PQSynergy™ is an international forum to share experiences, requirements, questions, information, customer requirements, problems and solutions in the fast growth area of quality of supply requirements of sensitive loads, energy conservation and management and power quality monitoring and solutions. For more information, you can visit the website: www.pqsynergy.com View and download papers: PQSynergy™ Papers Publishers ThailandContinue reading “PQSynergy™ Papers 2016”
Author Archives: PQBlog
Bank’s High 9’s Infrastructure Saved from Disaster
Published by Dranetz – BMI Case Studies The power system for this major NYC bank providing nationwide credit card and other financial transactions appeared to be performing satisfactorily. Fortunately, the proactive monitoring approach employed in this facility identified a power quality trend that could have caused a catastrophic failure. Non-symmetrical waveforms rich with even orderContinue reading “Bank’s High 9’s Infrastructure Saved from Disaster”
PQSynergy™ Papers 2015
PQSynergy™ is an international forum to share experiences, requirements, questions, information, customer requirements, problems and solutions in the fast growth area of quality of supply requirements of sensitive loads, energy conservation and management and power quality monitoring and solutions. For more information, you can visit the website: www.pqsynergy.com View and download papers: PQSynergy™ Papers Publishers EffectContinue reading “PQSynergy™ Papers 2015”
24/7 Customer Service Center
Published by Dranetz – BMI Case Studies In 2000, DHL Airways opened a new 24/7 customer service center to support its US customer base. To maximize uptime and ensure high reliability, a redundant UPS system was installed, protecting both the supply and the facility loads. Integral to the facility design was the Signature System powerContinue reading “24/7 Customer Service Center”
PQSynergy™ Papers 2014
PQSynergy™ is an international forum to share experiences, requirements, questions, information, customer requirements, problems and solutions in the fast growth area of quality of supply requirements of sensitive loads, energy conservation and management and power quality monitoring and solutions. For more information, you can visit the website: www.pqsynergy.com View and download papers: PQSynergy™ Papers Publishers AnContinue reading “PQSynergy™ Papers 2014”
PQSynergy™ Papers 2012
PQSynergy™ is an international forum to share experiences, requirements, questions, information, customer requirements, problems and solutions in the fast growth area of quality of supply requirements of sensitive loads, energy conservation and management and power quality monitoring and solutions. For more information, you can visit the website: www.pqsynergy.com View and download papers: PQSynergy™ Papers Publishers AdvancedContinue reading “PQSynergy™ Papers 2012”
Loose Bus Bar Bolts Cause Sags
Published by Dranetz – BMI Case Studies An administration building in a government complex in New Jersey had a transformer with a 4KV primary, 120/208V wye, 800A secondary. The buss duct ran up to a second-floor panel, which supplied an office area. Computer misoperations and lights flickering were occurring randomly for nearly two years. EmergencyContinue reading “Loose Bus Bar Bolts Cause Sags”
PQSIM 200™
A Power Practitioner™ Training Tool “A dedicated AC generator that produces voltage and current waveforms of the most common Power Quality disturbances” PQSIM 200™ was designed by Power Quality Experts with 30 years’ experience testing and documenting Power Quality. The PQSIM 200™ provides the user with the capability to select PQ events and their magnitudeContinue reading “PQSIM 200™”
Textile Industry Evaluation
Published by Dranetz – BMI Case Studies Despite their differences, continuous-process industries share underlying characteristics: they maintain continuous operations in facilities that represent substantial start-up costs and time but can be interrupted or disrupted by seemingly minor fluctuations in power quality. If the product stream is disrupted, lost productivity and lost product can create aContinue reading “Textile Industry Evaluation”
Thumping Sounds in the Closet
Published by Dranetz – BMI Case Studies Elevator control panels for the lower zone mid-rise elevators were on the nineteenth floor of a forty-story office building in a large midwestern city. It was fed with 480V transformer on the same floor, with the feeders to the controls rated at 800A. Excessive noise and vibration ofContinue reading “Thumping Sounds in the Closet”