
| PQ Standards IEEE-519-2014 Applicable for Industrial + Commercial Supply System | Tushar Mogre, TASTM PowerTek |
| Strategies of Maintenance Management in CCPP | Panida Boonyaritdachochai, Paveena Ketwong & Patcharachai Kaewwanna, B.Grimm |
| Technical Challenges of Remote Access to Instruments Over Mobile Network | Thomas Szollossy, B.Eng (EE), Senior Technical Support Engineer, Power Quality Thailand LTD |
| Unintended Consequences of DER Penetration in Distribution and Microgrids | Stephane Do, Global Product Manager, Power Standards Lab (PSL) |
| A New Harmonics Option for PQSim200 | Thaweesak Aranchot, Power Quality (Thailand) Co., Ltd. |
| Industrial Benchmarking of PQ and Various Methods and Merits | Tushar Mogre, TASTM PowerTek |
| Introducing a PQ Simulator-PQSim200 | Power Quality (Thailand) Co., Ltd. |
| The Opportunities for Battery Storage System in Demand Side | Jiravan MONGKOLTANATAS, Electrochemical Materials and System Lab (EMS), Materials for Energy Research Unit (MFERU), National Metal and Materials Technology Center (MTEC) |
| Power Quality in Singapore-The Past One Decade | Er. Muhammad Najmi Bin Bohari, Principal Consultant, Potentia Dynamics, MSc(Power Eng), B.Eng (EEE), P.Eng, ACPE, LEW, MIES, M-CIGRE |
| PSL Analyzer Products | Power Standards Lab (PSL) |
| Singapore Energy Deregulation and Smart Grid | Power Automation |
| Advances in Software for Power Quality Monitoring Systems | Brian W Todd, Vice President, Dranetz Technology, General Manager, Electrotek Concepts |
| Embedded Systems-The Perfect Solution for Microgrid Control | Keith Houghton, Linklaser Limited |
| New development of EV and Chargers in China | Qianlu Yan, Beijing Joint Harvest S&T Co., Ltd. |
| PEA Microgrid Design for Off-Grid Island | Chakphed Madtharad, Ph.D., Smart Grid Planning Division, PEA |
The Power Xplorer integrates the most advanced feature set available in a power monitoring instrument, with an easy-to-navigate, color graphical user interface. With high-speed sampling and data capture (1 microsecond/channel), this 8-channel workhorse simultaneously captures and characterizes thousands of parameters, using a range of standard and customizable operating modes. The unique measurement capabilities of the Power Xplorer include capture of low-medium-high frequency transients through peak, waveshape, rms duration and adaptive high-speed sampling, as well as power measurements to clearly characterize non-sinusoidal and unbalanced systems.
Dran-View 6 (DV6) software is included as part of our Dranetz HDPQ instrument packages and is compatible with all current and most legacy portable instruments from Dranetz.
Note: Software upgrade, new version is Dran-View 7 Professional and Enterprise Editions.
Dran-View 7 is a Windows based software package that enables power professionals to visualize and analyze power and energy monitoring data simply and quickly. It is a snap to navigate, delivers automated functionality, and incorporates powerful analytical capabilities and customizable options to meet the needs of each individual user. Dran-View is successfully used by thousands of customers around the world and has become the industry leading power management software tool.
Harmonics Analysis
The user can select from a variety of harmonic calculations and displays in DV6 (Figure 1).

Figure 1
The graph shows full spectrum (Figure 2), but a user may choose a subset for clarity of data or specific details.

Figure 2
User can save data as Excel spreadsheet (Figure 3).

Figure 3
6 Current channels from PX5-400
User selects the channels to be displayed


