Analysis of Design Solutions for Rotors with Permanent Magnets for Small Hydropower Plants (SHP)

Published by 1. Petr BOGATYREV, 2. Tomasz WOLNIK, ORCID: 1. 0000-0002-6589-8785; 2. 0000-0002-2636-8423


Abstract. The article presents an analysis of the influence design solutions of rotors with permanent magnets on the parameters and operating characteristics of a hydrogenerator designed for small hydropower plants (SHP). Internal Permanent Magnet (IPM) and Internal Permanent Magnet V-shaped rotor configurations were considered. The influence of the angle between permanent magnets on the value of the induced voltage and the final operating characteristics was analysed. The obtained results were compared with the rotor solution with magnets mounted on the surface, called Surface Permanent Magnet (SPM). Based on the analysis, the advantages and disadvantages of individual solutions designed for use in hydrogenerator of SHP were determined.

Streszczenie. W artykule przedstawiono analizę wpływu rozwiązań konstrukcyjnych wirników z magnesami trwałymi na parametry i charakterystyki eksploatacyjne hydrogeneratora przeznaczonego do małych elektrowni wodnych (MEW). Rozważano konfiguracje wirnika typu ang. Internal Permanent Magnet (IPM) oraz Internal Permanent Magnet V-shaped. Dokonano analizy wpływu kąta pomiędzy magnesami trwałymi na wartość indukowanego napięcia oraz końcowe charakterystyki eksploatacyjne. Uzyskane wyniki porównano z rozwiązaniem wirnika z magnesami montowanymi na powierzchni ang. Surface Permanent Magnet (SPM). Na podstawie przeprowadzonej analizy określono wady i zalety poszczególnych rozwiązań przeznaczonych do zastosowania w hydrogeneratorze MEW.

Keywords: hydrogenerator, rotor with permanent magnets, electromagnetic calculations
Słowa kluczowe: hydrogenerator, wirnik z magnesami trwałymi, obliczenia elektromagnetyczne

Introduction

In Poland, hydrological conditions for generating electricity from watercourses are not favorable compared to, for example, Norway or Sweden. However, there is great potential to develop unused infrastructure for the building of small hydropower plants, defined as objects with a total installed power up to 10 MW [1]. According to the inventory carried out in 2012 year by the National Water Management Authority, there are about 14000 objects with a water level of at least 0.7 m, of which only 4.5% is used to generate electricity [1,2]. Within of the European RESTOR Hydro project a map was developed defining over 50000 potential SHP locations in Europe, 8500 of which are located in Poland [3]. The report “Small hydropower plants in Poland” gives that there are 775 small hydropower plants in Poland, the vast majority of which are power plants with an installed power of less than 0.5 MW. The same report estimates that the technical potential in Poland for utilization in small hydropower plants amounts about 1500 MW of installed power. The current installed power of the SHP is 286 MW, which indicates about 20% utilization of the available national technical potential [1].

In Small Hydropower Plants (SHP) low-speed synchronous generators with permanent magnets are increasingly gaining popularity, mainly due to their higher energy efficiency, the possibility of eliminating the mechanical gearbox and higher controllability, allowing for better utilization of the available hydrological conditions of a given watercourse [2,4]. The design of the electromagnetic circuit of a permanent magnet generator rotor has a key influence on the obtained parameters and operational characteristics, the values of the induced voltage and the THD level of the phase and line-line voltage [5, 6, 7, 8]. This publication presents the results of calculations and numerical simulations carried out for various rotor design solutions for a permanent magnet synchronous generator with a target power of 100 kW and a rated rotational speed of 250 rpm, operating on a resistive load cosφ = 1. The analysis included a rotor with IPM-type recessed flat magnets, rotors with V-shaped recessed magnets with various values of the opening angles of permanent magnets, and an SPM-type rotor with magnets mounted on the yoke surface.

The aim of the simulations was to evaluate individual rotor design solutions in scope of the operational obtained parameters and to evaluate the general advantages and disadvantages of a given solution.

Calculation model

The calculation model of the generator was prepared in the ANSYS Electronics software and is shown in Figure 1.

