Voltage Transients Causing Diode Failures

Published by Dranetz – BMI Case Studies


A plastic extrusion manufacturer in the mid-West had a 480V delta feeding a plastic extrusion machine. The ASD-driven synchronous motor in the extruder had a half-wave bridge rectifier circuit to provide excitation voltage to the pole coils.

Diodes on the half-wave bridge exciter circuit were blowing out, and the filters to the SCRs were being damaged.

Three channels of the voltage supply feeding the extruder were monitored for just two seconds before enough data was collected to determine the cause of the failures. As shown in Figure 1, a burst of transients would occur three times a second. The RMS voltage did not change significantly during these transients.

Voltage Transients Causing Diode Failures figure1
Figure 1

Closer examination of the waveforms showed that the transients were a repetitive series of voltage transients, occurring six times a cycle on all three phases. An example of the voltage waveforms for one phase is shown in Figure 2.

 

Voltage Transients Causing Diode Failures figure2
Figure 2

These repetitive voltage transients are referred to as voltage notches. The maximum voltage of the transient could produce damage, and the notches that cross the zero axis could result in zero errors. lose examination of the transients is shown in Figure 3.

 

Voltage Transients Causing Diode Failures figure3
Figure 3

 

Analysis

The following were calculated values of this voltage disturbance monitoring period:

  • Number of transients: 192
  • Amplitude: -580 volts
  • Worst Absolute amplitude (from zero crossing): 864
  • Rise time: 1.0851 microseconds
  • Frequency (1/4*rise): 230.4 kilohertz
  • Number of zero crossing errors this frame: 146
  • Worst zero crossing width: 61440 microseconds
  • Worst zero crossing delta voltage: 168 volts
  • Worst notch area: 0.021475 volt-seconds

 

Transient Analysis

The absolute amplitude value confirmed the cause of the damage to the diodes, as this voltage exceeded the ratings of the diodes in the half-wave bridge. The extremely fast rise time and equivalent frequency greater than 100KHz of the transient indicates that the source of the transient is relatively close to the measuring point. This would indicate that the origin of these transients was an electronic switching load such as a bridge rectifier used on many electronic motor drives. The transients on other phase voltage channels were not the same polarity, but occurred at relatively the same time, as shown in Figure 4.

Zero crossing errors can cause timing problems with phase controlled and electronic loads. Clocks can run faster and power electronics, such as SCRs and switching diodes, can misfire and be damaged. Notching can also trip protective relaying, stress power electronics, and cause excessive heat in motors and transformers.

 

Voltage Transients Causing Diode Failures figure4
Figure 4

 

Harmonic Analysis

The harmonic analysis in Figure 5 of the initial waveform event of Phase BC Voltage shows the channel’s total harmonic distortion was 11.2%. The highest harmonic was the 2nd, at 8.3%. The high values of even harmonics is attributed to the half-wave rectifier, whose Fourier expansion is made up of solely even harmonics.
.

Voltage Transients Causing Diode Failures figure5
Figure 5

Repetitive voltage transients are usually caused by phase-angle controlled loads, such as three phase converters. A voltage notch results from two phases being momentarily short- circuited during the commutation period. In this case, they were creating by the ASD drive itself, which converts the AC to DC and then back to AC to control the motor’s speed and torque. The half-wave bridge used as the voltage exciter was the source of the abnormally high even harmonics.

The solution employed was to place MOVs with appropriate clamping voltage across the diodes in the bridge to prevent their destruction. Though not used at this site, special filters, such as certain line tracking filters, can be used to alleviate zero crossing errors. In addition, power conditioning devices, chokes or special filters could be used to “fill in” the notches and smooth out the waveform.

 

 

 

Harmonics Generated from the Source

Published by Dranetz – BMI Case Studies


The subject company manufactures meat products such as sausage, salami, and bologna. Most of their load consists of HVAC and refrigeration as they have about 6000 sq. ft. of cold room storage. They also have machinery such as grinders, slicers, and presses. The facility is served by a 120/240V through a utility-owned 500 kVA High-Leg Delta transformer that they share with another factory.

Interruptions occurred when a main 1200 amps circuit breaker was tripped frequently. The events occurred often and sometimes several times a day. Previous measurements had not shown the reason for the events as the highest measurement of current shown was 760 amps, which was not enough to cause the breaker to trip.

From the recordings, the following was noted:

At times the peak current exceeded the 1200A breaker rating without tripping the breaker. An interruption that was tied to such a peak current was detected only once during the measurement period. Further investigation from the wave forms captured determined that the voltages were distorted during such times. This distortion caused nuisance tripping of other breakers and caused the capacitor banks to fry.

A long-term measurement showed that the capacity of the breaker could be reached when a combination of tasks occurred at the same time.

Since most of the load at this site is linear, no harmonics are generated from within the facility. When we looked outside the factory, the cause of the distortion was traced to faulty power transformer.