PQSynergy™ is an international forum to share experiences, requirements, questions, information, customer requirements, problems and solutions in the fast growth area of quality of supply requirements of sensitive loads, energy conservation and management and power quality monitoring and solutions.
For more information, you can visit the website: www.pqsynergy.com
View and download papers:
| PQSynergy™ Papers | Publishers |
|---|---|
| Electric Vehicle Charger Case Study | Terry Chandler, A Power Quality PractitionerTM , Director of Engineering, Power Quality Inc. |
| Power Quality and Harmonic Causes and Effects with Paper Mill Factory | Danaisak Tangsakha, PEA Thailand |
| Power Quality Problem Analysis in VSPP | Surawut Bunnag, Chief of Power Quality Analysis Section, Provincial Electricity Authority (PEA Area 3 (Central) Nakhon Pathom) |
| Proactive Use of PQ Data Beyond Post-Mortem Analysis | Bill Howe, PE, Program Manager, Electric Power Research Institute (EPRI) |
| Robotic Welding in Auto Industry-Case Study Honda Cars | POWER |
| Synchrophasors for Distribution Systems | Thomas Pua, Product Development Engineer, Power Sensors Ltd |
| Thermal Modeling of Oil Immersed Transformer Using Temperature Rise Data | Nat Songkram, Power Quality Section, Provincial Electricity Authority, PEA |
| Developing an Improved Strategy for Valuing PQ | Bill Howe, PE, Program Manager, Electric Power Research Institute (EPRI) |
| Electrical Cars and Charging in China | Qianlu Yan, Beijing Joint Harvest S&T Co., Ltd. |
| Impact of Power Quality on Rice Mills | Provincial Electricity Authority, PEA |
| Power Quality in Building Services Case Studies & Examples from Singapore | Er. Muhammad Najmi Bin Bohari, Principal Consultant, Potentia Dynamics, MSc(Power Eng), B.Eng (EEE), P.Eng, ACPE, LEW, MIES, M-CIGRE |
| PQube 3 and Micro Power Quality | Power Sensors Ltd (PSL) |
| Reducing Generator Size and Fuel Consumption using Harmonic Mitigation | President & CEO Tony Hoevenaars, PEng, Mirus International Inc. |
| Safety Issues Caused by High Earth Resistance and Identifying Them Using Instruments | Thomas Szollossy, Senior Technical Support Engineer, Power Quality Thailand LTD |
| Secure Network Infrastructure for Mission Critical Data from Utility IoT | Peter Larsson, IoTium |
| Testing Power Quality Meters with the PQSim Training Tool | Terry Chandler, Director of Engineering, Power Quality Thailand LTD/Power Quality Inc. |
| Passive vs Active Harmonic Mitigation | Mirus International Inc. |
PQSynergy™ is an international forum to share experiences, requirements, questions, information, customer requirements, problems and solutions in the fast growth area of quality of supply requirements of sensitive loads, energy conservation and management and power quality monitoring and solutions.
For more information, you can visit the website: www.pqsynergy.com
View and download papers:
| PQSynergy™ Papers | Publishers |
|---|---|
| Thailand Integrates Large-Scale Wind Farms | Chakphed Madtharad, Ph.D., Provincial Electricity Authority (PEA) |
| Power Master 3 Series | Jay Babin, Power Quality Thailand LTD |
| Using Power Quality Data to Troubleshoot Utility Assets | Daniel Sabin, P.E., M.Eng., IEEE Fellow Principal Engineer & Software Architect, Electrotek Concepts |
| Design and Evaluation of PV Rooftop system in Thailand | Asst. Prof. Dr.-Ing. Boonyang Plangklang, Department of Electrical Engineering, Faculty of Engineering, Rajamangala University of Technology Thanyaburi,, RMUTT Thailand |
| Introducing a Power Quality Simulator | Terry Chandler, Director of Engineering, Power Quality Thailand LTD/Power Quality Inc. |
| Solving Customers’ Problems in Harsh Environment | SONEL |
| Advanced Power Quality Monitoring System in Hong Kong | Ir. Y.Y. LEE (MHKIE, MIET) &Nick K.W. CHAN, CLP Power Hong Kong Limited |
| Grid-Tied PV in Singapore – Power Quality Aspects and Its Challenges | Er. Muhammad Najmi Bin Bohari, MSc(Power Eng), B.Eng (EEE), P.Eng, MIES, M-CIGRE |
| Who is liable for damage when PQ supply is out of tolerance | Jay Babin & Itti Mangkornthong, Power Quality (Thailand) Co. Ltd. |
| Harmonic in the Modern Industry Auto Parts Industry and Harmonics | – |
| The Harmonic Load of Various Technologies lamps vs Traditional Lamps | Itti Mangkornthong, Power Quality (Thailand) Co. Ltd. |
| Harmonic Assessment for Cement Kiln | Suwipha Kittitanaphisarn, Chief of Power Quality Analysis Section, PEA Area 1(North) Chiangmai |
| Dranetz Commercial Message | Brian Todd, Vice President of Global Sales for Dranetz General Manager of Electrotek Concepts & Daniel Sabin, Principal Engineer & Software Architect, Electrotek |
| Decentralized Battery Energy Management Systems for Stand-Alone PV-Battery Systems | UmarinSangpanich (PhD.), Faculty of Engineering at Sriracha, Kasetsart University (Sriracha campus) |
| Ozone Water System | Thai Energy Conservation Co., Ltd |
| Leveraging Distributed Processing in the Smart Grid | Keith, Linklaser |
| Smart Grid for Modern City | – |
| Grid Modernization – a System Operator’s Perspective | Victor Wong, Sarawak Grid System Operator/Senior Vice-President, Sarawak Energy Berhad |
| Overvoltage Consideration in Grounding of Distributed Generation | Nat Songkram, Power Quality Section, Provincial Electricity Authority (PEA) |
| Harmonics in Electrical Power Systems – A Major Power Quality Issue | Baldev Raj Narang B.Sc. Engineering (Electrical), CEO Clariant Power System Ltd, Pune India & Co-Author Tushar Deshmukh BE MBA CMD, Clariant Power System Ltd, Pune India |
| EV Charging in Future | Qianlu Yan, Beijing Joint Harvest S&T Co., Ltd. |
| Thailand EE Policy for Standard and Labeling | Mr.Watcharin Boonyarit, Senior Scientist Department of Alternative Energy, Development And Efficiency Ministry of Energy, Thailand |
Published by Dranetz – BMI Case Studies
The power system for this major NYC bank providing nationwide credit card and other financial transactions appeared to be performing satisfactorily. Fortunately, the proactive monitoring approach employed in this facility identified a power quality trend that could have caused a catastrophic failure.
Non-symmetrical waveforms rich with even order harmonics indicate a problem in the power system. The problem was identified as a partial rectification by the UPS of the AC power instead of a full rectification. The UPS would have failed if the system had switched over.
While the bank did not experience any overt power quality problems, monitoring at the input and output of three separate UPS systems identified non-symmetrical waveforms and a trended increased in even-order harmonics. Since this harmonic pattern is indicative of an improperly operated power system, a spectrum analysis was performed. That analysis identified a partial rectification where a full rectification of the AC power should have occurred. Left alone, the UPS would have failed to perform. The UPS maintenance team was quickly brought in to repair the problem and ensure high 9’s reliability.

Have a WordPress.com account? Log in now.