Single-point and Multi-point Signal Grounding

Published by Lorenzo Mari, EE Power – Technical Articles: Single-point and multi-point Signal Grounding, April 16, 2021.


A grounding arrangement must be designed and implemented adequately for the electronic equipment’s proper performance

Introduction

The main categories for grounding electronic equipment are:

• Safety ground (AC and DC power ground) prevents shocks and fire hazards from the breakdown of components or wiring.

• Signal ground reduces noise resulting from electromagnetic fields, common impedances, or other interference coupling forms.

This article emphasizes typical methods employed for signal grounding.

In general, the electronic types of equipment have different circuits and systems, each having its grounding terminal. The method to interconnect these grounding points is fundamental to eliminate electromagnetic interference. Due consideration to the impedances introduced by the grounding conductors is of paramount importance.

Electrical Communications and Noise

Communication is the process of information transmission between two devices. An electrical communication system attains this function primarily through the use of electric devices and phenomena.

While transmitting electrical signals, specific unintended and undesirable effects take place. Broadly speaking, “noise” is any unintentional alteration of the signal shape. However, it is possible to distinguish three primary contaminants: distortion, interference, and noise.

Distortion changes the signal because of the system’s non-linear response to the desired signal. Turning off the signal disappears distortion.

Interference contaminates the desired signal due to extraneous signals — usually human-made — producing undesirable responses in a circuit or system. A circuit may respond to an undesired signal when the frequency of the undesired signal is within the operating frequency range of the circuit.

Noise is an electrical signal – random and unpredictable – from natural causes, external and internal to the system. Adding noise to a signal may partially obscure or destroy it. While distortion and interference also contaminate the signal, the uniqueness of noise is that, theoretically, it cannot be eradicated – posing a fundamental problem in electrical communications.

Common-mode Noise

Many ground system problems come from common impedance coupling.

When two or more electronic circuits share the same ground path, they also share the ground’s impedance, granting a noise coupling mechanism – the common-mode noise. 

Figure 1 shows a typical circuit using two signal wires and a common return current path. The source and load impedances connected to load 1 are Z1S and Z1L. Those related to load 2 are Z2S and Z2L.

The current I=I1+I2 flowing through the common-ground impedance Z causes a voltage Vc that undesirably affects the voltage across ZL1 and ZL2.  Note that the current flowing through one load affects the voltage across the other load.

Figure 1. Two signal wires with a common return current path.
Ground Plane

It is common to think of signal grounding as providing an equipotential point or plane used as a reference potential for a circuit or system. A ground plane is a sheet of metal connected to the ground. Ideally, every point on the ground plane should be at the ground potential.

In electrical technology, a plane is a surface on which every point is at the same voltage. A plane can be a sheet of metal, as shown in Figure 2.

Figure 2. Ideally, every two points on a ground plane should be at the same potential.
Figure 3. Ground plane.

But practical grounds are not equipotential. When the current looks for a low impedance path to return to the source, it generates a voltage difference along the path it flows through. Then, there will be minute voltage variations even in a small plane. The equipotential plane is an ideal target.

As shown in Figure 4, we sometimes employ a ring of conductors as a ground plane.

Figure 4. A ring of conductors used as a ground plane.
Typical Signal Grounding Configurations

When the objective is to reduce noise, several methods are available to interconnect the grounding points of various circuits in the same equipment or some equipment located in the same area.

The signal grounding configurations must be weighed concerning dimensions and frequency.

The typical signal grounding configurations are:

• Single-point

a. Series connection (Common ground or daisy chain)
b. Parallel connection

• Multi-point
• Hybrid

Single-point Grounding Configuration

Figure 5 shows a common ground or daisy chain configuration.

Figure 5. Common ground system.

This configuration is a series connection of the individual circuit grounds. The voltages at points a, b, and c are cumulative, being c the highest and the lowest. 

Va=(I1+I2+I3)∙Z1
Vb=(I1+I2+I3)∙Z1+(I2+I3)∙Z2
Vc=(I1+I2+I3)∙Z1+(I2+I3)∙Z2+I3∙Z3

The above equations clearly show the interaction between the circuits. When the ground currents flowing in the common paths are low or absent, the reference potential is essentially the same in all subsystems or equipment. Place the most critical stage closer to the ground point.

Avoid the series connection, especially when working with high frequencies since the rapid switching generates relatively high current impulses. Also, with circuits operating with very different energy levels – power and control – since the power equipment’s high energy impulses may couple to the control signals.

