METSyS Panel Capacity Analyzer (PCA)

Published by POWERetc Corporation, Corporate Headquarters,3350 Scott Blvd, Bldg. 55-03, Santa Clara, CA 95054. Phone: (408) 540-3199 Email: info@poweretc.com, Website: poweretc.com


The Right Tool for Conducting a Connected Load Study to Confirm Panel Capacity 

METSyS NEC 220 Current logger

The METSyS Panel Capacity Analyzer (PCA) is a specially-designed instrument for measuring and recording 3- or 4-phase current to confirm the distribution panel’s capacity in compliance with NFPA’s National Electrical Code (NEC) 2014 Article 220.87 and meeting the requirements for uniform load calculations in accordance with the requirements of the California Electrical Code (CEC).

The METSyS PCA packaged with POWERetc’s proprietary macro-based Excel spreadsheet provides users with the capability of conducting connected load studies of various lengths to meet specific regulatory requirements. This provides a definitive and documented result enabling electrical contractors and facilities engineers to quickly obtain electrical inspection approval when adding new loads to a panel. 

The process requires both the calculation of the average current over an extended period in order to confirm that – with planned load additions – will remain less than 80% of the breaker rating(s). In addition, the standard requires that MIN and MAX currents are also determined over the sampling period.

The METSyS logger samples every cycle using an 8-cycle “window” and calculates the average value of the 8-cycles. These readings are accumulated for the user-selected averaging period–10s, 30s, 1m, 5m, 10m, 15m, 30m, 60m–and the average of the averages is saved as the average value for the period and the minimum and maximum sample are saved as the MIN/MAX values. The PCA’s MIN/MAX values are really a composite of 8-cycles which will result in understating the peak inrush but is probably more reflective of levels that might cause breaker tripping problems.

METSyS 3-Phase Panel Capacity Analyzer including: 3-Phase 4000A MicroFlex bundle – 6″ diameter loop (also available with 2″ and 15″ diameter loops)

METSyS NEC 220 Current logger_Package

POWERetc METSyS Current Probe Kit Facilitates Safe 480V Panel Connected Load Studies. The CCPK-6 Cabinet Current Probe Kit enables routine panel capacity studies to be performed in 480V panels – without the need to open or power down the panel.

METSyS NEC 220 Current logger_Cabinet Current Probe Kit [CCPK-6]
Features

• True RMS current measurement (50 Hz and 60 Hz) – 3 phase + Neutral
• Calibrated Rogowski coils to ease interchangeability
• 2GB internal memory for non-volatile data storage
• A USB flash drive to be used for transferring the data from the logger to the PC
• A charge port for battery charging through the micro USB port
• A two-line LCD display and a three-button keypad to ease setup and data transfer
• Logging of measurements to internal memory
• Records Min, Max, Average and Peak currents
• Current display on an LCD screen
• 3 button simplified User Interface
• 72 Hour internal battery (for operation without connection to a power supply)
• Connectivity – Bluetooth (BLE) and USB Generates CSV log files for easy transfer to a PC
• iOS and Android apps
– Live reading display
– Log setup
– Start, Stop & Resume logging remotely
– Email logged data

Specifications

Electrical Characteristics

Measuring Range : 4000A AC RMS
Overload Capability : 10000 A
Accuracy ( 45-65Hz) : ± 1 % of reading ± 1 A
Position Sensitivity : ± 2.5%
Resolution : ± 1 A
Temperature Coefficient : ± 0.05% of reading / °C

Power Supply : Internal Rechargeable Lithium-Ion battery
Battery Life : 100 hours, typical. (Recharge fully depleted battery, 4-5 Hr)
Battery FULL/Charging/Not Charging Indication
Changing Voltage : Via USB micro-B charging socket (5V, 1 00mA)
Working Voltage (see Safety Standards section) : 600 V ACRMs or DC

Enclosure
Material : ABS
Dimensions : 160 (I) x 80 (w) x 45 (d) mm

Probe
Probe Conductor Diameter: 6mm (0.24″)
Probe Diameter : 50mm (2″), 150mm (6″), 375mm (15″), double insulated
Degree of Protection : IP67 (not certified by UL)
Phase Indication (Probe Color) : Black (A), Red (B), Blue (C), Gray (Neutral)

General Characteristics
Display : Back lit 2 line alpha numeric display
Log Intervals : 10s, 30s, 1 m, 2m, 5m, 10m, 15m, 30m, 60m.
Log Duration : 1, 3, 8, 24, 48, 72, Unlimited (Max 1 year@ 1 Os)
Data Transfer : Via USB memory stick (FAT 32)
File Format : Comma separated values file (.CSV)
Operating Temperature Range : -20 to +65 °c (-4° F to +149° F)
Storage Temperature Range : -40 to +85 °c (-40° F to + 167° F)

Safety Standards
EN 61010-1
EN 61010-2-032
600 VRMs, Category IV, Pollution Degree 2
EMC Standards
EN 61326-1


About POWERetc Corporation: POWERetc Corporation was founded by Bruce Lonie in March of 2019. With thirty plus years of experience as president and co-founder of PowerCET Corporation, Bruce has extensive experience in the investigation and diagnosis of complex electrical environment problems. The firm specializes in the application of electrical and electromagnetic monitoring equipment to identify and resolve complex productivity and equipment reliability issues. Services include the sale and rental of selected power and energy instruments, operational training, data analysis and report generation.