Harmonics Generated from the Source figure1

Harmonics Generated from the Source figure2

The utility replaced the transformer and enabled the factory to increase capacity and production. 

IEC 61000-4-30 Class A Edition 3

The IEC 61000-4-30 Class A standard defines the measurement methods, time aggregation, accuracy, and evaluation, for each power quality parameter to obtain reliable, repeatable and comparable results between various brands and models of PQ instruments and systems.

IEC 61000-3-30 Class A Edition 2

IEC 6100-4-30 Class A Edition 2 standardizes the measurements of:

  • Power frequency
  • Supply voltage magnitude
  • Flicker (by reference to IEC 61000-4-15)
  • Voltage dips/sags and swells
  • Voltage interruptions
  • Supply voltage unbalance
  • Voltage harmonics, and interharmonics (referenced to IEC 61000-4-7)
  • Mains signaling voltage
  • Rapid voltage changes
  • Magnitude of current
  • Current harmonics and interharmonics (referenced to IEC 61000-4-7)
  • Current unbalance


IEC 61000-4-30 Edition 3 Introduced new measurements definitions and PQ parameters.

“This third edition cancels and replaces the second edition published in 2008. This edition constitutes a technical revision”.

  • Rapid voltage changes
  • Flicker class F1
  • Magnitude of the current
  • Current unbalance
  • Current harmonics (by reference to IEC 61000-4-7)
  • Current interharmonics (by reference to IEC 61000-4-7)

Additional changes in harmonic parameters from IEEE 519 2014

The number of harmonics to be evaluated. In many application, 50 harmonics are not enough and modern DC to AC inverters used in Wind and Solar generation have significate harmonic component up to the 100th.


Recording resolution – the latest edition of the IEEE 519 requires a daily and weekly harmonic evaluation of both voltage and current at 150/180 cycles (~3sec) resolution per phase. An edition 3 compliant instrument must record this data and prepare a report from the instrument.

Why these revised standards are important to electric utilities?

1. Rapid Voltage Change (RVC) parameter captures voltage changes (sags) that can be disruptive to some loads without exceeding the standard of +/- 5% voltage change limit. An instrument that does not make RVC measurements will miss these events. So a utility may receive customer complaints (most common is light flickers) and not have any data to find the source of the complaint. (most common is large motor starts or other sudden load or distributed generation switching. (tripping)

2. The Edition 3 revision transfers the responsibility for measurement methods continue in this standard, but responsibility for influence quantities, performance, and test procedures are transferred to IEC 62586 -1 and -2.

Part 1, namely IEC 62586-1, was constructed to define a comprehensive PQ device product standard, coined within as PQIs. The standard outlines safety, electromagnetic compatibility (EMC), climatic, and mechanical requirements, and refers to IEC 62586-2 for functional aspects. These requirements serve to ensure the instrument’s robustness will be suitable for its installation within the severe environments of a power station or substation.

Part 2, IEC 62586-24, defines the functional tests cited in the first part of the series. These tests are intended to comprehensively verify the PQ measurement methods outlined in 4-30. This chapter was established to provide traceable and repeatable procedures to verify the compliance of each PQ metric outlined in 4-30. This firstly addresses the main shortcoming of 4-30 and ensures better method adherence between PQ meter manufacturers. Additionally, the standard allows regulatory laboratories adhering to ISO/IEC 170255 to issue conformance reports and certificates according to IEC 62586-1 or IEC 62586-2 (with compliance to IEC 62586-2 meaning compliance to IEC 61000-4-30). The latter provides PQ meter manufacturers a way to provide internationally recognized compliance for the entire scope of PQI requirements.

3. To help ensure accurate PQ metrics in the harsh installation environment of a power station or substation, a number of electromagnetic compatibility (EMC) and influence quantity tests were also added to the scope of the IEC 62586 series.

“IEC 62586-2:2013 specifies functional tests and uncertainty requirements for instruments whose functions include measuring, recording, and possibly monitoring power quality parameters in power supply systems, and whose measuring methods (class A or class S) are defined in IEC 61000-4-30. This standard applies to power quality instruments complying with IEC 62586-1. This standard may also be referred to by other product standards (e.g. digital fault recorders, revenue meters, MV or HV protection relays) specifying devices embedding class A or class S power quality functions according to IEC 61000-4-30. These requirements are applicable in single, dual- (split phase) and 3-phase a.c. power supply systems at 50 Hz or 60 Hz.”

4. Environmental impact on the instrument from a laboratory environment. (25 Degrees C to a substation environment 40 Degrees C + ) is now part of the requirement of this standard. Detailed measurement procedures for Harmonics including to the 100th are included. Reporting of the harmonics to IEEE 519-2014 with harmonic limits specified for 1 and 1 week are included.

5. Detailed measurement procedures for Harmonics including to the 100th are included.

6. Reporting of the harmonics to IEEE 519-2014 with harmonic limits specified for 1 and 1 week are included.

All of these issues can be defined as IEC 61000-4-30 Class A, Edition 3 compliant.