Fig.1. Cross-section and longitudinal section of the generator’s electromagnetic circuit and its geometric dimensions

The stator and winding data were identical for all analysed cases. In this publication, IPM (180), VPM (70), VPM (86), VPM (105) and SPM rotors were analyzed. The values given in brackets refer to the opening angle between the magnets. The basic parameters of the generator are presented in Table 1, while Figures 2-3 present models of the analysed rotors.

Table 1. Basic generator parameters for all analysed cases

.
Fig.2. Cross-section of the electromagnetic circuit of generator with a rotor a) IPM (180), b) VPM (70 yellow, 86 red, 105 green)

Fig.3. Cross section of the electromagnetic circuit of generator with SPM-type rotor

Table 2 presents basic data characterizing individual rotor solutions. Particular attention was paid to the used volume of permanent magnets, because it significantly affects the cost of production the rotor. It can be seen that the volume of the SPM rotor magnets is approximately 40% smaller than the volume of the magnets in the VPM (70) rotor.

Table 2. Basic data of the analysed rotor design solutions

.
Operating characteristics

For the calculation model presented in Figure 1, numerical simulations were carried out to determine the basic characteristics of the generator for various rotor design solutions. Figure 4 shows the waveforms of phase back EMF at no-load for different rotor solutions. The SPMtype rotor and the VPM-type rotor (70) have the highest value of induced back EMF at no-load, while the VPM-type rotor (180) has the lowest value. Figure 5-6 shows the calculated operating characteristics of the generator. The first one is the external characteristic, showing the value of the phase-to-phase voltage VLL at the generator terminals as a function of the electrical power Pel. The second characteristic is the efficiency η as a function of the electrical power Pel. The characteristics were determined at a load of cosφ = 1, without taking into account the control.

Table 3 shows the calculated values of the basic generator parameters assuming a load of cosφ =1. Due to the identical design and winding data of the armature, in all analyzed cases the comparison was made for a load current of 280 A, treated as the rated load.

Fig.4. Waveforms of phase back EMF at no-load for different rotor solutions

Fig.5. Characteristics VLL = f(Pel) for the analysed rotor variants at load cosφ = 1

Fig.6. Characteristics η = f(Pel) for the analyzed rotor variants at load cosφ = 1

Table 3. Calculated parameters of the generator for individual rotor solutions with permanent magnets

.

where:
IN – rated current,
E0LL – line to line back EMF at no-load,
VN – rated line to line voltage,
ΔV – percentage voltage drop,
PN – rated electrical power,
Pmax – max. electrical power,
ηN – rated efficiency.

Voltage THD factor

One of the main parameters of the generator is the voltage THD factor, which informs about the content of harmonics [9]. Figure 7 shows the phase voltage Vph waveforms at a rated load Iph = 280 A and cosφ = 1 for different rotor design solutions. The calculated THD values are presented in Table 4.

.
Fig.7. Output waveforms of phase voltages Vph at rated load Iph = 280 A and cosφ = 1 for different rotor solutions: a) IPM (180); b) VPM (105); c) VPM (86); d) VPM (70); e) SPM

Table 4. THD values of phase voltage

.

The highest content of harmonics is characteristic of the IPM (105) and IPM (180) rotor. The THD factor of the phase voltage under load for them is about 14%, while for the IPM (70) solution it is 3.2%. Of course, one should strive for as sinusoidal voltage waveforms as possible, but in the case of cooperation of a permanent magnet generator with the power grid, the power electronics converter is responsible for the correct shaping of the output voltage with an appropriately low THD factor.

Table 5 presents the determined amplitude values of individual harmonics. Apart from the first harmonic, the third harmonic has the largest amplitude for all rotor design solutions and it is this that mainly shapes the course of the obtained voltages.

Figure 8 present the amplitude of the main harmonic and higher harmonics of one phase of different rotors can be compared.

Table 5. Amplitude values of harmonic contents of phase voltage for different rotor type

.

Table 6. Percentage ratio of higher harmonic contents to the first harmonic of phase voltage for different rotor type.