Despite being susceptible to common-mode noise and being the least effective noise mitigation method, this technique is widespread because it is economical and straightforward.

The parallel connection eliminates the common impedances in grounding circuits by connecting them to the same point, as shown in Figure 6.

Figure 6. Parallel connection.

The parallel connection is the most suitable at low frequencies because there is no cross-coupling between the ground currents from different circuits, and voltages at points a, b, and c depend on each circuit’s current and impedance.

• Va=I1∙Z1
• Vb=I2∙Z2
• Vc=I3∙Z3

This configuration mitigates common-mode noise but is mechanically bulky and costly, requiring a lot of wire in an extensive system.

The wire inductance increases the ground impedance at high frequencies, reaching very high values under resonant conditions when the wire length coincides with odd multiples of a quarter wavelength (λ). The ground path should be shorter than 1/20 of the maximum frequency’s wavelength to prevent resonance effects.

Multi-point Grounding Configuration

The multi-point grounding configuration connects multiple circuits to a ground plane. Unlike the previous arrangement, where the ground connection is at a single point, it is here at several points distributed on a ground plane.

Figure 7 shows circuits connected to the closest ground plane, usually the chassis. A chassis ground connects to an electrical or electronic system’s metal frame – the enclosure containing the components in place.

Figure 7. Multi-point configuration.

The ground paths from each circuit to the ground plane should be short to reduce the impedance and avoid resonance.

This method reduces the individual circuits’ impedance by using short conductors and a low impedance ground plane – due to its low inductance.  The ground plane’s low impedance lessens the common-mode effect.

Employ single-point grounding at frequencies below 1 MHz. Above 10 MHz, multi-point grounding is best. Use single-point grounding between 1 MHz and 10 MHz, keeping the ground paths shorter than 1/20λ.

MIL standards recommend a maximum of 300 kHz for single-point grounding and multi-point grounding afterward.

Hybrid Grounding Configuration

The practice calls for combinations of single-point and multi-point methods for cost reasons and seeking a reasonable behavior to deal with noise.

Different frequencies see unlike configurations in a hybrid ground. Figure 8 is a typical hybrid ground configuration. The capacitive reactance – Xc=1/ωC – decreases as frequency increases, then the low frequencies see a series connection while the high frequencies see the multi-point ground.

Figure 8. Hybrid configuration (with capacitors).

The opposite effect occurs substituting the capacitors with inductors. Since Xl=ωL , the lower frequencies see a low reactance – multi-point – while the higher frequencies see a high reactance – series connection. This arrangement is practical to keep a single-point configuration while connecting the safety ground required by the National Electric Code. Inductors provide low reactance for the power frequency while signals see a high reactance. Figure 9 shows such a connection.

Figure 9. Hybrid configuration (with inductors).
An Overview of Signal Grounding

Noise is an undesirable electrical signal which contaminates an original – desired – signal. Noise can be external or internal to the electronic equipment.

An adequately designed grounding arrangement can reduce noise.

A ground plane is a conductive surface connected to the ground. Theoretically, every point on the ground plane should have the same potential.  The ground plane may be a solid metal sheet or a set of conductors forming a ring or a grid.

The typical signal grounding arrangements are single-point (series and parallel connections), multi-point, and hybrid.

The series configuration employs a series connection of the individual circuit grounds in a daisy chain manner.

All the ground terminals connect to the same point in the parallel connection, eliminating the common impedances.

The multi-point system uses a ground plane to which the circuits connect separately.

Hybrid systems behave differently at low and high frequencies. Depending on the frequency and the use of capacitors or inductors, they can act as single-point or multi-point.


Author: Lorenzo Mari holds a Master of Science degree in Electric Power Engineering from Rensselaer Polytechnic Institute (RPI). He has been a university professor since 1982, teaching topics as electric circuit analysis, electric machinery, power system analysis, and power system grounding. As such, he has written many articles to be used by students as learning tools. He also created five courses to be taught to electrical engineers in career development programs, i.e., Electrical Installations in Hazardous Locations, National Electrical Code, Electric Machinery, Power and Electronic Grounding Systems and Electric Power Substations Design. As a professional engineer, Mari has written dozens of technical specifications and other documents regarding electrical equipment and installations for major oil, gas and petrochemical capital projects. He has been EPCC Project Manager for some large oil, gas & petrochemical capital projects where he wrote many managerial documents commonly used in this kind of works.


Source URL: https://eepower.com/technical-articles/single-point-and-multi-point-signal-grounding/

Published by PQBlog

Electrical Engineer

Leave a comment