.
Summary

The analysis shows that the most favorable parameters are characterized by the generator with the VPM (70) and SPM rotors. For these rotor variants, the highest value of rated and maximum power, the highest efficiency, the lowest voltage drop and the highest overload capacity are obtained. The advantage of the VPM (70) design solution is that permanent magnets are naturally protected against mechanical damage by being placed in appropriate slots. In the case of SPM rotors, it is necessary to use additional forms of protection, for example by banding. The disadvantage of the VPM solution (70) in comparison to the SPM rotor is the much larger volume of permanent magnets, about 75% larger, which significantly increases the cost of production the rotor.

The magnets embedded deeper in the radial dimension of rotor (VPM) generally exhibit greater demagnetization resistance, and such electric machines are the most promising designs overall in terms of demagnetization resistance. However, it should be noted that the volume and mass of magnets typically increase as magnets are buried deeper. [10, 12]

The IPM topology presents the smallest losses through hysteresis, followed by SPM and VPM. These differences are due to the magnetic saturation and harmonics characteristic of each particular topology. For all topologies currents cause the rotor temperature to rise, affecting the efficiency and performance of the machine. [11]

Fig.8. Main and higher harmonic components of phase A for all rotor design solutions

REFERENCES

[1] Raport „Małe Elektrownie Wodne w Polsce”, praca zbiorowa w wyniku porozumienia UN GLOBAL COMPACT NETWORK POLAND z Ministerstwem Rozwoju i Technologii na rzecz realizacji Celów Zrównoważonego Rozwoju ONZ, w szczególności Celu 7 dotyczącego czystej energii. Warszawa, 2022r
[2] Bernatt J., Rossa R., Pistelok P., MEW z wysokosprawnym generatorem synchronicznym wzbudzanym magnesami trwałymi, Energetyka Wodna, 3/2015
[3] https://eref-europe.org/restor-hydro-database/
[4] Gawron S., Innowacyjne projekty maszyn elektrycznych z magnesami trwałymi i ich praktyczne zastosowania, Maszyny Elektryczne – Zeszyty Problemowe, Nr 1/2016 (109), str. 1-10
[5] Król E., Rossa R.: Prądnice synchroniczne z magnesami trwałymi umieszczonymi wewnątrz wirnika. Zeszyty Problemowe – Maszyny Elektryczne Nr 80/2008, BOBRME Komel, Katowice
[6] Glinka T.: Maszyny elektryczne wzbudzane magnesami trwałymi. Wydawnictwo Politechnik Śląskiej, Gliwice 2002
[7] Dobzhanskyi O., Grebenikov V., Gouws R., Gamalilia R., Hossain E.: Comparative thermal and demagnetization analysis of the PM Machines with neodymium and ferrite magnets, Energies 2022, 15, 4484
[8] Rossa R., Król E., Prądnice synchroniczne z magnesami trwałymi umieszczonymi wewnątrz wirnika, Maszyny Elektryczne – Zeszyty Problemowe, Nr 80/2008
[9] Bogatyrev P., Golec J., Gawron S., Opracowanie i wdrożenie systemów do wytwarzania energii elektrycznej z małych elektrowni wodnych, Maszyny Elektryczne, Zeszyty Problemowe, Nr 1/2023, str. 159-164
[10]Yinye Yang, Sandra M. Castano, Rong Yang, Michael Kasprzak, Berker Bilgin, Anand Sathyan, Hossein Dadkhah, Ali Emadi: Design and Comparison of Interior Permanent Magnet Motor Topologies for Traction Applications. IEEE Transactions on Transportation Electrification, October 2016
[11]Vascan Iulia, Claudia Martis, Florin Pop, Ion Barsan: PMSM Rotor Topologies for Automotive HVAC System. EV2019, Electric vehicles international conference & show, 3-4 October 2019.
[12]Yong Kong, Da Xu, Mingyao Lin: Efficiency modeling and comparison of surface and interior permanent magnet machines for electric vehicle, 9th International Conference on Power and Energy Systems Engineering (CPESE 2022), Doshisha University, Kyoto, Japan, 9–11 September 2022


Authors: Petr Bogatyrev, MSc. Łukasiewicz Research Network – Upper Silesian Institute of Technology, Centre for Electric Drives and Machines, ul. Karola Miarki 12-14, 44-100 Gliwice, E-mail: